Design calculation sheet

Project no.: S08060 Date: 19/10/2009 Sheet no.: 1 of 1 Computed by: A.A.
Subject: SAFA- DOMESTIC WATER CALCULATIONS Checked by: A.A.
Staff Residential building Approved by: A.E.

A-WATER DEMAND

FIXTURE TYPE QUANTITY FIXTURE UNIT TOTAL FU


LAV-1 36 1 36
WC (FT) 36 5 180
WC (FV) 0 10 0
SHOWER 36 3 108
HB 0 2.5 0
UR 0 5 0
JS 1 4 4
WT 0 2 0
DF 0 2 0
KS-1 36 4 144
FLOOR TOTAL FU 472

REQUIRED FLOW = 120 GPM


CONNECTION SIZE = 65mm

TOTAL REQUIRED FLOW = 120 GPM =7.57 L/S

B-PRESSURES
Friction
Estimated pipe length (m) = 62
Total Equiv. Length (m) = 77.5
Estimated Pipe Size (inch) = 2.5
Pressure drop, (psi / 100 ft) = 3.95
Total Friction Loss (psi) = 10
Total Friction Loss (m) = 6.8

STATIC HEAD IN METERS = 6.8 (GROUND )

RESIDUAL PPRESSURE IN METERS = 3.5

FRICTION LOSS IN METERS = 6.8

TOTAL HEAD IN METERS = 17.1 = 1.7132293 BARS