Commissioning certificate 12/2014
Customer : EETC
Feeder : B05+R2
Serial.-No.: In = 1 A f= 50 Hz UH = 220 V
dc
1. Relay Settings:
A printout of the relay settings is attached.
3. Measurements Test:
Connection:
Injection was done through test switch.
Injection Values:
3 currents with the rated values and balanced angels are injected according
to the following table:
N.B.: Tripping should be prevented from stopping the injection.
Current Voltage
Magnitu Angle Magnitud Angle
de () e ()
R 1A 0 57.735V 0
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 2 of 8
4. (Directional) Over Current Protection Test:
Test Procedure:
OMICRON Quick CMC Test module is used to inject currents on each phase
individually.
Pick up value is recorded when the tester stops injection by the stop contact.
For measuring the trip time , a value equals at least 1.5 times pick up value
should be injected.
Pick Up Test:
Time Test:
At twice the current setting
Set Values Measured values
Directional Test:
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 3 of 8
To simulate a fault on phase- A, the voltage of this phase is reduced while the other two phases are
healthy. The current of that phase is greater than the pick up value (1.23 A).The angle of this current is
changed in steps to rotate around the reference voltage V ref (rotated). The results are shown
in the following figure:
Phase Fault Rotation. Angle Measured Forward Zone
R +45 +39 / 0 /-128
S +45 +39 / 0 /-128
T +45 +39 / 0 /-128
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 4 of 8
Reverse
V Forward
T
VR
Reverse
Vref
VS rotated
Forward Vref
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 5 of 8
5. (Directional) Earth Fault Protection Test:
Test Procedure:
OMICRON Quick CMC Test module is used to inject currents and voltages on
each phase individually.
Pick up value is recorded when the tester stops injection by the stop contact.
For measuring the trip time, a value equals at least 1.5 times pick up value
should be injected.
Pick Up Test:
Directional Non-Directional
N 0.32 0.315 0.315
N.B Drop out is 0.285 Amp (Reset Factor = 90.5%)
Measured
Set Values
values
Phase 3Vo (V) 3Vopick up (V)
Time Test:
At twice the current setting
Set Values Measured values
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 6 of 8
Directional Test:
To simulate a fault on phase- A, the voltage of this phase is reduced to a value cause a polarizing voltage
(3Vo) > 5 V. while the other two phases are healthy. The current of that phase is greater than the pick up
value (0.12 A).The angle of this current is changed in steps to rotate around the reference voltage V ref
. The results are shown in the following figure:
(rotated)
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 7 of 8
5. Function Test:
LEDs Operation Tested According to setting OK
O/P Function Tested :
BO Destination
D.O.C Alarm RTK Alarm
BO3
Signal
K350 in +R2 K640 Lock Out
BO1
RTK Alarm
D.E.F Alarm RTK Alarm
BO4
Signal
K630 Lock Out
B02 K340 in +R1
RTK Alarm
Watch RTK Alarm
K323
Dog
Tested by Witnessed by
Siemens S.A.E Client :EETC
Name: Ismail M. Mosaed Name: Ahmed Esmat
Date: 18 -09-2016 Date: 18-09-2016
Signature Signature
Page 8 of 8