EMPLOYER DOC NO 80-F201007-IS-025 PROJ.

NO 142901

REVISION 1

EMPLOYERS REPRESENTATIVE APL JOB NO. F201007

SHT NO. SHEET 1 OF 27

CONTRACTOR PROJECT TITLE BPGIC FUJAIRAH TERMINAL, PHASE 1

LOCATION FUJAIRAH, UAE

SPECIFICATION & DATASHEET FOR 3.3KV MOTOR

FOR

BPGIC FUJAIRAH TERMINAL PHASE 1

FOR PROCUREMENT

REFERENCE TO MUCOG DOCUMENT NO.: (if any)

REVISION NO DESCRIPTIONS PREPARED BY CHECKED BY APPROVED BY

KARTHI VIRAJ TSF


1 ISSUED FOR PROCUREMENT
07/07/2016 07/07/2016 07/07/2016
KARTHI VIRAJ TSF
0 ISSUED FOR PROCUREMENT
06/06/2016 06/06/2016 06/06/2016
KARTHI VIRAJ TSF
D REVISED FOR APPROVAL
13/05/2016 13/05/2016 13/05/2016
KARTHI VIRAJ TSF
C REVISED FOR APPROVAL
02/09/2015 02/09/2015 02/09/2015
KARTHI VIRAJ TSF
B REVISED FOR APPROVAL
14/08/2015 14/08/2015 14/08/2015
KARTHI VIRAJ TSF
A ISSUE FOR APPROVAL
16/07/2015 16/07/2015 16/07/2015

THIS DOCUMENT IS THE PROPERTY OF AUDEX PTE LTD


THE INFORMATION CONTAINED HEREON MAY NOT BE USED OR COPIED IN ANY MANNER
WITHOUT THE WRITTEN PERMISSION OF AUDEX PTE LTD
EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 2 OF 27

TABLE OF CONTENTS
1. SCOPE .................................................................................................................................................. 3
2. SPECIFICATION DEVIATION AND CONCESSION CONTROL ......................................................... 3
3. APPLICABLE CODES AND STANDARDS ......................................................................................... 3
4. ORDER OF PRECEDENCE ................................................................................................................. 4
5. REFERENCE DOCUMENTS ................................................................................................................ 5
6. SERVICE CONDITIONS ....................................................................................................................... 5
7. DESIGN AND TECHNICAL REQUIREMENTS .................................................................................... 6
8. SPECIFIC DESIGN REQUIREMENTS ................................................................................................. 7
9. RATING PLATES ............................................................................................................................... 19
10. DOCUMENTATION ............................................................................................................................ 21
11. INSPECTION AND TESTING ............................................................................................................. 23
12. GUARANTEES ................................................................................................................................... 26
13. TRAINING ........................................................................................................................................... 26
14. START-UP .......................................................................................................................................... 26
15. PACKING AND SHIPMENT ............................................................................................................... 26
16. SPARE PARTS AND SPECIAL TOOLS ............................................................................................ 27
17. ATTACHMENTS ................................................................................................................................. 27

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 3 OF 27

1. SCOPE
This specification, together with the attachments, covers the minimum requirements
governing the design, manufacturing, testing and delivery of Medium Voltage (MV)
Induction Motor that are suitable for installation at various area for BPGIC Fujairah Terminal
Phase 1, AL Suda, Fujairah, UAE.

2. SPECIFICATION DEVIATION AND CONCESSION CONTROL

2.1 Deviations from this specification are acceptable only if the Vendor has listed in his
quotation the requirements that he cannot or does not wish to comply and the Employer /
Employer's Representative has accepted in writing the deviations, before the order is
placed.

2.2 In the absence of a list of deviations, it will be assumed that the Vendor fully comply with
this specification.

2.3 Any technical deviations to the purchase order and its attachments including, but not limited
to, the data sheets and specifications shall be sought by the Vendor through the
concession request format.

2.4 Concession requests shall require Employer's / Employer's Representative review &
approval prior to implementing the proposed changes. Changes which are implemented
without the approval of Employer/Employer's Representative shall be subject to rejection

3. APPLICABLE CODES AND STANDARDS


The Equipment shall be designed, manufactured, tested and supplied in accordance with
the accepted engineering design practices, attached data sheets, and applicable sections
of codes and standards as listed below, including any modifications, interpretation or
additions thereto by the Purchaser. Unless otherwise specified, all documents and
publications referred herein shall be the latest edition, revision or amendment in effect and
shall form an integral part of this specification. It may be noted that the list may not be
complete and additional requirements or codes are mentioned within the specification at
other locations. The Equipment shall also comply with the latest revisions of all the statutory
requirements, regulations and by-law enforced by the local authorities.
In case of conflict between the various codes, standards and this specification, the most
stringent of the requirements shall generally prevail and govern. The Bidder or the
Vendor/Manufacturer shall determine by careful scrutiny which of the requirements are in
conflict and which of them will be acceptable, and refer such conflicts and other matters
requiring interpretation to the attention of the Purchaser for his comment and ruling which
shall be final and adhered to
The following codes and standards, together with other requirements of this specification,
shall govern the design, ratings, manufacturing and testing of the Equipment: -

(1) IEC 60034 Rotating Electrical Machines.

(2) IEC 60072 Dimensions and Output Rating for Rotating Electrical Machines.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 4 OF 27

(3) IEC 60079 Electrical Apparatus for Explosive Gas Atmospheres function.

(4) IEC 60085 Electrical Insulation Thermal Classification.

(5) IEC 60317 Specification for Particular Types of Winding Wires.

(6) IEC 60529 Degrees of protection provided by enclosures (IP Code).

(7) IEC 60751 Industrial Platinum Resistance Thermometers and Platinum Temperature
Sensors.

(8) IEC 60851 Methods of Test for Winding Wires.

(9) IEC 60894 Guide for Test Procedure for the Measurements of Loss Tangent on Coils
and Bars for Machine Windings.

(10) IEC 62262 Degrees of Protection provided by Enclosures for Electrical Equipment
against external mechanical impact (IK Code).

(11) ISO 281 Rolling Bearing- Dynamic Load Rating and Rating Life.

(12) ISO 1680 Acoustic Test Code for the measurement of air-borne noises emitted by
rotating electrical machines.

(13) ISO 10816 Mechanical Vibration Evaluation of Machine Vibration by Measurements


on Non-rotating Parts: Part 1 General Guidelines.

The Manufacturer may consider the use of other relevant codes and standards which are at
least equal to those as indicated above.

4. ORDER OF PRECEDENCE
It shall be the vendors responsibility to be, or to become, knowledgeable of the
requirements of the referenced Codes and Standards.

In case of conflict, the order of precedence shall be:

1 Local statutory requirements, orders and by-laws


2 Data Sheet
3 This specifications and attached documents
4 Relevant project documents
5 Applicable codes and standards

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 5 OF 27

5. REFERENCE DOCUMENTS

1. MUCOG-142901-ELC-TS-009 Technical specification for induction motors

2. 80-F201007-LI-001 - ELECTRICAL LOAD LIST

3. 80-F201007-A1-103_SLD FOR 3.3KV SWITCHGEAR (SG-B-9601)

6. SERVICE CONDITIONS
6.1 SITE CONDITIONS

The MV Motor shall be designed and manufactured for use / installation in the following site
conditions:-

(1) Climatic Temperature


Maximum design temperature : 50o C (the surface temperature of outdoor
equipment may increase to 80o C due to direct
solar heat radiation)
Minimum design temperature : 7o C

(2) Relative humidity


Maximum design humidity : 100%
Minimum design humidity : 60%

(3) Rainfall
Design rainfall intensity : Rare, but heavy-design max intensity of 60 mm/hr
for one hour per day.

(4) Wind
Maximum design wind velocity : 160 km/h, 3 sec, gust wind

(5) Seismic Condition : Zone 2A based on UBC classification


Horizontal Acceleration = 0.15g (g=9.81 m/s2)
Vertical Acceleration = 0.075g (g=9.81 m/s2)

(6) Outdoor Atmosphere : Saliferous, sulphurous and often contains fine dust
and pollutants and Coastal marine environment

(7) Area Classification : The requisite equipment may use in Zone 1


classified areas with Gas Group of IIB and a
Temperature Class of T4.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 6 OF 27

6.2 ELECTRICAL POWER SUPPLY CHARACTERISTICS

Supply Voltage : AC 3.3KV 10%, 3-Phase, 3-Wire for MV motors.


: AC400V 10%, 3-Phase, 3-Wire for auxiliary LV motors.
: AC 230V 10%, 1-Phase, 2-Wire for anti-condensation space
heaters
Supply Frequency : 50Hz 5%

7. DESIGN AND TECHNICAL REQUIREMENTS

7.1 GENERAL

7.1.1 The insulating and dielectric materials used shall be non-toxic, flame-retardant, non-
tracking, non-hygroscopic and vermin resistant material and free of components that are
persistent and hazardous to the environment such as PCB, CFC, asbestos, etc.

7.1.2 Vendor shall give a notice of at least one year to the end user of equipment before phasing
out the product / spares to enable the end user to make placement of order for spares and
services.

7.1.3 The Motor and auxiliaries shall be suitable for continuous operation for periods of up to four
years without servicing and part replacement.

7.1.4 The MV Motor assembly shall have life expectancy of at least 25 years, when operating at
the rated current & voltage and maintaining under the specified service condition.

7.1.5 The Motors shall be designed duty type S1 (continuous running duty), according to IEC
60034-1 and shall be suitable for the load characteristics and operational duty of the driven
equipment

7.1.6 Within a span of 4 years, the periods of running may alternate with idle periods of maximum
6 months. At the end of such an idle period the motor shall, without requirement for
additional inspection, be suitable for another running period.

7.1.7 The offered equipment shall be brand new with state of the art technology and proven field
track record.

7.1.8 Proto-type equipment or parts shall not be offered and used.

7.1.9 All motors shall be of high efficiency energy saving type and tested / certified to the relevant
IEC codes and standards.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 7 OF 27

8. SPECIFIC DESIGN REQUIREMENTS

8.1 BASIC REQUIREMENT

8.1.1 General

8.1.1.1 The rating of the machine offered by the Vendor shall be in accordance with IEC 60072
Parts 1 and 2 and all insulation materials shall be class F, as defined in IEC 60034-18. The
rating of the machine offered by the Vendor shall be based on a class B temperature rise
for all parts of the machine windings based on site ambient temperature.

8.1.1.2 Starting method of the motor shall be as indicated in the relevant pump data sheet.

8.1.1.3 Motor Vendor shall coordinate with the pump and VFD/Soft starter Vendor where applicable
to meet the pump & starter (VFD / Soft starter) specification and their requirements. All
drawings / data sheets shall be submitted to the pump Supplier to ensure compatibility of
the pump with motor.

8.1.1.4 The frame size of the motors shall be a minimum of 10% in excess of mechanical duty.

8.1.1.5 Motors used for hazardous areas shall be of suitable design with necessary approval
obtained from BASEEFA or equivalent with certified ATEX certificates, authorized at the
country of origin and approved certifying authority for use in the particular areas specified.

8.1.1.6 All motors approved as above, shall have a separate name plate carrying the details of
such approval, fixed on the body adjacent to the main name plate.

8.1.2 Degree of Protection

8.1.2.1 The degree of protection shall be at least IP 65 for the motor, auxiliaries, terminal boxes
and bearing housings as per IEC 60529 and external mechanical impact protection IK 10
(able to sustain an impact force of 20J without damage)as per IEC 62262.

8.1.2.2 Motors for outdoor service shall be provided with special seals for the enclosure, joints,
bearing housing, terminal boxes etc., so that no extra protective covering for ingress of
water is required.

8.1.2.3 Vertical motors for outdoor installation shall be provided with a rain protective hood. All
external hardware or parts shall be zinc passivated or cadmium plated.

8.1.2.4 The enclosure shall be provided with certified threaded metallic plug to permit drainage of
condensed water from the inside.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 8 OF 27

8.1.3 Co-Planar Tolerance

8.1.3.1 For motor feet, the limit of variation between two points on any set of foots in the X or Y
direction shall be limited to a maximum of 80 microns.

8.1.4 Method of Cooling

8.1.4.1 Motor shall be air cooled with a method of cooling of IC 411 (TEFC) or IC 611 (TEAAC) in
accordance with IEC 60034-6.

8.1.4.2 Wherever service conditions indicated in the specification sheet are such that corrosive
agents are present in the surroundings. The following materials of construction for cooling
tubes shall be aluminium tubes having minimum thickness of 1.6 mm.

8.1.4.3 The cooling fans shall be suitable for bi-directional rotation of motors. These shall be
fastened to the motor shaft by means of compensating rings or will be balanced
independent of the motor. Guide key or reference points shall be supplied to prevent wrong
assembly. The cooling air shall be sucked from the non-driving end.

8.1.4.4 The cooling fans shall be made of non-sparking materials such as cast aluminum (LM-6
alloy)/cast iron.

8.1.4.5 The Vendor shall make sure that the cooling method provided is sufficient for the motor
running at low speed on VFD-operated pumps otherwise suitably rated auxiliary cooling
fans shall be provided.

8.1.4.6 Materials of construction of fans, tubes, etc. used shall be suitable for the environment
specified in the data sheet.

8.2 PERFORMANCE REQUIREMENT

8.2.1 Starting Characteristic

8.2.1.1 For MV motors the DOL-starting current shall not exceed 5 times the rated current of the
motor.

8.2.1.2 The accelerating torque at any speed and 80% rated voltage shall be not less than 10% of
motor rated full load torque. In any event the motor starting torque at 100% rated voltage
shall be not less than 1.7 times the torque obtained from a load curve which varies as the
square of the speed and is equal to 100% torque at rated speed.

8.2.1.3 The torque-speed characteristic of the motor with 80% rated voltage and rated frequency
applied at the motor terminals shall be adequate for starting the driven load under the most

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 9 OF 27

severe conditions, e.g., pump with open discharge. Under these conditions, the
accelerating torque shall not be less than 10% of the full load torque.

8.2.1.4 Starting torque and minimum torque of the motor shall be compatible with the speed torque
characteristics of the driven equipment under specified starting and operating conditions.

8.2.1.5 The motor torque during starting from zero to minimum driven equipment operating speed
shall be at least 10% greater than the driven equipment absorbed torque.

8.2.1.6 The locked rotor torque with 80% rated voltage and rated frequency applied at the motor
terminals should be more than 30% of the rated torque.

8.2.1.7 The breakdown torque shall not exceed 300% of the rated torque and should be higher
than 180% of the rated torque.

8.2.1.8 The pull-out torque shall be in excess of 135% of the rated torque for cylindrical rotor
motors and in excess of 150% of the rated torque for salient pole motors.

8.2.1.9 The pull-in torque shall be at least 60% of the rated torque for two, four and six-pole
machines. For machines with a pole number of eight and higher, the pull-in torque shall be
at least 45% of the rated torque.

8.2.1.10 All motors shall be suitable for DOL starting and for restarting with full opposite residual
voltage under full load condition with supply voltage ranging between 80% and 110% of the
rated value at the terminals of the motor. Manufacturer shall ensure that the end-winding
supports and the quality of the motor windings are suitable for supply reconnection onto full
motor residual voltage at total phase opposition, and that the shaft and active iron core
systems are suitable for supply reconnection onto full motor residual voltage at 180 degree
phase difference.

8.2.2 Number of Sequence Starts

8.2.2.1 At any voltage between 80 to 100% rated voltage, motors shall be capable of:

Three (3) successive starts with the motor initially at maximum ambient temperature
(cold starts)
Two (2) successive starts with the motor initially at full load operating temperature (hot
starts)
Six (6) minimum number of starts during first hour of continuous operation (e.g.
commissioning)
Four (4) evenly spaced starts

8.2.2.2 After a cooling period of 30 minutes at standstill, another starting sequence of at least two
successive starts shall be possible.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 10 OF 27

8.2.3 Running Up time and Allowable Running

8.2.3.1 The Vendor shall furnish the running-up time at 80% and 100% rated voltage applied at the
motor terminals.

8.2.3.1 The Vendor shall furnish the maximum allowable running-up time at 80% and 100% rated
voltage applied at the motor terminals.
8.2.4 Stalling Time

8.2.4.1 The Vendor shall furnish the maximum allowable stalling time with rated voltage and 80%
voltage and rated frequency applied at the motor terminals.

8.2.4.2 Data to be provided shall include both "hot" and "cold" stalling time.

8.2.5 Temperature Limitation

8.2.5.1 The maximum allowable temperature rise of the electric motor is dependent on:

The maximum coolant temperature.


The maximum allowable temperature of the insulation materials used in the motor.
Although the insulation materials used in the motor shall be at least Class F materials
the maximum continuous operating temperature at full load and rated voltage and
frequency applied shall be limited to the maximum permissible temperature for Class B
materials at an ambient temperature
The particular situation in which the motor is used, e.g., limiting temperatures in
hazardous area.

8.2.6 Motor Vibration

8.2.6.1 To permit evaluation of balance and vibration of rotating electrical machines, it is necessary
to measure on the machine alone (non-rotating parts). The test conditions should be
properly defined to enable reproducible tests to be carried out and to provide comparable
measurements.

8.2.6.2 Vendor shall provide vibration monitoring probes for motors where such monitoring is
deemed critical for safe operation of the equipment and indicated in the motor data sheet.
Motor vibrations measured at the bearing must not exceed the limits as specified in relevant
IEC standards.

8.2.6.3 The test conditions and values of vibration shall be as described in detail in IEC 60034-14.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 11 OF 27

8.2.7 Noise Level

8.2.7.1 The maximum sound pressure level shall not exceed 85 dB (A) in the work area, i.e., any
position accessible to personal not less than 1 meter from equipment surfaces.

8.2.7.2 The requirements apply in the absence of reverberation and background noise from other
sources and for all operating conditions between no-load and full-load.

8.2.7.3 If the noise measurements are performed under no-load conditions, the maximum allowable
noise limits shall, for 2 and 4-pole machines be 2 dB (A) more stringent and for machines
with a higher number of poles be 4 dB (A) more stringent than the values stated above or in
the requisition.

8.2.7.4 If the mean sound pressure level is used to evaluate the noise emission of the motor, the
maximum allowable noise limit shall be taken 1.5 dB (A) more stringent.

8.2.7.5 If the motor produces narrow-band noise with total or impulsive components the maximum
allowable noise limits shall be 5 dB (A) more stringent than the values stated above or in
the requisition.

8.2.7.6 In situations where more than one reduction factor to the maximum allowable noise limit
applies, the total reduction shall be the linear sum of the individual reductions. Motors
should preferably meet the maximum allowable noise limits by design and not by corrective
measures.

8.2.7.7 The acoustic measures, if applied, shall not obstruct routing inspection and maintenance
activities such as lubrication of bearings and inspection of oil levels. The maximum
allowable temperature rise of the motor windings and bearings shall not exceed the limits
specified in this specification.

8.2.8 Pulsating Stator Current


8.2.8.1 Motors driving equipment which requires a variable torque during each revolution, e.g.
reciprocating compressors or pumps shall have sufficient inertia to limit the variations in the
motor stator current to a value not exceeding:
40% of the full-load current for cage-induction motors.

8.2.8.2 The additional inertia necessary to comply with the current variation and speed irregularity
requirements should be added to the rotating mass of the motor.

8.2.8.3 If this requirement cannot be met, approval shall be obtained from the Employer /
Employers Representative regarding an alternative design. (The basis for determining this
vibration shall be by oscillography measurement and not by ammeter reading).
8.2.8.4 Generally this test will be part of a site acceptance test.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 12 OF 27

8.3 CONSTRUCTIONAL REQUIREMENT

8.3.1 Motor Housing

8.3.1.1 Materials that are persistent in or toxic to the environment or that are considered potential
carcinogens shall not be used.

8.3.1.2 The use of hygroscopic materials should be avoided. The materials used shall be selected
to prevent contact corrosion.

8.3.1.3 Transport units heavier than 25 kg shall have eye bolts, lugs or extension pieces clearly
identifiable to be used for hoisting. Eye bolts shall not be part of the equipment type of
protection.

8.3.1.4 Motors weighting over 600 kg shall have jacking bolts or facilities to lift the motor with the
aid of a mechanical jacking device to facilitate the alignment of the motor with the driven
equipment.

8.3.1.5 Motors shall be provided with external earthing facilities. The earthing facility shall be
clearly marked with the appropriate symbol.

8.3.1.6 Two earth points should be provided on each motor body. These points should be welded
on motor body and continuity should be available even after motor paint.

8.3.2 Stator Frame

8.3.2.1 All motor frames and bearing end-shields shall be constructed of ferrous metals. Motor
frames made of aluminum alloy are not acceptable.

8.3.2.2 Corresponding mounting surfaces for horizontal motors shall be in the same plane and
within a tolerance of 0.15 mm per meter distance between surfaces.

8.3.2.3 Motor frame including bearing supports shall have sufficient strength and rigidity to avoid
distortion or increased vibration as a result of external mechanical forces, e.g. tightening of
fixing bolts.

8.3.2.4 After tightening one or more of the fixing bolts, the deflection of the motor's feet from the
horizontal plane shall be less than 50mm.
8.3.2.5 All welding and welding inspection shall comply with AWS D1.1 or other approved
equivalent codes and standards.

8.3.2.6 Intermittent welds, stitch welds or tack welds are not allowed on any structural part of the
motor frame including the outer enclosure. This requirement does not apply to parts of the
motor frame where the use of continuous welds would cause deformation of the part.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 13 OF 27

8.3.3 Direction of Rotation

8.3.3.1 Motors shall be suitable for bi-directional rotation. In case of any design limitation, the same
shall be indicated in the offer and to coordinate with the driven equipment.

8.3.3.2 In either case, a plate showing the direction of rotation corresponding to the phase terminal
markings shall be fitted at the driving end shield of the motors.

8.3.4 Anti-Condensation Heaters

8.3.4.1 The motors shall be provided with anti-condensation heaters of fully insulated design to
prevent condensation when the motor is kept idle for long period.

8.3.4.2 The heaters shall be suitable for operation on a single phase, 230V, 50Hz.

8.3.4.3 Anti-condensation heaters shall be arranged to provide uniform heating of stator and, if
applicable, rotor windings and should maintain the temperature of the motor windings
approximately 5C above external ambient temperature.

8.3.4.4 The surface temperature of the heater element or of the motor enclosure shall not exceed
the limiting ignition temperature as specified.

8.3.4.5 The connecting leads of the heater elements shall be brought out to terminals in a separate
heater terminal box mounted on the motor frame. A prominent warning label shall be
provided, as shown "Warning - Circuit May Be Live".

8.3.5 Windings

8.3.5.1 The complete insulation system of motor, including all insulation materials, shall meet the
requirements for class F insulation.

8.3.5.2 All insulation materials used for both stator and, if applicable, rotor and exciter windings
shall be at-least class F materials in accordance with IEC 60085.

8.3.5.3 Stator windings of motors shall be made of high quality enameled wire with suitable ground
and inter-phase insulation.

8.3.5.4 After installation of the windings and connection of the coils, the windings shall be fully
impregnated to restrict the movement of the coils and to realize adequate heat dissipation.
Impregnation by means of dry vacuum/pressure method (vacuum impregnation) is
preferred. Coating by painting is not recognized as impregnation and is not acceptable.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 14 OF 27

8.3.5.5 All windings shall be adequately supported, braced and blocked to provide sufficient rigidity
and to limit end winding vibration and subsequent cracking of the winding insulation.

8.3.5.6 Windings shall be able to withstand the dynamic forces which result from frequent starting
and starting against full opposite residual voltage.

8.3.6 Terminal Boxes

8.3.6.1 The cable glands shall be of the double compression type and shall provide seal around
both inner and outer sheaths, electrical bond and inner sheath and clamp the armor.
8.3.6.2 Gland plates and glands to be used for single core cables shall be made of non-magnetic
material.

8.3.6.3 The terminal box shall be located at the right hand side of the horizontal motor looking from
the driving-end.

8.3.6.4 Inside the terminal box, an earthing clamp or bolt of adequate dimensions shall be provided
for connection of the cable earthing. The earthing facility shall be clearly marked with 'the
appropriate symbol.

8.3.6.5 Auxiliary equipment fitted to the motor, e.g., temperature detectors, vibration monitors, shall
be wired a separate auxiliary terminal boxes fitted to the side of the motor and complying
with the above requirements.

8.3.6.6 Terminal boxes shall have threaded entries with ISO metric threads to suit compression
cable glands of size identified by Contractor.

8.3.6.7 For M.V. Motors, design of terminal boxes shall be such that it may be possible to rotate by
90 degree arrange top / bottom /side entry of cables at site.

8.3.6.8 All terminal boxes for the MV motors shall be Vendor's standard box with ingress protection
of IP 65.

8.3.6.9 The main terminal box shall be made of steel. Terminal boxes made of cast-iron are not
acceptable.

8.3.6.10 The main terminal body shall be of Phase segregated type non-compounded filled designs
A terminal box so designed that phase segregation is provided by earthed metallic barriers
forming completely distinct individual phase compartments so as to restrict any electrical
breakdown to an earth fault.
8.3.6.11 Main terminal boxes should be constructed in such a way that the cable can be connected
without a requirement for pulling the cable through a fixed opening in the box.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 15 OF 27

8.3.6.12 The lowest part of the terminal box, including cable gland and other miscellaneous parts,
shall be not lower than the lowest part of the motor.

8.3.6.13 For explosion-proof motors, Exe or Exd type of terminal boxes shall be used.

8.3.6.14 The cable box shall be air insulated and cold shrink terminations or heat shrinkable
terminations shall be used. Compound filled cable boxes are not acceptable.

8.3.6.15 The motor cables shall be able to enter the terminal box from bottom unless otherwise
specified by the Purchaser. The lowest part of the terminal box, including cable glands and
other miscellaneous parts, shall be not lower than the lowest part of the motor frame.
8.3.7 Bushing and Terminals

8.3.7.1 Terminal marking of the main cable connections and the direction of the rotation shall be in
accordance of IEC 60034-8.

8.3.7.2 Terminal marking of auxiliary cable connections shall be in accordance with the relevant
motor wiring diagrams.

8.3.7.3 Terminal blocks should be made of synthetic resin. The use of porcelain is not allowed.

8.3.7.4 Terminal connections shall be constructed in such a way that direct contact between
screws, bolts or nuts and the conductor is avoided.

8.3.7.5 The bushings and insulators shall be fully rated for the rated motor voltage and be capable
of withstanding both the dynamic and thermal effects of a through fault short circuit current
for at least 0.2 seconds.

8.3.7.6 The distance between bushings and earthed parts of the terminal box shall be based on the
applicable distances for air insulated installation.

8.3.8 Rotor

8.3.8.1 The shaft shall be made of one-piece, heat-treated steel.

8.3.8.2 Welding on finished shafts is not allowed. Shafts and/or spiders subjected to welding shall
be post-weld stress relieved.

8.3.8.3 Rotors of all motors shall be dynamically balanced at nominal speed with half the key (HK)
fitted in the keyway(s). The shaft-end should be permanently marked with the indication
'HK'. The rotor design shall allow for the addition of balancing weights. Balancing weights
shall not be of lead or similar ductile material.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 16 OF 27

8.3.8.4 If metal is to be removed to achieve dynamic or static balance it shall be removed in a


manner that maintains the structural integrity of the rotor and does not result in harmful or
distortive hot spots.

8.3.8.5 Rotors of motors above 250 kW shall be subjected to an over speed test twice, at 1.2 times
rated speed for a duration of 2 minutes.

8.3.8.6 The over speed test shall be considered as satisfactory if no permanent abnormal
deformation is apparent.

8.3.9 Fans

8.3.9.1 The external fan and if applicable the separately mounted internal fan(s), shall be
individually balanced.

8.3.9.2 The external fans shall be of non-corroding material or shall be treated with a corrosion
resistant coating.

8.3.9.3 The flow of cooling air shall be in the direction of the driven equipment.

8.3.9.4 Motors fitted with unidirectional fans shall be provided with an arrow permanently indicating
the direction of rotation. Indication by means of a painted or adhesive arrow is not
acceptable.

8.3.9.5 Cooling impeller fans for motors installed in classified areas shall be made of spark-free
aluminium alloy material (containing less than 0.2% of copper and not more than 6 % of the
magnesium by mass). Special reinforced thermosetting plastic fans which are conducting
sufficiently to prevent the accumulation of static electric charges, may be used but subject
to prior written approval from the Purchaser. The free space between the external fan and
any stationary part of the motor shall be at least 1/100 of the maximum diameter of the fan
and shall not be less than 1 mm. If both opposing parts are machined, the clearance
distance shall not be less than 1 mm.

8.3.10 Couplings

8.3.10.1 The coupling design shall be based on the maximum transient torques which can be
expected at the coupling in case of a two or three-phase short-circuit at the motor terminals.

8.3.10.2 The coupling components shall be balanced individually and the assembled coupling shall
be balanced as a unit by the driven equipment Vendor.

8.3.10.3 The motor Vendor shall mount the balanced coupling hub as supplied by the driven
equipment Vendor.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 17 OF 27

8.3.10.4 When the coupling hub does not fully cover the shaft-key, the motor Vendor should
machine the key in such a way that residual unbalance is eliminated.

8.3.10.5 The shaft-ends shall be provided with a suitable threaded hole or holes to facilitate the
assembly or removal of coupling and bearing races.

8.3.10.6 Shaft extensions, keys and key-ways shall be in accordance with IEC 60072 Parts 1 and 2.

8.3.10.7 For motors with rated output in excess of 1000 kW an integrally flanged shaft-end design or
a tapered shaft-end design for hydraulically fitted coupling should be considered. Vendor
shall furnish the proposed shaft-end design in case no design is specified.

8.4 PROTECTIVE SYSTEMS

8.4.1 Winding Temperature Detectors

8.4.1.1 RTD shall be provided for sensing all MV motor winding and motor bearings (DE and NDE).

8.4.1.2 RTD shall be PT100 resistance elements in accordance with IEC 60751.

8.4.1.3 All MV motors shall be provided with evenly distributed embedded resistance temperature
detectors in the 3-phase stator windings (1 + 1 in each phase) for measurement of winding
temperature. These shall be located in locations where the highest temperature is likely to
occur

8.4.1.4 For VFD-operated motors, one number of RTD sensor for hot air (motor frame temperature)
shall be provided only where specified.

8.4.1.5 RTD elements shall be suitable for 3-wire connections. The RTD elements shall be wired to
a separate auxiliary terminal box mounted on the motor frame.

8.4.2 Dial Type Thermometers

8.4.2.1 In VFD-operated MV motors, the measurement-of hot air (motor-frame temperature) and
bearing temperature (of oil-lubricated type of bearings) by dial-type thermometers shall be
provided wherever required. The dial-type thermometers shall be provided with threshold
markings and settings for alarm and trip together with volt-free output contacts where
specified. Alternatively, RTD type sensors shall be used.

8.4.2.2 The arrangement shall consist of a dial type of mercury-in-steel thermometer so mounted
that its stem is located in the maximum temperature region.

8.4.2.3 For bearing temperature measurement, separate thermometers shall be provided for each
bearing.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 18 OF 27

8.4.2.4 For grease-lubricated bearings, temperature measurement arrangement shall be provided


only where specified.

8.4.3 Bearing and Lubrication

8.4.3.1 Motors shall have grease lubricated ball or roller type bearings or of the manufacturer's
standard design.
8.4.3.2 The bearings shall be chosen to give a minimum L-10 rating life of 5 yrs. (40,000 hrs.) at
rated operating conditions. (The L -10 rating life is the number of hours at constant speed
that 90 % of a group of identical bearings will complete or exceed before the first evidence
of the failure).

8.4.3.3 Bearings shall be protected to eliminate contamination, loss of lubricant and to prevent
intrusion of fine dust and sand particles.

8.4.3.4 Housings for grease-lubricated bearings shall be provided with openings accessible from
the exterior of the motor; one with a pressure grease fitting and one to serve as a drain and
vent during greasing.

8.4.3.5 Unless specified otherwise, the bearings shall be adequate to absorb axial thrust provided
by the motor itself or due to shaft expansion.

8.4.3.6 Bearing shall be suitable for both directions of rotation of the motor.

8.4.3.7 The minimum re-lubrication interval shall be 4000 hours for horizontal motors and 2000
hours for vertical motors.

8.4.3.8 Motors shall be able to run with forced lubrication switched off or failed within specified
duration. During testing and commissioning the motor shall be able to run unloaded for a
period of 10minutes without forced lubrication and. or separate cooling applied.

8.4.3.9 Pre-lubricated sealed bearings may be considered provided a full guarantee is given for 4
to 5 years of trouble free service without the necessity of re-lubrication.

8.4.3.10 Motors shall be designed to permit removing / replacement of bearings.

8.4.3.11 The motors shall have facility for on-line greasing. Necessary grease nipples for on-line
lubrication from outside shall be provided for both DE & NDE bearing.

8.4.3.12 When grease nipples are provided, these shall be associated, where necessary, with
appropriately located relief devices to ensure passage of grease through the bearings.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 19 OF 27

8.4.3.13 Vertical motors shall be provided with thrust bearings suitable for the load imposed by the
driven equipment.

8.4.3.14 Oil lubricated bearing housings shall have the following features:

Oil reservoirs of sufficient depth to serve as a settling chamber.

Oil reservoirs fitted with constant level oilers (Trico or equivalent) on non-force-lubricated
bearings.

Cleanable or replaceable oil level indicator marked with acceptable high and low level
limits. (The indicator shall be designed such that oil will not get trapped in it, as this could
give a false reading).

Fill and drain openings (Drain opening shall be at the lowest point in the reservoir).

Equalizers and vents.

Ring slingers or other devices to prevent loss of oil.

8.5 ADDITIONAL REQUIREMENTS IN HAZARDOUS AREA

8.5.1 Zone 1 Area

8.5.1.1 Motors for use in Zone 1 areas within group installations shall be suitable for gas group IIB
and temperature class T4, unless otherwise specified in the requisition.

8.5.1.2 Type of protection shall be Exd (e) in accordance with IEC 60079-1. The motor shall be Exd
type but the terminal box shall be Exe type.

8.5.1.3 Motors used in Zone-1 areas shall be certified by ATEX / IECEX confirming compliance
with IEC 60079-1.

9. RATING PLATES

9.1 Rating plates shall be made of stainless steel material (SS 316L) and shall be fixed to a
non-removable part of the motor frame.

9.2 Information provided on the rating plates shall be in line with IEC 60034-1 and shall include
but not limited to the data as specified below :-

Manufacturers name

Serial number, model number and year of manufacturing

Manufacturing codes and standards

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 20 OF 27

Year of manufacturing

Enclosure ingress protection of motor frame and terminal boxes

Explosion protection of motor frame and terminal boxes as per IEC 60079

Explosion protection of auxiliaries such as instruments, protective devices, cooling fans,


etc., as per IEC 60079

Explosive gas atmosphere classification

Explosion proof certificate number

KW ratings

Rated RPM

Rated voltage and winding connections

Rated full load current

Rated frequency and numbers of phases

Rated speed

Range of operating temperatures

Insulation class and temperature rise limit

Power factor at full load

Efficiency at full load

Direction of rotation

Cooling method

Mounting method

Total weight

Type of lubricants, re-lubrication intervals, minimum and maximum allowable quantity of


lubricants for DE and NDE bearings (maintenance instruction)

Type of bearing at DE and NDE, serial numbers, size, clearance, shaft and housing fir
for DE and NDE bearings

Insulated bearings at DE and NDE

Recommended oil pressure (for forced lubricated bearings)

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 21 OF 27

Locked rotor current at rated voltage and frequency

Locked rotor torque at rated voltage and frequency

Allowable running-up time at rated voltage and 80% of rated voltage

Equipment tag number

9.3 Separate name plates shall be provided for the followings:-

Main terminal box

Auxiliary terminal boxes for RTD sensors, space heater, auxiliary cooling fan (for VFD-
operated motors), etc.

Frequency inverter parameter settings

Maintenance instructions

Operation cautions

9.4 The name plates shall be machine-engraved (black letters on white background)

9.5 Items required tagging shall be tagged with their specific item numbers.

9.6 Tags shall be corrosion resistant material and shall be impression-stamped.

9.7 Tags shall be attached to each component with a stainless steel strap, wire or hardware.

9.8 Motor shaft or the end-play shall be marker shall be provided to indicate the magnetic
center.

10. DOCUMENTATION

10.1 The following documents shall be provided by the vendor / manufacturer as a minimum but
not be limited to the following:-

10.1.1 Duly filled motor datasheet;

10.1.2 Overall and assembly drawings showing main dimensions, arrangement of components,
terminal boxes, foundation loading and gravity centre point location;

10.1.3 Dynamic Load Details (horizontal and vertical forces) ;

10.1.4 Control schematics and wiring diagrams covering all equipment pertaining to the motor;

10.1.5 Bearing arrangement/alignment drawing with data to replace the bearings/bearing lining for
motors;

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 22 OF 27

10.1.6 Speed torque characteristics;

10.1.7 Starting current versus time characteristics;

10.1.8 Efficiency & PF versus output power;

10.1.9 Thermal withstands characteristics of motor, hot/cold;

10.1.10 Motor thermal time constant;

10.1.11 Nameplate Data;

10.1.12 Detailed component list;

10.1.13 Recommended spare parts lists;

10.1.14 Incoming and outgoing cable arrangement details;

10.1.15 QC Manual and QC procedure;

10.1.16 Inspection Test Plan;

10.1.17 Any relevant drawings, literature, calculations, certificates or any relevant drawings as
requested by Employer / Employers Representative.

10.2 Each drawing shall be provided with a title block in the bottom right-hand corner
incorporating the following information:-

10.2.1 Official trade name of the Vendor/Manufacturer;

10.2.2 Vendor/Manufacturers drawing number;

10.2.3 A symbol or letter indicating the latest issue or revision;

10.2.4 Drawing title giving the description of contents whereby the drawing can be identified;

10.2.5 PO number and item tag numbers.

10.3 Revisions to drawing shall be identified with Triangular symbols adjacent to the alterations,
a brief description in tabular form of each revision shall be given, and if applicable, the
authority and date of the revision shall be listed. The term "Latest Revision" shall not be
used.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 23 OF 27

10.4 All the documents mentioned above shall be finally submitted as dossier in a compact disc
(electronic copy) format.

10.5 Language used by vendor shall be in English.

10.6 No manufacturing / fabrication is allowed to commence until all submitted documents are
given final approval from Employer / Employers Representative.
11. INSPECTION AND TESTING

11.1 During manufacturing, the motors shall be subject to inspection by Contractor/Employer's


Inspector and/or by a Third-party Inspection Agency authorized by the Employer.

11.2 The Vendor/Manufacturer shall carry out the complete range of Routine and Performance
Tests as specified by IEC 60034.

11.3 All the type, routine and performance tests, as specified, shall be witnessed by the
Contractor/Employers Inspector and/or Third-party Inspection Agency as authorized by the
Employer. The Manufacturer shall give prior notice of minimum 4 weeks to the Contractor
for witnessing the tests.

11.4 All the type tests, routine tests and performance tests, as specified, shall be carried out at
manufacturer's shop under his care and expense.
FAT & SAT procedures shall be submitted in advance for review and approval by the
Contractor/Employer prior to the tests.
Tests shall be carried out in accordance with this specification and the relevant IEC and
ISO recommendations, unless otherwise agreed.

11.5 Tests Certificates/Reports duly signed by the Contractor/Employers Inspector at the end of
the tests shall be a part of final documentation but this will not release the responsibility of
the Vendor/Manufacturer to deliver the equipment complying with the specification.

11.6 The manufacturer shall submit all internal test records of the tests carried out by him on the
purchased equipment at least one week before the final inspection and testing of the
equipment.

11.7 Performance tests shall be carried out on all motors. The performance test of motor shall at
least include but not limited to the following tests in the motor vendor/manufacturers
works:-
Winding resistance (cold)
Full load heat run
Winding resistance (hot)
Calculated winding temperature rise
Calculated winding resistance at 20C
Bearing temperature rise

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 24 OF 27

Slip at full and load


Efficiency at full and load
Power factor at full and load
Motor current unbalance at full load
Locked rotor current (effects of saturation on the measured values shall be taken into
account)
Locked rotor torque (effects of saturation on the measured values shall be taken into
account)
No-load current
No-load losses
Vibration severity
Di-electric test on:
o Motor windings
o Anti-condensation heater(s)
o Built-in temperature detectors
Insulation resistance on:
o motor windings - before heat run & after heat run and di-electric test
o Anti- condensation heater(s)
o Built-in temperature detectors
o Bearing insulation
Polarization index test on motor windings
Shaft voltage at no-load
Noise test
Torque speed curve
Sleeve bearing inspection, if applicable.
Physical inspection for compliance with this specification

11.8 The manufacturer shall carry out routine tests on electric motors that are not subjected to
Performance Test. Routine tests shall include at least but not limited to the followings in the
motor vendor/manufacturers work :-

Winding resistance (cold)


Calculated winding resistance at 20C
Locked rotor current (the effects of saturation on the measured values shall be taken into
account)
Locked rotor torque (the effects of saturation on the measured values shall be taken into
account)
No-Load current
No-load losses
Vibration severity
Di-electric test on:
o Motor windings
o Anti-condensation heater(s)

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 25 OF 27

o Built-in temperature detectors


Insulation resistance on
o Motor windings
o Anti-condensation heater(s)
o Built-in temperature detectors
o Bearing insulation
Physical inspection on compliance with this specification

11.9 The manufacturer shall submit the following certificates/reports for verification by the
Contractor/employers Inspector, and/or Third-party Inspector as authorized by the
Employer:-

Test certificate for degree of protection of enclosure


Short circuit test for terminal box
Impulse test certificate
Test certificates issued by the recognized independent test house for hazardous area
motors.
Approval certificates issued by Statutory Authorities for hazardous area motors
License and marking as required by Statutory Authorities for explosion-proof motors

11.10 Though the motors shall be accepted on the basis of the satisfactory result of the testing at
the shop, it shall not absolve the Vendor/Manufacturer from liability regarding the proper
functioning and performance of the motors when coupled to the driven equipment at site.

11.11 The motors and associated equipment shall have test certificates issued by recognized
independent test house (ATEX/BASEEFA/LCIE/UL/FM or equivalent). All indigenous
motors shall conform to IEC Standards and shall be certified by International testing
agencies. All motors (indigenous and imported) shall also have valid statutory approvals as
applicable for the specified location. All indigenous explosion-proof motors shall have valid
license & marking as required by statutory authorities For VFD driven motors, motor
nameplate shall clearly indicate that the motor is suitable for operation with variable
frequency drive along with VFD make and model number.

11.12 The motors shall be first shop-tested in motor manufacturers shop and then ship to Pump
manufacturers shop for the performance of integrated tests together with the job pumps
and the job VFDs/Soft Starters before shipment to site.

11.13 Before leaving the vendors work, the motors shall have been fully inspected and tested,
and all test records/certificates/reports shall have been approved and signed off by the
Contractor/Employers Inspector and/or Third-party Inspector as authorized by the
Employer. All punch-list items, as a result of the FAT, shall have been cleared by the motor
vendor/manufacturer and approved by the Contractor/Employers Inspector, and/or Third-
party Inspector as authorized by the Employer before shipment is allowed.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 26 OF 27

12. GUARANTEES

12.1 Vendor shall guarantee the process performance and mechanical design of all equipment
supplied under this specification when operated at the conditions specified herein.

12.2 Vendor shall guarantee that all the materials included in his scope of supply are of the best
quality, free from faults in design and poor workmanship and fulfill satisfactorily the
specified operating and design conditions.

12.3 Vendor/Manufacturer complied with the provisions of this Specification and Codes,
Standards and Specifications mentioned herein, does not relieve Contractor / Vendors
responsibility to furnish materials of proper design, mechanically suited to meet the required
conditions.

12.4 Vendor/Manufacturer shall be responsible to make all the necessary or desirable


modifications, replacements or repairs, free of charge, if any kind of defect in design,
material, poor workmanship or operating characteristics, arises during the guarantee period.

13. TRAINING

The Motor Vendor shall provide training for Employers operations, maintenance and service
personnel. The training shall include classroom discussion of the theory of operation of the
motor, as well as trouble shooting, maintenance and service methods for the supplied
equipment.

14. START-UP

The Motor Vendor shall provide the field services of a factory trained technician, as
necessary to supervise installation, inspect, install, test and start-up all equipment provided.

15. PACKING AND SHIPMENT

15.1 The Vendor shall ensure that all packing and protection supplied for the materials are
adequate to maintain the material guarantees.

15.2 Items supplied loose required for erection at site shall be packed together with the Motor.

15.3 Preparation for shipment shall be in accordance with the Vendor's standards and as noted
herein. The Vendor shall be solely responsible for the adequacy of the preparation for
shipment provisions with respect to materials and application and to provide equipment at
the destination in ex-works condition when handled by commercial carriers.

15.4 Adequate protection shall be provided to prevent mechanical damage and atmospheric
corrosion in transit and at the jobsite.

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


EMPLOYER EMPLOYERS REPRESENTATIVE CONTRACTOR

DOCUMENT TITLE DOCUMENT NO APL JOB NO. F201007 PROJ NO. 142901
SPECIFICATION & DATA 80-F201007-IS-025
SHEET FOR 3.3KV MOTOR REV. NO. 1 SHEET NO. 27 OF 27

15.5 If the motors are intended to be imported, it shall be the sole responsibility of the Vendor /
Contractor to ensure that the motors are properly packed for safe transport by road and
ocean freight. The motors shall be delivered, mechanically completed and cleaned and
packed in suitable sea-worthy packing to preserve the cleanliness during any storage,
intermediate transport, shipment, till installation.
15.6 Any wood packaging material intended to be used to import electrical items shall be heat
treated or duly fumigated with Methyl Bromide and stamped or branded with a mark of
compliance. Such procedures are to be executed in strict compliance to accepted
international standard.

15.7 After inspection and test, equipment shall be completely free of water and dry before start
of preparation for shipment.

15.8 Equipment shall be packed, securely anchored and skid mounted when required. Bracing,
supports and rigging connections shall be provided to prevent damage during transit, lifting
or unloading.

16. SPARE PARTS AND SPECIAL TOOLS

16.1 Vendor shall be responsible for the supply of all spares required for start-up and
commissioning of the Motor and its accessories.

16.2 Vendor shall also recommend and quote for the supply of required spare parts for a normal
operation for a minimum of 2 years.

16.3 Any special tools required for installation and maintenance of the motor shall be provided
by vendor / manufacturer.

17. ATTACHMENTS

Attachment : MV Motor Data Sheets

S/No. Pump Tag No. Service


1 PM-201/202/203/204 GO/MGO Ship Loading Pump
2 PM-301/302 FO Ship Loading Pump/CS Blending
3 PM-303 FO Ship Loading Pump
4 PM-501/502 Blending Pump
5 Deleted (PM-FWP-501A_ Fire Pump)

PREPARED FOR BPGIC FUJAIRAH TERMINAL PHASE 1


Sheet 1 of 2
Data Sheet for AC Motor

Rev. C D 0 1 Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Karthi Karthi Karthi Karthi Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Viraj Viraj Viraj Viraj Chkd.
Location : AL Suda, Fujairah, UAE Appd. TSF TSF TSF TSF Appd.
Project no: 142901 Date 02/09/2015 13/05/2016 06/06/2016 07/07/2016 Date

Driven Equipment : 12 Preferred method of cooling : IC 411


1 Service : GO/MGO Ship Loading Pump n self-cooled o separately cooled
2 Tag no.: PM-201, 202, 203 & 204 o air-to-air o air-to-water
13 Finished paint : MP ______ (Note 8)
Basic requirements :
1 Type of motor : o synchronous n induction Applicable Standards :
n squirrel cage o slip-ring 1 n IEC 60034 - Rotating electrical machines
o pole changing type 2-speed 2 n IEC 60079 - Electrical apprartus for explosive gas atmospheres
2 Rated continuous output : 590 kW (Note 8) 3 n IEC 60085 - Thermal classification and classes of insulation.
3 Duty : n continuous o standby Site conditions :
o intermittent, type: S 1 1 Design temp. : 50 C Maximum (Note 7)
4 Synchronous speed : rpm. No. of poles : 2 Max. design humidity : 100 % Maximum
5 Direction of rotation : n CW n CCW(facing DE) 3 Max. rainfall intensity : 66 mm/hr (for one hour per day)
6 Supply system : 3.3 KV(10%),3ph., 50 Hz(5%) 4 Site elevation : <1000 m (above mean sea level)
7 Fault level : max. 31.5kA min. ______ MVA 5 Location :
8 Motor starting method : o Indoor n outdoor (direct solar exposure)
o DOL o star-delta n land n coastal (marine environment)
o auto-transf. o VSD o offshore n dusty (fine dust & pollutants)
o rotor resistance n electronic soft starter with bypass circuit n corrosive o snow hoar-frost
o no-load o on load n desert, sand storms n tropical rains
o reversible o Open-transition 6 Area classification :
9 No. of starts per year : 1000 o Safe Area
10 Max. sound pressure (1m distance) : < 85 dB(A) n Zone-1 , group IIB , temp. T4
11 Unit trafo included : o yes n no (as per IEC 60079 ______________________ ).
7 Cooling water temp :
Construction : max : ______ C min: ______ C
1 Stator winding connection : n star o delta
2 Stator frame : o Aluminium n Cast iron Accessories :
o steel 1 n Common base-plate (with driven equipment)
3 Enclosure : n TEFC n explosion-proof EEx'd' 2 Space heaters : n yes, (Note 5) o no
o non-sparking Ex'n' o increased safety EEX'e' 3 Protective device : o leakage switch
o pressurised EEx'p' o dust ignition-proof o thermal switch
4 Terminal box : EEx'd' n EEx'e' o ____________________
5 Ingress protection : Motor enclosure, IP65 4 Temp. detectors : n yes o no
Terminal box, IP65 , Bearing casing, IP65 n RTD o PTC o ______
6 Insulation class : F with temp rise limit of class : B n 2 numbers per phase n One each at DE & NDE bearings
7 Type of construction & Mounting arrangements : IM B3 5 CT: o yes n no
o vertical n horizontal (Note 6) o location ________________
o foot o flange o _____ class _______ , ratio _____ , VA ______ ,
8 Bearing & lubrication system : class X CT :
o Journal o Roller n Ball element knee vol. : ______ V at ______ A excitation current,
o self o forced o sealed wdg. resistance : ______ ohm at 75C
n greased o lube oil pump 6 Vibration switch : o yes n no
o oil pump - shaft driven o moto-supply ______ 7 Other control & monitoring devices _________________
9 Terminal box location (viewed from non-driven end):
Main : o right n left o top Inspection & Testing :
n rotatable 360 per 90 1 Performance test : n yes o no
Heater : o right n left o top 2 Sample coil test : o yes n no
n rotatable 360 per 90 3 Noise test : n yes o no
RTD sensors o right n left o top 4 Production test : n yes o no
n rotatable 360 per 90 5 o Special test (specify) : ______________________
6 Witnessed : n yes o no
10 Cables Cross-sec Type Overall diameter Diameter over inner sheath of armor wire
Main 3C x 185 mm CU/XLPE/GSWA/PVC 65 mm mm mm
Heater 2C x 2.5 mm CU/XLPE/GSWA/PVC 13.6 mm mm mm
RTD sensors 7T x 2.5 mm CU/XLPE/GSWA/PVC 30 mm mm mm
11 Cable Gland Required Make Type Entry Thread Size
Main n yes o no 1 M75S x 2.5
Heater n yes o no M20 x 2.5
RTD sensors n yes o no M32 x 2.5

12 Mechanical Impact protection IK 10


Notes :
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Refer to Attachment for additional requirements on squirrel cage induction motor.
3 Tick or check whichever is applicable / required.
4 MP - Manufacturer Proposal.
5 AC 230 V, 1-Ph, 50 Hz.
6 Supplier to confirm the mounting arrangement suitable for the specified pump.
7 Maximum 80oC for equipment directly exposed to solar radiation.
8 To be confirmed by the vendor.
Specific Requirements :
Pump vendor to submit separate motor data sheet for each pump tag no. as indicated
in this requisition sheet.
Sheet 2 of 2

Data Sheet for AC Motor


(To be complete by Motor Manufacturer)

Rev. A B C D Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Chkd.
Location : AL Suda, Fujairah, UAE Appd. Appd.
Project No: 142901 Date Date

DATA TO BE FURNISHED BY MANUFACTURER


A General D Motor Performance Data :
1 Manufacturer : 4/4 load 3/4 load 1/2 load 1/4 load no load
2 Pump Tag No. : 1 Efficiency (%)
3 Local Agent : 2 Stator current (A)
3 Power factor
3 P.O. No. : 4 Speed (rpm)
4 Model / Type : 5 Locked rotor torque : ___________________% of full load torque.
5 Country of origin : 6 Pull-up torque : ________________________% of full load torque.
7 Breakdown torque : ____________________% of full load torque.
B Construction 8 Starting current : ___________ A
1 Winding insulation : Temp. rise limit : 9 Critical speed : _____________ rpm
2 Stator winding connection : 10 Time te' (for EEx'e' motors) : __________________sec.(< 10 sec)
3 Stator frame material : 11 Motor inertia : _______________________ (kg sq.m..)
4 Bearings No. Make Type 12 Total weight : _______________________ kg
DE 13 At Un At 0.8Un
NDE a Locked rotor current
5 Bearing lifetime : b Locked rotor torque
6 Bearing with insulation : c Pull-up torque
7 Type & Make of lubrication : d Breakdown torque
8 Type of cooling fan impeller : e Running-up time
9 Type of end (fan) cover : f Allowable running-up time
g Slip (%)
C Basic Data h Maximum stalling time (Cold)
1 Frame size : i Maximum stalling time (Hot)
2 Rated voltage & tolerances : j Starting current
3 Rated frequency & tolerances : k
4 Motor rating : l
5 IP of motor and aux. enclosure: 14 Max. sound pressure (1m distance) : ___________dB(A)
6 IP of terminal box and bearing housings : 15 Restart with full opposite residual voltage : Yes / No
7 Suitable for installation in classified area : Yes / No 16 Allowable consecutive starts: Cold : ______ Hot : _______
- Zone : 17 Warm-up time constant :
- Gas group : 18 Cold-down time constant :
- Temperature classification : 19 Warm-up time constant (under locked rotor condition) :
8 Explosion protection type : 20 Vibration in mm/sec
- Motor frame :
- Terminal box : E Miscellaneous
9 Standard complied : 1 Anti-condensation space heater provided : Yes / No
10 ATEX 95 compliance : Yes / No - Operating voltage & wattage :
-Explosion protection certificate : Yes / No 2 Suitable for VFD operation : Yes / No
- Issued by : 3 Protective devices provided :
11 Method of cooling : 4 Nos. of pair of poles :
12 Method of mounting : 5 Suitable to operate on 60 Hz power supply : Yes / No

Notes:
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Circle on selected items, where applicable.
3 Provide list of deviations from Purchaser's requirements, if any.
4 Equipment is able to sustain without any detrimental effect when subjecting to 2 and 3-phase short-circuit at the motor terminals.
5 Integrity of the equipment will not suffer when reconnected to the supply source with full opposite residual voltage after a brief power interruption.
Sheet 1 of 2
Data Sheet for AC Motor

Rev. C D 0 1 Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Karthi Karthi Karthi Karthi Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Viraj Viraj Viraj Viraj Chkd.
Location : AL Suda, Fujairah, UAE Appd. TSF TSF TSF TSF Appd.
Project no: 142901 Date 02/09/2015 13/05/2016 06/06/2016 07/07/2016 Date

Driven Equipment : 12 Preferred method of cooling : IC 411


1 Service : FO Ship Loading Pump + Cutter Stock Blending n self-cooled o separately cooled
2 Tag no.: PM-301 & 302 o air-to-air o air-to-water
13 Finished paint : MP ______ (Note 8)
Basic requirements :
1 Type of motor : o synchronous n induction Applicable Standards :
n squirrel cage o slip-ring 1 n IEC 60034 - Rotating electrical machines
o pole changing type 2-speed 2 n IEC 60079 - Electrical apprartus for explosive gas atmospheres
2 Rated continuous output : 950 kW (Note 8) 3 n IEC 60085 - Thermal classification and classes of insulation.
3 Duty : n continuous o standby Site conditions :
o intermittent, type: S 1 1 Design temp. : 50 C Maximum (Note 7)
4 Synchronous speed : rpm. No. of poles : 2 Max. design humidity : 100 % Maximum
5 Direction of rotation : n CW n CCW(facing DE) 3 Max. rainfall intensity : 66 mm/hr (for one hour per day)
6 Supply system : 3.3 KV(10%),3ph., 50 Hz(5%) 4 Site elevation : <1000 m (above mean sea level)
7 Fault level : max. 31.5kA min. ______ MVA 5 Location :
8 Motor starting method : o Indoor n outdoor (direct solar exposure)
o DOL o star-delta n land n coastal (marine environment)
o auto-transf. n VFD o offshore n dusty (fine dust & pollutants)
o rotor resistance o electronic soft starter with bypass circuit n corrosive o snow hoar-frost
o no-load o on load n desert, sand storms n tropical rains
o reversible o Open-transition 6 Area classification :
9 No. of starts per year : 1000 o Safe Area
10 Max. sound pressure (1m distance) : < 85 dB(A) n Zone-1 , group IIB , temp. T4
11 Unit trafo included : o yes n no (as per IEC 60079 ______________________ ).
7 Cooling water temp :
Construction : max : ______ C min: ______ C
1 Stator winding connection : n star o delta
2 Stator frame : o Aluminium n Cast iron Accessories :
o steel 1 n Common base-plate (with driven equipment)
3 Enclosure : n TEFC n explosion-proof EEx'd' 2 Space heaters : n yes, (Note 5) o no
o non-sparking Ex'n' o increased safety EEX'e' 3 Protective device : o leakage switch
o pressurised EEx'p' o dust ignition-proof o thermal switch
4 Terminal box : EEx'd' n EEx'e' o ____________________
5 Ingress protection : Motor enclosure, IP65 4 Temp. detectors : n yes o no
Terminal box, IP65 , Bearing casing, IP65 n RTD o PTC o ______
6 Insulation class : F with temp rise limit of class : B n 2 numbers per phase n One each at DE & NDE bearings
7 Type of construction & Mounting arrangements : IM B3 5 CT: o yes n no
o vertical n horizontal (Note 6) o location ________________
o foot o flange o _____ class _______ , ratio _____ , VA ______ ,
8 Bearing & lubrication system : class X CT :
o Journal o Roller n Ball element knee vol. : ______ V at ______ A excitation current,
o self o forced o sealed wdg. resistance : ______ ohm at 75C
n greased o lube oil pump 6 Vibration switch : o yes n no
o oil pump - shaft driven o moto-supply ______ 7 Other control & monitoring devices _________________
9 Terminal box location (viewed from non-driven end):
Main : o right n left o top Inspection & Testing :
n rotatable 360 per 90 1 Performance test : n yes o no
Heater : o right n left o top 2 Sample coil test : o yes n no
n rotatable 360 per 90 3 Noise test : n yes o no
RTD sensors o right n left o top 4 Production test : n yes o no
n rotatable 360 per 90 5 o Special test (specify) : ______________________
6 Witnessed : n yes o no
10 Cables Cross-sec Type Overall diameter Diameter over inner sheath of armor wire
Main 3C x 185 mm CU/XLPE/GSWA/PVC 65 mm mm mm
Heater 2C x 2.5 mm CU/XLPE/GSWA/PVC 13.6 mm mm mm
RTD sensors 7T x 2.5 mm CU/XLPE/GSWA/PVC 30 mm 1 mm mm
11 Cable Gland Required Make Type Entry Thread Size
Main n yes o no M75S x 2.5
Heater n yes o no M20 x 2.5
RTD sensors n yes o no M32 x 2.5
12 Mechanical Impact protection IK 10

Notes :
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Refer to Attachment for additional requirements on squirrel cage induction motor.
3 Tick or check whichever is applicable / required.
4 MP - Manufacturer Proposal.
5 AC 230 V, 1-Ph, 50 Hz.
6 Supplier to confirm the mounting arrangement suitable for the specified pump.
7 Maximum 80oC for equipment directly exposed to solar radiation.
8 To be confirmed by the vendor.
Specific Requirements :
Pump vendor to submit separate motor data sheet for each pump tag no. as indicated
in this requisition sheet.
Sheet 2 of 2

Data Sheet for AC Motor


(To be complete by Motor Manufacturer)

Rev A B C D Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) Made Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd. Chkd.
Location : AL Suda, Fujairah, UAE Appd. Appd.
Project No: 142901 Date Date

DATA TO BE FURNISHED BY MANUFACTURER


A General D Motor Performance Data :
1 Manufacturer : 4/4 load 3/4 load 1/2 load 1/4 load no load
2 Pump Tag No. : 1 Efficiency (%)
3 Local Agent : 2 Stator current (A)
3 Power factor
3 P.O. No. : 4 Speed (rpm)
4 Model / Type : 5 Locked rotor torque : ___________________% of full load torque.
5 Country of origin : 6 Pull-up torque : ________________________% of full load torque.
7 Breakdown torque : ____________________% of full load torque.
B Construction 8 Starting current : ___________ A
1 Winding insulation : Temp. rise limit : 9 Critical speed : _____________ rpm
2 Stator winding connection : 10 Time te' (for EEx'e' motors) : __________________sec.(< 10 sec)
3 Stator frame material : 11 Motor inertia : _______________________ (kg sq.m..)
4 Bearings No. Make Type 12 Total weight : _______________________ kg
DE 13 At Un At 0.8Un
NDE a Locked rotor current
5 Bearing lifetime : b Locked rotor torque
6 Bearing with insulation : c Pull-up torque
7 Type & Make of lubrication : d Breakdown torque
8 Type of cooling fan impeller : e Running-up time
9 Type of end (fan) cover : f Allowable running-up time
g Slip (%)
C Basic Data h Maximum stalling time (Cold)
1 Frame size : i Maximum stalling time (Hot)
2 Rated voltage & tolerances : j Starting current
3 Rated frequency & tolerances : k
4 Motor rating : l
5 IP of motor and aux. enclosure: 14 Max. sound pressure (1m distance) : ___________dB(A)
6 IP of terminal box and bearing housings : 15 Restart with full opposite residual voltage : Yes / No
7 Suitable for installation in classified area : Yes / No 16 Allowable consecutive starts: Cold : ______ Hot : _______
- Zone : 17 Warm-up time constant :
- Gas group : 18 Cold-down time constant :
- Temperature classification : 19 Warm-up time constant (under locked rotor condition) :
8 Explosion protection type : 20 Vibration in mm/sec
- Motor frame :
- Terminal box : E Miscellaneous
9 Standard complied : 1 Anti-condensation space heater provided : Yes / No
10 ATEX 95 compliance : Yes / No - Operating voltage & wattage :
-Explosion protection certificate : Yes / No 2 Suitable for VFD operation : Yes / No
- Issued by : 3 Protective devices provided :
11 Method of cooling : 4 Nos. of pair of poles :
12 Method of mounting : 5 Suitable to operate on 60 Hz power supply : Yes / No

Notes:
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Circle on selected items, where applicable.
3 Provide list of deviations from Purchaser's requirements, if any.
4 Equipment is able to sustain without any detrimental effect when subjecting to 2 and 3-phase short-circuit at the motor terminals.
5 Integrity of the equipment will not suffer when reconnected to the supply source with full opposite residual voltage after a brief power interruption.
Sheet 1 of 2
Data Sheet for AC Motor

Rev. C D 0 1 Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Karthi Karthi Karthi Karthi Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Viraj Viraj Viraj Viraj Chkd.
Location : AL Suda, Fujairah, UAE Appd. TSF TSF TSF TSF Appd.
Project no: 142901 Date 02/09/2015 13/05/2016 06/06/2016 07/07/2016 Date

Driven Equipment : 12 Preferred method of cooling : IC 411


1 Service : FO Ship Loading Pump n self-cooled o separately cooled
2 Tag no.: PM-303 o air-to-air o air-to-water
13 Finished paint : MP ______ Note (8)
Basic requirements :
1 Type of motor : o synchronous n induction Applicable Standards :
n squirrel cage o slip-ring 1 n IEC 60034 - Rotating electrical machines
o pole changing type 2-speed 2 n IEC 60079 - Electrical apprartus for explosive gas atmospheres
2 Rated continuous output : 950 kW (Note 8) 3 n IEC 60085 - Thermal classification and classes of insulation.
3 Duty : n continuous o standby Site conditions :
o intermittent, type: S 1 1 Design temp. : 50 C Maximum (Note 7)
4 Synchronous speed : rpm. No. of poles : 2 Max. design humidity : 100 % Maximum
5 Direction of rotation : n CW n CCW(facing DE) 3 Max. rainfall intensity : 66 mm/hr (for one hour per day)
6 Supply system : 3.3 KV(10%),3ph., 50 Hz(5%) 4 Site elevation : <1000 m (above mean sea level)
7 Fault level : max. 31.5kA min. ______ MVA 5 Location :
8 Motor starting method : o Indoor n outdoor (Direct solar exposure)
o DOL o star-delta n land n coastal (marine environment)
o auto-transf. o VSD o offshore n dusty (fine dust & pollutants)
o rotor resistance n electronic soft starter with bypass circuit n corrosive o snow hoar-frost
o no-load o on load n desert, sand storms n tropical rains
o reversible o Open-transition 6 Area classification :
9 No. of starts per year : 1000 o Safe Area
10 Max. sound pressure (1m distance) : < 85 dB(A) n Zone-1 , group IIB , temp. T4
11 Unit trafo included : o yes n no (as per IEC 60079 ______________________ ).
7 Cooling water temp :
Construction : max : ______ C min: ______ C
1 Stator winding connection : n star o delta
2 Stator frame : o Aluminium n Cast iron Accessories :
o steel 1 n Common base-plate (with driven equipment)
3 Enclosure : n TEFC n explosion-proof EEx'd' 2 Space heaters : n yes, (Note 5) o no
o non-sparking Ex'n' o increased safety EEX'e' 3 Protective device : o leakage switch
o pressurised EEx'p' o dust ignition-proof o thermal switch
4 Terminal box : EEx'd' n EEx'e' o ____________________
5 Ingress protection : Motor enclosure, IP65 4 Temp. detectors : n yes o no
Terminal box, IP65 , Bearing casing, IP65 n RTD o PTC o ______
6 Insulation class : F with temp rise limit of class : B n 2 numbers per phase n One each at DE & NDE bearings
7 Type of construction & Mounting arrangements : IM B3 5 CT: o yes n no
o vertical n horizontal (Note 6) o location ________________
o foot o flange o _____ class _______ , ratio _____ , VA ______ ,
8 Bearing & lubrication system : class X CT :
o Journal o Roller n Ball element knee vol. : ______ V at ______ A excitation current,
o self o forced o sealed wdg. resistance : ______ ohm at 75C
n greased o lube oil pump 6 Vibration switch : o yes n no
o oil pump - shaft driven o moto-supply ______ 7 Other control & monitoring devices _________________
9 Terminal box location (viewed from non-driven end):
Main : o right n left o top Inspection & Testing :
n rotatable 360 per 90 1 Performance test : n yes o no
Heater : o right n left o top 2 Sample coil test : o yes n no
n rotatable 360 per 90 3 Noise test : n yes o no
RTD sensors o right n left o top 4 Production test : n yes o no
n rotatable 360 per 90 5 o Special test (specify) : ______________________
6 Witnessed : n yes o no
10 Cables Cross-sec Type Overall diameter Diameter over inner sheath of armor wire
Main 3C x 185 mm CU/XLPE/GSWA/PVC 65 mm mm mm
Heater 2C x 2.5 mm CU/XLPE/GSWA/PVC 13.6 mm mm mm
RTD sensors 7T x 2.5 mm CU/XLPE/GSWA/PVC 30 mm 1 mm mm
11 Cable Gland Required Make Type Entry Thread Size
Main n yes o no M75S x 2.5
Heater n yes o no M20 x 2.5
RTD sensors n yes o no M32 x 2.5

12 Mechanical Impact protection IK 10

Notes :
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Refer to Attachment for additional requirements on squirrel cage induction motor.
3 Tick or check whichever is applicable / required.
4 MP - Manufacturer Proposal.
5 AC 230 V, 1-Ph, 50 Hz.
6 Supplier to confirm the mounting arrangement suitable for the specified pump.
7 Maximum 80oC for equipment directly exposed to solar radiation.
8 To be confirmed by the vendor.
Specific Requirements :
Pump vendor to submit separate motor data sheet for each pump tag no. as indicated
in this requisition sheet.
Sheet 2 of 2

Data Sheet for AC Motor


(To be complete by Motor Manufacturer)

Rev. A B C D Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Chkd.
Location : AL Suda, Fujairah, UAE Appd. Appd.
Project No: 142901 Date Date

DATA TO BE FURNISHED BY MANUFACTURER


A General D Motor Performance Data :
1 Manufacturer : 4/4 load 3/4 load 1/2 load 1/4 load no load
2 Pump Tag No. : 1 Efficiency (%)
3 Local Agent : 2 Stator current (A)
3 Power factor
3 P.O. No. : 4 Speed (rpm)
4 Model / Type : 5 Locked rotor torque : ___________________% of full load torque.
5 Country of origin : 6 Pull-up torque : ________________________% of full load torque.
7 Breakdown torque : ____________________% of full load torque.
B Construction 8 Starting current : ___________ A
1 Winding insulation : Temp. rise limit : 9 Critical speed : _____________ rpm
2 Stator winding connection : 10 Time te' (for EEx'e' motors) : __________________sec.(< 10 sec)
3 Stator frame material : 11 Motor inertia : _______________________ (kg sq.m..)
4 Bearings No. Make Type 12 Total weight : _______________________ kg
DE 13 At Un At 0.8Un
NDE a Locked rotor current
5 Bearing lifetime : b Locked rotor torque
6 Bearing with insulation : c Pull-up torque
7 Type & Make of lubrication : d Breakdown torque
8 Type of cooling fan impeller : e Running-up time
9 Type of end (fan) cover : f Allowable running-up time
g Slip (%)
C Basic Data h Maximum stalling time (Cold)
1 Frame size : i Maximum stalling time (Hot)
2 Rated voltage & tolerances : j Starting current
3 Rated frequency & tolerances : k
4 Motor rating : l
5 IP of motor and aux. enclosure: 14 Max. sound pressure (1m distance) : ___________dB(A)
6 IP of terminal box and bearing housings : 15 Restart with full opposite residual voltage : Yes / No
7 Suitable for installation in classified area : Yes / No 16 Allowable consecutive starts: Cold : ______ Hot : _______
- Zone : 17 Warm-up time constant :
- Gas group : 18 Cold-down time constant :
- Temperature classification : 19 Warm-up time constant (under locked rotor condition) :
8 Explosion protection type : 20 Vibration in mm/sec
- Motor frame :
- Terminal box : E Miscellaneous
9 Standard complied : 1 Anti-condensation space heater provided : Yes / No
10 ATEX 95 compliance : Yes / No - Operating voltage & wattage :
-Explosion protection certificate : Yes / No 2 Suitable for VFD operation : Yes / No
- Issued by : 3 Protective devices provided :
11 Method of cooling : 4 Nos. of pair of poles :
12 Method of mounting : 5 Suitable to operate on 60 Hz power supply : Yes / No

Notes:
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Circle on selected items, where applicable.
3 Provide list of deviations from Purchaser's requirements, if any.
4 Equipment is able to sustain without any detrimental effect when subjecting to 2 and 3-phase short-circuit at the motor terminals.
5 Integrity of the equipment will not suffer when reconnected to the supply source with full opposite residual voltage after a brief power interruption.
Sheet 1 of 2
Data Sheet for AC Motor

Rev. C D 0 1 Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Karthi Karthi Karthi Karthi Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Viraj Viraj Viraj Viraj Chkd.
Location : AL Suda, Fujairah, UAE Appd. TSF TSF TSF TSF Appd.
Project no: 142901 Date 02/09/2015 13/05/2016 06/06/2016 07/07/2016 Date

Driven Equipment : 12 Preferred method of cooling : IC 411


1 Service : Blending Pump n self-cooled o separately cooled
2 Tag no.: PM-501 & 502 o air-to-air o air-to-water
13 Finished paint : MP ______ (Note 8)
Basic requirements :
1 Type of motor : o synchronous n induction Applicable Standards :
n squirrel cage o slip-ring 1 n IEC 60034 - Rotating electrical machines
o pole changing type 2-speed 2 n IEC 60079 - Electrical apprartus for explosive gas atmospheres
2 Rated continuous output : 250 kW (Note 8) 3 n IEC 60085 - Thermal classification and classes of insulation.
3 Duty : n continuous o standby Site conditions :
o intermittent, type: S 1 1 Design temp. : 50 C Maximum (Note 7)
4 Synchronous speed : rpm. No. of poles : 2 Max. design humidity : 100 % Maximum
5 Direction of rotation : n CW n CCW(facing DE) 3 Max. rainfall intensity : 66 mm/hr for one hour per day
6 Supply system : 3.3 KV(10%),3ph., 50 Hz(5%) 4 Site elevation : <1000 m (above mean sea level)
7 Fault level : max. 31.5kA min. ______ MVA 5 Location :
8 Motor starting method : o Indoor n outdoor (direct solar exposure)
o DOL o star-delta n land n coastal (marine environment)
o auto-transf. o VSD o offshore n dusty (fine dust & pollutants)
o rotor resistance n electronic soft starter with bypass circuit n corrosive o snow hoar-frost
o no-load o on load n desert, sand storms n tropical rains
o reversible o Open-transition 6 Area classification :
9 No. of starts per year : 1000 o Safe Area
10 Max. sound pressure (1m distance) : < 85 dB(A) n Zone-1 , group IIB , temp. T4
11 Unit trafo included : o yes n no (as per IEC 60079 ______________________ ).
7 Cooling water temp :
Construction : max : ______ C min: ______ C
1 Stator winding connection : n star o delta
2 Stator frame : o Aluminium n Cast iron Accessories :
o steel 1 n Common base-plate (with driven equipment)
3 Enclosure : n TEFC n explosion-proof EEx'd' 2 Space heaters : n yes, (Note 5) o no
o non-sparking Ex'n' o increased safety EEX'e' 3 Protective device : o leakage switch
o pressurised EEx'p' o dust ignition-proof o thermal switch
4 Terminal box : EEx'd' n EEx'e' o ____________________
5 Ingress protection : Motor enclosure, IP65 4 Temp. detectors : n yes o no
Terminal box, IP65 , Bearing casing, IP65 n RTD o PTC o ______
6 Insulation class : F with temp rise limit of class : B n 2 numbers per phase n One each at DE & NDE bearings
7 Type of construction & Mounting arrangements : IM B3 5 CT: o yes n no
o vertical n horizontal (Note 6) o location ________________
o foot o flange o _____ class _______ , ratio _____ , VA ______ ,
8 Bearing & lubrication system : class X CT :
o Journal o Roller n Ball element knee vol. : ______ V at ______ A excitation current,
o self o forced o sealed wdg. resistance : ______ ohm at 75C
n greased o lube oil pump 6 Vibration switch : o yes n no
o oil pump - shaft driven o moto-supply ______ 7 Other control & monitoring devices _________________
9 Terminal box location (viewed from non-driven end):
Main : o right n left o top Inspection & Testing :
n rotatable 360 per 90 1 Performance test : n yes o no
Heater : o right n left o top 2 Sample coil test : o yes n no
n rotatable 360 per 90 3 Noise test : n yes o no
RTD sensors o right n left o top 4 Production test : n yes o no
n rotatable 360 per 90 5 o Special test (specify) : ______________________
6 Witnessed : n yes o no
10 Cables Cross-sec Type Overall diameter Diameter over inner sheath of armor wire
Main 3C x 185 mm CU/XLPE/GSWA/PVC 65 mm mm mm
Heater 2C x 2.5 mm CU/XLPE/GSWA/PVC 13.6 mm mm mm
RTD sensors 7T x 2.5 mm CU/XLPE/GSWA/PVC 30 mm 1 mm mm
11 Cable Gland Required Make Type Entry Thread Size
Main n yes o no M75S x 2.5
Heater n yes o no M20 x 2.5
RTD sensors n yes o no M32 x 2.5

12 Mechanical Impact protection IK 10

Notes :
1 This data sheet shall be read in conjunction with the driven equipment spec. no.80-F201007-IS-025
2 Refer to Attachment for additional requirements on squirrel cage induction motor.
3 Tick or check whichever is applicable / required.
4 MP - Manufacturer Proposal.
5 AC 230 V, 1-Ph, 50 Hz.
6 Supplier to confirm the mounting arrangement suitable for the specified pump.
7 Maximum 80oC for equipment directly exposed to solar radiation.
8 To be confirmed by the vendor.
Specific Requirements :
Pump vendor to submit separate motor data sheet for each pump tag no. as indicated
in this requisition sheet.
Sheet 2 of 2

Data Sheet for AC Motor


(To be complete by Motor Manufacturer)

Rev. A B C D Initial issue


Client : Brooge Petroleum and Gas Investment Company (BPGIC) By Made
Plant : BPGIC Fujairah Terminal - Phase 1 Chkd Chkd.
Location : AL Suda, Fujairah, UAE Appd. Appd.
Project No: 142901 Date Date

DATA TO BE FURNISHED BY MANUFACTURER


A General D Motor Performance Data :
1 Manufacturer : 4/4 load 3/4 load 1/2 load 1/4 load no load
2 Pump Tag No. : 1 Efficiency (%)
3 Local Agent : 2 Stator current (A)
3 Power factor
3 P.O. No. : 4 Speed (rpm)
4 Model / Type : 5 Locked rotor torque : ___________________% of full load torque.
5 Country of origin : 6 Pull-up torque : ________________________% of full load torque.
7 Breakdown torque : ____________________% of full load torque.
B Construction 8 Starting current : ___________ A
1 Winding insulation : Temp. rise limit : 9 Critical speed : _____________ rpm
2 Stator winding connection : 10 Time te' (for EEx'e' motors) : __________________sec.(< 10 sec)
3 Stator frame material : 11 Motor inertia : _______________________ (kg sq.m..)
4 Bearings No. Make Type 12 Total weight : _______________________ kg
DE 13 At Un At 0.8Un
NDE a Locked rotor current
5 Bearing lifetime : b Locked rotor torque
6 Bearing with insulation : c Pull-up torque
7 Type & Make of lubrication : d Breakdown torque
8 Type of cooling fan impeller : e Running-up time
9 Type of end (fan) cover : f Allowable running-up time
g Slip (%)
C Basic Data h Maximum stalling time (Cold)
1 Frame size : i Maximum stalling time (Hot)
2 Rated voltage & tolerances : j Starting current
3 Rated frequency & tolerances : k
4 Motor rating : l
5 IP of motor and aux. enclosure: 14 Max. sound pressure (1m distance) : ___________dB(A)
6 IP of terminal box and bearing housings : 15 Restart with full opposite residual voltage : Yes / No
7 Suitable for installation in classified area : Yes / No 16 Allowable consecutive starts: Cold : ______ Hot : _______
- Zone : 17 Warm-up time constant :
- Gas group : 18 Cold-down time constant :
- Temperature classification : 19 Warm-up time constant (under locked rotor condition) :
8 Explosion protection type : 20 Vibration in mm/sec
- Motor frame :
- Terminal box : E Miscellaneous
9 Standard complied : 1 Anti-condensation space heater provided : Yes / No
10 ATEX 95 compliance : Yes / No - Operating voltage & wattage :
-Explosion protection certificate : Yes / No 2 Suitable for VFD operation : Yes / No
- Issued by : 3 Protective devices provided :
11 Method of cooling : 4 Nos. of pair of poles :
12 Method of mounting : 5 Suitable to operate on 60 Hz power supply : Yes / No

Notes:
1 This data sheet shall be read in conjunction with the driven equipment spec. no. 80-F201007-IS-025
2 Circle on selected items, where applicable.
3 Provide list of deviations from Purchaser's requirements, if any.
4 Equipment is able to sustain without any detrimental effect when subjecting to 2 and 3-phase short-circuit at the motor terminals.
5 Integrity of the equipment will not suffer when reconnected to the supply source with full opposite residual voltage after a brief power interruption.