Sie sind auf Seite 1von 64

Catalog D 11 November 2002

sinamics
SINAMICS G150
Drive Converter Cabinet Units
75 kW to 800 kW
Related Catalogs

SINAMICS G110 DA 11.1


Inverter Chassis Units
0.12 kW to 3 kW
Order No.:
German: E86060-K5511-A111-A1
English: E86060-K5511-A111-A1-7600

DC Motors DA 12

Order No.:
German: E20002-K4012-A101-A2
English: E20002-K4012-A101-A2-7600

SIMOREG DC-MASTER DA 21.1


Digital Chassis Converters

Order No.:
German: E86060-K5321-A111-A1
English: E86060-K5321-A111-A1-7600

SIMOREG DC-MASTER 6RM70 DA 22


Digital Converter Cabinet Units

Order No.:
German: E86060-K5122-A101-A1
English: E86060-K5122-A101-A1-7600

SIMOVERT MV Medium-Voltage Drives DA 63


660 kVA to 7200 kVA

Order No.:
German: E86060-K5363-A101-A1
English: E86060-K5363-A101-A1-7600

SIMOVERT MASTERDRIVES VC DA 65.10


2.2 kW to 2300 kW

Order No.:
German: E86060-K5165-A101-A3
English: E86060-K5165-A101-A3-7600

Low-Voltage Motors M 11

Order No.:
German: E86060-K1711-A101-A3
English: E86060-K1711-A101-A3-7600

Components for CA 01
automation

Order No.:
German: E86060-D4001-A100-C1
English: E86060-D4001-A110-C1-7600

A&D Mall

Internet:
www.siemens.com/automation/mall

Trademarks

All designations in this catalog marked with are registered


trademarks of Siemens AG.
Other names in this catalog may be trademarks which, if
used by third parties for their own purposes, may violate
the rights of the trademark owner.
SINAMICS G150 Introduction Welcome to A&D
Totally Integrated
Drive Converter Automation
SINAMICS 1
Cabinet Units
Catalog D 11
November 2002 SINAMICS G150 Benefits
Application
Design
Revised edition
January 2004 Functions

Siemens AG 2004
Technical data
Selection and ordering
2
data
Accessories
Options

Dimensional drawings Versions A and C


Mechanical connection
data

Planning Customers terminal


information block
Dimension and selection
information
Line-side components

The products and sys-


Components in the 4
DC link
tems described in this
catalog are manufac- Load-side components
tured/distributed under and cables
application of a certified Motors
quality management
system in accordance
with DIN EN ISO 9001. Services and Training
The certificate is re- Documentation Service & Support
cognized by all IQNet
countries.
Documentation

Appendix Siemens contacts


worldwide
A&D Online-services

s
Subject index
Order No. index
Terms and Conditions of 6
sale and delivery
Export regulations
Welcome to
Automation and Drives

We would like to welcome you to Automation and

Drives and our comprehensive range of products,

systems, solutions and services for production and

process automation and building technology

worldwide.

With integrated automation blocks, powerful

engineering tools and innovative concepts such as

Totally Integrated Automation and Totally Integrated

Power, we deliver solution platforms based on

standards that offer you a considerable savings

potential.

Discover the world of our technology now. If you need

more detailed information, please contact one of your

regional Siemens partners.

They will be glad to assist you.

1/2 Siemens D 11 Modified January 2004


Siemens D 11 Modified January 2004 1/3
Totally Integrated Automation
innovations for more productivity

With the launch of Totally Integrated Automation in 1996, we


were the first ones on the market to consistently implement
the trend from equipment to an integrated automation
solution, and have continuously improved the system ever
since.
Whether your industry is process- and production-oriented or
a hybrid, Totally Integrated Automation is a unique common
solution platform that covers all the sectors.
Totally Integrated Automation is an integrated platform for the

ERP
Enterprise
Resource
Planning Ethernet

Production Material
MES Order Management
Management
Manufacturing
Execution Ethernet
Systems Production
Operations
Equipment
Management
Recording

SIMATIC NET SINAUT Telecontrol SIMATIC


Control Industrial System Software
Communication

SIMATIC
Machine Vision
Ethernet

Industrial

Industrial
Ethernet Industrial Wireless
Safety Integrated Communication/
MOBIC
PROCESS FIELD

PROFIBUS
SIMATIC
PC-based Automation

AS-Interface
Building
Technology
Actuator-Sensor ECOFAST IP65
Interface Level Decentral
instabus EIB Automation System

1/4 Siemens D 11 Modified January 2004


entire production line - from receiving to technical processing
and production areas to shipping. Thanks to the system-oriented
engineering environment, integrated, open communications
as well as intelligent diagnostics options, your plant now
benefits in every phase of the life cycle.
In fact, to this day we are the only company worldwide that
can offer a control system based on an integrated platform
for both the production and process industry.

Plant Product Specification


Information Management System
Management
SIMATIC IT Framework
Production Modeler
Detailed Laboratory
Production Information
Scheduling Management System

SIMOTION
Motion Control System

SENTRON SIMATIC SIMATIC PCS 7 SIMATIC HMI


Circuit Distributed Process Control Human Machine
Breakers I/O System Interface

SIMATIC
Controller/
Automation Field Instru-
System mentation/
Analytics
Sensor SINUMERIK
Technology
IQ-Sense Numeric Control
HART
SIMODRIVE

SIMOCODE-DP Drive Systems


PROFIBUS PA Motor Protection
and Control

Siemens D 11 Modified January 2004 1/5


SINAMICS

1 SINAMICS

Overview
Applications 7 Complex individual drives in centrifuges, presses, extruders,
elevators, as well as conveyor and transport systems.
SINAMICS is the new range of converters from Siemens de-
signed for mechanical and plant engineering applications. 7 Drive line-ups in textile, plastic film, and paper machines, as
SINAMICS offers solutions for all drive tasks: well as in rolling mill plants.
7 Simple pump and fan applications in the process industry. 7 Highly dynamic servo drives for machine tools, as well as
packaging and printing machines.

SINAMICS G SINAMICS S

Extrusion Forming/Shaping

Packaging
Pumps/Fans

Printing Machines

Textiles

G_D212_EN_00053
Conveyor Systems Rolling Mills
Machine Tools

SINAMICS applications

Versions Platform Concept and Totally Integrated Automation


Depending on the application, the SINAMICS range offers the All SINAMICS versions are based on a platform concept. Joint
ideal version for any drive task. hardware and software components, as well as standardized
7 SINAMICS G is designed for standard applications with asyn- tools for design, configuration, and commissioning tasks ensure
chronous motors. These applications have less stringent re- high-level integration across all components. SINAMICS han-
quirements regarding the dynamics and accuracy of the mo- dles a wide variety of drive tasks with no system gaps. The dif-
tor speed. ferent SINAMICS versions can be easily combined with each
other.
7 SINAMICS S handles complex drive tasks with synchro-
nous/asynchronous motors and fulfills stringent requirements SINAMICS is a part of Siemens Totally Integrated Automation.
regarding: Integrated SINAMICS systems covering configuration, data
- Dynamics and accuracy storage, and communication at automation level, ensure low-
- Integration of extensive technological functions in the drive maintenance solutions with SIMATIC , SIMOTION , and
control system. SINUMERIK .

1/6 Siemens D 11 Modified January 2004


SINAMICS

SINAMICS 1

Configuration, Programming Automation Systems


and Commissioning Tools SIMATIC SIMOTION SINUMERIK

STEP 7

Drive ES

SCOUT

STARTER SINAMICS
SIZER

Motors
Asynchronous Motors Synchronous Motors

G_D212_EN_00054
SINAMICS as part of the Siemens modular automation concept

Quality to DIN EN ISO 9001


SINAMICS conforms with the most exacting quality require-
ments. Comprehensive quality assurance measures at the pro-
duct design stage, as well as in all development and production
processes, ensure a consistently high level of quality.
Of course, our quality assurance system is certified by an inde-
pendent authority to DIN EN ISO 9001.

Siemens D 11 Modified January 2004 1/7


SINAMICS

1 Notes

1/8 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units

2/2 Overview

2/2 Benefits

2/2 Application

2/2 Design

2/4 Functions

2/7 Technical data


2/8 Derating data
2/9 EMC information

2/10 Selection and ordering data

2/11 Accessories

2/12 Options
2/13 Option selection matrix
2/15 Examples for ordering
2/16 Description of options

Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Overview Benefits
Easy handling of the drive from the project engineering phase
through to the operating phase is provided by
Compact and modular design with optimum ease of servicing
Problem-free planning
Ready to connect, therefore easy to install
Fast, menu-prompted commissioning without complex para-
meterization
Clear and convenient operation using a comfortable graphical
2 operator panel with measured values displayed in plain text or
in a quasi-analog bar display.

Application
Drives such as pumps, fans or compressors do not normally
require a high overload reserve, nor do they require closed-loop
control with high performance or actual speed feedback.
For these applications, SINAMICS G150 offers a low-cost solu-
tion tailored to actual requirements.
The drive converter cabinet units are available in two versions
depending on the selection of required options:
7 Version A
All the available power supply connection components can be
installed, as required, such as main control switch, circuit-
breaker, main contactor, line fuses, radio interference sup-
pression filter or motor components as well as additional mon-
itoring devices.
7 Version C
This is a particularly space-optimized design, without line-side
components. This version can be implemented, for example,
when the required power supply connection components are
installed in an existing central low-voltage distribution unit
SINAMICS G150 drive converter cabinet units, versions A and C (MCC).
Worldwide application
SINAMICS G150 drive converter cabinet units are ideally suited
to variable-speed drives with low demands on control perfor- SINAMICS G150 drive converter cabinet units are manufactured
mance and without regenerative feedback such as in accordance with the applicable international standards and
regulations and are therefore suitable for use worldwide (see
Pumps Technical Data).
Fans
Compressors. Design
They are available for the following voltages and outputs: The SINAMICS G150 drive converter cabinet units are charac-
Voltage Output terized by their compact, modular and service-friendly design.
380 V to 480 V 110 kW to 560 kW A wide range of options is available depending on the cabinet
version, permitting optimum adaptation of the drive system to
660 V to 690 V 75 kW to 800 kW the respective demands (see Options).
Degrees of protection IP20 (standard) and as an option IP21,
IP23 and IP54

2/2 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

I Design (continued)
Options

-X1
2
Power supply connection PE

1)
Main control switch

Fuses 1)

Main contactor 1)

Line reactor uK = 2%
< 500 kW as standard
> 500 kW only as
option L23!
AC
Rectifier
DC

DC link

DC

Converter
AC

G_D011_EN_00016b
-X2
Motor connection PE

Converter version A

Converter version C

Options

1) With an output current >800 A, the main control switch,


fuses and main contactor are replaced by a circuit-breaker.

Example of the design of a SINAMICS G150 drive converter cabinet unit, Basic design of a SINAMICS G150 drive converter cabinet unit with the
version A options on the input side which define the version

Siemens D 11 Modified January 2004 2/3


SINAMICS G150
Drive converter cabinet units
Versions A and C

p Functions
Operator panel The following figures show examples of plain-text displays dur-
ing different phases of operation.
The converter is equipped with an operator panel in the cabinet
door with the following features as a human machine interface The operator panel is used to perform First commissioning.
and for commissioning:
Graphical LCD with backlighting for plain-text display and Bar J mv w x x mq i g s q q mw w ms r mr k t e v e q i x i v z e py i w
display of process variables
t 4 7 4 8 V e x i h Q s x s v Z s px e k i : = 4 2 4 Z
LEDs for display of operational status t 4 7 4 9 V e x i h Q s x s v G y v v i r x 7 5 4 2 4 E

JB'BHQBE
2 Help function with description of causes and remedies for t 4 7 4 ; V e x i h Q s x s v S y x t y x 4 2 4 o [
faults and alarms t 7 4 5 4 V e x i h Q s x s v J v i u y i r g } 4 2 4 L ~
Keypad for operational control of a drive L i pt g l e r k i S O
Local/remote switchover for selection of input point
(priority assigned to operator panel or customers terminal Only 5 motor parameters have to be entered: output, speed, cur-
block/PROFIBUS) rent, voltage and frequency. These data can be obtained from
the motor rating plate and entered into the form shown on the
Numeric keypad for input of setpoint or parameter values display by means of a brief, menu-prompted procedure.
Function keys for prompted navigation in the menus
In the subsequent screen form, the parameter values are en-
Two-stage safety strategy to prevent unintentional or unautho- tered that are used for automatic control optimization.
rized changes in settings. Operation of the drive from the oper-
ator panel can be disabled by a password, in which case only For Running the display indicates current data such as setpoint
parameter values and process variables can be displayed in and actual values as absolute values or (parameterizable) up to
the panel. The OFF key is factory-set to active, but it can also three process variables in a quasi-analog bar display.
be deactivated by the customer. A password can be used to
V y r r mr k 5 6 > 6 9 > 7 4
block unauthorized converter parameter changes. R w i x 5 8 9 4 24 4 v t q R e g x 5 8 9 4 24 v t q
IP54 degree of protection (when installed). J s y x 8 < 29 4 L ~ Z s y x 7 < 9 27 Z
Q 6 ; 4 4 R q Mq s x ; 8 < E

JB'BBHQBE
T e g x 8 5 4 o [
R e g x >
5 8 9 4 24 v t q 4 ) 9 4 5 4 4 )

V y r r mr k 5 6 > 6 9 > 7 4
R w i x 5 8 : 9 29 4 v t q T e g x 8 5 4 o [
J s y x 8 < 29 4 L ~ Z s y x 7 < 9 27 Z
Mq s x

JB'BHQBE
; 8 < E 4 ) 9 4 5 4 4 )
R e g x
5 8 : 9 v t q

Any Alarms that occur are indicated by flashing of the yellow


ALARM LED; any Faults are indicated by a lit red FAULT
LED. In the status line of the display, an additional reference to
the cause is indicated in plain text.

E pe v q w i u y i r g i q i q s v }

E 4 4 9 6 7 > J e r f ps g o i h
E 4 4 9 4 8 > G s r z i v x i v S z i v x i q t i v e x y v i e g x mz i
JB'BHQBG

L i pt e g x 2 g pi e v f e g o
Operator panel
E g x y e p J e y px
The plain text for display on the operator panel is stored in two J 4 4 4 5 S z i v g y v v i r x
languages, whereby the language currently required can be se- J 4 4 4 6 H G 1 pmr o S z i v z s px e k i
lected via a parameter (English/German as standard, for other
JB'BHQBF

combinations see Options).

L i pt t v i z f e g o e g o r s { 2

2/4 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Functions (continued)
Communication with higher-level control and customers
terminal block
A PROFIBUS interface on the control unit and a terminal block
are available as customer interfaces for control.
This customers terminal block permits connection to the higher-
level control using analog and digital signals as well as the con-
nection of additional units.
The customers terminal block contains
8 digital inputs 2
4 bidirectional inputs/outputs
2 analog inputs (differential)
2 analog outputs
2 relay outputs (changeover)
Input for KTY84 temperature sensor or PTC thermistor
10 V auxiliary voltage output for analog setpoint input
24 V auxiliary voltage output for digital inputs

Customers terminal block

For a detailed description of the interfaces, see the section


Planning information.

Siemens D 11 Modified January 2004 2/5


SINAMICS G150
Drive converter cabinet units
Versions A and C

Functions (continued)
Open-loop control and closed-loop control functions
The converter control contains a high-quality sensorless vector
control with speed and current controls as well as motor and
converter protection.
Software and protection functions
The software functions available as standard are described be-
low:
2 Software and protection functions Description
Setpoint input The setpoint can be entered internally or externally: internally as a fixed setpoint, motorized potentiome-
ter setpoint or jog setpoint; externally via the PROFIBUS interface or via an analog input of the cus-
tomers terminal block. The internal fixed setpoint and the motorized potentiometer setpoint can be
switched or adjusted by control commands from all interfaces.
Ramp-function generator The ramp-function generator prevents unintentional step changes in setpoints, and thus mechanical
overloading of the drive train. The functions it offers include separately adjustable ramp-up and ramp-
down times.
Vdc max controller1) The Vdc max controller automatically prevents overvoltages in the DC link, e.g. with ramp-down times
which have been set too short.
Automatic restart1) The automatic restart switches on the drive again following a power failure and system recovery.
Flying restart1) The flying restart permits connection of the converter to a rotating motor.
I 2 t acquisition for motor protection The motor temperature is calculated in a motor model stored in the converter software, taking into
account the current speed. Perfect accuracy in determining the motor temperature is, however, not pos-
sible because, for example, the ambient temperature is not considered. For greater accuracy, an input
for a KTY84 temperature sensor or PTC thermistor is provided on the customers terminal block.
Evaluation of motor temperature Motor protection by evaluation of a KTY84 temperature sensor or PTC thermistor. When connecting a
KTY84 sensor, the limits for alarm or shutdown can be set. When connecting a PTC thermistor, the
response to triggering can be defined (alarm or shutdown).
Motor blocking protection A blocked motor is detected and protected from thermal overload by a fault shutdown. Monitoring is per-
formed at operating frequencies over 10% of the rated motor frequency.
Power section protection
Earth fault monitoring on output side An earth fault on the output side is detected by a total current monitor and results in shutdown in
earthed-neutral systems.
Electronic short-circuit protection on A short-circuit between motor and converter (on the converter output terminals, in the motor cable, in the
output side terminal box) is detected and shut down.
Thermal overload protection Triggering of the overheating threshold selectively results in a shutdown or automatic influencing of the
control (pulse frequency, output current) so that a reduction in the thermal load is achieved.
Following elimination of the cause of the fault (e.g. improvement in ventilation), the original operating val-
ues are automatically selected again.

1) Factory setting: not activated (parameterizable)

2/6 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Technical data
Electrical data
Supply voltages and output ranges 380 V to 480 V 3 AC, 10% (-15% < 1 min) 110 kW to 560 kW
660 V to 690 V 3 AC , 10% (-15% < 1 min) 75 kW to 800 kW
Types of supplies TN/TT supplies or insulated supplies (IT supplies)
Power frequency 47 Hz to 63 Hz
Output frequency 0 Hz to 83 Hz
Power factor
- Fundamental mode > 0.98 2
- Total 0.93 to 0.96
Converter efficiency > 98%
Control technique Sensorless vector control or V/f control
Fixed speeds 3 fixed speeds plus 1 minimum speed, parameterizable
Skip frequency ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital
12 bit analog
Braking mode Optional via braking unit
Mechanical data
Degree of protection IP20 (higher degree of protection up to IP54 optional)
Protection class According to EN 50 178, Part 1
Type of cooling Forced air cooling
Sound pressure level LpA (1 m) 72 dB at 50 Hz line frequency
Shock protection BGV A2
Cabinet system Rittal TS 8, doors with double-barb lock, three-section base plates for feeding cables through
Paint RAL 7035 (indoor requirements)
Compliance with standards
Standards EN 60 146-1, EN 61 800-2, EN 61 800-3, EN 50 178, EN 60 204-1, EN 60 529
CE marking According to EMC directive No. 89/336/EC and low voltage directive No. 73/23/EC
Electromagnetic compatibility RI suppression filter according to EN 55 011, Class A1, available as option (for TN/TT systems)
RI suppression According to EMC product standard for variable-speed drives EN 61 800-3 (restricted distribution)

Operation Storage Transport


Ambient conditions
Ambient temperature 0 C to +40 C -25 C to +55 C -25 C to +70 C
Up to +50 C see derating data Above -40 C for 24 hours
Relative humidity range 5% to 95% 5% to 95% 5% to 95% at 40 C
(non-condensing)
corresponds to 3K3 acc. to corresponds to 1K4 acc. to corresponds to 2K3 acc. to
IEC 60 721-3-3 IEC 60 721-3-1 IEC 60 721-3-2
Site altitude Up to 2000 m above sea level without derating, see derating data for > 2000 m
Mechanical stability
Vibratory load
- Deflection 0.075 mm at 10 Hz to 58 Hz 1.5 mm at 5 Hz to 9 Hz 3.5 mm at 5 Hz to 9 Hz
- Acceleration 9.8 m/s2 at > 58 Hz to 200 Hz 5 m/s at > 9 Hz to 200 Hz 10 m/s at > 9 Hz to 200 Hz
- corresponds to 1M2 acc. to corresponds to 2M2 acc. to
IEC 60 721-3-1 IEC 60 721-3-2
Shock load
- Acceleration 100 m/s2 at 11 ms 40 m/s2 at 22 ms 100 m/s2 at 11 ms
corresponds to 3M4 acc. to corresponds to 1M2 acc. to corresponds to 2M2 acc. to
IEC 60 721-3-3 IEC 60 721-3-1 IEC 60 721-3-2

Deviations from the specified classes are underlined.

Siemens D 11 Modified January 2004 2/7


SINAMICS G150
Drive converter cabinet units
Versions A and C

Technical data (continued)


Derating data
Compensation of current derating as a function of site altitude /
ambient temperature
If the converters are operated at a site altitude > 2000 m above
sea level, the maximum permissible output current can be cal-
culated using the following tables according to the selected de-
gree of protection for the cabinet unit. The permissible compen-
sation between the site altitude and the ambient temperature
2 has already been taken into account in the defined values.

Site altitude above Current derating


sea level at an ambient temperature of
m
20 C 25 C 30 C 35 C 40 C 45 C 50 C
0-2000 95.0% 90.0%
2001-2500 96.3% 91.4% 86.6%
2501-3000 100% 96.2% 92.5% 87.9% 83.3%
3001-3500 96.7% 92.3% 88.8% 84.3% 79.9%
3501-4000 97.8% 92.7% 88.4% 85.0% 80.8% 76.5%

Current derating as a function of ambient temperature and site altitude for


cabinet units with IP20, IP21 and IP23 degree of protection

Site altitude above Current derating


sea level at an ambient temperature of
m
20 C 25 C 30 C 35 C 40 C 45 C 50 C
0-2000 98% 93% 90% 85% 81%
2001-2500 100% 99% 94% 90% 86% 82% 77%
2501-3000 95% 90% 86% 83% 79% 74%
3001-3500 96% 91% 87% 83% 80% 75% 71%
3501-4000 92% 87% 83% 79% 76% 72% 68%

Current derating as a function of ambient temperature and site altitude for


cabinet units with IP54 degree of protection

Voltage derating as a function of site altitude


In addition to the current derating, the voltage derating must also be considered according to the following table at
site altitudes > 2000 m above sea level
Site altitude above Max. input Voltage derating Max. input Voltage derating
sea level voltage at a rated input voltage of voltage at a rated input voltage
of
m V 380 V 400 V 420 V 440 V 460 V 480 V V 660 V 690 V
0-2000 480 690 100%
2001-2250 461 96% 660 96%
2251-2500 451 98% 94% 648 98% 94%
2501-2750 432 100% 98% 94% 90% 621 95% 90%
2751-3000 422 95% 91% 88% 607 92% 88%
3001-3250 408 97% 93% 89% 85% 586 89% 85%
3251-3500 394 98% 93% 89% 85% 82% 565 85% 82%
3501-3750 380 95% 91% 87% 83% 79% 545 83% 79%
3751-4000 365 96% 92% 87% 83% 80% 76% 524 80% 76%

Voltage derating as a function of site altitude

2/8 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Technical data (continued)


EMC information Earthing
The electromagnetic compatibility according to the definition of The PE conductor must be dimensioned considering the follow-
the EMC directive, describes the ability of a device to function ing data:
satisfactorily in an electromagnetic environment without itself No inadmissible contact voltages must be generated
causing electromagnetic interference which is unacceptable for (< 50 V AC or 120 V DC, EN 50 178 Subsection 5.3.2.2,
other devices in this environment. In order to ensure that the rel- IEC 60 364, IEC 60 543) in the event of an earth fault resulting
evant EMC standards are complied with, the devices must dem- from voltage drops of the earth fault current on the
onstrate a sufficiently high immunity, on the one hand, and inter- PE conductor.
ference emission must be limited to compatible values, on the
other. The product standard EN 61 800-3, relevant to variable-
speed drives describes the requirements for residential and in-
The earth fault current flowing in the PE conductor must not ex-
cessively load the PE conductor.
2
dustrial sectors. If it is possible in the event of a fault to EN 50 178 Subsection
8.3.3.4 that continuous currents may flow via the PE conductor,
Immunity its cross-section must be dimensioned according to this con-
The units satisfy the requirements of the EMC product standard, tinuous current.
EN 61 800-3, for the industrial sector and thus the lower values The cross-section of the PE conductor must be selected accord-
regarding immunity required by the residential sector as well. ing to EN 60 204-1, EN 60 439-1 and IEC 60 364.
Interference emission and RI suppression
Cross-section of outer conduc- Minimum cross-section of
The EMC directive requires that an industrial system as a whole tor external PE conductors
is electromagnetically compatible with its environment. Up to 16 mm2 At least the cross-section of the
The following measures must be provided to limit the interfer- outer conductor
ence emission: 16 mm2 to 35 mm2 16 mm2
RI suppression filters, including line reactors for reduction of Above 35 mm2 At least half the cross-section of
conducted interference the outer conductor
Shielded motor and signal cables to reduce electromagneti- Switchgear and motors are usually earthed with one local earth
cally emitted interference electrode. With this constellation, the earth fault current flows
Compliance with the installation guidelines. via the parallel earth connections and is divided. Despite the
conductor cross-sections used according to the above table,
In systems with SINAMICS G150 drive converter cabinet units
no inadmissible contact voltages occur with this earthing.
and other components such as contactors, switches, evaluation
Experience with different grounding configurations, however,
units, automation units, etc. it must be ensured that no interfer-
shows that it is best to feed the ground wire from the motor di-
ence is emitted to the outside and also that the individual units
rectly to the converter. In the interests of EMC and in order to
do not cause any interference among themselves.
avoid shaft currents, symmetrical motor cables should be used
The most important associated measures are: rather than four-conductor cables. The ground connection
The components of a system must be accommodated in a con- (protective conductor, PE) must be routed separately or ar-
trol cabinet which acts like a Faraday cage. ranged symmetrically in the motor cable. The symmetry of the
PE conductor is achieved with a conductor that surrounds all
Signal and motor cables must be shielded and the shields the phase conductors or a cable in which the three phase con-
must be connected to earth at both ends. ductors and three ground conductors are arranged symmetri-
Signal cables should be spatially separated from power cables cally.
(by at least 200 mm). If necessary, screening plates are to be The fast control of the converters limits the load current (motor
provided. and earth fault currents) to an rms value corresponding to the
Please refer to the product documentation for further measures rated current. For this reason we recommend that the cross-
and details. section of the PE conductor is dimensioned in the same man-
ner as the cross-section of the outer conductor for earthing of
the control cabinet.

Siemens D 11 Modified January 2004 2/9


SINAMICS G150
Drive converter cabinet units
Versions A and C

Selection and Ordering Data


Output Rated Rated Basic Power Cooling Sound SINAMICS G150 SINAMICS G150
(at 400 V (at 460 V, input output load loss air pressure drive converter drive converter
1 2
or 690 V) 60 Hz) current ) current current ) require- level LpA cabinet unit cabinet unit
ment (1 m) at
50/60 Hz Version A Version C
kW hp A A A kW m3/s dB Order No. Order No.

Supply voltage 380 V to 480 V AC


110 150 239 210 205 2.9 0.17 67/68 6SL3710-1GE32-1AA0 6SL3710-1GE32-1CA0
2 132 200 294 260 250 3.8 0.23 69/73 6SL3710-1GE32-6AA0 6SL3710-1GE32-6CA0
160 250 348 310 302 4.4 0.36 69/73 6SL3710-1GE33-1AA0 6SL3710-1GE33-1CA0
200 300 405 380 370 5.3 0.36 69/73 6SL3710-1GE33-8AA0 6SL3710-1GE33-8CA0
250 400 519 490 477 6.4 0.36 69/73 6SL3710-1GE35-0AA0 6SL3710-1GE35-0CA0
315 500 639 605 590 8.2 0.78 70/73 6SL3710-1GE36-1AA0 6SL3710-1GE36-1CA0
400 600 785 745 725 9.6 0.78 70/73 6SL3710-1GE37-5AA0 6SL3710-1GE37-5CA0
450 700 883 840 820 10.1 0.78 70/73 6SL3710-1GE38-4AA0 6SL3710-1GE38-4CA0
560 800 1034 985 960 14.4 1.48 72/75 6SL3710-1GE41-0AA0 6SL3710-1GE41-0CA0

Supply voltage 660 V to 690 V AC


75 103 85 80 1.7 0.17 67/68 6SL3710-1GH28-5AA0 6SL3710-1GH28-5CA0
90 119 100 95 2.1 0.17 67/68 6SL3710-1GH31-0AA0 6SL3710-1GH31-0CA0
110 141 120 115 2.7 0.17 67/68 6SL3710-1GH31-2AA0 6SL3710-1GH31-2CA0
132 174 150 142 2.8 0.17 67/68 6SL3710-1GH31-5AA0 6SL3710-1GH31-5CA0
160 201 175 171 3.8 0.36 69/73 6SL3710-1GH31-8AA0 6SL3710-1GH31-8CA0
200 234 215 208 4.2 0.36 69/73 6SL3710-1GH32-2AA0 6SL3710-1GH32-2CA0
250 280 260 250 5.0 0.36 69/73 6SL3710-1GH32-6AA0 6SL3710-1GH32-6CA0
315 353 330 320 6.1 0.36 69/73 6SL3710-1GH33-3AA0 6SL3710-1GH33-3CA0
400 436 410 400 8.1 0.78 72/75 6SL3710-1GH34-1AA0 6SL3710-1GH34-1CA0
450 493 465 452 9.1 0.78 72/75 6SL3710-1GH34-7AA0 6SL3710-1GH34-7CA0
560 608 575 560 10.8 0.78 72/75 6SL3710-1GH35-8AA0 6SL3710-1GH35-8CA0
710 774 735 710 13.5 1.48 72/75 6SL3710-1GH37-4AA0 6SL3710-1GH37-4CA0
800 852 810 790 14.7 1.48 72/75 6SL3710-1GH38-1AA0 6SL3710-1GH38-1CA0
1) The specified currents include 10 A for external auxiliaries, as
required e.g. for option L19.
2) See Planning information Dimensioning and selection information
Overload capability.

Drive converter version A Drive converter version C

2/10 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Accessories
Output Converter Cable protection fuse Rated Frame Cable protection fuse Rated Frame
(at (at current size to (incl. semiconductor current size to
400 V 460 V, with existing fuse switch DIN protection) without fuse DIN
or 60 Hz) disconnector 43 620-1 switch disconnector 1) 43 620-1
690 V)
kW hp Type 6SL3710 -... Order No. A Order No. A

Supply voltage 380 V to 480 V AC


110 150 -1GE32-1 . A0 3NA3 252 315 2 3NE1 230-2 315 1
132 200 -1GE32-6 . A0 3NA3 254 355 2 3NE1 331-2 350 2 2
160 250 -1GE33-1 . A0 3NA3 365 500 3 3NE1 334-2 500 2
200 300 -1GE33-8 . A0 3NA3 365 500 3 3NE1 334-2 500 2
250 400 -1GE35-0 . A0 3NA3 372 630 3 3NE1 436-2 630 3
315 500 -1GE36-1 . A0 3NA3 475 800 4 3NE1 438-2 800 3
400 600 -1GE37-5 . A0 3NA3 475 800 4 3NE1 448-2 850 3
450 700 -1GE38-4 . A0 Circuit-breaker - - Circuit-breaker - -
560 800 -1GE41-0 . A0 Circuit-breaker - - Circuit-breaker - -

Supply voltage 660 V to 690 V AC


75 -1GH28-5 . A0 3NA3 132-6 125 1 3NE1 022-2 125 00
90 -1GH31-0 . A0 3NA3 132-6 125 1 3NE1 022-2 125 00
110 -1GH31-2 . A0 3NA3 136-6 160 1 3NE1 224-2 160 1
132 -1GH31-5 . A0 3NA3 240-6 200 2 3NE1 225-2 200 1
160 -1GH31-8 . A0 3NA3 244-6 250 2 3NE1 227-2 250 1
200 -1GH32-2 . A0 3NA3 252-6 315 2 3NE1 230-2 315 1
250 -1GH32-6 . A0 3NA3 354-6 355 3 3NE1 331-2 350 2
315 -1GH33-3 . A0 3NA3 365-6 500 3 3NE1 334-2 500 2
400 -1GH34-1 . A0 3NA3 365-6 500 3 3NE1 334-2 500 2
450 -1GH34-7 . A0 3NA3 352-6 2x315 2 3NE1 435-2 560 3
560 -1GH35-8 . A0 3NA3 354-6 2x355 3 3NE1 447-2 670 3
710 -1GH37-4 . A0 3NA3 365-6 2x500 3 3NE1 448-2 850 3
800 -1GH38-1 . A0 Circuit-breaker - - Circuit-breaker - -
1) When drive converter cabinets units (I < 800 A) are used without
option L26, the user must take care for relevant precautions consider-
ing cable and semiconductor protection. For currents up to 800 A we
recommend the use of the combined fuse 3NE1....

Siemens D 11 Modified January 2004 2/11


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options
When ordering a converter with options, the suffix -Z must be Example:
appended to the Order No. followed by the order code(s) for the 6SL3710-1GE32-1CA0-Z
required option(s). +M07+D60+...
See also ordering examples.
Available options Order code with version A with version C
Input options
RI suppression filter Limit Class A1 (TN, TT systems) L00

2 Main contactor (for currents < 800 A)


Without line reactor in output range < 500 kW (available soon)
L13
L22




Line reactor 2% possibly required for P > 500 kW L23
Main control switch incl. fuses or circuit-breaker L26
EMC shield bus 1) (cable connection from below) M70
PE busbar 1) (cable connection from below) M75
Output options
Output filter L08
EMC shield bus 1) (cable connection from below) M70
PE busbar 1) (cable connection from below) M75
Motor protection and safety functions
EMERGENCY STOP button in cabinet door L45
EMERGENCY STOP category 0, 230 V AC or 24 V DC, uncontrolled stop L57
EMERGENCY STOP category 1, 230 V AC , controlled stop 2) L59
EMERGENCY STOP category 1, 24 V DC, controlled stop 2) L60
Thermistor-motor protection device with PTB approval (alarm) L83
Thermistor-motor protection device with PTB approval (shutdown) L84
PT100 evaluation device (for six sensors) L86
Insulation monitoring L87
Additional shock protection M60
Increase in degree of protection
IP21 degree of protection M21
IP23 degree of protection M23
IP54 degree of protection M54

possible
not possible

See the selection matrix for permissible combinations


of options.

1) This option is listed for the input and output options but is only required
once.
2) The shutdown requirements must be observed for this option. Addi-
tional braking units may be required.
Drive converter version A Drive converter version C

2/12 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
Available options Order code with version A with version C
Mechanical options
Plinth 100 mm high, RAL 7022 M06
Cable connection area 200 mm high, RAL 7035 M07
Connection to power supply from the top M13
Motor connection from the top M78
Top-mounted crane transport assembly for cabinets M90
Miscellaneous options 2
Connection for external auxiliary equipment (controlled, max. 10 A) L19
Cabinet illumination with service socket L50
Anti-condensation heating for cabinet L55
Braking unit 100 kW L61
Braking unit 200 kW L62
Special painting of cabinet 3) Y09
Languages
Documentation in English/French D58
Documentation in English/Spanish D60
Documentation in English/Italian D80
Rating plate and operator panel in English/French T58
Rating plate and operator panel in English/Spanish T60
Rating plate and operator panel in English/Italian T80
Converter acceptance inspection in customers presence
Visual inspection F03
Functional test of converter without connected motor F71
Functional test of converter with test bay motor (no load) F75
Converter insulation test F77
Customer-specific converter acceptance inspections (on request) F97

possible
not possible

See the selection matrix for permissible combinations


of options.

3) Option Y.. requires to be specified in plain text.

Drive converter version A Drive converter version C

Siemens D 11 Modified January 2004 2/13


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
Option selection matrix
Certain options can mutually exclude one another.
possible combinations
not possible

Electrical options
2 L00 L08 L13 L19 L22 L23 L26 L45 L50 L55 L57 L59 L60 L61 L62 L83 L84 L86 L87
L00 1)
L08
L13 2) 3) 3) 3)
L19
L22
L23 1)
L26 2) 3) 3) 3)
L45
L50
L55
L57 3) 3)
L59 3) 3)
L60 3) 3)
L61
L62
L83
L84
L86
L87

1) For converters < 500 kW/700 hp, the line reactor (Order code L23) is
included in the scope of supply of the converter.
For converters > 500 kW/700 hp, the option L23 must be ordered sep-
arately, if
the converters are operated on supply systems with a high level of
short-circuit power (RSC > 20) (see planning information) or
where an RI suppression filter is used (option L00).
2) Combination L13/L26 only possible for currents < 800 A.
Circuit-breakers are used above 800 A and provide the same function
as options L13 and L26.
3) Either L13, or with currents > 800 A, L26 (circuit-breaker) required.
Braking units may be necessary depending on the required shutdown
time of the drive.

2/14 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
Mechanical options/electrical options
L00 L08 M06 M07 M13 M21 M23 M54 M60 M70 M75 M78 M90
L00 4)
L08
M06
M07
M13 5) 5)
M21 6) 2
M23
M54
M60 6)
M70 4) 5) 5)
M75 5) 5)
M78 5) 5)
M90

4) Option L00 includes option M70.


possible combinations
5) If the line (option M13) and motor (option M78) are connected from
above, the EMC shield bus and PE busbar are not required in the not possible
lower part of the cabinet.
6) Available for converters in the voltage range from 400 V to 250 kW and
690 V to 315 kW only. Option M60 is already available as standard for
higher power ratings.

Rating plate data


T58 T60 T80
T58
T60
T80

Examples for ordering


Example 1 Example 2
Task: Task:
A drive converter cabinet unit is required to control the fan speed A 280 kW pump for pressure compensation control is to be sup-
for a 380 kW fan drive for connection to an existing 400 V MCC plied via a converter for a completely new district heating pump-
outgoing circuit. The rated speed of the fan is 975 rpm. As a re- ing station. A 690 V power supply is available. The site altitude
sult of the ambient conditions, the converter should be installed is 350 m above sea level and the ambient temperature is 40 C.
on a 100 mm plinth and designed to the IP54 degree of protec- The rated speed of the pump is 740 rpm. The pump unit, com-
tion. The site altitude is < 1000 m and the ambient temperature plete with motor, is located in an unmanned substation, so the
is 45 C. winding temperature of the motor is to be monitored by a PT100
resistance thermometer and evaluated by the converter. The
Solution: color of the converter cabinet is to be RAL 3002.
Due to the existing MCC outgoing circuit, the power supply con-
nection components such as the main control switch, main con- Solution:
tactor and line fuses can be omitted and the space-saving Select a drive converter cabinet unit 315 kW, 690 V in Version A
version C can be selected. For this constellation, taking into ac- with the following options:
count the derating factors for IP54 degree of protection and for L26 (main control switch including fuses),
the increased ambient temperature, select a drive converter L13 (main contactor),
cabinet unit 450 kW, 400 V with the options L86 (PT100 evaluation unit) and
M06 (cabinet plinth 100 mm) and Y09 (special cabinet paint finish).
M54 (IP54 degree of protection).
The Order No. is therefore:
The Order No. is therefore: 6SL3710-1GH33-3AA0-Z
6SL3710-1GE38-4CA0-Z +L26 +L13 +L86 +Y09
+M06 +M54 cabinet color RAL 3002

Siemens D 11 Modified January 2004 2/15


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
Description of options L22
Without line reactor
L00
RI suppression filter Limit Class A1 (TN, TT systems) If the converter is powered via a separate transformer, or if the
ratio between the line short-circuit power at the connection point
RI suppression filters to EN 55 011, Limit Class A1 (industrial and the rated converter power is low, the line reactor supplied as
networks) are available for earthed networks for the complete standard with converters < 500 kW can be omitted (see plan-
power range of the converters. The RI suppression filters, to- ning information). When an RI suppression filter (option L00) is
gether with the line reactor, reduce the RI voltage on the con- used, however, the line reactor is necessary.
verter. With converter outputs > 500 kW, the option L23 must be
2 ordered separately. L23
Line reactor uK = 2%
To allow the EMC shield of the power cables to be connected in
conformance with EMC regulations, an EMC shield bus (option The line reactor is supplied as standard in converters up to
M70) is factory fitted at the converter input and output. A sepa- 500 kW. For converters of > 500 kW, the line reactor (uK = 2%) is
rate order is not required in this case. available as an option, because converters in this output range
are often connected to a medium-voltage system via transform-
L08 ers matched to the converter output.
Output filter
L26
An output filter reduces the voltage load of the motor winding by Main control switch incl. fuses or circuit-breaker
reducing the voltage slopes at the motor terminals which are
caused by converter operation. At the same time, the capacitive Up to 800 A, a switch disconnector with externally mounted
charge-reversal currents are reduced which cause additional fuses is available as the main control switch. With currents above
loading on the converter output when long motor cables are 800 A, a circuit-breaker is used instead of the switch-disconnec-
used. tor. The circuit-breaker is activated and supplied within the con-
verter.
Provided that the permitted cable types are used and the maxi-
mum cable lengths are observed, the voltage limits permitted for Terminal Meaning
Siemens motors will be complied with (see Planning information, -X50:
Table Maximum cable lengths with and without output filter). 1 Checkback contact (NO contact)
main control switch/circuit-breaker closed
L13
Main contactor (for currents <800 A) 2 Checkback contact (NC contact)
main control switch/circuit-breaker closed
The SINAMICS G150 drive converter cabinet units are designed
as standard without a line contactor. Option L13 is needed if a 3 Root
switching element is required to disconnect from the supply L45
(necessary with EMERGENCY STOP). The contactor is activated EMERGENCY STOP button
and supplied within the converter.
The EMERGENCY STOP button with protective collar is fitted in
Terminal Meaning
-X50: the door of the drive converter cabinet unit and its contacts are
connected to a terminal block. In combination with options L57,
4 Checkback contact (NO contact), contactor closed L59 and L60, the EMERGENCY STOP functions of Category 0 or
5 Checkback contact (NC contact), contactor closed 1 can be activated.
6 Root Terminal Meaning
-X120:
L19 1 Checkback contact from EMERGENCY STOP button in
Connection for external auxiliary equipment cabinet door
A switched outgoing circuit fused at max. 10 A for external aux- 2 Checkback contact from EMERGENCY STOP button in
iliary equipment (e.g. separately driven fan for motor). cabinet door
The voltage is tapped at the converter input, and therefore has 3 Checkback contact from EMERGENCY STOP button in
the same level as the connection voltage. cabinet door *)
4 Checkback contact from EMERGENCY STOP button in
The outgoing circuit can be controlled internally by the converter cabinet door *)
or externally.
Terminal Meaning Range *) Factory setting in converter with options L57 to L60
-X155:
L50
1 L1 380 V to 690 V AC Cabinet illumination with service socket
2 L2 380 V to 690 V AC A universal lamp with integral service socket is fitted per cabinet
3 L3 380 V to 690 V AC element.
11 Contactor control 230 V AC The power supply (on terminal block -X390) for the cabinet illu-
mination with socket must be provided externally and fused at
12 Contactor control 230 V AC
max. 10 A. The cabinet illumination can be switched on manually
13 Checkback from circuit-breaker 230 V AC/0.5 A; or automatically using an integral motion detector. The mode is
24 V DC/2 A switch-selected.
14 Checkback from circuit-breaker 230 V AC/0.5 A; Terminal Meaning
24 V DC/2 A -X390:
15 Checkback from contactor 230 V AC/6 A 1 L1 (230 V AC)
16 Checkback from contactor 230 V AC/6 A 2 N
PE PE 3 PE

2/16 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
L55
Terminal Meaning
Anti-condensation heating for cabinet -X120:
The anti-condensation heating is recommended for low ambient 7 Looping in of the EMERGENCY STOP button from the sys-
temperatures and high humidity to prevent the generation of tem side; remove jumper 7-8!
condensation. A 100 W cabinet heater is fitted per cabinet ele-
8 Looping in of the EMERGENCY STOP button from the sys-
ment (two heaters are fitted per element with widths from tem side; remove jumper 7-8!
800 mm to 1200 mm).
15 On for manual start; remove jumper 15-16!
The power supply for the anti-condensation heating (110 V to
230 V AC, terminal block -X240) must be provided externally
and be fused at max. 16 A.
16
17
On for manual start; remove jumper 15-16!
Checkback Triggering of safety combination
2
Terminal Meaning 18 Checkback Triggering of safety combination
-X240:
L60
1 L1 (110 V to 230 V AC)
EMERGENCY STOP category 1 (24 V DC)
2 N
EMERGENCY STOP category 1 for uncontrolled stop according
3 PE to EN 60 204.
L57 The function comprises rapid shutdown of the drive via fast stop
EMERGENCY STOP category 0 (230 V AC or 24 V DC) using a deceleration ramp to be parameterized by the user. Dis-
connection of the voltage is subsequently performed as de-
EMERGENCY STOP category 0 for uncontrolled stop according scribed above for EMERGENCY STOP category 0.
to EN 60 204.
It may be necessary to use a braking unit to achieve the required
The function comprises disconnection of the converter voltage shutdown times.
via the line contactor with bypassing of the electronics using a
safety combination according to EN 60 204-1. The motor then Important: Option L60 can only be used if the converter can be
coasts down. On delivery, the button circuit is preset for electrically separated from the mains, that is, option L13 for con-
230 V AC. Jumpers must be reset for use with 24 V DC. verter currents of 800 A and option L26 for converter currents
of > 800 A.
Important: Option L57 can only be used if the converter can be
electrically separated from the mains, that is, option L13 for con- Terminal Meaning
verter currents of 800 A and option L26 for converter currents -X120:
of > 800 A. 7 Looping in of the EMERGENCY STOP button from the sys-
Terminal Meaning tem side; remove jumper 7-8!
-X120: 8 Looping in of the EMERGENCY STOP button from the sys-
7 Looping in of the EMERGENCY STOP button from the sys- tem side; remove jumper 7-8!
tem side; remove jumper 7-8! 15 On for manual start; remove jumper 15-16!
8 Looping in of the EMERGENCY STOP button from the sys- 16 On for manual start; remove jumper 15-16!
tem side; remove jumper 7-8!
17 Checkback Triggering of safety combination
15 On for monitored start; remove jumper 15-16!
18 Checkback Triggering of safety combination
16 On for monitored start; remove jumper 15-16!
17 Checkback Triggering of safety combination L61, L62
Braking units
18 Checkback Triggering of safety combination
It may be necessary to use braking units on drives which are ca-
L59 pable of regenerative operation.
EMERGENCY STOP category 1 (230 V AC)
The braking unit consists of two devices: A braking chopper in-
EMERGENCY STOP category 1 for uncontrolled stop according stalled in the converter cabinet and an external braking resistor
to EN 60 204. (IP20 degree of protection). The braking unit functions as an au-
tonomous unit and does not require an external power supply.
The function comprises rapid shutdown of the drive via fast stop The kinetic energy is converted into heat in an externally located
using a deceleration ramp to be parameterized by the user. Dis- braking resistor during the deceleration process. A maximum
connection of the voltage is subsequently performed as de- cable length of 50 m is permissible between the braking chop-
scribed above for EMERGENCY STOP category 0. per and the braking resistor. In this manner, it is possible to dis-
It may be necessary to use a braking unit to achieve the required sipate the heat outside the converter location.
shutdown times. L61: Braking unit P20 = 100 kW
Important: Option L59 can only be used if the converter can be L62: Braking unit P20 = 200 kW
electrically separated from the mains, that is, option L13 for con- P 20: Maximum output for a duration of 20 s, cyclic time 90 s
verter currents of 800 A and option L26 for converter currents If higher braking powers are required along with the braking
of > 800 A. units specified here, braking units can be connected in parallel
for higher converter ratings. A braking chopper is assigned to
each braking resistor. Configurations for connecting braking
units in parallel available on request.

Siemens D 11 Modified January 2004 2/17


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
L83 L87
Thermistor motor protection device (alarm) Insulation monitoring
Thermistor motor protection unit (with PTB approval) for PTC An insulation monitor is required if the converter is operated on
thermistor sensors (PTC resistor type A) for alarm. The power an isolated-neutral system. The unit monitors the complete elec-
supply for the thermistor motor protection unit and the evaluation trically connected circuit for insulation faults.
are provided within the converter.
An alarm is output in the event of a fault.
Terminal Meaning
-F127: Important: Only one insulation monitor must be used within an
electrically connected circuit.
2 T1 Connection of sensor loop
The response concept in the event of an earth fault in the iso-
T2 Connection of sensor loop
lated-neutral system can vary, so output relays are available for
L84 linking to a system-side control. It is also possible, however, to
Thermistor motor protection unit (shutdown) link the outputs on the system-side into the converter monitoring.
Thermistor motor protection unit (with PTB approval) for PTC Terminal Meaning
-A1-A101:
thermistor sensors (PTC resistor type A) for shutdown. The
power supply for the thermistor motor protection unit and the 11 Alarm relay ALARM 1
evaluation are provided within the converter. 12 Alarm relay ALARM 1
Terminal Meaning 14 Alarm relay ALARM 1
-F125:
21 Alarm relay ALARM 2
T1 Connection of sensor loop
22 Alarm relay ALARM 2
T2 Connection of sensor loop
24 Alarm relay ALARM 2
L86 M+ External kW display 0 A to 400 A
PT100 evaluation unit
M- External kW display 0 A to 400 A
The PT100 evaluation unit can monitor up to 6 sensors. They can
be connected in a two-wire or three-wire system. The limits can R1 External reset key (NC contact or wire jumper, otherwise
the fault code is not stored)
be freely selected for each channel.
R2 External reset key (NC contact or wire jumper)
In the factory setting, the channels are divided into two groups
of three channels. With motors, it is therefore possible to monitor T1 External test button
three PT100s in the stator winding and two PT100s in the motor T2 External test button
bearings. Unused channels can be suppressed using appropri-
ate parameter settings. M06
Pinth 100 mm high, RAL 7022
The output relays are integrated into the internal fault and shut-
down sequence of the converter. The signals can also be picked The additional cabinet plinth permits larger bending radii for ca-
up by the customer via two spare fault signalling relays. Also bles (cable inlet from below) or routing of cables within the plinth.
available are two freely-programmable analog outputs (0/4 mA
The plinth is always painted in RAL 7022. Special painting of the
to 20 mA or 0/2 V to 10 V) for incorporation into a higher-level
plinth is not possible. The plinth is delivered completely assem-
control.
bled with the cabinet. The height of the operator panel is
Terminal Meaning changed accordingly.
-A1-A140:
M07
T11 to T13 PT100; sensor 1; group 1 Sensors can be con- Cable connection area 200 mm high, RAL 7035
nected to the PT100
T21 to T23 PT100; sensor 2; group 1 evaluation unit using The cable connection area is of a rigid sheet-steel construction
two-wire or three-wire and increases the flexibility for cable inlet (from below) or per-
techniques. mits cable routing within the cable connection area. The plinth is
T31 to T33 PT100; sensor 3; group 1
With a two-wire tech- delivered completely assembled with the cabinet. The height of
T41 to T43 PT100; sensor 1; group 2 nique, inputs Tx1 and the operator panel is changed accordingly.
Tx3 must be used. With
T51 to T53 PT100; sensor 2; group 2
a three-wire technique, Important: The cable connection area is always painted in
input Tx2 must be con- RAL 7035. If special painting is required for the cabinet (Order
nected in addition code Y09), the cable connection area is also in this special
T61 to T63 PT100; sensor 3, group 2 (x = 1, 2, ..., 6) painting.
51/52/54 Relay output
Limit group 1 reached; (changeover contact)
61/62/64 Relay output
Limit group 2 reached; (changeover contact)
Ground (OUT 1) Analog output OUT 1; sensor group 1
U1 (OUT 1) Analog output OUT 1; sensor group 1
I1 (OUT 1) Analog output OUT 1; sensor group 1
Ground (OUT 2) Analog output OUT 2; sensor group 2
U2 (OUT 2) Analog output OUT 2; sensor group 2
I2 (OUT 2) Analog output OUT 2; sensor group 2

2/18 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
M13 M54
Line connection from above IP54 degree of protection
For the line connection from above, the control cabinet is fitted Drive converter cabinets to the IP54 degree of protection are
with an additional hood. The connection straps for the power ca- supplied with additional hoods as well as plastic ventilation
bles, the clamping bar for mechanically securing the cables, an grilles and a filter medium for the air inlet and outlet. The cabinet
EMC shield bus, and a PE busbar are located within the hood. height is increased by 400 mm. The covers used with the option
M60 are included in the scope of supply. They are standard
The hood adds an extra 405 mm to the cabinet height. The bus- components of the air guides within the cabinet and are adapted
bars for connection from above are fully mounted when the sys- accordingly. Maintenance of the filters should be performed in
tem is delivered. To facilitate transport, the hoods are delivered
separately and must be mounted on site. A crane transport as-
accordance with the ambient conditions. 2
sembly (option M90) can also be used. This must be removed For transport reasons, the hoods are delivered separately and
on site, however, so that the hoods can be attached. Note that must be fitted on site.
rope spreaders are used if the lifting eyes are low down.
Important: The derating factors for the output current must be
A 5 mm aluminum mounting plate (with no holes) is fitted in the observed in the case of the IP54 degree of protection.
roof of the cover for feeding in the cables. Depending on the
number of cables and the cross-sections used, holes for attach- Important: The hoods are painted as standard in RAL 7035. If a
ing cable glands for feeding in the cables must be drilled in this special color is specified for the cabinet (Order code Y09), the
mounting plate on site. hoods are also to be painted in this special color. The molded
plastic components (e.g. ventilation grilles) are in RAL 7035 and
The hoods have degree of protection IP21. Plastic ventilation cannot be painted.
grilles and filter mats are also supplied with options M23 and
M54. M60
Additional shock protection
The hoods are painted in RAL 7035 as standard. If the cabinet is
painted in a special color (code Y09), the hoods are also painted The drive converter cabinet units are designed according to
in this special color. Ventilation grilles used with degrees of pro- BGV A2 as standard. The option M60 provides additional covers
tection IP23 and IP54 are available in RAL 7035 and cannot be (beyond arms reach) in the area of the AC bars and over the
painted. power section (can only be chosen as an option for converters
of max. 250 kW in the 400 V range and for converters of max.
The covers used with the option M60 are included in the scope 315 kW in the 690 V range with degrees of protection IP20 and
of supply. They are standard components of the air guides within IP21; otherwise available as standard).
the cabinet and are adapted accordingly.
M70
Note: The control cables are connected as before from below. EMC shield bus (cable connection from below)
The standard line connection from below is not available with op-
tion M13. Shielded power cables for mains supply or motor infeed are at-
tached to the EMC shield bus. The option L00 (RI suppression
M21 filter) already includes the EMC shield bus as standard.
IP21 degree of protection
M75
Cabinet version to IP20, but with additional roof and canopy. The PE busbar (cable connection from below)
cabinet height is increased by 250 mm.
The protective conductors for mains supply or motor infeed are
For transport reasons, the roof and canopy are delivered sepa- attached to the PE busbar.
rately and must be fitted on site.
It can be ordered as an option for converters of low power and
Important: The top covers and canopies are painted in currents I < 700 A. The PE busbar is fitted as standard for output
RAL 7035 as standard. If the cabinet is painted in a special color currents I > 700 A or with cabinet groups consisting of several
(code Y09), the hoods and canopies are also painted in this spe- elements.
cial color.
M23
IP23 degree of protection
Drive converter cabinet units to the IP23 degree of protection are
supplied with additional hoods as well as plastic ventilation
grilles for the air inlet and outlet. The cabinet height is increased
by 400 mm. The covers used with the option M60 are included
in the scope of supply. They are standard components of the air
guides within the cabinet and are adapted accordingly.
For transport reasons, the hoods are delivered separately and
must be fitted on site.
Important: The hoods are painted as standard in RAL 7035. If a
special color is specified for the cabinet (Order code Y09), the
hoods are also to be painted in this special color. The molded
plastic components (e.g. ventilation grilles) are in RAL 7035 and
cannot be painted.

Siemens D 11 Modified January 2004 2/19


SINAMICS G150
Drive converter cabinet units
Versions A and C

Options (continued)
M78 F03, F71, F75, F77, F97
Motor connection from above Converter acceptance inspections in customers presence
To connect the motor from above, the control cabinet is fitted Code Description
with an additional hood. The connection straps for the power ca- F03 Visual The tests are carried out when the converter
bles, the clamping bar for mechanically securing the cables, an inspection is de-energized.
EMC shield bus, and a PE busbar are located within the hood. The inspection involves the following tasks:
The hood adds an extra 405 mm to the cabinet height. The bus- Checking the degree of protection
bars for connection from above are fully mounted when the sys- Checking the equipment (components)
2 tem is delivered. To facilitate transport, the hoods are delivered
separately and must be mounted on site. A crane transport as- Checking the equipment identifiers
sembly (option M90) can also be used. This must be removed Checking the clearance and creepage dis-
on site, however, so that the hoods can be attached. Note that tances
rope spreaders are used if the lifting eyes are low down. Checking the cables
Checking the customer documentation
A 5 mm aluminum mounting plate (with no holes) is fitted in the
roof of the cover for feeding in the cables. Depending on the Submitting the acceptance report
number of cables and the cross-sections used, holes for attach- F71 Functional After the converter has been visually
ing cable glands for feeding in the cables must be drilled in this test of inspected while de-energized, the rated volt-
mounting plate on site. converter age is applied. No current flows from the
without converter output.
The hoods have degree of protection IP21. Plastic ventilation con- The inspection involves the following tasks:
grilles and filter mats are also supplied with options M23 and nected
M54. motor Visual inspection (see option F03)
Checking the power supply
The hoods are painted in RAL 7035 as standard. If the cabinet is
painted in a special color (code Y09), the hoods are also painted Checking the protection and monitoring de-
vices (simulation)
in this special color. Ventilation grilles used with degrees of pro-
tection IP23 and IP54 are available in RAL 7035 and cannot be Checking the ventilators
painted. Testing the pre-charging function
The covers used with the option M60 are included in the scope Functional test without connected motor
of supply. They are standard components of the air guides within Submitting the acceptance report
the cabinet and are adapted accordingly. F75 Functional The inspection involves the following tasks:
Note: The control cables are connected as before from below. test of Visual inspection (see option F03)
converter
The standard motor connection from below is not available with with test Checking the power supply
option M78. bay motor Checking the protection and monitoring de-
(no load) vices (simulation)
M90
Top-mounted crane transport assembly for cabinets Checking the ventilators
Testing the pre-charging function
Single cabinets with a width of up to 600 mm have transport eye-
bolts. Transport rails are used for cabinet widths of 800 mm or Functional test with test bay motor (no load)
more. Submitting the acceptance report

Y09 After the converter has been visually


Special cabinet paint finish inspected while de-energized, the
rated voltage is applied. Low-level
The converter cabinet units are supplied in RAL 7035 as stan- current flows from the converter out-
dard. If you require a special color, please specify this in plain put to operate the test bay motor (no
text when you order. You can choose any RAL colors that are load).
available as powder paints. If options such as a cable wiring
compartment (code M07), top covers and canopies (code M21), F77 Converter The inspection involves the following tasks:
insulation High-voltage test
hoods (codes M23/M54), or a cable connection from above test
(codes M13/M78) are required for the converter cabinet units, Measuring the insulation resistance
these are supplied in the same color as the cabinet ordered.
F97 Customer- If converter acceptance inspections are
Plastic components (e.g. ventilation grilles) are available in specific required that are not covered by options F03,
RAL 7035 and cannot be painted. converter F71, F75, or F77, customer-specific accep-
accep- tance inspections/additional tests (code F97)
tance can be ordered on request and after techni-
inspec- cal clarification.
tions (on
request)

2/20 Siemens D 11 Modified January 2004


Dimensional drawings

3/2 Drive converter cabinet units


Version A

3/7 Drive vonverter cabinet units


Version C

3/10 Mechanical connection data

Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Version A

Dimensional drawings
380 V to 480 V, 110 kW to 160 kW
660 V to 690 V, 75 kW to 315 kW

2 4 0 0 1 Minimum ceiling height for


wall installation
< M 2 3 >
< M 5 4 >
2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0
area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
< L 2 6 >
IP21 Option M21
IP23 Option M23
1 0 0 0 6
IP54 Option M54
10 Transport unit

3 7 7 Options ar shown in gray

U 1 V 1 W 1 U 2 V 2 W 2
L 1 L 2 L 3 T 1 T 2 T 3
2 5

< M 7 5 >

0
< M 0 6 >
-1 0 0
< M 0 7 >
-2 0 0
G _ D 0 1 1 _ x x _ 0 0 0 0 1

1 0
8 0 6
7 9 7
6 7 5 1 6
1 8

6 4 0
6 0 5

4 4 0

4 7 5
1 3 0

5
8 0
8 0

8 7
1 5

3 5

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

3/2 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Version A

Dimensional drawings (continued)


380 V to 480 V, 200 kW to 250 kW
2 4 0 0 1 Minimum ceiling height for
wall installation
< M 2 3 >
< M 5 4 > 2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0 area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
< L 2 6 > IP21 Option M21
6
IP23 Option M23
1 0 0 0
IP54 Option M54
10 Transport unit

7 7
Options ar shown in gray

U 1 V 1 W 1 U 2 V 2 W 2
3
L 1 L 2 L 3 T 1 T 2 T 3

P E < M 7 5 > P E

0
< M 0 6 >
-1 0 0
< M 0 7 >
2 5

-2 0 0 G _ D 0 1 1 _ x x _ 0 0 0 0 2

1 0
1 0 0 6
9 9 7
8 7 5 1 6
1 8

4 0 0 4 0 0
4 4 0

4 7 5
6 0 5

1 3 0

5 5
8 0
8 0

1 5

3 5
8 7

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

Siemens D 11 Modified January 2004 3/3


SINAMICS G150
Drive converter cabinet units
Version A

Dimensional drawings (continued)


380 V to 480 V, 315 kW
660 V to 690 V, 400 kW to 560 kW
2 4 0 0 1 Minimum ceiling height for
wall installation
< M 2 3 >
< M 5 4 >
2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0 area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
< L 2 6 > IP21 Option M21
6
IP23 Option M23
1 0 0 0
IP54 Option M54
10 Transport unit

3 7 7
Options ar shown in gray

U 1 V 1 W 1 U 2 V 2 W 2
L 1 L 2 L 3 T 1 T 2 T 3
2 5

P E < M 7 5 > P E P E < M 7 5 > P E

0
< M 0 6 >
-1 0 0
< M 0 7 >
-2 0 0 G _ D 0 1 1 _ x x _ 0 0 0 0 3 a

1 0
1 2 0 6
1 1 9 7
1 0 7 5 1 6
1 8

5 0 0 5 0 0
6 0 5

4 4 0

4 7 5
1 3 0

5 5
8 0
8 0

1 5

3 5
8 7

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

3/4 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Version A

Dimensional drawings (continued)


380 V to 480 V, 400 kW to 450 kW
2 4 0 0 1 Minimum ceiling height for
wall installation
< M 2 3 >
< M 5 4 > 2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0
area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
< L 2 6 > IP21 Option M21
6
IP23 Option M23
1 0 0 0
IP54 Option M54
10 Transport unit
U 1 V 1 W 1
L 1 L 2 L 3
7
Options ar shown in gray
7

U 2 V 2 W 2
3
T 1 T 2 T 3
2 5

P E P E P E P E

0
< M 0 6 >
-1 0 0
< M 0 7 >
-2 0 0
G _ D 0 1 1 _ x x _ 0 0 0 0 4 b

1 0
1 2 0 6
1 1 9 7
4 7 5 4 7 5 1 6
1 8

4 4 0 4 4 0
6 0 5
4 4 0

4 7 5
1 3 0

5 5
8 0
8 0

1 5

3 5
8 7

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

Siemens D 11 Modified January 2004 3/5


SINAMICS G150
Drive converter cabinet units
Version A

Dimensional drawings (continued)


380 V to 480 V, 560 kW
660 V to 690 V, 710 kW to 800 kW
2 4 0 0 1 Minimum ceiling height for
wall installation
< M 2 3 >
< M 5 4 > 2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0 area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
IP21 Option M21
< L 2 6 >
IP23 Option M23
1 0 0 0 6
IP54 Option M54
7 10 Transport unit
U 1 V 1 W 1

3 L 1 L 2 L 3
7
Options ar shown in gray

U 2 V 2 W 2
T 1 T 2 T 3
2 5

P E P E P E P E

0
< M 0 6 >
-1 0 0
< M 0 7 >
-2 0 0
G _ D 0 1 1 _ x x _ 0 0 0 5 b

1 0
1 6 0 6
1 5 9 7
4 7 5 8 7 5 1 6
1 8

4 4 0 4 0 0 4 0 0
4 4 0

4 7 5
6 0 5

1 3 0

5 5 5
8 0
8 0

8 7
1 5

3 5

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

3/6 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Version C

Dimensional drawings (continued)


380 V to 480 V, 110 kW to 250 kW
660 V to 690 V, 75 kW to 315 kW
2 4 0 0 1 Minimum ceiling height for
wall installation
< M 2 3 >
< M 5 4 >
2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0 area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
IP21 Option M21
IP23 Option M23
IP54 Option M54
10 Transport unit
7
U 2 V 2 W 2
Options ar shown in gray
3
U 1 V 1 W 1
< M 7 5 > L 1 L 1 L 1
P E P E
2 5

0
< M 0 6 >
-1 0 0
< M 0 7 >
-2 0 0 G _ D 0 1 1 _ x x _ 0 0 0 0 6

1 0
4 0 6
3 9 7
2 7 5 1 6
1 8

2 4 0
6 0 5
4 4 0

4 7 5
1 3 0

5
8 0
8 0

1 5

3 5

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

Siemens D 11 Modified January 2004 3/7


SINAMICS G150
Drive converter cabinet units
Version C

Dimensional drawings (continued)


380 V to 480 V, 315 kW to 450 kW
660 V to 690 V, 400 kW to 560 kW
2 4 0 0
1 Minimum ceiling height for
wall installation
< M 2 3 > < M 2 3 > 2 Ventilation grille
< M 5 4 > < M 5 4 >
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
area
1 6 5 0
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
IP21 Option M21
IP23 Option M23
IP54 Option M54
10 Transport unit

Options ar shown in gray


3
7 7
U 1 V 1 W 1 U 2 V 2 W 2 U 1 V 1 W 1 U 2 V 2 W 2
L 1 L 2 L 3 T 1 T 2 T 3 L 1 L 2 L 3 T 1 T 2 T 3
2 5

P E < M 7 5 > P E P E P E
0
< M 0 6 > < M 0 6 >
-1 0 0
< M 0 7 > < M 0 7 >
-2 0 0 G _ D 0 1 1 _ e n _ 0 0 0 0 7 c

3 1 5 k W (3 8 0 - 4 8 0 V ) 4 0 0 k W a n d
4 0 0 k W to 5 6 0 k W 4 5 0 k W
(6 6 0 - 6 9 0 V ) (3 8 0 - 4 8 0 V )
1 0
6 0 6
5 9 7
4 7 5 1 6
1 8

4 4 0
6 0 5
4 4 0

4 7 5
1 3 0

5
8 0
8 0

1 5

3 5

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

3/8 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Version C

Dimensional drawings (continued)


380 V to 480 V, 560 kW
660 V to 690 V, 710 kW to 800 kW
2 4 0 0 1 Minimum ceiling height for
wall installation
< M 2 3 >
< M 5 4 >
2 Ventilation grille
3 Air outlet area
2 0 0 5
4 Air inlet area
5 Cable inlet from below
possible within the shaded
1 6 5 0
area
7 Power connection
8 Option, degree of protection
9 Degree of protection
IP20
IP21 Option M21
IP23 Option M23
IP54 Option M54
10 Transport unit

Options ar shown in gray


7 7 3
U 1 V 1 W 1 U 2 V 2 W 2
L 1 L 2 L 3 T 1 T 2 T 3
P E P E

0
< M 0 6 >
-1 0 0
< M 0 7 >
2 5

-2 0 0 G _ D 0 1 1 _ x x _ 0 0 0 2 0 b

1 0
1 0 0 6
9 9 7
8 7 5 1 6
1 8

4 0 0 4 0 0
4 7 5
4 4 0
6 0 5

1 3 0

5 5
8 0
8 0

1 5

3 5

Degree of protection:

1 1 2 6 5 0
2 3 5 0 2 3 5 0 2
3 3
3 3
3 3 3 3
2 2 5 0

2
G _ D 0 1 1 _ x x _ 0 0 0 4 0

4 4 4

8 < M 2 1 > 8 < M 2 3 > < M 5 4 >


9 IP 2 0 9 IP 2 1 9 IP 2 3 /5 4

Siemens D 11 Modified January 2004 3/9


SINAMICS G150
Drive converter cabinet units
Connections

Mechanical connection data


The following table lists the recommended or maximum permis- If the conditions are different (cable routing, bundling of cables,
sible supply system and motor cable connections. ambient temperature), please observe the planning information
for cable routing.
The recommended cross-sections are based on the listed fuses
and with single routing of the three-core cable at an ambient
temperature of 40 C.
Out- Converter Weight Power supply connection Motor connection Cabinet earthing
put
(stan- Recommended Max. conductor Mounting Recommended Max. conductor Mounting Mounting Remarks
dard cross-section cross-section screw cross-section cross-section screw screw
ver-
sion) M12 M12 M12
kW Type kg DIN AWG/ DIN AWG/ (No. of DIN AWG/ DIN AWG/ (No. of (No. of
DE MCM VDE MCM holes) VDE MCM VDE MCM holes) holes)
6SL3710 - ... mm2 mm2 mm2 mm2
Version A, 380 V to 480 V
110 -1GE32-1AA0 320 2x70 2x(000) 4x240 4x600 (2) 2x70 2x(000) 2x150 2x(400) (2) (2)
132 -1GE32-6AA0 320 2x95 2x(4/0) 4x240 4x600 (2) 2x95 2x(4/0) 2x150 2x(400) (2) (2)
160 -1GE33-1AA0 390 2x120 2x(300) 4x240 4x600 (2) 2x120 2x(300) 2x150 2x(400) (2) (2)
200 -1GE33-8AA0 480 2x120 2x(300) 4x240 4x600 (2) 2x120 2x(300) 2x150 2x(400) (2) (2)
250 -1GE35-0AA0 480 2x185 2x(500) 4x240 4x600 (2) 2x185 2x(500) 2x240 2x(600) (2) (2)
315 -1GE36-1AA0 860 2x240 2x(600) 4x240 4x600 (2) 2x240 2x(600) 4x240 4x(600) (2) (2)
3 400
450
-1GE37-5AA0 865
-1GE38-4AA0 1075
2x300
4x150
2x(800)
4x(400)
4x240
8x240
4x600
8x600
(2)
(4)
2x300
4x150
2x(800)
4x(400)
4x240
4x240
4x(600)
4x(600)
(2)
(2)
(10)
(16)
Cu rail
Cu rail
560 -1GE41-0AA0 1360 4x185 4x(500) 8x240 8x600 (4) 4x185 4x(500) 6x240 6x(600) (3) (18) Cu rail
Version A, 660 V to 690 V
75 -1GH28-5AA0 320 50 (00) 4x240 4x600 (2) 50 (00) 2x70 2x(000) (2) (2)
90 -1GH31-0AA0 320 50 (00) 4x240 4x600 (2) 50 (00) 2x150 2x(400) (2) (2)
110 -1GH31-2AA0 320 70 (000) 4x240 4x600 (2) 70 (000) 2x150 2x(400) (2) (2)
132 -1GH31-5AA0 320 95 (4/0) 4x240 4x600 (2) 95 (4/0) 2x150 2x(400) (2) (2)
160 -1GH31-8AA0 390 120 (300) 4x240 4x600 (2) 120 (300) 2x150 2x(400) (2) (2)
200 -1GH32-2AA0 390 2x70 2x(000) 4x240 4x600 (2) 2x70 2x(000) 2x150 2x(400) (2) (2)
250 -1GH32-6AA0 390 2x95 2x(4/0) 4x240 4x600 (2) 2x95 2x(4/0) 2x185 2x(500) (2) (2)
315 -1GH33-3AA0 390 2x120 2x(300) 4x240 4x600 (2) 2x120 2x(300) 2x240 2x(600) (2) (2)
400 -1GH34-1AA0 860 2x185 2x(500) 4x240 4x600 (2) 2x185 2x(500) 4x240 4x600 (2) (2)
450 -1GH34-7AA0 860 2x185 2x(500) 4x240 4x600 (2) 2x185 2x(500) 4x240 4x600 (2) (2)
560 -1GH35-8AA0 860 2x240 2x(600) 4x240 4x600 (2) 2x240 2x(600) 4x240 4x600 (2) (2)
710 -1GH37-4AA0 1320 3x185 3x(500) 8x240 8x600 (4) 3x185 3x(500) 6x240 6x600 (3) (18) Cu rail
800 -1GH38-1AA0 1360 4x150 4x(400) 8x240 8x600 (4) 4x150 4x(400) 6x240 6x600 (3) (18) Cu rail
Version C, 380 V to 480 V
110 -1GE32-1CA0 225 2x70 2x(000) 2x240 2x600 (1) 2x70 2x(000) 2x150 2x(400) (1) (2)
132 -1GE32-6CA0 225 2x95 2x(4/0) 2x240 2x600 (1) 2x95 2x(4/0) 2x150 2x(400) (1) (2)
160 -1GE33-1CA0 300 2x120 2x(300) 2x240 2x600 (1) 2x120 2x(300) 2x150 2x(400) (1) (2)
200 -1GE33-8CA0 300 2x120 2x(300) 2x240 2x600 (1) 2x120 2x(300) 2x150 2x(400) (1) (2)
250 -1GE35-0CA0 300 2x185 2x(500) 2x240 2x600 (1) 2x185 2x(500) 2x240 2x(600) (1) (2)
315 -1GE36-1CA0 670 2x240 2x(600) 8x240 8x600 (4) 2x240 2x(600) 8x240 8x(600) (4) (2)
400 -1GE37-5CA0 670 2x300 2x(800) 8x240 8x600 (4) 2x300 2x(800) 8x240 8x(600) (4) (8) Cu rail
450 -1GE38-4CA0 670 4x150 4x(400) 8x240 8x600 (4) 4x150 4x(400) 8x240 8x(600) (4) (8) Cu rail
560 -1GE41-0CA0 980 4x185 4x(500) 8x240 8x600 (4) 4x185 4x(500) 8x240 8x(600) (4) (10) Cu rail
Version C, 660 V to 690 V
75 -1GH28-5CA0 225 50 (00) 2x240 2x600 (1) 50 (00) 2x70 2x(000) (1) (2)
90 -1GH31-0CA0 225 50 (00) 2x240 2x600 (1) 50 (00) 2x150 2x(400) (1) (2)
110 -1GH31-2CA0 225 70 (000) 2x240 2x600 (1) 70 (000) 2x150 2x(400) (1) (2)
132 -1GH31-5CA0 225 95 (4/0) 2x240 2x600 (1) 95 (4/0) 2x150 2x(400) (1) (2)
160 -1GH31-8CA0 300 120 (300) 2x240 2x600 (1) 120 (300) 2x150 2x(400) (1) (2)
200 -1GH32-2CA0 300 2x70 2x(000) 2x240 2x600 (1) 2x70 2x(000) 2x150 2x(400) (1) (2)
250 -1GH32-6CA0 300 2x95 2x(4/0) 2x240 2x600 (1) 2x95 2x(4/0) 2x185 2x(500) (1) (2)
315 -1GH33-3CA0 300 2x120 2x(300) 4x240 4x600 (1) 2x120 2x(300) 2x240 2x(600) (1) (2)
400 -1GH34-1CA0 670 2x185 2x(500) 4x240 4x600 (2) 2x185 2x(500) 4x240 4x600 (2) (2)
450 -1GH34-7CA0 670 2x185 2x(500) 4x240 4x600 (2) 2x185 2x(500) 4x240 4x600 (2) (2)
560 -1GH35-8CA0 670 2x240 2x(600) 4x240 4x600 (2) 2x240 2x(600) 4x240 4x600 (2) (2)
710 -1GH37-4CA0 940 3x185 3x(500) 8x240 8x600 (4) 3x185 3x(500) 6x240 6x600 (3) (18) Cu rail
800 -1GH38-1CA0 980 4x150 4x(400) 8x240 8x600 (4) 4x150 4x(400) 6x240 6x600 (3) (18) Cu rail

3/10 Siemens D 11 Modified January 2004


Planning information

4/2 Customers terminal block

4/4 Dimensioning and selection


information

4/5 Line-side components

4/6 Components in the DC link

4/8 Load-side components and


cables

4/9 Motors

4/11 Motor selection and converter


assignment

Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Customers terminal block

Planning information
A PROFIBUS interface on the control unit and the customers ter- The customers terminal block contains
minal block are available as interfaces for customer control. 8 digital inputs (DI)
The customers terminal block permits connection to the higher- 4 bidirectional inputs/outputs (DI/DO)
level control using analog and digital signals as well as the con- 2 analog inputs (differential) (AI)
nection of additional units.
2 analog outputs (AO)
2 relay outputs (changeover) (DO)
1 input for KTY84 temperature sensor or PTC thermistor
(Temp.)
10 V auxiliary voltage output for analog setpoint input
24 V auxiliary voltage output for digital inputs

+
[1] Drive ON/OFF1 M + M
[2] Increase setpoint -X524 -X521
+ AI 0+ 1
[3] Decrease setpoint + 24 V
A S500.2 [9]
+ D AI 0- 2
[4] Acknowledge fault
M AI 1+ 3
[5] Selection of operation M A S500.1
terminal block/PROFIBUS M D AI 1- 4 [10]
M
[6] Interlocking of local 5
operation P 10
6
[7] Selection M
7
fixed setpoint Bit 0 N 10
[8] Selection 8
M
fixed setpoint Bit 1
-X520
[9] Analog input for [1] -X522
1
setpoint speed DI 0 1
[2] AO 0V+ V
2 [11]
[10] Analog input DI 1 2
[3] AO 0-
(reserved) 3
DI 2 3
[4] AO 0C+ A
[11] Analog output for 4 2)
DI 3 4
actual speed value AO 1V+ V
5
M1 5 [12]
[12] Analog output for 1) AO 1-
4 actual motor current
value
6
M
AO 1C+
6
7
A

-X540 + Temp
[13] Connection of a KTY84 8 [13] J
1 - Temp
temperature sensor or + 24 V
PTC thermistor 2
+ 24 V -X541
[14] Ready to start 3 P24V
+ 24 V 1
(digital output as + 3)
4 2 [14]
factory setting) + 24 V DI/DO 8
5 DO 3 [15]
[15] Local/remote status + 24 V DI/DO 9
Out/In
display 6 DI 5V 4 [16]
+ 24 V DI/DO 10
(digital output as
7 24 V 5 [17]
factory setting) + 24 V DI/DO 11
8 6
[16] As digital inputs/ + 24 V M
[17] outputs, freely
parameterizable -X530 -X542
[18] Checkback signal [5] 1 DO 0 1
DI 4
"Inverter enable" [6] 2 2
DI 5 [18]
[19] Checkback signal [7] 3 3
"Converter no fault " DI 6
[8] 4 DO 1 4
DI 7 V
5 5 [19]
M2
1) 6 6
M

G_D011_EN_00015b

1) The jumpers must be inserted for this circuit example (M: ground, internal; M1 or M2: external)
2) Parameterizable as current or voltage source
3) Parameterizable individually as digital input/digital output (factory setting: set as output by default)

Customers terminal block

4/2 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Customers terminal block

Planning information (continued)


Customers terminal block in accordance with factory setting
Terminal No. Type Factory setting Remarks
X540: 1-8 P24 24 V DC supply voltage for inputs DI0 to DI7
and DI/DO8 to DI/DO11
X520: 1 DI0 Digital input electrically isolated via optocou- ON/OFF 1 Inputs are freely parameterizable
pler
X520: 2 DI1 Increase setpoint
X520: 3 DI2 Decrease setpoint
X520: 4 DI3 Acknowledge fault
X520: 5 M1 Reference ground for digital inputs DI0 to DI3
X520: 6 M Reference ground for P24
Auxiliary voltage for the digital inputs
X530: 1 DI4 Digital input electrically isolated via optocou- Terminal block/PROFIBUS selection Terminal block=1 PROFIBUS=0
pler Inputs are freely parameterizable
X530: 2 DI5 Interlocking of local operation
X530: 3 DI6 Selection of fixed setpoint Bit 0
X530: 4 DI7 Selection of fixed setpoint Bit 1
X530: 5 M2 Reference ground for digital inputs DI4 to DI7
X530: 6 M Reference ground for P24
Auxiliary voltage for the digital inputs
X541: 1 P24
X541: 2 DI/DO8 Digital inputs/Digital outputs Ready to start (set as digital output Inputs/outputs are freely para-
non-floating by default) meterizable
X541: 3 DI/DO9 Local/Remote status display (set as
digital output by default)
X541: 4 DI/DO10 Set as output by default
X541: 5 DI/DO11 Set as output by default
X541: 6 M Reference ground of P24 and ground of digital
inputs/digital outputs
X521: 1 AI 0 + Analog inputs designed as differential inputs Setpoint speed Positive differential input for
for the following ranges: Factory setting 0 mA to 20 mA voltage/current
10 V to +10 V
X521: 2 AI 0 -
+4 mA to +20 mA
Negative differential input for
voltage/current 4
X521: 3 AI 1 + 20 mA to +20 mA reserved Positive differential input for
0 mA to +20 mA voltage/current
X521: 4 AI 1 - Switch S500 is used to select either voltage Negative differential input for
input or current input voltage/current
X521: 5 P10 10 V auxiliary voltage (10 mA) for connecting +10 V
a potentiometer for setpoint input via an analog
X521: 6 M input Reference ground for 10 V
X521: 7 N10 10 V
X521: 8 M Reference ground for 10 V
X522: 1 AO 0V+ Analog outputs for the following ranges: Actual speed value Analog output voltage +
X522: 2 AO 0 Bez 10 V to +10 V Factory setting 0 mA to 20 mA Common reference point for
+4 mA to +2 mA current/voltage
X522: 3 AO 0A+ 20 mA to +20 mA Analog output current +
X522: 4 AO 1V+ 0 mA to +2 mA Actual motor current value Analog output voltage +
X522: 5 AO 1 Bez Factory setting 0 mA to 20 mA Common reference point for
current/voltage
X522: 6 AO 1A+ Analog output current +
X522: 7 KTY+ Temperature sensor KTY84 The type of sensor must be selected
X522: 8 KTY- 0 C to 200 C or PTC (Rcold 1.5 kOhm)
X542: 1 DO 0.NC Relay output, changeover contact Checkback: inverter enable NC contact
X542: 2 DO 0.COM Max. switching voltage: 250 V AC, 30 V DC Root
X542: 3 DO 0.NO Max. switching capacity at 250 V AC: 2000 VA NO contact
Max. switching capacity at 30 V DC: 240 W
X542: 4 DO 1.NC Relay output, changeover contact Checkback: converter no fault NC contact
X542: 5 DO 1.COM Max. switching voltage: 250 V AC, 30 V DC Root
X542: 6 DO 1.NO Max. switching capacity at 250 V AC: 2000 VA NO contact
Max. switching capacity at 30 V DC: 240 W

Siemens D 11 Modified January 2004 4/3


SINAMICS G150
Drive converter cabinet units
Dimensioning and selection information

Planning information (continued)


Rated data and continuous operation of converters for EMERGENCY STOP functions
drives with low demands on control performance
The EMERGENCY STOP function may be specified for certain
The SINAMICS G150 drive converter cabinet units are designed drive applications. According to EN 60 204, an EMERGENCY
for applications with low demands on dynamics and control ac- STOP must be designed as a stop of category 0 or as a stop of
curacy, offering no possibility of regenerative feedback. category 1.
They are designed for motorized operation at the supply volt- They are defined as follows:
ages specified in the selection tables, whereby voltage varia-
tions within the defined tolerances have been taken into ac- Stop of category 0:
count. Uncontrolled shutdown by immediately switching off the power
The currents specified in the selecting and ordering data are supply; the motor coasts to a standstill. Corresponds to an im-
available here for the entire frequency/speed setting range. mediate inverter stop in conjunction with intrinsically safe dis-
connection of the main contactors, or circuit-breaker in the case
As far as the rated currents are concerned, the units are dimen- of high power systems.
sioned for continuous operation with the listed rated output cur-
rents. The values of standard 6-pole Siemens motors were used Stop of category 1:
as the basis. Controlled shutdown where the power supply is retained until
standstill has been reached. This can be implemented by means
When selecting a suitable converter it must be taken into ac- of a rapid stop in conjunction with subsequent intrinsically safe
count that the rated current of the converter must be at least disconnection of the main contactors or the circuit-breaker.
as large as the motor current at full torque and at the required
load point. Note:
In the case of converters that do not have braking facilities, only
a stop of category 0 is meaningful. An EMERGENCY STOP of
Overload capability category 1 generally requires a braking facility (braking unit or
converter with regenerative feedback).
The SINAMICS G150 drive converter cabinet units offer an over-
current reserve, for example, in order to overcome breakaway The category must be selected using a risk evaluation for the
torques. The following overload currents are possible if the con- drive.
verter is operated for at least 290 s/240 s with a maximum of its
To achieve this the drives can be roughly divided into the follow-
base load current before and after a case of overload:
ing groups:
150% for 10 s or 7 Types of drive with respect to EMERGENCY STOP
110% for 60 s.
Case A:
Drives which are braked down to zero speed by the connected
load within a short time when switched off.

4 Typical example: Pumps. An EMERGENCY STOP with stop ac-


cording to category 0 is sufficient here.
Case B:
Drives with large centrifugal masses which are braked down to
zero speed by the connected load when switched off.
Typical example: Fans. An EMERGENCY STOP with stop ac-
cording to category 0 is sufficient here if the coasting time can
be tolerated. If stopping is required, however, within a specific
time when an EMERGENCY STOP occurs, it may be necessary
to provide a stop according to category 1. This requires, under
certain conditions, a braking facility even if this is not necessary
for the actual drive application.

4/4 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Line-side components

Planning information (continued)


Line fuses
The combined fuses (3NE1.) for line and semiconductor protec-
tion are recommended to protect the converter. These fuses are Connection point of Connection point of
specially adapted to the requirements of the input rectifiers transformer converter
semiconductors to be protected: S k2 line S transf S k1
Superfast Power
supply Converter
Adapted to the limit current integral of the semiconductor
G_D011_EN_00022c
Low arc voltage Mains power uk transf %
input inductance
Improved current limiting (lower let-through values)
See Options for order numbers and assignments of these fuses.
Please refer to Engineering Information, Order No.
E20001-A700-P302-X-7600, for the description and technical
data of the fuses. In this case, the line short-circuit power Sk1 at the connection
point of the converter is approximately:
Line reactor
A line reactor is required for a high line short-circuit rating on the
one hand to protect the converter itself from excessively high S k1 = Stransf / (uk transf + Stransf / Sk2 line )
harmonic currents and therefore from overloads and on the other
hand to limit the harmonic effects on the system to permissible S transf Rated output of transformer
values. The harmonic currents are limited by the complete in-
u k transf Per-unit impedance of transformer
ductance comprising the line reactor and mains power input in-
ductance. Line reactors can be omitted if the line infeed induc- S k2 line Short-circuit power of higher-level voltage
tance is increased sufficiently, i.e. the value of RSC must be
sufficiently small.
It is better to connect high output converters to medium-voltage
RSC=Relative Short-Circuit power: Ratio of short-circuit power
systems via transformers to minimize harmonic effects on the
SK Line at the supply connection point to fundamental apparent
system, so for this reason, the cabinet units above 500 kW are
output Sconv of the connected converters (according to
not fitted as standard with line reactors.
EN 50 178/VDE 0160).
However, a line reactor (option L23) is always required if
the ratio RSC > 20 in the case of cabinet units > 500 kW, or,
an RI suppression filter is used.
Connection point of
converter RI suppression filters

S k line The SINAMICS G150 drive converter cabinet units comply with

Line Converter
the EMC product standard EN 61 800-3 for electrical drives pro-
vided that the units are integrated into the system in compliance
4
G_D011_EN_00023c with EMC requirements.
Mains power input Line reactor
inductance The RI suppression filters, together with the line reactor, reduce
any noise voltages generated by the converter. Compliance with
the limits of EN 55 011 Class A1 for industrial areas is assured
when using the proposed filters provided that the system is an
earthed-neutral system (TN system).
The following applies to the SINAMICS G150 drive converter
cabinet units:
Output Line reactor Line reactor
can be omitted required
kW for RSC Order code for RSC Order code
< 200 43 L22 > 43 -
200 to 500 33 L22 > 33 -
> 500 20 - > 20 L23

In practice, the line configuration on which individual converters


operate is often not known, i.e. the line short circuit power at the
connection point of the converter is not known, so it is recom-
mended that a line reactor is always connected in series with the
converter. For this reason, drive converter cabinet units up to an
output of 500 kW are equipped as standard with a 2% line reac-
tor.
The line reactor can only be omitted (option L22), if the value for
RSC is lower than that shown in the above table. This is the case
when, as shown in the following figure, the converter is con-
nected to the line through a transformer with the appropriate rat-
ing.

Siemens D 11 Modified January 2004 4/5


SINAMICS G150
Drive converter cabinet units
Components in the DC link

Planning information (continued)


Braking Units and Braking Resistors
Braking units are used when regenerative energy occurs occa- P/P 20
sionally and briefly, for example when the brake is applied to the
drive (emergency stop). The braking units (options L61, L62)
comprise a chopper power unit and a load resistor, which must 1.50
be attached externally.
1.25 P 15
Two braking units, which cover a wide range and are supplied
with a braking power of 100 kW and 200 kW, are available for the

G_D011_EN_00035
1.00 P 20
SINAMICS G converter series. For higher braking powers, brak-
ing units can be connected in parallel for larger converters (on 0.75
request).
0.50 P 40
A thermal contact, which can be integrated in the warning and P DB
shutdown train of the converter, is installed in the braking resistor 0.25
for monitoring.
Determining the required braking units and braking resistors 10 15 20 30 40 50 60 70 80 90 s 100 t

For periodic duty cycles with a load duration of 90 s, the


mean braking power value within this duty cycle must be de- P DB = Permanent braking power
termined. The relevant period must be used as a time basis. P 15 = 5 x P DB = Output which is permissible every 90 s for 15 s
For periodic duty cycles with a load duration of 90 s or for P 20 = 4 x P DB = Output which is permissible every 90 s for 20 s
sporadic braking operations, a 90 s time segment in which the P 40 = 2 x P DB = Output which is permissible every 90 s for 40 s
greatest mean value occurs must be selected. A 90 s period
must be set as a time basis.
When selecting the braking units/braking resistors, you must
take into account not only the mean braking power value but Load diagram
also the required peak braking power.
Basic data Calculating the P20 power
Supply Contin- Chop- Rated Peak Braking Max.
voltage uous per chop- chop- resistor current
chop- power per per RB P20 = 4.5 x Mean braking power
per P40 power power

G_D011_EN_00036
power P20 P15
PDB
no yes
380 V 25 kW 50 kW 100 kW 125 kW 4.4 189 A Maximum output x 0.8 P20
480 V 7.5%
4 380 V
480 V
50 kW 100 kW 200 kW 250 kW 2.2
7.5%
378 A
P 20 = 4.5 x Mean braking power P 20 = 0.8 x Maximum output
660 V 25 kW 50 kW 100 kW 125 kW 9.8 127 A
690 V 7.5%
660 V 50 kW 100 kW 200 kW 250 kW 4.9 255 A
690 V 7.5%
To reduce the voltage stress on the motor and converter, the re-
sponse threshold at which the braking unit is activated and the
DC link voltage generated can be reduced. For example, the DC
link voltage for the converters in the voltage range from 380 V to
480 V can be reduced from 774 V to 673 V. This also reduces the
possible peak power. Factor 1.06 rather than factor 0.8 must be
used here.
The ON/OFF statuses of the brake chopper are controlled by a
2-point controller. The respective response thresholds are shown
in the following table:
Converter voltage range Response threshold of braking unit
380 V to 480 V 774 V (673 V)
660 V to 690 V 1158 V (1070 V)

4/6 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Components in the DC link

Planning information (continued)


Example 1 Example 2

Mean Mean
braking power braking power

200 200
kW kW

G_D011_EN_00037

G_D011_EN_00038
150 15 s 150

100 90 s 100
17 s
50 50 90 s

10 20 30 40 50 60 70 80 90 s 100 t 10 20 30 40 50 60 70 80 90 s 100 t

The mean braking power is calculated as follows: The mean braking power is calculated as follows:
Mean braking power = 180 kW x 15 s / 90 s = 30 kW Mean braking power = 110 kW x 17 s / 90 s = 20.78 kW
P 20 = 4.5 x 30 kW = 135 kW P 20 = 4.5 x 20.78 kW = 93.5 kW
Peak power = 0.8 x 180 kW = 144 kW Peak power = 0.8 x 110 kW = 88 kW
Result: The peak power to be generated is a determining factor Result: The mean braking power to is a determining factor in the
in the configuration of the braking unit and braking resistor, that configuration of the braking unit and braking resistor, that is, a
is, a braking unit or braking resistor of 144 kW must be pro- braking unit or braking resistor of 93.5 kW must be provided.
vided. Choose the 100 kW braking unit (option L61).
Choose the 200 kW braking unit (option L62).
When the response threshold is reduced, the required braking
When the response threshold is reduced, the required braking power (P20) is calculated as follows:
power (P20) is calculated as follows:
Mean braking power = 110 kW x 17 s / 90 s = 20.78 kW
Mean braking power = 180 kW x 15 s / 90 s = 30 kW
P 20 = 4.5 x 20.78 kW = 93.5 kW
P 20 = 4.5 x 30 kW = 135 kW
Peak power = 1.06 x 110 kW = 116.6 kW
Peak power = 1.06 x 180 kW = 190.08 kW
Result: The peak power to be generated is a determining factor
Result: The peak power to be generated is a determining factor in the configuration of the braking unit and braking resistor, that
in the configuration of the braking unit and braking resistor, that
is, a braking unit or braking resistor of 190.08 kW must be pro-
is, a braking unit or braking resistor of 116.6 kW must be pro-
vided.
4
vided. Choose the 200 kW braking unit (option L62).
Choose the 200 kW braking unit (option L62).

Siemens D 11 Modified January 2004 4/7


SINAMICS G150
Drive converter cabinet units
Load-side components and cables

Planning information (continued)


Output filters
The switching frequencies of the IGBT converter result in high without output filter with output filter
rates of voltage rise dv/dt at the converter output. When using
long motor cables, these result in an additional current load on 6
the converter through the capacitive charge reversal currents. 2
U LL/U rated U LL/U rated
Furthermore, the high rates of voltage rise as well as the result- du/dt du/dt
4
ing voltage peaks at the motor terminals increase the electrical
winding load on the motors compared to direct line operation. 1
2
The output filters with their adapted inductances, in conjunction
with the cable capacitances, reduce the capacitive charge re-
versal currents in the motor cables and limit the rate of voltage 0 0
0 100 200 m 300 0 100 200 m 300
rise dv/dt as well as the voltage peaks LL at the motor terminals Cable length Cable length
depending on the motor cables.
The table shows the maximum motor cable lengths which can be U LL/U rated

G_D011_EN_00026b
connected with and without output filters (option L08). The val- du/dt in kV/ms
ues apply to all standard motor cables and those recommended
by Siemens. Longer cable length may only be used following
clarification.
Required cable cross-sections for power supply and motor
Converter Maximum cable lengths connections
Supply Output Protoflex Shielded Unshielded
voltage EMC 3 Plus cable, e.g.: cable, e.g.: It is always recommendable to use 3-wire three-phase cables or
Protodur Protodur to connect several cables of this type in parallel. There are two
NYCWY NYY main reasons for this:
Without output filter In this manner, the high IP54 degree of protection or better can
be achieved for the motor terminal box without any problems
380 V - 480 V 110 kW 300 m 200 m 300 m because the cables are introduced into the terminal box via
380 V - 480 V 132 kW - 560 kW 300 m 300 m 450 m screwed glands and the number of possible glands is limited
660 V - 690 V 75 kW - 800 kW 300 m 100 m 150 m
by the geometry of the terminal box. Single cables are less suit-
able.
With output filter
With three-phase cables, the summed ampere-turns over the
380 V - 480 V 110 kW 300 m 300 m 450 m cable outer diameter is equal to zero and they can be routed in
380 V - 480 V 132 kW - 560 kW 300 m Not Not (conductive, metal) cable ducts or racks without any notice-
required required up able currents (earth current or leakage current) being induced
up to to 450 m in these conductive, metal connections. The danger of induced
300 m leakage currents and thus of increased cable sheath losses is
4 660 V - 690 V 75 kW - 800 kW 300 m 200 m 300 m greater for single cables.

Maximum cable lengths without and with output filter


The cable cross-section required depends on the current trans-
mitted in the cable. The permissible current load on cables is de-
fined e.g. in DIN VDE 0298 Part 2 / DIN VDE 0276-1000. It de-
The diagrams show the voltage load at the motor terminals with pends on the one hand on ambient conditions such as
and without output filters. The rates of voltage rise dv/dt as well temperature and on the other hand on the type of routing with
as the voltage peaks of the phase-to-phase voltage LL are single cables providing relatively good cooling and common
shown depending on the length of the motor cable type NYCWY routing of cables resulting in mutual heating and much poorer
which can be considered as a typical representative of shielded ventilation. In this context, please refer to the applicable reduc-
cables. The cable lengths specified represent the actual dis- tion factors for these boundary conditions in DIN VDE 0298
tance between the converter and motor taking into consideration Part 2 / DIN VDE 0276-1000. With an ambient temperature of
influencing factors such as routing of parallel cables and current 40 C, the cross-sections of copper cables can be based on the
carrying capacity. following tables.
The insulation stressing of the motors must be checked. Cross-section Current carrying capacity according to
For Siemens motors, see Planning information Motors. DIN VDE 0298 Part 2 at 40 C
For third-party motors, the insulation stressing must be of 3-wire With single With multiple routing on common
checked with the manufacturer. cables routing cable rack
50 mm2 138 A 95 A
70 mm2 176 A 121 A
95 mm2 212 A 146 A
120 mm2 245 A 169 A
150 mm2 282 A 194 A
185 mm2 323 A 222 A
240 mm2 380 A 261 A
300 mm2 418 A 289 A

For higher current levels, cables must be connected in parallel.

4/8 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Motors

Planning information (continued)


Motor types 1LA and 1LG Self-ventilated motors with degree of protection IP55
(1LG4/1LG6 and 1LA8)
It is generally recommended to use the proven 1LA and 1LG
standard motors from Siemens.
With respect to thermal stress, these motors can also be used at
the full rated output even with converter operation, with partial
utilization according to temperature class F. If exclusive utiliza-
tion according to temperature class B is required, the output
must be reduced by 10%.

Constant flux Field weakening


range range
M /M n
With forced ventilation

100
%
90
Motors 1LG4/1LG6
80

Utilization according to
G_D011_EN_00024b

70
temperature class F

60 Utilization according to
temperature class B

10 20 30 40 50 60 70 80 Hz f

Typical response of permissible torque with self-cooled motors


(e.g. 1LA) with rated frequency of 50 Hz

When considering the voltage stress, the standard insulation of 4


the motors means that unlimited converter-fed operation is pos-
sible at voltages V 500 V. Furthermore, the cable lengths must
be observed taking into account the cable types used.
Using the assignment tables, you can select a suitable motor
type for a converter and a defined drive power. Motors 1LA8

For detailed motor data, see Catalog M11. The 1LG4/1LG6 and 1LA8 motors are self-ventilated motors to
the IP55 degree of protection.
Both the internal fan and the external fan that are built in to every
motor are permanently connected to the shaft.
The cooling effect therefore directly depends on the motor
speed.
Other motors
The 1PH7/1PL6 compact asynchronous motors can be used in
addition to the 1LA and 1LG motors. These motors are recom-
mended for:
Wide speed range with high maximum speed
Limited mounting space.
The 1PH7/1PL6 motors are one to two shaft heights smaller than
comparable standard asynchronous motors with the same rated
output.

Siemens D 11 Modified January 2004 4/9


SINAMICS G150
Drive converter cabinet units
Motors

Planning information (continued)


Rated current Permissible and non-permissible motor/con- For motor winding temperature monitoring with motors of the
verter combinations 1LA8 and 1LG4/1LG6 series, as an alternative, PT100 tempera-
ture sensors (resistance thermometers) are also available. Either
Drives with a quadratic load torque require the full torque at their option A60 (3 x PT100) or A61 (6 x PT100) can be specified on
rated speed. At the required load point, the rated current of the ordering the motors.
converter must be at least as large as the motor current at full
torque. A separate evaluation unit is required (option L86) for evaluation
of the PT100 temperature sensor in the drive converter cabinet
Rated motor current greater than rated converter current unit.
If a motor is to be used whose rated current is greater than the Motors of the 1MJ series with flameproof enclosures require ther-
rated converter current, this means that the motor can only be mistors and release mechanisms approved by PTB (German
operated at partial load. The following limit must be observed: Federal Testing Laboratory) (options L83 and L84).
The maximum possible converter current (overload current)
should be greater than or equal to the rated current of the con- Bearing currents
nected motor. A high clock frequency of the output voltage is required to pro-
If this dimensioning instruction is not observed, current peaks vide the motor with currents which are as sinusoidal as possible
may occur as a result of the lower leakage inductance of larger (smooth running, oscillation torque, additional losses). The re-
motors; these peaks can lead either to switch-off or a continuous sulting steep voltage pulses cause capacitive charge reversal
reduction in output by the internal protection circuit. currents in the existing capacitances (motor cables and wind-
ings). This physical effect is particularly evident with larger mo-
Rated motor current significantly smaller than rated converter tors. The circuit may be closed via the bearings and the high-fre-
current quency capacitive current pulses may destroy the bearings in a
worst-case scenario. To avoid this risk, it is recommended that
With the sensorless vector control used, the rated motor current the bearings at the non-drive-end of the motor are insulated in
must be at least of the rated converter current. the case of converter-fed motors.
Mains connection voltages >500 V for 1LA and 1LG motors The insulated bearing is standard for all 1LA8 motors that are
The standard insulation of the 1LA and 1LG motors is designed designated for converter operation.
such that converter-fed operation without limitation is only possi- An insulated bearing on the non-drive end is available as an op-
ble at voltages V 500 V. At voltages V > 500 V, a higher electric tion for motors of the 1LG4/1LG6 series starting at frame size
strength is required for the motor. 280 (Order code: L27).
Motors of the 1LA8 and 1LG6 series are also available with a An additional measure for reducing the bearing currents even
higher insulation resistance of the winding system for converter- further is to use an output filter (option L08), shielded motor ca-
fed operation with connection voltages up to 690 V; no filters are bles and good earthing of the motor housing. It is recommended
required in this case. These motors are identified by an M as to route the earth cable from the motor directly to the converter.
the 10th digit of the Order No. (e.g. 1LA8315-2PM).
Since these processes involve high frequencies, asymmetry in
With the strengthened insulation system, less space is available the circuits must be kept to a minimum. Only symmetrical multi-
4 for the same number of windings in the grooves compared to the
standard version, resulting in a slightly reduced rated output for
core motor cables must be used (do not use single or four-con-
ductor cables!). The ground connection (protective conductor,
these motors. PE) must be arranged symmetrically in the motor cable to pre-
Motor protection vent shaft currents with base frequencies. The symmetry of the
PE conductor is achieved with a conductor that surrounds all the
Motor protection is provided by the converter software with I2t phase conductors or a cable in which the three phase conduc-
sensing. tors and three ground conductors are arranged symmetrically.
More precise motor protection is possible by direct acquisition Operation of motors with type of protection d
of the temperature using KTY84 sensors or PTC thermistors fit-
ted in the motor winding. Siemens asynchronous motors of the 1MJ series can be oper-
ated as explosion-proof motors with flameproof enclosure
For KTY84 sensors, when ordering motors of the 1LA8 and EEx de IIC connected either to the line supply or the converter.
1LG4/1LG6 series, specify motor option A23. For motors of the
1PH7 and 1PL6 series, the sensors are fitted as standard. In accordance with the test guidelines, the motors of the 1MJ se-
ries must be equipped with thermistors.
If PTC thermistors are required, when ordering motors of the
1LG4/1LG6 series, motor option A11 or A12 must be specified. If 1MJ motors are connected to converters, their maximum per-
For motors of the 1LA8 series, the sensors are fitted as standard. missible torque must be reduced, depending on the load char-
acteristic when utilized according to temperature class B just
The KTY84 sensor and PTC thermistor can be evaluated by con- like the motors of the 1LA series with the same power.
nection to the customers terminal block in the drive converter
cabinet unit. 1MJ motors have a terminal box to the increased safety type of
protection EEx e II as standard.

4/10 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Motor selection and converter assignment

Planning information (continued)


The assignments made in the tables should be considered as The specified drive power values are valid for motors with insu-
recommendations. lation class F, utilized to class F, at a supply voltage of 400 V or
690 V.
You can find exact data on the recommended motors in Catalog
M 11.
Drive shaft SINAMICS G150 drive Motor type
power converter cabinet unit
Number of poles
kW Type 2 4 6 8
Converter supply voltage 380 V to 480 V
100 1LG4310-2AB6. 1LG4310-4AA6. 1LG4316-6AA6. 1LG4317-8AB6.
110 6SL3710-1GE32-1 . A0 1LG6310-2AB6. 1LG6310-4AA6. 1LG6316-6AA6. 1LG6317-8AB6.
118 1LG4313-2AB6. 1LG4313-4AA6. 1LG4317-6AA6. 1LG4318-8AB6.
132 6SL3710-1GE32-6 . A0 1LG6313-2AB6. 1LG6313-4AA6. 1LG6317-6AA6. 1LG6318-8AB6.
144 1LG4316-2AB6. 1LG4316-4AA6. 1LG4318-6AA6.
160 6SL3710-1GE33-1 . A0 1LG6316-2AB6. 1LG6316-4AA6. 1LG6318-6AA6. 1LA8315-8PB..
180 1LG4317-2AB6. 1LG4317-4AA6.
200 6SL3710-1GE33-8 . A0 1LG6317-2AB6. 1LG6317-4AA6. 1LA8315-6PB.. 1LA8317-8PB..
250 6SL3710-1GE35-0 . A0 1LA8315-2PC.. 1LA8315-4PB.. 1LA8317-6PB.. 1LA8355-8PB..
315 6SL3710-1GE36-1 . A0 1LA8317-2PC.. 1LA8317-4PB.. 1LA8355-6PB.. 1LA8357-8PB..
355 1LA8353-2PC.. 1LA8353-4PB.. 1LA8403-8PB..
400 6SL3710-1GE37-5 . A0 1LA8355-2PC.. 1LA8355-4PB.. 1LA8357-6PB.. 1LA8405-8PB..
450 6SL3710-1GE38-4 . A0 1LA8403-6PB.. 1LA8407-8PB..
500 1LA8357-2PC.. 1LA8357-4PB.. 1LA8405-6PB.. 1LA8453-8PB..
560 6SL3710-1GE41-0 . A0 1LA8403-2PC.. 1LA8403-4PB.. 1LA8407-6PB.. 1LA8455-8PB..

Siemens D 11 Modified January 2004 4/11


SINAMICS G150
Drive converter cabinet units
Motor selection and converter assignment

Planning information (continued)


Drive shaft SINAMICS G150 drive Motor type
power converter cabinet unit
Number of poles
kW Type 2 4 6 8
Converter supply voltage 660 V to 690 V
75 6SL3710-1GH28-5 . A0 1LG6280-2PM8. 1LG6280-4PM8. 1LG6310-6PM8. 1LG6313-8PM8.
90 6SL3710-1GH31-0 . A0 1LG6283-2PM8. 1LG6283-4PM8. 1LG6313-6PM8. 1LG6316-8PM8.
110 6SL3710-1GH31-2 . A0 1LG6310-2PM8. 1LG6310-4PM8. 1LG6316-6PM8. 1LG6317-8PM8.
132 6SL3710-1GH31-5 . A0 1LG6313-2PM8. 1LG6313-4PM8. 1LG6317-6PM8. 1LG6318-8PM8.
145 1LA8315-8PM8.
160 6SL3710-1GH31-8 . A0 1LG6316-2PM8. 1LG6316-4PM8. 1LG6318-6PM8.
180 1LA8317-8PM8.
190 1LA8315-6PM8.
200 6SL3710-1GH32-2 . A0 1LG6317-2PM8. 1LG6317-4PM8..
230 1LA8355-8PM8.
235 1LA8315-4PM8. 1LA8317-6PM8.
240 1LA8315-2PM8.
250 6SL3710-1GH32-6 . A0
290 1LA8317-4PM8. 1LA8357-8PM8.
300 1LA8317-2PM8. 1LA8355-6PM8.
315 6SL3710-1GH33-3 . A0
335 1LA8403-8PM8.
340 1LA8353-4PM8.
345 1LA8353-2PM8.
375 1LA8405-8PM8.
380 1LA8357-6PM8.
385 1LA8355-4PM8.
390 1LA8355-2PM8.
400 6SL3710-1GH34-1 . A0
425 1LA8407-8PM8.
4 435
450 6SL3710-1GH34-7 . A0
1LA8403-6PM8.

480 1LA8357-4PM8.
485 1LA8357-2PM8. 1LA8405-6PM8. 1LA8453-8PM8.
545 1LA8403-2PM8. 1LA8403-4PM8. 1LA8407-6PM8. 1LA8455-8PM8.
560 6SL3710-1GH35-8 . A0
600 1LA8457-8PM8.
610 1LA8405-2PM8.
615 1LA8405-4PM8. 1LA8453-6PM8.
680 1LA8407-2PM7.
690 1LA8407-4PM7. 1LA8455-6PM7.
710 6SL3710-1GH37-4 . A0
775 1LA8453-2PM7.
780 1LA8457-6PM7.
785 1LA8453-4PM7.
800 6SL3710-1GH38-1 . A0
875 1LA8455-2PM7.

4/12 Siemens D 11 Modified January 2004


Services and
documentation

5/2 Training

5/3 Service & Support

5/4 Documentation

Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Training

Overview
Basic courses
7 SINAMICS system overview
(DR-SN-UEB, 2 days)
This course, specially for sales personnel and decision-mak-
ers gives an overview of the SINAMICS drives concept and its
place in the existing universe of Siemens drives. The system
overview will be explained with information about the funda-
mentals of motor and converter technology. Product dimen-
sioning and commissioning are explained and illustrated with
brief exercises.
7 SINAMICS project engineering course
(DR-SNG-PRJ, 2 days)
A course specially for design engineers and sales personnel
with the task of dimensioning drives systems with SINAMICS.
The basic relationships in the calculation of drive systems are
taught, different applications of SINAMICS are calculated and
illustrated with exercises on the PC.
Advanced courses
7 SINAMICS drive converter cabinet units Service
Our training center offers a comprehensive course program for (DR-SNG-EXP, 3 days, prerequisite: Servicing experience)
SINAMICS including project engineering and maintenance train- A course specially for service personnel who support end us-
ing. ers with troubleshooting. Apart from topics such as compo-
The courses are designed in a modular structure and are tai- nent replacement, BICO technology, trace functions and other
lored to specific target groups: software functions, aspects of electrical connection and elec-
tromagnetic compatibility are also taught and trained in prac-
Sales personnel and decision-makers tical exercises. An original SINAMICS G150, 110 kW drive
Design engineers converter cabinet unit is used for training purposes.
Service and maintenance personnel. 7 SINAMICS communication
(DR-SN-KOM, 3 days, prerequisite: STEP 7 knowledge)
The course program comprises basic courses (prerequisite:
general knowledge of electrical engineering, e.g. home study A course specially for programmers and service personnel
course Drive engineering for beginners) and advanced who require extensive knowledge of PROFIBUS, RS232 and
courses. operator panel communications interfaces as well as I/O ter-
minals. The emphasis is on PROFIBUS with Routing, TeleSer-
All courses take place in Nuremberg-Moorenbrunn or can also vice and the libraries for DriveES SIMATIC for cyclic and non-
be offered locally to you (with the exception of the Service cyclic data transfer.
course).
The complete list of training courses offered by SITRAIN can be
requested by calling the Infoline +49-(0)180-52 35 611 or you
will find them in the following publications:

Order No.
Katalog ITC, German E86060-K6850-A101-B4
Data and price list E86060-P6850-A101-C7
incl. Course information system on
CD-ROM, German
Course information system SITRAIN E86060-D6850-A100-B9-7400
on separate CD-ROM,
German/English

5 You will find our complete course program with up-to-date addi-
tional dates, the current number of applicants and additional in-
formation on the Internet at:
http://www.sitrain.com

Contact address:
Siemens AG
A&D Training Center
Gleiwitzer Str. 555
90475 Nuremberg-Moorenbrunn, Germany
Tel.: +49-(0)180-52 35 611
Fax: +49-(0)180-52 35 612
E-mail: A&D.kursbuero@nbgm.siemens.de

5/2 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Service & Support

Configuration and Software Engineering


Support in configuring and de-
veloping with customer-oriented
services from actual configura-
tion to implementation of the au-
tomation project. 1)

.I
Service On Site
With Service On Site we offer
In the face of harsh competition you need optimum conditions to
services for startup and mainte-
keep ahead all the time:
nance, essential for ensuring
A strong starting position. A sophisticated strategy and team for
system availability.
the necessary support - in every phase.
Service & Support from Siemens provides this support with a In Germany
complete range of different services for automation and drives. 0180 50 50 444 2)
In every phase: from planning and startup to maintenance and
upgrading.
Our specialists know when and where to act to keep the produc-
tivity and cost-effectiveness of your system running in top form.
Repairs and Spare Parts
Online Support In the operating phase of a ma-
The comprehensive information chine or automation system we
system available round the provide a comprehensive repair
clock via Internet ranging from and spare parts service ensur-
Product Support and Service & ing the highest degree of oper-
Support services to Support ating safety and reliability.
Tools in the Shop.
In Germany
http://www.siemens.com/ 0180 50 50 448 2)
automation/service&support

Optimization and Upgrading


Technical Support To enhance productivity and
Competent consulting in techni- save costs in your project we of-
cal questions covering a wide fer high-quality services in opti-
range of customer-oriented ser- mization and upgrading. 1)
vices for all our products and
systems.
Tel.: +49 (0)180 50 50 222
Fax: +49 (0)180 50 50 223
E-Mail:
adsupport@siemens.com

Technical Consulting
Support in the planning and de-
signing of your project from de-
5
tailed actual-state analysis,
target definition and consulting
on product and system ques-
tions right to the creation of the
automation solution. 1)

1) Get in touch with the sales contact in your region for questions about these
services. Our Helpline (tel.: +49 (0) 180 50 50 111) will also put you
through to the right contact or just visit our Internet site.
2) For country-specific telephone numbers go to our Internet site at:
http://www.siemens.com/automation/service&support

Siemens D 11 Modified January 2004 5/3


SINAMICS G150
Drive converter cabinet units
Documentation

Overview
The product documentation comprises detailed operating in-
structions that comprise the following parts:
Description
Mounting instructions
Commissioning guide
Description of functions
Maintenance instructions
Spare parts list
as well as product-specific wiring and engineering documenta-
tion.
The documentation is supplied with the converter in En-
glish/German as standard.
If one of the following languages is required, this must be noted
when the converter is ordered by means of the applicable order
code:

Language Order code


English/French D58
English/Spanish D60
English/Italian D80

5/4 Siemens D 11 Modified January 2004


Appendix

6/2 Siemens contacts


worldwide

6/3 A&D Online services


6/3 A&D in the WWW
6/3 Produkt selection using the
interactive catalog
6/3 Easy Shopping with the A&D Mall

6/4 Subject index


Order No. index

6/5 Terms and Conditions of sale


and delivery

6/5 Export regulations

Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Siemens contacts worldwide
At
http://www.siemens.com/automation/partner
you can find details of Siemens contact partners worldwide re-
sponsible for particular technologies.
You can obtain in most cases a contact partner for
Technical Support,
Spare parts/repairs,
Service,
Training,
Sales or
Consultation/engineering.
You start by selecting a
Country,
Product or
Sector.
By further specifying the remaining criteria you will find exactly
the right contact partner with his/her respective expertise.

6/2 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
A&D Online services

A&D in the WWW


A detailed knowledge of the range of products and services
available is essential when planning and configuring automation
systems. It goes without saying that this information must always
be fully up-to-date.
The Siemens Automation and Drives Group (A&D) has therefore
built up a comprehensive range of information in the World Wide
Web, which offers quick and easy access to all data required.
Under the address
http://www.siemens.com/automation
you will find everything you need to know about products, sys-
tems and services.

Product Selection Using the Interactive Catalog


Detailed information together with convenient interactive
functions:
The interactive catalog CA 01 covers more than 80,000 products
and thus provides a full summary of the Siemens Automation
and Drives product base.
Here you will find everything that you need to solve tasks in the
fields of automation, switchgear, installation and drives.
All information is linked into a user interface which is easy to
work with and intuitive.
After selecting the product of your choice you can order at the
press of a button, by fax or by online link.
Information on the interactive catalog can be found in the Inter-
net under
http://www.siemens.com/automation/ca01
or on CD-ROM:
Automation & Drives CA 01,
Order No.: E86060-D4001-A110-C1-7600

Easy Shopping with the A&D Mall


The A&D Mall is the virtual department store of Siemens AG in
the Internet. Here you have access to a huge range of products
presented in electronic catalogs in an informative and attractive
way.
Data transfer via EDIFACT allows the whole procedure from se-
lection through ordering to tracking of the order to be carried out
online via the Internet.
Numerous functions are available to support you.
For example, powerful search functions make it easy to find the
required products, which can be immediately checked for avail-
ability. Customer-specific discounts and preparation of quotes
can be carried out online as well as order tracking and tracing.
Please visit the A&D Mall on the Internet under:
http://www.siemens.com/automation/mall

Siemens D 11 Modified January 2004 6/3


SINAMICS G150
Drive converter cabinet units
Appendix

Subject index Order No. index


Page Page
A&D in the WWW 6/3 1LA8 4/11
Accessories 2/11 1LG4/1LG6 4/11
Ambient conditions 2/7 3NA3 2/11
Application 2/2 3NE1 2/11
Benefits 2/2 6SL3710 2/10
Braking resistor 4/6
Cable protection fuses 2/11
Compliance with standards 2/7
Components in the DC link 4/6
Conditions of sale and delivery 6/5
Connections 3/10
Contacts worldwide 6/2
Control functions 2/6
Current derating 2/8
Customer's terminal block 2/5, 4/2
Derating data 2/8
Design 2/2
Dimensional drawings 3/1
Dimensioning and selection information 4/4
Documentation 5/4
Easy Shopping with the A&D Mall 6/3
Electrical data 2/7
EMC information 2/9
Export regulations 6/5
Functions 2/2
Interactive catalog 6/3
Line fuses 4/5
Line reactor 4/5
Line-side components 4/5
Load-side components and cables 4/8
Mechanical connection data 3/10
Mechanical data 2/7
Mechanical stability 2/7
Motor selection and converter assignment 4/11
Motors 4/9
Online services 6/3
Operator panel 2/4
Options
Description 2/16
Examples for ordering 2/15
Order code 2/12
Selection matrix 2/14
Output filters 4/8
Overview 2/2
Planning information 4/1
Components in the DC link 4/6
Customer's terminal block 4/2
Dimensioning and selection information 4/4
Line-side components 4/5
Load-side components and cables 4/8
Motors 4/9
Motor selection and converter assignment 4/11
RI suppression filters 4/5
Selection and ordering data 2/10
Service & Support 5/3
Services and documentation 5/1
SINAMICS, overview 1/6
Site altitude 2/8
Software and protection functions 2/6
Support 5/3
Technical data 2/7
Totally Integrated Automation (TIA) 1/4
Training 5/2
6 Voltage derating 2/8
Worldwide application 2/2

6/4 Siemens D 11 Modified January 2004


SINAMICS G150
Drive converter cabinet units
Appendix

Terms and Conditions of Sale and Delivery Export regulations


By using this catalog you can acquire hardware and software The products listed in this catalog may be subject to Euro-
products described therein from the Siemens AG subject to the pean/German and/or US export regulations.
following terms. Please note! The scope, the quality and the con- Therefore, any export requiring a license is subject to approval
ditions for supplies and services, including software products, by the competent authorities.
by any Siemens entity having a registered office outside of Ger-
many, shall be subject exclusively to the General Terms and Con- According to current provisions, the following export regulations
ditions of the respective Siemens entity. must be observed with respect to the products featured in this
catalog:
for customers with a seat or registered office in Germany
The General Terms of Payment as well as the General Conditions AL Number of the German Export List.
for the Supply of Products and Services of the Electrical and
Products marked other than N require an export
Electronics Industry shall apply.
license.
For software products, the General License Conditions for Soft- In the case of software products, the export des-
ware Products for Automation and Drives for Customers with ignations of the relevant data medium must also
Seat or registered Office in Germany shall apply. be generally adhered to.
for customers with a seat or registered office outside of Goods labeled with an AL not equal to N are
Germany subject to a European or German export authori-
zation when being exported out of the EU.
The General Terms of Payment as well as the General Conditions
for Supplies of Siemens, Automation and Drives for Customers ECCN Export Control Classification Number.
with a Seat or registered Office outside of Germany shall apply.
Products marked other than N are subject to a
For software products, the General License Conditions for Soft- reexport license to specific countries.
ware Products for Automation and Drives for Customers with
Seat or registered Office outside of Germany shall apply. In the case of software products, the export
designations of the relevant data medium must
General also be generally adhered to.
The prices are in (Euro) ex works, exclusive packaging. Goods labeled with an ECCN not equal to N are
The sales tax (value added tax) is not included in the prices. subject to a US re-export authorization.
It shall be debited separately at the respective rate according to
the applicable legal regulations. Even without a label or with an AL: N or ECCN: N, authoriza-
tion may be required due to the final destination and purpose for
In addition to the prices of products which include silver and/or which the goods are to be used.
copper, surcharges may be calculated if the respective limits of
the notes are exceeded. The deciding factors are the AL or ECCN export authorization
indicated on order confirmations, delivery notes and invoices.
Prices are subject to change without prior notice. We will debit
the prices valid at the time of delivery. Errors excepted and subject to change without prior notice..
The dimensions are in mm. Illustrations are not binding.
Insofar as there are no remarks on the corresponding pages,
- especially with regard to data, dimensions and weights given -
these are subject to change without prior notice.
Comprehensive Terms and Conditions of Sale and Delivery are
available free of charge from your local Siemens business office
under the following Order Nos.:
6ZB5310-0KR30-0BA0
(for customers based in the Federal Republic of Germany)
6ZB5310-0KS53-0BA0
(for customers based outside of the Federal Republic of
Germany)
or download them from the Internet:
www.siemens.com/automation/mall
(Germany: A&D Mall Online-Help System)

Siemens D 11 Modified January 2004 6/5


SINAMICS G150
Drive converter cabinet units
Appendix

Responsible for
Technical contents:
Siemens AG, A&D LD M PM
General editing:
Siemens AG, A&D PT 5, Erlangen

Siemens AG Order No.: E86060-K5511-A101-A1-7600


6 Automation & Drives
Large Drives
Printed in Germany
KG K 0204 3.0 BD 60 En/422241
Postfach 4743
D-90025 Nrnberg
Germany

6/6 Siemens D 11 Modified January 2004


Catalogs of the
Automation and Drives Group (A&D)
Further information can be obtained from our branch offices
http://www.siemens.com/automation/partner

Automation & Drives Catalog Low-Voltage Controls and Distribution Catalog


Interactive catalog on CD-ROM Low-Voltage Controlgear, Switchgear and Systems NS K
Components for Automation & Drives CA 01 Communication-Capable Controlgear,
Controlgear with SIRIUS, SIGUARD Safety Systems,
Control and Signalling Devices, Switchgear,
Transformers and DC Power Supplies,
Automation Systems for Machine Tools Main- and EMERGENCY-STOP Switches,
SINUMERIK & SIMODRIVE NC 60 Control Switches, Terminal Blocks
Cables, Connectors and System Components NC Z BERO - Sensors for Automation NS BERO
Products and Systems NS PS
for Low-Voltage Power Distribution
Drive Systems SENTRON WL NS WL
Variable-Speed Drives
SINAMICS G150 Drive Converter Cabinet Units D 11 Motion Control System SIMOTION PM 10
SINAMICS G110 Inverter Chassis Units D 11.1
DC Motors DA 12 Process Instrumentation and Analytics
DC Drives Preferred Series up to 500 kW DA 12.1 Field Instruments for Process Automation FI 01
Measuring Instruments for Pressure,
DC Drives Preferred Series 215 kW to 1500 kW DA 12.2
Differential Pressure, Flow, Level and Temperature,
SIMOREG DC MASTER 6RA70 Digital Chassis DA 21.1 Positioners and Liquid Meters
Converters
PDF: Indicators for panel mounting MP 12
SIMOREG K 6RA22 Analog Chassis Converters DA 21.2
SIREC Recorders and Accessories MP 20
SIMOREG DC MASTER 6RM70 Digital Converter DA 22
SIPART, Controllers and Software MP 31
Cabinet Units
SIWAREX Weighing Systems WT 01
SIMOVERT PM Modular Converter Systems DA 45
Continuous Weighing and Process Protection WT 02
SIEMOSYN Motors DA 48
Gas Analysis Equipment for the Process Industry PA 10
MICROMASTER 410/420/430/440 Inverters DA 51.2
PDF: Process Analytics, PA 11
MICROMASTER 411/COMBIMASTER 411 DA 51.3 Components for the System Integration
SIMOVERT MV Medium-Voltage Drives DA 63
SIPAN Liquid Analysis PA 20
SIMOVERT MASTERDRIVES Vector Control DA 65.10
SIMOVERT MASTERDRIVES Motion Control DA 65.11 SIMATIC Industrial Automation Systems
Synchronous and asynchronous servomotors for DA 65.3 SIMATIC PCS Process Control System ST 45
SIMOVERT MASTERDRIVES
PDF: SIMATIC S5/505 Automation Systems ST 50
SIMODRIVE 611 universal and POSMO DA 65.4
Components for Totally Integrated Automation and ST 70
Low-Voltage Three-Phase-Motors Micro Automation
Project Manual M 10 SIMATIC PCS 7 Process Control System ST PCS 7
Squirrel-Cage Motors, Totally Enclosed, Fan-Cooled M 11 PDF: Add-ons for the SIMATIC PCS 7 ST PCS 7.A
Automation Systems for Machine Tools SIMODRIVE NC 60 Process Control System
AC Main Spindle Motors 1PM, 1FE, 1PH SIMATIC Control Systems ST DA
AC Servomotors 1FT, 1FK
AC Linear motors 1FN SIPOS Electric Actuators
Converter System SIMODRIVE 611 Electric Rotary, Linear and Part-turn Actuators MP 35
Converter Systems SIMODRIVE POSMO A/CD/CA/SI Electric Rotary Actuators for Nuclear Plants MP 35.1/.2
Drive and Control Components for Hoisting Equipment HE 1
Systems Engineering
Power supplies SITOP power KT 10.1
Electrical Installation Technology System cabling SIMATIC TOP connect KT 10.2
PDF: ALPHA Small Distribution Boards and ET A1 MOBY Identification Systems KT 21
Distribution Boards Industrial Microcomputers SICOMP KT 51
PDF: ALPHA Side-by-Side Switchgear Cabinets ET A3
PDF: BETA Modular Installation Devices ET B1 System Solutions
PDF: DELTA Switches and Outlets ET D1 Applications and Products for Industry are part of the
PDF: GAMMA Building Management Systems ET G1 interactive catalog CA 01

TELEPERM M Process Control System


Human Machine Interface Systems SIMATIC HMI ST 80 AS 235, AS 235H and AS 235K automation systems PLT 111
PDF: AS 488/TM automation systems PLT 112
Operating and monitoring with WinCC/TM PLT 123
Industrial Communication and Field Devices IK PI CS 275 bus system PLT 130

PDF: These catalogs are only available as pdf files.


The information provided in this catalog contains descriptions or
characteristics of performance which in case of actual use do
not always apply as described or which may change as a result of
further development of the products. An obligation to provide
the respective characteristics shall only exist if expressly agreed
in the terms of contract. Availability and technical specifications
are subject to change without notice.

Siemens AG

Automation and Drives


Large Drives
Postfach 4743, D-90025 Nrnberg
Germany
www.siemens.com/sinamics-g150 Order No. E86060-K5511-A101-A1-7600