Beruflich Dokumente
Kultur Dokumente
7HFKQRORJ\VRIWZDUHPRGXOH
IRUWKH
FORVHGORRSFRQWURORIFUDQHGULYHV
with
AL: N
ECCN: N
Statistical product number: 49019900
Notes/FAQs (frequently Asked Questions):
With load-dependent field weakening you must pay attention to the input of output
hyperbole characteristic (P527-P538). The output hyperbole characteristic must be either
normalised to the device current or the current of the SIMOREG DC MASTER 6RA70 (to
the T300/pcd 4) must be scaled to the motor current. (module hoisting gear)
When semi-automatic mode is selected, the master switch enters the maximum speed
setpoint. Depending on the speed setpoint polarity the position setpoint 1 or position
setpoint 2 is selected.
A positive speed setpoint needs a position setpoint1, which is larger than the actual
position, to approach the target position.
A negative speed setpoint needs a position setpoint2, which is smaller than the actual
position, to approach the target position.
(module hoisting gear, holding gear, slewing gear and traversing gear)
Notes/FAQs (frequently Asked Questions):
When semi-automatic mode is selected, the master switch enters the maximum speed
setpoint. Depending on the speed setpoint polarity the position setpoint 1 or postion
setpoint 2 is selected.
A positive speed setpoint needs a position setpoint 1, which is larger than the actual
position, to approach the target positon.
A negative speed setpoint needs a position setpoint 2, which is smaller than the actual
position, to approach the target positon.
Changes
Version Date Changes
V1.10 01.07.99
V1.11 01.11.99 - Type transformation of parameter (H171-H174): Nominal pulse num-
ber for 100 % position (H171, H173 transformed; H172, H174 de-
leted)
V1.20 01.01.01 - New function braking with constant distance added
- Parameter for factory setting added
- Max. process data of the communication board have been increased
to 16 process data words
- free process data has been connected with the basic drive / com-
munication board
- Selection of closed-loop position control via control word is possible
- Allocation of digital inputs and digital outputs has been changed for
commissioning purposes
- Overspeed monitoring in field-weakening range added
- Allocation of the alarm display has been changed
- Signal position control active has been included
- Setting of position difference has been modified when synchronous
operation is chosen
V1.21 01.02.01 - Overspeed monitoring in field-weakening range revised
NOTES
This documentation describes the software implementation of the closed-loop technology control
of crane drives.
The installation, connection and commissioning of the equipment and modules is not described
here. These are provided in sufficient detail in the Instruction Manual of the equipment.
The information on danger, warning notes and cautionary measures should also be taken from
the appropriate Instruction Manuals of the devices.
Further, it is assumed that the equipment is installed, commissioned and serviced by suitably
trained and qualified personnel, who are both knowledgeable about the product itself as well as
the particular industry sector.
This document also doesnt describe basic and simpler functions related with crane drives.
No part of this publication may be reproduced or transmitted in any form or by any means, elec-
tronic or mechanical, including photocopy, recording, or any information storage and retrieval
system, without permission in writing from the publisher.
STRUCTURE
'HVFULSWLRQRIWKHFRQFHSW
Presently, SIMOREG DC-MASTER 6RA70 devices are being used for the closed-loop control of DC
crane drives and SIMOVERT MASTER DRIVES CUVC for AC drives.
In order to implement the technological closed-loop control tasks and functions, in almost all cases, it
is necessary to use an additional T300 technology processor in the units mentioned above.
The T300 is a freely-configurable technology processor with analog and digital inputs and outputs, two
connections for pulse encoders, serial interfaces etc. On the plant/system side, these connections are
routed to the SE300 terminal block. This is connected to the T300 technology module using screened
round cables. (For this application, only the pulse encoder connections, the analog inputs and outputs
and the serial interfaces are used. The digital inputs and outputs are only used for commissioning
purposes.)
The sub-modules (Eproms, program memory modules) for the T300 are programmed with the
STRUC programming language from SIMADYN D. However, these are not required for this particular
application.
The T300 technology module is used in the electronics box of the drive converter units as option
board (slot 2). Module T300 is shown on Page 9, the installation on Page 8 as well as a connection
example on page 16.
For the various crane drive types, the necessary and frequently required closed-loop control struc-
tures and functions required for these drives, are combined in drive-specific software modules. These
are listed in the table on Page 10 together with the functions which have been implemented.
If other functions are required, which are not listed in the table on the next page, then these must be
implemented as custom software.
With the software, the open-loop- and closed-loop control tasks are clearly separated. These are exe-
cuted in the systems which have been designed for these purposes, i.e. the implementation of all of
the open-loop control functions in the SIMATIC as well as implementation of all closed-loop control
functions which are distributed in the drive control system.
Digital interlocking, e.g. controlling contactors, generating enable signals for the drive must therefore
be implemented in the higher-level open-loop control system. Only the drive-specific closed-loop
control circuits and functions are implemented in the freely-programmable technology modules.
The closed-loop technology control is realized in the technology modules. However, the closed-loop
speed control and the closed-loop current control in the basic drives are fully utilized.
The complete control (control words and setpoint-actual values) of the drive converters is realized via
this interface. (The communication board CBP/CBP2 has to be inserted in slot G via the adaption
board ADB (slot 3)).
The essential signals from the automation system to the drives are four 16-bit control words as well as
the setpoints for the speeds and the position setpoint for a closed-loop position control.
The communications between the technology module and a basic drive is realized through a DPR (dual
port Ram).
The setpoint is entered from the master switch via ET200, SIMATIC and Profibus to the drive unit.
The position actual values must be sensed for the closed-loop position control of a drive. In many
cases, this can be realized using the speed encoder is mounted on the motor.
For the grab position control of a grab crane or for the closed-loop synchronous control of two drives,
it is necessary to sense the position actual values of both drives. This can also be realized using the
pulse encoder, mounted on the motor for the speed actual values.
The pulse encoder signals for the speed actual value sensing are fed to the basic drives and for the
position actual value sensing, to the technology module. It is also possible to mount additional pulse
encoders on the cable drum.
The necessary parameters are defined as technology parameters and these can be set and changed.
They are set via the basic drive operator panel. It is also possible to parameterize the units (basic
drive and technology module) using the SIMOVIS service tool. (The database of the T300 technology
module is included in delivery.)
An overview of the concept is shown in the following block diagram using as an example, the holding-
and closing gear of a grab crane. The block diagram is also valid for an individual drive or a master-
slave drive.
control words
n** status words
n*
s*
ET ET ET
CB CB
peer to peer
TB n*, i* TB
master switch
HW and SW
GG GG
1 2 3 4 5 6 7 8
Memory module
for slot in T300
X132 (RS232)
Peer-to-peer-
connection X133 (RS485)
(to other T300
units, to the SCB2 X134 (RS485)
or SIMOREG
6RA24)
X136
SC58 SC60
Length of
1 the round 1
cables: 2 m
+RLVWLQJJHDU
Load-depending field weakening Position sensing with synchronization (of the position)
Heavy load operation (reduced setpoint) Closed-loop position control (for automatic- or
Jogging manual operation)
Ramp-function generator changeover for field- Non-linear master switch setpoint
weakening and heavy loads Pre-limit switch
Changeover to synchronous operation control with Start pulse
one-only (manual) setting of the position difference Monitoring functions
(slave operation) Current distribution monitoring
Braking with constant distance
+ROGLQJJHDU
Non-linear master switch setpoint Position sensing with synchronization (of the position)
Closed-loop position control (for automatic or Pre-limit switch
manual operation) Monitoring functions
Jogging Influencing the ramp-function generator dependent
Working angle-dependent accelerating time on the system deviation
Working angle-dependent slewing speed
7UDYHUVLQJJHDUPDVWHU
Non-linear master switch setpoint Position sensing with synchronization (of the position)
Closed-loop position control (for automation- or Pre-limit switch
manual operation) Monitoring functions
Jogging Current distribution monitoring
Changeover to synchronous operation control with
one-only (manual) setting of the position difference
(slave operation)
7UDYHUVLQJJHDUVODYH
The communications between these two systems is implemented via Profibus SINEC L2-DP.
This serial peripheral SINEC L2-DP bus system is optimized for extremely fast cyclic master-slave
operation. In this case, the drives are always operated as slaves; the higher-level system has the
master function, which in this case is the SIMATIC.
The net data structure with which a DP master can access the drives is described in the following text.
The SINEC L2-DP transfers the net data with the SRD utility (Send and Request with Data). This
means, that net data are always transferred via the bus, both from the master to the slave as well as
in return telegrams from the slave to the master.
The master formulates a task, the slave processes this task and formulates the appropriate response.
There is precisely one task in each telegram from the master to the slave; there is precisely one re-
sponse in each telegram from the slave to the master.
The length and structure of the net data are permanently specified, and are known as 3arameter 3ro-
cess data 2bjects (332).
Five types are defined to transfer net data (PPO), with which process data, i.e. control words, status
words, setpoints and actual values can be simultaneously transferred, also parameters from the
master to the slave and vice versa.
The PPOs are sub-divided into two areas: 3.: (parameter identification value)
3=' (process data)
The PKW area allows parameter values to be read and written into and parameter descriptions and
texts read. Every drive parameter can be visualized or changed via this mechanism.
The PZD area contains all of the necessary signals which are required for process control. These
include control words and setpoints from the automation to the drive and status words and actual
values from the drive to the automation system.
The advantage in this case is that in a telegram, both the cyclically required process data can be
transferred, and it is also possible to simultaneously access parameters (reading/writing).
1
Cyclical data can be freely-configured by using the communication board CBP2 with the Engineer-
ing Tool DriveES (no PPO-type). There are up to 16 process data words configurable. Independent
from the amount of process data a parameter area (PKW) is configurable. So you are not dependent
on the 5 predetermined PPO types.
System connector
Fixing screw
LED (green)
LED (yellow)
LED (red)
Fixing srcew
PKW PZD
PZD1 PZD2
IND PWE STW1 HSW PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
ZSW1 HIW
1st 2nd 3rd 4th 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th
PPO1
PPO2
PPO3
PPO4
PPO5
The data transfer within the "slave modules", i.e. between the drive converter and CB, is realized
using internal SIEMENS data transfer mechanisms, the so-called device response. The data is
transferred between the communications module and drive converter via the DUAL PORT RAM
(DPR).
Data transfer between the communications module CB and the basic drive is realized via a dual port
RAM coupling (DPR). Both sides, CB and basic drive can access the memory of the dual port RAM
writing and reading. The dual port RAM chip is provided on the CB.
If an additional TB technology module is provided, then this is switched between the CB and the basic
drive. In this case, the dual port RAM of the CB is the interface to the TB and dual port RAM on the
TB is the interface to the basic drive (configuration TB-CB basic drive).
The initialization data transferred between CB and the basic drive is not influenced by the TB, i.e. the
technology module copies the data from its dual port RAM one-to-one into the dual port RAM of the
CB and vice versa. The function must be appropriately configured in the TB.
16 pieces of process data can be transferred in both directions between the TB and basic drive.
This communications connection is generally used for master-slave drives, where the master setpoint
for the slave drive(s) is (are) entered from the master drive.
This is also the case for holding- and closing gears of a grab crane where the speed setpoint for the
closing gear and the current setpoint for the current equalization control is transferred to the closing
gear via this coupling.
This coupling is realized using a fast peer-to-peer connection between the technology modules.
A maximum of 5 PZD data words can be transferred in both directions via this interface.
peer
to
peer
T300 5 unit 2
words
1 2 3 4 5 6 7 8
control word 1
IG
control word technology 1
setpoints
ET200 ET200
functions functions
n* n* ML
2
PROFIBUS i*
SINEC L2 DP
M
technological
control
nist
n
1 i* T
nist
monitoring
acknowledge monitoring
sist acknowledge
nist nist
status word 1
status word 2
1 2 3 4 5 6 7 8
1.8 basic signal characteristics and structure of the closed-loop control I&S IT PS Erl 35 01.02.01 V 1.21 page 16
1.9 Connecting-up diagram for the T300
2 pulse encoder inputs
+24 V +24 V
Fine HTL-signal level, max.
pulse Input frequency 400 kHz
Coarse
Zero- +15 V Zero-
+15 V Input current per channel:
pulse pulse
pulse 90 0 90 0 4 mA
X5.538 537535 533 531 540 539 548 547 545 543 541 549
+15V X133
Pulse encoder Pulse encoder
detection 1 detection 2
6
X5
Serial interface 1
7
501 e.g. for service,
+ A RS485, 2-wire
+10
- V 502 - 8
start-up with PC/PG
D
T/Rx+
503
+ A 9
+10
- V 504 - D T/Rx- Either RS232 or RS485
10
505 interface useable!
+ A X132
+10
- V 506 - D RxD 1
TTL
7 analog inputs 507 RxD 2
Differential inputs + A RS232
+10
- V 508 - D 3
11 bits + sign
10 V/ k 4
511
+ A 5
+10
- V 512 - D X134
513 RS485, 4-wire
+ A Tx+ 13
+10 V 514 -
Micro-
- D
processor Tx- 14
515 Serial interface 2
A
CPU:
+ Rx+ 11 (peer-to-peer)
+10
- V 516 - D 80C186
20 MHz Rx- 12
X6
15
+24 V 610
+ 11 bit + VZ X5
601 D 509
602 A
510
603
8 binary inputs D
604 519
24 V DC A
(input current 605 520
4 analog outputs
8 mA typical) 606
D 521
11 bits + sign
607 + 10 V / 10 mA.
A
608 522
D 523
+24 V 630
A
524
+
611 X6
639 +24 V
612
Slot for 631
613 memory
8 binary inputs 632
614 module, e.g.
24 V DC MS 300 633 8 binary outputs
(input current 615
634 24 V DC / max. 100 mA
8 mA typical) 616 Base load 40 mA for
635
617 external P24 infeed which
636
can also come from
618 637 the basic unit
638
640
VZ = sign
In order to establish error-free communications and functionality between SIMATIC and the drive unit,
the following parameter settings must be made in the basic drive of the converter or inverter. De-
pending on the selected BICO data set, these settings are made in index 1 or 2. These are:
3=' &RQWUROZRUG
The bits assigned by the SIMATIC must be interlocked with the appropriate parameters (refer to
the Compendium Vector Control, function chart 180). The following parameterization must be
made if, for example, all control bits are assigned by the SIMATIC.
P554.1 or 2 = 3100
P555.1 or 2 = 3101
P558.1 or 2 = 3102
P561.1 or 2 = 3103
P562.1 or 2 = 3104
P563.1 or 2 = 3105
P564.1 or 2 = 3106
P565.1 or 2 = 3107
P568.1 or 2 = 3108
P569.1 or 2 = 3109
P571.1 or 2 = 3111
P572.1 or 2 = 3112
P573.1 or 2 = 3113
P574.1 or 2 = 3114
P575.1 or 2 = 3115
Otherwise, the parameters which are to be not controlled from the SIMATIC, should be left in the
factory setting.
3=' 6SHHGVHWSRLQW
P443.1 or 2 = 3002
The bits assigned by the SIMATIC should be interlocked with the appropriate parameters (refer to
the Compendium Vector Control, function chart 190). The following parameterization must be
made, if for example, all control bits are to be assigned by the SIMATIC.
P576.1 or 2 = 3300
P577.1 or 2 = 3301
P578.1 or 2 = 3302
P579.1 or 2 = 3303
P580.1 or 2 = 3304
P581.1 or 2 = 3305
P582.1 or 2 = 3306
P583.1 or 2 = 3307
P584.1 or 2 = 3308
P585.1 or 2 = 3309
P586.1 or 2 = 3310
P587.1 or 2 = 3311
P588.1 or 2 = 3312
P589.1 or 2 = 3313
P590.1 or 2 = 3314
P591.1 or 2 = 3315
Otherwise, the parameters which are not to be controlled from the SIMATIC, should be left in the
factory setting.
3=' 6WDUWSXOVH
P506.1 or 2 = 30042
3=' 6WDWXVZRUG
P734.1 = 32
3=' 6SHHGDFWXDOYDOXH
P734.2 = 148
3=' 6WDWXVZRUG
P734.3 = 33
3=' &XUUHQWVHWSRLQW
P734.4 = 168
3=' 6\VWHPGHYLDWLRQ
P734.5 = 152
The remaining available process data can be connected and used individually.
2
The start pulse has to be parameterized just for hoisting gear, holding gear and closing gear (mod-
ules 1-3) because it is only relevant for these gears
Introduction and overview V1.21 19 01.02.2001
Copyright Siemens AG All Rights Reserved
1.10.2 SIMOREG DC MASTER 6RA70
3=' &RQWUROZRUG
The bits assigned by the SIMATIC are interlocked with the appropriate parameters (refer to the
Instruction Manual SIMOREG DC MASTER, function chart 33). The following parameterization
must be made, if for example, all of the control bits are to be assigned by the SIMATIC.
P654.1 or 2 = 3100
P655.1 or 2 = 3101
P658.1 or 2 = 3102
P661.1 or 2 = 3103
P662.1 or 2 = 3104
P663.1 or 2 = 3105
P664.1 or 2 = 3106
P665.1 or 2 = 3107
P668.1 or 2 = 3108
P669.1 or 2 = 3109
P671.1 or 2 = 3111
P672.1 or 2 = 3112
P673.1 or 2 = 3113
P674.1 or 2 = 3114
P675.1 or 2 = 3115
Otherwise, the parameters which are not to be controlled from the SIMATIC, should be left in the
factory setting.
3=' 6SHHGVHWSRLQW
The bits assigned by the SIMATIC are interlocked with the appropriate parameters (refer to the
Instruction Manual SIMOREG DC MASTER, function chart 34). The following parameterization
must be made if, for example, all of the control bits are assigned by the SIMATIC.
P676.1 or 2 = 3300
P677.1 or 2 = 3301
P678.1 or 2 = 3302
P679.1 or 2 = 3303
P680.1 or 2 = 3304
P681.1 or 2 = 3305
P682.1 or 2 = 3306
P683.1 or 2 = 3307
P684.1 or 2 = 3308
P685.1 or 2 = 3309
P686.1 or 2 = 3310
P687.1 or 2 = 3311
P688.1 or 2 = 3312
P689.1 or 2 = 3313
P690.1 or 2 = 3314
P691.1 or 2 = 3315
Otherwise, the parameters which are not to be controlled from the SIMATIC, should be left in the
factory setting.
3=' 6WDUWSXOVH
P501 = 30043
3=' 6WDWXVZRUG
U734.1 = 32
3=' 6SHHGDFWXDOYDOXH
U734.2 = 167
3=' 6WDWXVZRUG
U734.3 = 33
3=' &XUUHQWVHWSRLQW
U734.4 = 120
3=' 6\VWHPGHYLDWLRQ
U734.5 = 165
The remaining available process data can be individually connected and used.
3
The start pulse has to be parameterized just for hoisting gear, holding gear and closing gear (mod-
ules 1-3) because it is only relevant for these gears
Introduction and overview V1.21 21 01.02.2001
Copyright Siemens AG All Rights Reserved
7HFKQRORJ\VRIWZDUHPRGXOH
IRUWKH
FORVHGORRSFRQWURORIFUDQHGULYHV
PRGXOHKRLVWLQJJHDU
STRUCTURE
'HVFULSWLRQRIWKHIXQFWLRQV
This application of the T300 module works with a speed scaling of 100% for maximum speed.
For closed-loop controlled drives, for various operating cases, an attempt is made to increase the
speed above the rated speed. This is used, for example, for hoisting gear of cranes at partial loads to
increase the handling performance, i.e. moving more loads in less time.
This function is implemented using the load-dependent field weakening.
Step 1
When field weakening is selected (using the master switch), depending on the load, in addition to the
maximum value for the base speed range, entered from the master switch, a supplementary speed
setpoint, permissible for the actual load, is generated for field weakening.
The load actual value is determined from the torque-generating current and the accelerating torque,
which is determined via the speed actual value. The values for current and acceleration are inte-
grated-up over several sampling times to obtain a precise determination, and the arithmetic average
generated.
Step 2
When accelerating, the torque-generating current is measured, which, in the base speed range, is
directly proportional to the total torque M provided by the motor. The accelerating torque of the rotat-
ing masses (moment of inertia j) and the accelerating torque of the load is subtracted from this total
torque.
The subsequent torque equation is used to calculate the steady-state load currents:
Step 3
After the steady-state load actual value has been calculated (steady-state torque ML of the load), the
permissible supplementary speed setpoint is calculated for field weakening. This is dependent on the
calculated torque for P = PN (via the output hyperbole characteristic of the motor, implemented as
parameterizable polygon characteristic).
Step 4
The calculated, load-dependent supplementary speed setpoint is then included in the setpoint input of
the master switch and a total setpoint generated for the speed setpoint input. When accelerating, it is
added with that from the master switch, and when decelerating, can be added or multiplied with that
from the master switch.
M
MM = Mload + MBload + MBrot + Mfriction
MBload
MM : motor total torque
MBrot Mload : steady-state load torque
MBload : acceleration torque
Mfriction of load
MBrot : acceleration torque
Mload of rotating masses
t Mfriction : friction torque
1 2 3 4 5 6 7 8
output motorized
hyperbole potentiometer
i
Mload n** Zus
calculation of load current
i > iN
1 2 3 4 5 6 7 8
Using this function, the drive can be sensitively operated via the master switch for manual position-
ing.
Often, the master switch supplies a setpoint, which is directly proportional to its deflection angle. In
order that at low deflection angles, lower speed setpoints are obtained than those which would linearly
correspond to the deflection angle, the master switch setpoint is controlled as a non-linear function.
This means, that when changing the deflection angle at low angles of deflection, this results in speed
changes which are lower than the same change of the deflection angle in the center and higher de-
flection range. In practice this means that the drive can be manually and precisely corrected. The
non-linear function is implemented in the I and III quadrants using 3 adjustable straight line sections.
B6
B5
x A1 A2 A3 B4
n** linear n** non-linear
x
y
B3 A4 A5 A6
master switch B2
B1
1 2 3 4 5 6 7 8
This function is required, if the hoisting gear is used to hoist loads which exceed the rated load.
For heavy load operation, loads exceeding the rated load can be hoisted. Generally, however, this is
only permissible at reduced speeds as a result of the mechanical crane design. Thus, for this operat-
ing mode, the master switch setpoint is multiplied by a selectable factor of < 1. This means that the
deflection range can be fully utilized with a reduced setpoint input.
ramp-function
generator
n** n*
100% 0
1
50%
selection
heavy duty
1 2 3 4 5 6 7 8
This function prevents the drive approaching the limit switch or entering the buffer zone at full speed.
When a pre-limit switch is passed-over, the speed setpoint in front of the ramp-function generator is
limited to a selectable speed. The position of the pre-limit switch with respect to the limit switch or the
buffer zone is dimensioned, so that the drive is reliably braked via the ramp-function generator from
the maximum speed down to the selectable pre-limit switch speed.
ramp-function
generator
TH TR
0% 0 n**
e.g. nmax. 1
n*
master switch
n*
(vmax - vVE) TR
s= = e.g. 20m
2
nVE
appr. TR
s = 20m
1 2 3 4 5 6 7 8
Using this function, the drive can be moved with small speed setpoint intervals. This is required, for
example, to attach the cable to the hoisting gear.
ramp-function
generator speed controller
0
1
jogging
setpoint
command jogging
direction 1
command jogging
direction 2
command jogging
direction 1
command jogging t
direction 2
jogging setpoint
direction 1
jogging setpoint t
direction 2
1 2 3 4 5 6 7 8
jogging
speed controller
n* i*
nist
selection
enable start
pulse
1 2 3 4 5 6 7 8
start pulse
This function is required for hoisting gear with field weakening in order to prevent the drive going to its
current limit when accelerating in the field-weakening range.
At low loads (steady-state load torque), in order to increase the load handling performance, the speed
is increased to a permissible speed, corresponding to the load, by reducing the field current. This
means, that in the field weakening range, the accelerating torque available is appropriately reduced.
For the steady-state load torque and the accelerating torque of the load, only that lower torque, corre-
sponding to the lower load, is required. The accelerating torque of the rotating masses remains the
same due to the unchanged moment of inertia (this is independent of the load).
For hoisting gear, the ramp-function generator is normally set, so that the drive, when accelerating
and hoisting with rated load, and full motor field, is just about to go into current limiting. This keeps
the accelerating- and decelerating travel as short as possible.
If in the field-weakening range, the ramp-function generator is also set to the base speed range val-
ues, when accelerating in the field-weakening range, the drive goes into current limiting as the avail-
able accelerating torque in the field-weakening range is not adequate for the same acceleration of the
base speed range with unchanged moment of inertia (the accelerating torque of the rotating masses
is independent of the load.
If the ramp-function generator is set, so that the drive when accelerating, even in field weakening,
doesnt go into current limiting, for constant acceleration in the base speed- and field weakening
ranges, long accelerating- and decelerating distances are obtained.
In order to optimize this, the ramp-up time can be extended at the transition into the field-weakening
range.
For heavy load operation, in order to reduce the accelerating torque, a high accelerating time can be
immediately switched-in when selecting heavy load operation.
n*
nFS
nbase
1 2 3 4 5 6 7 8
ramp-function generator changeover in the field weakening range and when selecting heavy load duty
This function is required, if the drive should be closed-loop position controlled or have closed-loop
synchronous operation control.
The position actual value has to be synchronized, if the position actual value of the drive which
should be controlled, should be set to an absolute position at a point on the travel. This corrects erro-
neous measurements or erroneous pulses.
The prerequisite for positioning (closed-loop position control) of a drive or closed-loop synchronous
position control of two drives is the ability to sense the actual position. This, in almost all cases, can
be realized using the speed encoder mounted to the motor (pulse encoders are used, analog ta-
chometers are not suitable).
Technology module T300 has, in the form of its terminal module, pulse encoder sensing inputs 1 and
2 which can be simultaneously read-in from a block.
The pulse encoder signals are routed to the basic drive for actual speed sensing the technology
module for actual value sensing.
For closed-loop position control of a drive, under certain circumstances, it is necessary to synchronize
the position actual value of the drive at a point along the complete travel. For instance, this is always
required, if errors in the position actual value sensing of the drive occur as a result of the pulse en-
coder and the influence of noise and disturbances.
The synchronization function has the task to correct this possibly erroneous position actual value. In
this case, the sensed actual value position is re-referenced to an absolute synchronizing mark.
When the synchronizing point is passed (synchronizing mark), this is sensed per hardware using a
Bero via the zero pulse encoder, and the position actual value is thus synchronized.
Further, it is also possible to sense this synchronizing point via the SIMATIC and to synchronize the
system to a specified value via the control word from the SIMATIC.
In this case, the counter of this actual value sensing is set once at a defined point along the total
travel, to an absolute position actual value corresponding to this specific point. Thus, this corrects
possible wheel slip or erroneous pulses.
This means that synchronization represents a position actual value correction. The synchronization
has nothing to do with the basic closed-loop control structure, as when synchronizing, the position
actual value is only corrected at the synchronizing point.
For closed-loop synchronous position control of two drives, the actual value position difference sens-
ing, implemented for the slave operation, can also be used, if it is sufficient to manually set the posi-
tion difference once, to which the system should be controlled.
At changeover, the actual position difference value is saved as setpoint. This is used with the closed-
loop synchronous operation control as setpoint until it is again cancelled.
However, if automatic synchronization is required at certain intervals (e.g. due to the possibility of
erroneous pulses) at several synchronization points, then the traversing gear slave module must be
used.
For the closed-loop position synchronous control for both drives, the position actual values of both
drives must be sensed. The pulse encoder, mounted on the motor for the speed actual values can be
used for this purpose.
The pulse encoder signals are routed to the basic drive for speed actual value sensing and to the
technology board of the second drive for position actual value sensing.
However, the position actual value of the drive must always be connected to pulse encoder sensing
input 1 and that of the master drive to pulse encoder sensing input 2 (for the slave).
setpoints setpoints
AAT
ramp-function
position control
AAT generator
<0%
WSR2
hw-syn. via 1
index signal WSR1 0 1 hw-syn. via index
input 0
+ signal input
WSAUT -
synchronisation
SE SE controller
AGL y=x
actual y
x
X5M position X5M position
sist s
value difference
X5N evaluation nist X5N evaluation
synchron nist
WSSYN WSSYN
n* n*
i* i*
nact nact
M T M T
T T
1 2 3 4 5 6 7 8
hard- and software structure for position and synchronisation control I&S IT PS Erl 35 01.02.01 V 1.21 page: 12
2.9 Closed-loop position control
This function is required if a drive should approach a specified target closed-loop position controlled
in the shortest time.
The demand for ever increasing handling performance has meant that for hoisting drives, the drives
must be able to approach a specified target position as quickly as possible.
By applying the position equations and taking into account limiting conditions, it can be determined
that this can be achieved using the square root function.
v = 2as
If this relationship is implemented, the drive can approach a specified point, closed-loop position con-
trolled, in the optimum time. The master switch enters the speed setpoint. If the drive approaches the
target, then from a calculated initiation point, the speed setpoint from the master switch is limited as a
function of the position. The position actual value is available from a pulse encoder. The SIMATIC
specifies the final target (position setpoint).
When the semi-automatic- or automatic modes are selected, a speed setpoint is automatically en-
tered, dependent on the position setpoint input (polarity) (from the SIMATIC).
After the optimum speed setpoint has been calculated, dependent on the actual position actual value
difference, this setpoint is conditioned corresponding to the particular operating mode.
For example, in manual operation, only the speed direction is enabled, in which the master switch is
set.
On the other hand, in the automatic mode, both directions of rotation must be enabled, so that the
drive can automatically correct itself, for instance, after it has passed the target position.
Further, it is possible to select a parameterizable crawl speed, if the position controller output has
reached (fallen below) this parameterizable value.
speed setpoint
speed setpoint (S7) 0% 0 to CU
speed
0 1
setpoint
1
setpoint
AAT enable
(S7)
+100% 0
1
-100%
x x
y>x y>x
0% y 0% y
master switch
polarity
T
hw-syn. via index signal input pulse sist
synchronisation setpoint from S7 encoder x
y>x 0
sw-syn. via control word from S7
evaluation 0% y
1
AAT
1
1 2 3 4 5 6 7 8
signal flow chart position control overview I&S IT PS Erl 35 01.02.01 V 1.21 page: 14
2.10 Possibility of changing over to slave operation with closed-loop synchronous operation
control and single (manual) setting of the position difference
This function is required, if two or several hoisting- or traversing drives which are normally operated
closed-loop speed controlled individually and independently of one another, must operate in synchro-
nism with one another for specific operating situations.
This is the case, for example, if trolleys or traversing gears, which are not mechanically coupled, must
hoist or move a common load.
For this operating case, it is necessary to provide closed-loop synchronous position control between
the trolleys or between the hoisting gears. Initially, the drives operate in single-motor operation to
connect-up a load, and can then be changed-over at any position to closed-loop synchronous opera-
tion control.
When two drives are operated in synchronism, the slave drive follows the master drive, closed-loop
synchronous position controlled with a position difference setpoint, which should be saved.
At changeover, the actual position difference value is saved as setpoint. This is used as setpoint for
the closed-loop synchronous operating control until it is cancelled again.
For this operating case, the separately speed-controlled drives must also be coupled with one another
through the control system via a synchronous operation control in the slave drive. They must also
operate in synchronism (position) even when the load is unevenly distributed.
The synchronous operation controller is superimposed on the closed-loop speed control of the slave
drive. The inputs of the synchronous operation controller are the stored position difference actual
value as setpoint and the actual position difference value as actual value. The output of the synchro-
nous operation controller acts as supplementary setpoint at the setpoint of the slave drive speed con-
troller.
When closed-loop synchronous operation control is activated, and a position difference develops
between the drives, then the slave drive receives a supplementary speed setpoint via the synchro-
nous operation controller. This operates this drive with an increased or decreased speed setpoint,
until the position difference is again zero. The supplementary setpoint (the intervention of the sup-
plementary setpoint from the synchronous operation controller) should in this case be a maximum of
20% to 30% of the max. drive speed.
1 2 3 4 5 6 7 8
speed setpoint to
0% 0 basic unit i*
speed setpoint (S7) 1
setpoint
position setpoint (S7)
enable (S7)
actual position
value
position synchronization
value (S7) pulse sist
encoder
T evaluation
peer to peer
synchronize
slave
n-controller
speed setpoint to
speed setpoint (S7) 0% 0 basic unit i*
0 1
1
evaluation X
selection
synchronism
enable (S7)
synchronize synchronization
controller (S7)
1 2 3 4 5 6 7 8
signal flow chart synchronization control overview I&S IT PS Erl 35 01.02.01 V 1.21 page: 17
2.11 Current distribution monitoring
This function can be used for slave drives (if it is practical). For a master-slave drive, it monitors that
the total torque (current) is evenly distributed over both drives. However, as described above, this is
not always the case.
CBP CBP
ramp-function ramp-function
generator generator
n* peer to peer n*
i* i*
monitoring
status word
- bit 8
+
T300 T300
n* i* n* i*
CU CU
master slave
1 2 3 4 5 6 7 8
This function continually monitors the speed setpoint and speed actual value, which, when the system
is operating correctly, must approximately correspond with one another.
This monitoring function responds, for example, if the closed-loop control goes to its current limit due
to an overload or a stalled drive, as the speed actual value can no longer follow the speed setpoint.
However, if the setpoint is less than the response difference, then there is a no signal output if the
actual value is missing. This fault is detected using the interrupted tachometer monitoring function of
the basic drives.
This function can be used for speed-actual-actual monitoring if a drive is equipped with a speed ac-
tual value- and position actual value encoder.
If a drive has, in addition to a pulse encoder for the speed actual value, also a pulse encoder for the
position actual value, which is not mounted to the motor, but for example, to the drum, then monitor-
ing can be realized by evaluating the speeds supplied from both encoders. For instance, this can be
used to monitor the gearboxes or couplings for two rigidly coupled drives.
This monitoring function represents a software centrifugal switch. Using this monitoring function, a
signal can be generated when a selectable speed is exceeded.
Values of between 110-150% of the maximum permissible operating speed are set for these over-
speed protective devices. When an overspeed monitoring function responds, appropriate shutdown
mechanisms can be initiated.
If the field weakening speed is enabled, a signal is generated when the sum of the calculated speed
and an adjustable offset is exceeded.
This function monitors the speed and responds if the selected limit is fallen below.
This signal is mainly used to close the brake. It is also used, for example, in the hoisting gear module
to calculate the supplementary speed setpoint for load-dependent field weakening.
actual speed
signal to status word
value from
+ (technology) bit 4
basic unit -
actual speed
value from
technology board
(NAV)
closed-loop control monitoring
overspeed monitoring
actual speed
signal to status word
value from
(technology) bit 2
basic unit
1 2 3 4 5 6 7 8
monitorings
This function is required, if a drive should slow down from a variable field-weakening speed to zero
speed in sink-operation with a constant braking distance. Braking distance means the resulting way,
which is covered via gearbox and mechanics from the beginning of deceleration to standstill.
Speeds in the field-weakening range can be divided in fixed base speed (nominal speed) and a vari-
able additional speed, which is load-dependent. The braking distance from base speed (nominal
speed) to zero speed is fixed via the scaled deceleration time (H366-H368) (deceleration time from
100% to 0%) of the ramp-function generator (and constant). To get a fixed braking distance from the
variable field-weakening speed to base speed (additional speed), the ramp-down time is calculated
and depends on the corresponding field-weakening speed.
For this calculation the ramp-down time from maximum speed to base speed is needed. This time
has to be parameterized via parameter H391 (scaled to 100%). That the ramp-down time from 100%
to 0% is set to the parameter.
Braking from a variable field-weakening speed to zero speed is realised with the calculated ramp-
time.
With speed below base speed there is a changeover to the parameterized ramp-down time. (H366-
H368)
To use the function braking with constant distance correct, you have to enable the function with pa-
rameter H390 = 1. $GGLWLRQDO you have to select the initiation point from 100% of the root function for
the signal position control active (H267 = 1).
delta s
n*
nMax =100%= 2nGrund
nGrund
t
ramp-down time TR
(H366-368)
1 2 3 4 5 6 7 8
FORVHGORRSFRQWURORIFUDQHGULYHV
PRGXOHKRLVWLQJJHDU
STRUCTURE
SURFHVVGDWDSDUDPHWHUHWF
This application of the T300 is provided for 16 receive and send process data from or to the Commu-
nication Board. The process data words 11-16 could only be configured and used with the Engineer-
ing Tool DriveES and the Communication Board CBP2. The following tables show the allocation of
the process data words. Further on the tables show the goal or source of the process data words, i.e.
the connection of the process data (T300, base unit CU or Communication Board CB).
SURFHVVGDWDIURPDXWRPDWLRQV\VWHPWR7 JRDO
T300 / base
PCD1 control word 1 STEU1
unit
PCD2 speed setpoint from master switch WNMS T300
PCD3 control word 2 STEU2 base unit
PCD4 control word 1 (technology) STEU_TB1 T300
PCD5 control word 2 (technology) STEU_TB2 T300
PCD6 position setpoint direction 1 WSR1 T300
PCD7 position setpoint direction 2 WSR2 T300
PCD8 position setpoint automatic WSAUT T300
PCD9 position synchronization value WSSYN T300
PCD10 start pulse STI T300
PCD11 PCD11_Empf PZD11_Emp base unit
PCD12 PCD12_Empf PZD12_Emp base unit
PCD13 PCD13_Empf PZD13_Emp base unit
PCD14 PCD14_Empf PZD14_Emp base unit
PCD15 PCD15_Empf PZD15_Emp base unit
T300 / base
PCD16 PCD16_Empf PZD16_Emp
unit
SURFHVVGDWDIURP7WRDXWRPDWLRQV\VWHP VRXUFH
This application of the T300 is provided for 16 receive and send process data from or to the base unit.
The process data, which arent used in this application, are connected between the base unit and the
Communication Board. The following tables show the allocation of the process data words. Further on
the tables show the goal or source of the process data words, i.e. the connection of the process data
(T300, base unit CU or Communication Board CB).
SURFHVVGDWDIURP7WREDVHXQLW 6RXUFH
SURFHVVGDWDIURPEDVHXQLWWR7 JRDO
The allocation of the control words for the technology board in this application are appropriately the
following tables. The tables show the level (high- (H) or low-active (L)) of the commands. A descrip-
tion of each control bit follows the tables.
FRQWUROZRUGWHFKQRORJ\
FRQWUROZRUGWHFKQRORJ\
Bit 16 free
Bit 17 free
Bit 18 free
Bit 19 free
Bit 20 load current saved (L) ILS
Bit 21 selection position control (H) AWR
Bit 22 free
Bit 23 free
Bit 24 free
Bit 25 free
Bit 26 free
Bit 27 free
Bit 28 free
Bit 29 free
Bit 30 free
Bit 31 free
A high-signal sets the speed setpoint to the base unit to the value, parameterized via the parameter
H333 (independent of the master switch setpoint / speed setpoint from automation system PCD2).
The setpoint should be for example positive for the direction 1. A low-signal doesnt influence the
master switch setpoint.
%LWFRPPDQGMRJJLQJGLUHFWLRQ+MRJJLQJGLUHFWLRQ/MRJJLQJGLUHFWLRQRII
A high-signal sets the speed setpoint to the base unit to the value, parameterized via the parameter
H332 (independent of the master switch setpoint).The setpoint should be for example negative for the
direction 2 (reverse to direction 1). Command jogging direction 1 has priority, if command jogging
direction 1 and command jogging direction 2 are set together (high). A low-signal doesnt influence
the master switch setpoint.
%LWHQDEOHVWDUWSXOVH+HQDEOHVWDUWSXOVH/GLVDEOH
A high-signal enables the start pulse. At selected start pulse (H453 = 0), the set value (H448) or the
value via automation system decays with the decay time (H451) after low-high level change of the
signal.
%LWQRVHOHFWLRQKHDY\GXW\+QRKHDY\GXW\/KHDY\GXW\
A low-signal evaluates the master switch setpoint via the value of parameter H224 and the ramp-up
or ramp-down time of parameter H362/H366 is active. A high-signal doesnt influence the master
switch setpoint and the ramp-up or ramp-down time of parameter H363/H367 is active.
%LWHQDEOHILHOGZHDNHQLQJ+HQDEOHILHOGZHDNHQLQJ/GLVDEOH
With selected operation mode field weakening via parameter H241 = 1, a high-signal enables the
calculated (plausible) load-dependent additional speed setpoint. Field weakening is demanded via
master switch setpoint (>95% or <-95%, the max. speed must be scaled to 100%). The master switch
setpoint is scaled via parameter H225, if field-weakening is disabled. So the nominal speed couldnt
exceeded.
%LW FRPPDQG SUHOLPLW VZLWFK + SUHOLPLW VZLWFK QRW UHDFKHG / SUHOLPLW VZLWFK
UHDFKHG
A low-signal limits the master switch setpoint to a parameterized value (H311). This signal is deliv-
ered from a proximity switch. A high-signal is delivered, if the switch isnt reached. Then the master
switch setpoint isnt influenced.
%LWHQDEOHSRVLWLRQFRQWURO+HQDEOHSRVLWLRQFRQWURO/GLVDEOH
A high-signal enables the position difference between position setpoint and actual position value. So
the calculation of the position-dependent speed limit is possible. The position control must be se-
lected via control word 2 (technology) bit 21 or H274/H275 before you enable the position control to
influence the speed limit correct. A low-signal sets the speed limit to 0%.
%LWHQDEOHV\QFKURQL]DWLRQFRQWUROOHU+HQDEOHV\QFKURQL]DWLRQFRQWUROOHU/GLVDEOH
A high-signal enables the synchronization controller. A low-signal disables the synchronization con-
troller.
module 1: hoisting gear V 1.21 6 01.02.2001
process data, parameter, etc. Copyright Siemens AG All Rights Reserved
%LWVHOHFWLRQDXWRPDWLFPRGH+DXWRPDWLFPRGH/QRDXWRPDWLFPRGH
A high-signal selects automatic mode. In the automatic mode a drive approach a set target (PCD 8)
with max. speed (100%, independent of master switch setpoint). A selection of automatic mode sup-
poses a selection and a release of position control.
In manual mode (automatic mode isnt selected (low-signal); but position control is selected and en-
abled) the position setpoint direction 1 (PCD 6) or 2 (PCD 7) is active dependent on the polarity of the
master switch setpoint (Software limit switch-function).
%LWVHOHFWLRQV\QFKURQLVP+V\QFKURQLVP/QRV\QFKURQLVP
A high-signal selects the operation mode synchronism. The speed setpoint is set via peer-to-peer-
coupling from master drive. This control is only relevant for slave drives.
%LWV\QFKURQL]HDFWXDOSRVLWLRQYDOXH+V\QFKURQL]H/QRV\QFKURQL]H
A high-signal sets the actual position value to the position synchronization value (PCD 9) given via
automation system.
%LWORDGFXUUHQWVDYHG+ORDGFXUUHQWQRWVDYHG/ORDGFXUUHQWVDYHG
A high-signal doesnt influence the calculated load current. A low-signal saves the actual load current.
So for example the calculated load current of the hoist mode could be saved and also used for sink
mode.
%LWVHOHFWLRQSRVLWLRQFRQWURO+SRVLWLRQFRQWURO/QRSRVLWLRQFRQWURO
A high-signal selects position control. The speed intervention to the master switch setpoint is enabled.
A low-signal limits the master switch setpoint only to +/- 100%.
The allocation of the control words 1 and 2 are appropriately the operating instruction of the base unit
(6SE70 or 6RA70). The following tables show the level (high- (H) or low-active (L)) of the commands.
A description of each control bit you find in the operating instruction of the base unit.
FRQWUROZRUG
FRQWUROZRUG
The allocation of the status word of the technology board in this application is appropriately the fol-
lowing table. The table shows the level (high- (H) or low-active (L)) of the signals. A description of
each status bit follow the table.
VWDWXVZRUGWHFKQRORJ\
%LWVLJQDOIDXOWHQFRGHU+QRIDXOW/IDXOW
A low-signal shows a configuring error of the encoder. The bit is just reset to high-level via the ac-
knowledge command.
%LW VLJQDO VSHHG VHWSRLQWDFWXDO YDOXH GLIIHUHQFH VDYHG + QR VSHHG VHWSRLQWDFWXDO YDOXH
GLIIHUHQFHVDYHG/VSHHGVHWSRLQWDFWXDOYDOXHGLIIHUHQFHVDYHG
A low-signal shows a deviation of the actual speed compared to the speed setpoint, which is larger
than the value parameterized via H456/H457. A larger deviation is saved and the bit is just reset to
high-level via the acknowledge command.
%LWVLJQDORYHUVSHHGVDYHG+QRRYHUVSHHG/RYHUVSHHG
A low-signal shows, if the actual speed is greater than the limit parameterized via H459/H460/H471. A
greater actual speed is saved and the bit is just reset to high-level via the acknowledge command.
A high-signal shows a deviation of the actual speed compared to speed 0, which is larger than the
value parameterized via H461/H462.
A low-signal shows a deviation of the actual speed (T300) compared to the actual speed from the
base unit, which is larger than the value parameterized via H466/H467. A larger deviation is saved
and the bit is just reset to high-level via the acknowledge command.
%LWVLJQDOIDXOWFRXSOLQJ7WREDVHXQLW+ QRIDXOW/IDXOW
A low-signal shows an error between the coupling T300 / base unit. The bit is just reset to high-level
via the acknowledge command.
%LWVLJQDOIDXOWFRXSOLQJWRDXWRPDWLRQV\VWHP +QRIDXOW/IDXOW
A low-signal shows an error between the coupling T300 / automation system (Communication Board).
The bit is just reset to high-level via the acknowledge command.
%LWVLJQDOHQDEOHILHOGZHDNHQLQJ+HQDEOH/GLVDEOH
A high-signal shows, if the field weakening is enabled. This supposes the release via control word 1
(technology) bit 4 and the release via load calculation.
%LWVLJQDOIDXOWFXUUHQWGLVWULEXWLRQGLIIHUHQFH+QRIDXOW/IDXOW
A low-signal shows a deviation of the current setpoint/slave compared to the current setpoint/master,
which is larger than the value prameterized via H469/H470. A larger deviation is saved and the bit is
just reset to high-level via the acknowledge command. This monitoring is only active if synchronism is
selected (control word 1 (technology) bit 12) (slave drive).
%LWVLJQDOIDXOWFRXSOLQJSHHUWRSHHU +QRIDXOW/IDXOW
A low-signal shows an error between peer-to-peer-coupling. The bit is just reset to high-level via the
acknowledge command.
%LW VLJQDO ILHOG ZHDNHQLQJ SRLQW UHDFKHG + ILHOG ZHDNHQLQJ SRLQW UHDFKHG / ILHOG
ZHDNHQLQJSRLQWLVQWUHDFKHG
A high-signal shows, if the actual speed is larger than the field-weakening point limit parameterized
via (H463/H464). This is only relevant for DC-drives.
ORFNHG
A high-signal shows, if the ramp-function generator output is equal to the ramp-function generator
input (the ramp-function generator isnt active.). A low-level shows, if the RFG is active or locked.
WLYH
The allocation of the status words 1 and 2 are appropriately the operating instruction of the base unit
(6SE70 or 6RA70). The following tables show the level (high- (H) or low-active (L)) of the signals. A
description of each status bit you find in the operating instruction of the base unit.
VWDWXVZRUG
VWDWXVZRUG
UHFHLYHIURP&RPPXQLFDWLRQ%RDUG&%
UHFHLYHIURPEDVHXQLW&8
d 065 EGG10.Y1 status word 1 from base unit CU Type: V2 page 5/2
d 066 EGG10.Y2 actual speed value from base unit CU Type: N2 page 5/2
d 067 EGG10.Y3 status word 2 from base unit CU Type: V2 page 5/2
d 068 EGG10.Y4 current setpoint from base unit CU Type: N2 page 5/2
d 069 EGG10.Y5 setpoint-actual value difference from CU Type: N2 page 5/2
d 070 EGG10.Y6 PCD 6 from base unit (to CB connected) Type: N2 page 5/2
d 071 EGG10.Y7 PCD 7 from base unit (to CB connected) Type: N2 page 5/2
d 072 EGG10.Y8 PCD 8 from base unit (to CB connected) Type: N2 page 5/2
d 073 EGG100.Y1 PCD 9 from base unit (to CB connected) Type: N2 page 5/2
d 074 EGG100.Y2 PCD 10 from base unit (to CB connected) Type: N2 page 5/2
d 075 EGG100.Y3 PCD 11 from base unit (to CB connected) Type: N2 page 5/2
d 076 EGG100.Y4 PCD 12 from base unit (to CB connected) Type: N2 page 5/2
d 077 EGG100.Y5 PCD 13 from base unit (to CB connected) Type: N2 page 5/2
d 078 EGG100.Y6 PCD 14 from base unit (to CB connected) Type: N2 page 5/2
d 079 EGG100.Y7 PCD 15 from base unit (to CB connected) Type: N2 page 5/2
d 080 EGG100.Y8 PCD 16 from base unit (to CB connected) Type: N2 page 5/2
d 081 EGG20.Y status word 1 to CB Type: V2 page 5/6
evaluation actual speed value from base unit Type: N2
H 082 EGG30.X2 Min: -200% 100 % page 5/3
CU Max: 199,9%
d 083 EGG40.Y status word 2 to CB Type: V2 page 5/6
Type: N2
H 084 EGG50.X2 evaluation current setpoint from base unit CU Min: -200% 100 % page 5/3
Max: 199,9%
evaluation setpoint-actual value difference Type: N2
H 085 EGG60.X2 Min: -200% 100 % page 5/3
from CU Max: 199,9%
Type: N2
H 086 EGG70.X2 evaluation PCD 6 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 087 EGG80.X2 evaluation PCD 7 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 088 EGG90.X2 evaluation PCD 8 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 089 EGG110.X2 evaluation PCD 9 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 090 EGG120.X2 evaluation PCD 10 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 091 EGG130.X2 evaluation PCD 11 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 092 EGG140.X2 evaluation PCD 12 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 093 EGG150.X2 evaluation PCD 13 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 094 EGG160.X2 evaluation PCD 14 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
DQDORJLQSXWV
Type: N2
H 133 AE20.X2 evaluation analog input A Min: -200% 100 % page 7/2
(terminal SE 300 X5/501,502) Max: 199,9%
Type: N2
H 134 AE50.X2 evaluation analog input B Min: -200% 100 % page 7/2
(terminal SE 300 X5/503,504) Max: 199,9%
Type: N2
H 135 AE80.X2 evaluation analog input C Min: -200% 100 % page 7/2
(terminal SE 300 X5/505,506) Max: 199,9%
Type: N2
H 136 AE110.X2 evaluation analog input A Min: -200% 100 % page 7/2
(terminal SE 300 X5/507,508) Max: 199,9%
Type: N2
H 137 AE30.X2 offset analog input A Min: -200% 0% page 7/3
Max: 199,9%
Type: N2
H 138 AE60.X2 offset analog input B Min: -200% 0% page 7/3
Max: 199,9%
Type: N2
H 139 AE90.X2 offset analog input C Min: -200% 0% page 7/3
Max: 199,9%
Type: N2
H 140 AE120.X2 offset analog input D Min: -200% 0% page 7/3
Max: 199,9%
d 141 AE30.Y analog input A after evaluation and offset Type: N2 page 7/3
d 142 AE60.Y analog input B after evaluation and offset Type: N2 page 7/3
d 143 AE90.Y analog input C after evaluation and offset Type: N2 page 7/3
d 144 AE120.Y analog input D after evaluation and offset Type: N2 page 7/3
UHFHLYHSHHUWRSHHU
DFWXDOSRVLWLRQDQGVSHHGVHQVLQJ
d 187 ERX520.Y actual speed value from position encoder Type: N2 page 9/7
(track 1)
VHWSRLQWSUHSDUDWLRQ
Type: B1
H 205 W10.I selection source for speed setpoint Min: 0 0 page 10/1
(0 = from CB / 1 = from analog input 1) Max: 1
d 206 W10.Y speed setpoint before polygon curve Type: N2 page 10/2
Type: N2
H 207 W20.A1 polygon curve value X1 (speed setpoint input) Min: -200% -100 % page 10/2
Max: 199,9%
Type: N2
H 208 W20.B1 polygon curve value Y1 (speed setpoint input) Min: -200% -100 % page 10/2
Max: 199,9%
Type: N2
H 209 W20.A2 polygon curve value X2 (speed setpoint input) Min: -200% -60 % page 10/2
Max: 199,9%
Type: N2
H 210 W20.B2 polygon curve value Y2 (speed setpoint input) Min: -200% -60 % page 10/2
Max: 199,9%
Type: N2
H 211 W20.A3 polygon curve value X3 (speed setpoint input) Min: -200% -30 % page 10/2
Max: 199,9%
Type: N2
H 212 W20.B3 polygon curve value Y3 (speed setpoint input) Min: -200% -30 % page 10/2
Max: 199,9%
Type: N2
H 213 W20.A4 polygon curve value X4 (speed setpoint input) Min: -200% 30 % page 10/2
Max: 199,9%
Type: N2
H 214 W20.B4 polygon curve value Y4 (speed setpoint input) Min: -200% 30 % page 10/2
Max: 199,9%
Type: N2
H 215 W20.A5 polygon curve value X5 (speed setpoint input) Min: -200% 60 % page 10/2
Max: 199,9%
Type: N2
H 216 W20.B5 polygon curve value Y5 (speed setpoint input) Min: -200% 60 % page 10/2
Max: 199,9%
Type: N2
H 217 W20.A6 polygon curve value X6 (speed setpoint input) Min: -200% 100 % page 10/2
Max: 199,9%
Type: N2
H 218 W20.B6 polygon curve value Y6 (speed setpoint input) Min: -200% 100 % page 10/2
Max: 199,9%
d 219 W35.Y speed setpoint after pologon curve Type: N2 page 10/2
d223 W130.Y speed setpoint after selection auto.-manual Type: N2 page 10/3
(speed setpoint by selected operation mode)
Type: N2
H 224 W140.X1 reduce factor for heavy-duty operation Min: -200% 50 % page 10/2
(evaluation speed setpoint with selection heavy-duty) Max: 199,9%
speed setpoint after selection (no) heavy-duty
d225 W150.Y2 Type: N2 page 10/3
operation
base speed at field weakening Type: N2
H 226 W320.X (max. speed is limited to 100%; the base speed is scaled by Min: -200% 50 % page 10/2
the speed range) Max: 199,9%
selection mode field weakening Type: B1
H 241 W370.I (0 = operation mode without field weakening / 1 = operation Min: 0 0 page 10/4
mode with field weakening) Max: 1
speed setpoint after selection (no) field weak-
d 242 W380.Y Type: N2 page 10/4
ening
SRVLWLRQFRQWURO
V\QFKURQL]DWLRQFRQWUROOHU
FKDQJHRYHU
d 310 W420.Y speed setpoint after position control Type: N2 page 10/5
Type: N2
H 311 W410.X1 speed at pre-limit switch Min: -200% 12 % page 10/4
(speed setpoint after overdrive of the pre-limit switch) Max: 199,9%
d 312 W430.Y speed setpoint after pre-limit switch Type: N2 page 10/5
d 330 W470.Y speed setpoint after selection (no) synchronism Type: N2 page 10/7
d 331 W460.Y speed setpoint after selection (no) jogging Type: N2 page 10/6
Type: N2
H 332 W440.X1 jogging setpoint direction 2 (negative direction) Min: -200% -10 % page 10/4
Max: 199,9%
Type: N2
H 333 W440.X2 jogging setpoint direction 1 (positive direction) Min: -200% 10 % page 10/4
Max: 199,9%
d 334 W480.Y speed setpoint after setpoint enable Type: N2 page 10/7
UDPSIXQFWLRQJHQHUDWRU
Type: N2 (scal)
H 362 W570.X1 ramp-up time 1 (ramp-up time at selected heavy-duty
Min: 10ms 4000 ms page 15/4
and not released/signaled field-weakening point) Max: 20000ms
ramp-up time 2 (ramp-up time at not selected heavy-duty Type: N2 (scal)
H 363 W570.X2 and not released/signaled field-weakening point => normal Min: 10ms 4000 ms page 15/4
operation) Max: 20000ms
Type: N2 (scal)
H 364 W580.X2 ramp-up time 3 (ramp-up time at selected/ signaled
Min: 10ms 4000 ms page 15/5
field-weakening point) Max: 20000ms
Type: N2 (scal)
H 366 W530.X1 ramp-down time 1 (ramp-down time at selected heavy-
Min: 10ms 4000 ms page 15/4
duty and not released/signaled field-weakening point) Max: 20000ms
ramp-down time 2 (ramp-down time at not selected Type: N2 (scal)
H 367 W530.X2 heavy-duty and not released/signaled field-weakening point Min: 10ms 4000 ms page 15/4
=> normal operation) Max: 20000ms
Type: N2 (scal)
H 368 W540.X2 ramp-down time 3 (ramp-down time at selected/ sig-
Min: 10ms 4000 ms page 15/5
naled field-weakening point) Max: 20000ms
enable ramp-up-/ ramp-down time for field
Type: B1
H 370 W510.I2 weakening point (0 = no changeover / 1 = changeover of Min: 0 0 page 15/3
ramp-up ramp-down time with reach the field weakening Max: 1
point)
Type: N2
H 374 W630.LU upper setpoint limit at RFG Min: -200% 100 % page 10/7
(upper speed limit at ramp-function generator output) Max: 199,9%
Type: N2
H 375 W630.LL lower setpoint limit at RFG Min: -200% -100 % page 10/8
(lower speed limit at ramp-function generator output) Max: 199,9%
VWDUWSXOVH
Type: B1
H 445 STI05.I selection source for load-dependent start pulse Min: 0 0 page 15/2
(0 = from CB / 1 = from analog input 4) Max: 1
Type: R2
H 446 STI10.T filtering time load-dependent start pulse Min: 10ms 40 ms page 15/2
Max:163840ms
PRQLWRULQJV
Type: R2
H 455 UEB20.T filtering time setpoint-actual value difference Min: 20ms 2000 ms page 14/6
Max:327680ms
setting value for signal setpoint-actual value Type: N2
H 456 UEB30.M Min: -200% 10 % page 14/6
difference Max: 199,9%
hysteresis for signal setpoint-actual value dif- Type: N2
H 457 UEB30.HY Min: -200% 1% page 14/6
ference Max: 199,9%
Type: R2
H 458 UEB60.T filtering time actual speed value Min: 20ms 20 ms page 14/6
Max:327680ms
Type: N2
H 459 UEB68.X1 setting value for signal overspeed Min: -200% 110 % page 14/6
Max: 199,9%
Type: N2
H 460 UEB70.HY hysteresis for signal overspeed Min: -200% 2% page 14/6
Max: 199,9%
Type: N2
H 461 UEB90.M setting value for zero speed signal Min: -200% 5% page 14/6
Max: 199,9%
Type: N2
H 462 UEB90.HY hysteresis for zero speed signal Min: -200% 1% page 14/6
Max: 199,9%
Type: N2
H 463 UEB100.M setting value for signal field weakening speed Min: -200% 70 % page 14/6
(relevant for DC-drives) Max: 199,9%
Type: N2
H 464 UEB100.HY hysteresis for signal field weakening speed Min: -200% 0% page 14/6
(relevant for DC-drives) Max: 199,9%
filtering time speed actual-actual value differ- Type: R2
H 465 UEB130.T Min: 20ms 2000 ms page 14/2
ence Max:327680ms
Type: N2
H 466 UEB140.M setting value for stopping nact- nact -difference Min: -200% 15 % page 14/3
Max: 199,9%
Type: N2
H 467 UEB140.HY hysteresis for stopping nact nact -difference Min: -200% 1% page 14/3
Max: 199,9%
filtering time current actual-actual value differ- Type: R2
H 468 UEB190.T Min: 20ms 2000 ms page 14/3
ence Max:327680ms
Type: N2
H 469 UEB200.M setting value for stopping Imaster-Islave-difference Min: -200% 15 % page 14/3
Max: 199,9%
Type: N2
H 470 UEB200.HY hysteresis for stopping Imaster-Islave -difference Min: -200% 1% page 14/3
Max: 199,9%
offset to calculated field-weakening speed for Type: N2
H 471 UEB66.X1 Min: -200% 10 % page 14/6
signal overspeed Max: 199,9%
:1=
Type: N2
H 501 Z05.X2 evaluation actual speed value (from base unit CU) Min: -200% 100 % page 12/1
Max: 199,9%
d 502 Z05.Y2 evaluated actual speed value Type: N2 page 12/1
d 546 Z750.Q indication I > IN (1 = load current is bigger than nominal Type: B1 page 13/3
current)
decision lock field weakening Type: B1
H 547 Z755.I2 (0 = no lock, if load current is larger than nominal current / Min: 0 1 page 13/3
1 = lock FWS, if load current is larger than nominal current) Max: 1
d 548 Z840.Q indication reset FW Type: B1 page 13/5
selection additive or multiplicative field
Type: B1
H 549 Z905.I4 weakening (1 = additive FW; with speed setpoint lower Min: 0 1 page 13/6
than 98% the FW is locked / 0 = multiplicative FW; the Max: 1
release FW exists to speed 0)
JHQHUDO
VHQGWR&RPPXQLFDWLRQ%RDUG&%
VHQGWREDVHXQLW&8
Type: N2
H 913 SGG20.X2 evaluation speed setpoint to base unit CU Min: -200% 100 % page 6/5
Max: 199,9%
Type: N2
H 915 SGG30.X2 evaluation start pulse to base unit CU Min: -200% 100 % page 6/5
Max: 199,9%
d 945 SGG20.Y2 speed setpoint to base unit CU Type: N2 page 6/7
d 947 SGG30.Y2 start pulse to base unit CU Type: N2 page 6/7
d 954 ECB220.Y2 PCD 11 to base unit CU (from CB connected) Type: N2 page 6/7
d 955 ECB240.Y2 PCD 12 to base unit CU (from CB connected) Type: N2 page 6/7
d 956 ECB260.Y2 PCD 13 to base unit CU (from CB connected) Type: N2 page 6/7
d 957 ECB280.Y2 PCD 14 to base unit CU (from CB connected) Type: N2 page 6/7
d 958 ECB300.Y2 PCD 15 to base unit CU (from CB connected) Type: N2 page 6/7
d 959 ECB320.Y2 PCD 16 to base unit CU (from CB connected) Type: N2 page 6/7
DQDORJRXWSXWV
Type: O2
H 960 AA10.XCS control input multiplexer for analog output H Min: 0 1 page 7/5
Max: 32767
Type: O2
H 961 AA50.XCS control input multiplexer for analog output J Min: 0 1 page 7/5
Max: 32767
Type: O2
H 962 AA90.XCS control input multiplexer for analog output K Min: 0 1 page 7/5
Max: 32767
Type: O2
H 963 AA130.XCS control input multiplexer for analog output L Min: 0 1 page 7/5
Max: 32767
d 964 AA10.Y actual output value AO H Type: N2 page 7/6
d 965 AA50.Y actual output value AO J Type: N2 page 7/6
VHQGSHHUWRSHHU
The faults (and alarms) generated from the technology board T300 are send to the base unit. The
base unit shut down the drive with the fault message. This configured system of the T300 saves the
faults. So the faults generated from the T300 cannot acknowledge via base unit. The technology
faults must be acknowledged via bit 7 of control word 1, when the inverter release (control word 1 bit
4) isnt high (s. function plans)
) The difference of speed sensing of - Check the pulse encoder connection
fault speed-actual-actual T300 and base unit is larger than of theT300 and base unit.
value monitoring the parameterised value. - Check the actual speed of T300
(r187) and base unit to plausibility (for
example <>0).
- Check the connection of the send
data from base unit to T300
- Check the parameterised value
) The coupling between T300 and - Check the right insert of the T300 in
fault coupling T300 / base base unit isnt correct working. the righthand slot 2 of the electronic
unit box
- Check the local bus adapter LBA
) The coupling between T300 and - Check the right insert of the CBx in
fault coupling T300 / CBx Communication Board isnt correct the center slot 3 of the electronic box
working. (Slot G)
- Check the connection to CPU
) The peer to peer coupling mas- - Check the connection to master/slave
fault coupling peer to peer ter/slave of the T300 isnt correct
working.
) The difference of the torque-genera- - Check the parameterised values
fault current distribution ting current of master and slave is - Check the mechanic
monitoring larger than the parameterised value.
FORVHGORRSFRQWURORIFUDQHGULYHV
PRGXOHKRLVWLQJJHDU
selection
jogging selection
(S7) synchron-
position setpoint (S7) command ism (S7)
pre-limit
switch (S7)
enable selection
position synchron-
control (S7) ism (S7)
synchronization
selection controller
synchronism (S7) y=x position difference setpoint
y
synchronization value (S7) x
pulse
increments from slave encoder actual position difference value
increments from master
evalua-
tion
enable
synchronization
controller (S7) enable start
synchronize actual
position value (S7) pulse (S7)
T300 X134 CU
receive send
peer to peer peer to peer
from master to slave
1 2 3 4 5 6 7 8
020
005
5 control word 2 (technology) 0
1
STEU_TB2 [3/5]
[2/5] NSTTB2
006
0
6 position setpoint direction 1 WSR1 [11/1]
021
CB X135 007 100%
022
DUAL 7 position setpoint direction 2 WSR2 [11/1]
PORT
008 100%
RAM 023
CB TB 8 position setpoint automatic WSAUT [11/1]
009 100%
024
9 position synchronization value WSSYN [9/2]
010 100%
025
10 start pulse STI [15/2]
011 100%
026
11 PCD11_Empf PZD11_Emp [6/4]
012 100%
027
12 PCD12_Empf PZD12_Emp [6/4]
013 100%
028 parameter:
13 PCD13_Empf PZD13_Emp [6/4] connected to base
unit CU
014 100% xxx : display parameter
029 (only usable with DriveES
14 PCD14_Empf PZD14_Emp [6/4] (no PPO-type))
015 100%
030 xxx : setting parameter
15 PCD15_Empf PZD15_Emp [6/4]
016 100%
031
16 PCD16_Empf PZD16_Emp [6/4] [7/5]
100%
032
FES5 [14/1]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - receive from CB I&S IT PS Erl 35 01.02.01 V 1.21 page: 1/16
terminal PIN T300 PIN T300 terminal
0 0
SE300 X6 X136 X136 SE300 X6
0 1
0 2 binary output 1
1 binary input 1 21
601 inverter enable 3 [10/3] MFFS enable field weakening 631
ramp-function generator enable 4
2 binary input 2 0 5 binary output 2 22
602 [14/5] FIVERS fault current distribution difference 632
setpoint enable 6
acknowledge 7
binary input 3 NSTEU1 [1/6] binary output 3 23
603
3 0 8 [14/8] MXNGS overspeed 633
0 9
1 10 binary output 4
4 binary input 4 [14/8] MXN0
24
604 0 11 speed = 0 634
0 12
5 binary input 5 0 13 binary output 5 25
605 [14/4] FIGNSS speed actual-actual value differ. 635
0 14
0 15
6 binary input 6 binary output 6 26
606 [14/3] FKGERS fault coupling T300 to base unit 636
14 binary input 12
614 0 16
0 17
15 binary input 13 0 18
615
0 19
load current saved 20
16 binary input 14
616 selection position control 21
selection position control and 0 22
17 binary input 15 enable position control occurs 0 23
617 NSTTB2 [1/6]
with binary input 11 0 24
0 25
18 binary input 16 0 26
618
0 27 the operation via binary inputs or
0 28 outputs isnt intented with this
19
24V + 619 P24 extern 0 29 application.
- 0 30 the binary inputs or outputs are only
20
0 31 to simplify the commissioning etc..
620 M24 extern
1 2 3 4 5 6 7 8
block diagram: hoisting gear - simulation control words I&S IT PS Erl 35 01.02.01 V 1.21 page: 2/16
0 OFF1 (L) EIN 0 command jogging direction 1 (H) KTA [10/4]
1 OFF2 (L) AUS2 1 command jogging direction 2 (H) KTB [10/4]
2 OFF3 (L) AUS3 2 enable start pulse (H) FST [15/4] [15/6]
3 inverter enable (H) FWR [16/5] 3 no selection heavy duty (H) ASL [10/2] [15/5]
033 4 ramp-function generator enable (H) FHG [10/8]
036 4 enable field weakening (H) FFS [10/1]
5 ramp-function generator start (H) SHG 5 command pre-limit switch (L) KVE [10/4]
6 setpoint enable (H) FWN [10/7] [15/3] 6
7 acknowledge () QUITT [16/5] 7 enable position control (H) FRS [11/3] [11/6]
[1/7] STEU1 [1/7] STEU_TB1
8 jogging bit 0 (H) TIPP1 8 enable synchronzation controller (H) FGR [10/4]
9 jogging bit 1 (H) TIPP2 9 selection automatic mode (H) AAT [10/3] [11/2] [11/6]
10 control requested (H) FAG 10
11 clockwise phase sequence enable (H) RDF 11
12 counter-clockwise phase sequence enable (H) LDF 12 selection synchronism (H) AGL [8/3] [10/1] [10/6] [14/2]
13 motorized potentiometer raise (H) MOPOH 13
14 motorized potentiometer lower (H) MOPOT 14
15 external fault 1 (L) STOEX1 15 synchronize actual position value (H) SYN [9/2]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - control words I&S IT PS Erl 35 01.02.01 V 1.21 page: 3/16
send to CB
081
[5/5] ZUST1 status word 1 1
881
[9/7] FIGS signal fault encoder (L) 0
[14/8] MXNDS signal speed setpoint-actual value diff. saved (L) 1 [5/5] XNGG actual speed value 2
[14/8] MXNGS signal overspeed saved (L) 2
[14/8] MXNO signal speed = 0 (H) 3 100% 083
849
[14/4] FIGNSS signal fault speed actual-actual value differ. (L) 4 [5/5] ZUST2 status word 2 3
[14/3] FKGERS signal fault coupling T300 to base unit (L) 5
[14/3] FKS5S signal fault coupling to automation system (L) 6 883
[10/3] MFFS signal enable field weakening (H) 7
status word (technology) 4
[14/5] FIVERS signal fault current distribution difference (L) 8
[14/3] FKPPS signal fault coupling peer to peer (L) 9 884
10
11 [9/7] XS1 actual position value 5
[14/8] MXNFS signal field weakening point reached (H) 12
[10/8] KQE signal RFG input = RFG output (H) 13 100% 885
852
14 [5/5] PZD6_Send PCD 6_Send 6
[11/7] AWR signal position control active (H) 15
886 X135 CB
[5/5] PZD7_Send PCD 7_Send 7 DUAL
PORT
887 RAM
[5/5] PZD8_Send PCD 8_Send 8 TB CB
888
[5/5] PZD9_Send PCD 9_Send 9
889
[5/5] PZD10_Send 0
1
PCD 10_Send 10
[12/8] WNZM
0 890
connected from
base unit CU 848 [5/5] PZD11_Send PCD 11_Send 11
891
[5/5] PZD12_Send PCD 12_Send 12
892
[5/5] PZD13_Send PCD 13_Send 13
only usable with DriveES 893
(no PPO-type)
[5/5] PZD14_Send PCD 14_Send 14
894
[5/5] PZD15_Send PCD 15_Send 15
895
[5/5] PZD16_Send PCD 16_Send 16
FSS5 [14/1]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - send to CB I&S IT PS Erl 35 01.02.01 V 1.21 page: 4/16
receive from CU
065
1 status word 1 ZUST1 [4/4]
066
2 actual speed value XNGG [4/4] [7/5] [12/1]
[13/5] [14/1] 0 signal ready to switch on (H) EINBE
067 100% [14/5] [15/2] 1 signal ready (H) BETRBE
082
3 status word 2 ZUST2 [4/4] 2 signal run (H) BETRIEB
3 signal fault (H) STOERUNG
068 4 signal OFF2 (L) KEINAUS2
081
5 signal OFF3 (L) KEINAUS3
4 current setpoint WIGG [7/5] [8/5] [12/1] 6 signal switch-on inhibit (H) EINSPERR
[13/1] [14/1]
7 signal alarm (H) WARNUNG
069 100%
084 8 signal setpoint-actual value deviation (L) KEINWXAB
5 setpoint-actual value differ. ENGG [14/5] 9 signal PcD control requested (H) FAGGEF
10 signal comparison value reached (H) VGWER
070 100% 11 signal low voltage fault (H) STOEUSP
085
6 PCD 6_Send PZD6_Send [4/4] 12 signal request to energize main contactor (H) HSANGEST
13 signal ramp-function generator active (H) HLGAKT
071 100% 14 signal positive speed setpoint (H) RECHTDF
086 15 signal kin. buffering / flex. response active (H) KIPAK
7 PCD 7_Send PZD7_Send [4/4]
072 100%
087
CU X137
8 PCD 8_Send PZD8_Send [4/4]
DUAL
PORT 073 100%
RAM 088
CU TB 9 PCD 9_Send PZD9_Send [4/4]
074 100%
089
10 PCD 10_Send PZD10_Send [4/3] 16 signal flying restart or excitation active (H) FANGAK
17 signal synchronism reached (H) SYNCER
075 100% 18 signal overspeed (L) KEIUED
090 19 signal external fault 1 (H) STOEEX1
11 PCD 11_Send PZD11_Send [4/4] 20 signal external fault 2 (H) STOEEX2
083
076 100% 21 signal external alarm (H) WARNEX
091 22 signal converter overload alarm (H) WARNI2T
12 PCD 12_Send PZD12_Send [4/4] 23 signal converter overtemperature fault (H) STOEUTMP
077 100% 24 signal converter overtemperature alarm (H) WARNUTMP
092 25 signal motor overtemperature alarm (H) WARNMTMP
13 PCD 13_Send PZD13_Send [4/4] 26 signal motor overtemperature fault (H) STOEMTMP
078 (only usable with DriveES 27 reserve
100%
093 (no PPO-type)) 28 signal motor pulled out / blocked fault (H) STOEMBLK
14 PCD 14_Send PZD14_Send [4/4] 29 signal bypass contactor energized (H) UEBSAN
079 100% 30 signal synchronizing error (H) FBSYN
094 31 signal pre-charging active (H) VORLAK
15 PCD 15_Send PZD15_Send [4/4] [7/5]
080 100%
095 connected to
16 PCD 16_Send PZD16_Send [4/4] [7/5] communication board CB
100%
096
FEGG [14/1]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - receive from CU I&S IT PS Erl 35 01.02.01 V 1.21 page: 5/16
send to CU
033
[1/7] STEU1 control word 1 1
945
[10/8] WNGG speed setpoint 2
100% 035
913
[1/5] STEU2 control word 2 3
947
[15/7] WST setpoint start impulse 4
100%
915
0% 5
0% 6
0% 7
X137 CU
0% 8 DUAL
PORT
RAM
TB CU
0% 9
0% 10
954
[1/5] PZD11_Emp PCD 11_Empf 11
955
[1/5] PZD12_Emp PCD 12_Empf 12
956
958
[1/5] PZD15_Emp PCD 15_Empf 15
959
[1/5] PZD16_Emp PCD 16_Empf 16
FSGG [14/1]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - send to CU I&S IT PS Erl 35 01.02.01 V 1.21 page: 6/16
terminal PIN T300 PIN T300 terminal
SE300 X5 X131 X131 SE300 X5
[10/8] WNGG
-10V...+10V 133 137 141 964 968 972 -10V...+10V
[1/5] PZD16E
100% 0% 0% 0% 100%
501 input 1+ [10/6] WNUTI output 1
A D 509
1
input 1-
D
AE1 [7/5] [10/1] [10/7] WNSWF MUX A
9
[5/5] PZD15S
134 138 142 965 969 973
[10/4] WNASL
100% 0% [10/3] WNAV 0% 100%
503 input 2+ [10/4] WNFS output 2
A D 519
3
input 2-
D
AE2 [7/5] [11/1] [5/5] XNGG MUX A
17
[11/7] WNSU
135 139 143 966 970 974
[11/7] WNSL
100% 0% [11/8] WNLU 0% 100%
505 input 3+ [11/8] WNLL output 3
A D 521
5
input 3-
D
AE3 [7/5] [11/1] [9/7] XS1 MUX A
19
506 6 [11/3] ES
[10/3] WGL GND
18 522
[7/4] AE3
962
1
[5/5] PZD16S
136 140 144 967 971 975
[11/2] WS
100% 0% [10/2] WNXMS 0% 100%
507 input 4+ [10/2] WNYMS output 4
A D 523
7
input 4-
D
AE4 [7/5] [15/2] [15/7] WST MUX A
20
1 2 3 4 5 6 7 8
block diagram: hoisting gear - AI + AO I&S IT PS Erl 35 01.02.01 V 1.21 page: 7/16
receive peer to peer send peer to peer
145 980
WNMA WNMA
1 WNMA [10/6] [10/8] WNGG 1
146 981
WIMA WIMA
2 WIMA [7/5] [14/1] [5/5] WIGG 2
X134
X134
+Tx
3 3 3
+Rx
1
TB TB
-Rx -Tx
2 4
4 4
5 5
1 0
FEPP 1
FEPP [14/1]
FSPP [14/1]
AGL
[3/7]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - send / receive peer to peer I&S IT PS Erl 35 01.02.01 V 1.21 page: 8/16
185
pulse encoder 1 187
pulse encoder input 1 100%
0H0000 XNTB
165 IT1 Y1 XNTB [7/5] [14/1]
500 40ms
167 PR1 186
1000
169 RS1
XS1
2000000 YP1 XS1 [4/4] [7/5] [11/1]
171 RP1
0H0000
175 CW1
[3/7] SYN
1 S1
180
[1/5] WSSYN
0
y=x SV1
1
y
x
183
pulse encoder 2
pulse encoder input 2
0H0000
166 IT2
500
168 PR2
1000
170 RS2
2000000
173 RP2
0H0000
176 CW2
pulse encoder 1 + 2
0
SDP
1 SD
179 0%
WSSYNDP
0 XSD12
y=x 1
SVD YDP XSD12 [7/5] [10/1]
y
x FIG
QFC S
182 QN FIGS [4/1]
[16/8] RESET R
1 INIT
0
1 NOT
1s T 0
1 2 3 4 5 6 7 8
block diagram: hoisting gear - actual position sensing I&S IT PS Erl 35 01.02.01 V 1.21 page: 9/16
[3/7] AGL
308
1 & 280 281
0
y=x [7/5]
y WGL
x 1
0
W
0%
[9/7] XSD12 X1 290 307
0% X2
10ms 5% 0% 0 WNZUSATZ
282 LU
1
-5%
283 LL
30 306
284 KP 500ms
1000ms AGL
285 TN [3/7]
1
286 HI
EN
207-218
ES-POL KVE X
[11/3] [3/7] 0% M
0,5% KQE
x 383 L QM
[4/1] [13/1]
0% y>x MS-POL [11/1] [15/3] 0%
y
384 HY
-10%
332 0
+10% 1 KTI
333
50%
224 0
1
100%
[3/7] KTA
[14/5] ASL
[15/2] [3/7]
225
[3/7] KTB
1
n-Grund
50%
226 0 WNFFS
1
[12/8] WNZM
1 2 3 4 5 6 7 8
block diagram: hoisting gear - speed setpoint channel I&S IT PS Erl 35 01.02.01 V 1.21 page: 10/16
x
y>x ES-POL
0% y
[10/2]
+/- 100%
x x>=y W_N_ACT [15/3]
y y>x
W & WACT [4/1] [2/6]
WNFS 0
262 [10/4] 98% 1
FRS
0% X
[3/7]
0
2
265 KP EN
267
250 251
-/+ 100% 1
[1/5] WSR1 0
[7/5] -/+ 100%
1 0
[1/5] WSR2 0
WS 0% 100%
1
W
1 [7/5] 264
0 S ES 266
MS-POL X W
[10/3] [7/5] [10/5]
254 AAT [7/5]
1 KP EN 0% X MIN 0 100% 0 WNLU
[3/7] WNSU
AE2 1 0 0 1
12 0
[7/4] 1 1
263 KP EN 5% 1
1 270
[1/5] WSAUT 0
0
AAT 1
1
[7/4] AE3 FRS [3/7] 272
[3/7]
1 x 0
0 y>x
268 y 274
-100% 0% 5%
255
AWR
[3/7]
[7/5] [10/5]
[9/7] XS1 0
x ESPOL [7/5] -100% 0 WNLL
0% 1 y>x 0 WNSL 0
0% y 1
1 0 1
-5% 1
271
0 0
AAT 1
[3/7] 273
x 0
x>y
269 y 275
-5%
1
AWR
[3/7]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - position control I&S IT PS Erl 35 01.02.01 V 1.21 page: 11/16
100% 0
111% 1
517
[12/2] Senken
4%
523 1 1
0
IReib
IReib 527-538
540
100%
524 525 539 551 LU 555
522 0% 50%
0% 100% 552 LL
[3/7]
ILS y=x WNZMBER
y SV WNZM
WIGG x 2000ms [4/3]
[5/5]
IL TU
[10/1]
2000ms
display parameter: 553 TD [14/5]
526
541 0% CU
502, 505, 507, 508, 509, 510, 511, 512, 514, 516, 518, 519, 520, 521 CD
[13/4] I > IN
setting parameter:
[13/8] FFSSD
554
&
1
XNGG
[5/5]
nist
x MFEUN SETINT x
x>y [13/2] Mittelwertbildung:
503
22%
y
MES
x MFEOB
41% x>y S ABSP
504 y Q
MXN0 R
[14/8]
OBGR
[13/5]
x
y>x Senken [12/2]
0% y
1 2 3 4 5 6 7 8
block diagram: hoisting gear - WNZ 1 I&S IT PS Erl 35 01.05.02 V 1.22 page: 12/16
[10/8] KQE
542 T 0
500ms
[5/5] XNGG x
546 [12/2] OBGR x>y
y &
[5/5] WIGG 1 & S
0
X QU Q I > IN [12/6]
0% R 1
[10/2] WNXMS x x>y 549
20ms 100%
543 544 M
95% y y>x & 1
10%
545 HY QL
547 & x
1 y>x
1 y &
[12/2] MES x
x>y x x>y
195% y
-95% y y>x
[12/2] WI x
x>y
1
195% y
550
548
S
dn/dt FFSSD [10/1]
1
[12/2] x S Q
x>y Q R
195% y R RFS [12/6]
[14/8] MXNO
[14/8] MXNO
[12/4] SETINT 1
1 2 3 4 5 6 7 8
block diagram: hoisting gear - WNZ 2 I&S IT PS Erl 35 01.05.02 V 1.22 page: 13/16
communication monitoring
overspeed monitoring
intern FKS5
[1/2] FES5 fault coupling to Communication Board CB [16/1]
[4/7]
intern
FSS5
FKOP
& RESET
S
R
QN FKS5S [4/1] [16/1] [5/5] XNGG X QU
MXNG
S
QN MXNGS [4/1] [2/6]
[16/8] RESET R
20ms
458 M [16/8]
110% 2%
459 0
460 HY QL
1
[10/2] n-Grund 0
AGL 1%
WIMA [3/7] 470 HY QL
[8/3]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - monitorings I&S IT PS Erl 35 01.05.02 V 1.22 page: 14/16
start pulse
445 453
447 454
0 0
0%
[1/5] STI 0 1
1 0 0% 0 0
WST [6/4] [7/5]
[7/4] AE4 30% 0
1 1
40 ms 448 1
446 0%
1 1000ms
451
449 FST
FST [3/7]
[3/7]
4000ms
362 0
4000ms 1 0
363 4000ms 1
TU [10/7]
364
[14/8] MXNFS
0 &
370
ASL [3/7]
4000ms
367 1
391 392 4000ms 0
0
366 4000ms 0
4s 60 s 368 1
TD [10/7]
1
Ermittlung der
[10/2] n-Grund
Rcklaufzeit fr
[5/5] XNGG wegkonstantes
Bremsen
Freigabe Weg-
[10/3] MFFS NOT konstantes Bremsen
0
390 W_N_ACT
[11/7]
MS-Pol FWN
[10/3] [3/4]
1 2 3 4 5 6 7 8
block diagram: hoisting gear - start pulse and RUT I&S IT PS Erl 35 01.02.01 V 1.21 page: 15/16
send faults and alarms to base unit CU
fault messages:
[3/4] QUITT
1
[14/7] MXND 0
[14/7] MXNG 1
0 2
0 3 1
0 4 1 NOT QUI_IN [15/3]
827 0
0 5 10s T 0
0 6
0 7 NQI_IN
base unit CU
0 8
829
& alarms 97-112 [15/2]
0 9 0HFFFF
0 10
0 11 factory setting
0 12
0 13 with change of parameter H832 from 0 to 1 the technology parameter (1000-
0 14 1999/ d-,H-Parameter) are reset. Therefore the power is to switch off and on.
0 15
After that the technology parameter are reset.
1 2 3 4 5 6 7 8
block diagram: hoisting gear - general I&S IT PS Erl 35 01.02.01 V 1.21 page: 16/16