ALSECURE & ALSECURE PLUS

FIRE SAFETY CABLES


Table of content

About Nexans 3

QICC ISO Certificates 4

ALSECURE - Technical Literature 8

ALSECURE - Type Test 17

ALSECURE BS, Cu/XL-HFFR H07Z-R 19

ALSECURE IEC LV, XLPE Insulation, HFFR 0.6/1KV 22

ALSECURE IEC LV, XLPE Insulation, SWA, HFFR 0.6/1 kV 29

ALSECURE IEC LV, XLPE Insulation, AWA, HFFR 0.6/1 kV 35

ALSECURE BS LV, XLPE Insulation, SWA, HFFR 0.6/1 kV 38

ALSECURE BS LV, XLPE Insulation, AWA, HFFR 0.6/1 kV 43

ALSECURE PLUS - Technical Literature 46

ALSECURE PLUS NX100 Approvals 51

ALSECURE PLUS NX300 Approvals 52

ALSECURE PLUS NX400 Approvals 55

ALSECURE PLUS NX100 BS, Cu/Mica/XL-HFFR 56

ALSECURE PLUS IEC LV, Mica, XLPE, SWA, HFFR 0.6/1 kV 59

ALSECURE PLUS NX300 BS LV, Mica, XLPE Insulation, HFFR 0.6/1 kV 65

ALSECURE PLUS NX400 LV, Mica, XLPE, SWA, HFFR 0.6/1 kV 70

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 2 / 75
About Nexans

Nexans brings energy to life through an extensive range of cables and cabling solutions that deliver increased
performance for our customers worldwide. Nexans teams are committed to a partnership approach that supports
customers in four main business areas: Power transmission and distribution (submarine and land), Energy resources
(Oil & Gas, Mining and Renewables), Transportation (Road, Rail, Air, Sea) and Building (Commercial, Residential and
Data Centers). Nexans strategy is founded on continuous innovation in products, solutions and services, employee
development, customer training and the introduction of safe, low-environmental-impact industrial processes.
In 2013, Nexans became the first cable player to create a Foundation to introduce sustained initiatives for access to
energy for disadvantaged communities worldwide.
We have an industrial presence in 40 countries and commercial activities worldwide, employing close to 26,000 people
and generating sales in 2015 of 6.2 billion euros.
Nexans is listed on Euronext Paris, compartment A.

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 3 / 75
QICC ISO Certificates

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 4 / 75
QICC ISO Certificates

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 5 / 75
QICC ISO Certificates

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 6 / 75
QICC ISO Certificates

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 7 / 75
ALSECURE - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 8 / 75
ALSECURE - Technical Literature

FIRE REACTION:

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 9 / 75
ALSECURE - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 10 / 75
ALSECURE - Technical Literature

LOW SMOKE FUME OR LOW SMOKE LOW HALOGEN (LSF / LSLH) COMPOUND

The low halogen content and low corrosivity of low smoke fume cables lies somewhat in

between that of fire retardant cables and LSZH cables.

LSF/LSLH cables also contain halogen but the content is much less than that of PVC normal cables.

LSF/LSLH cables are designed to reduce the spread of fire, toxic gases and smoke during fire. The LSF cables are
usually manufactured from flame retardant PVC blended with HCL additive and smoke absorbent.

These materials help improve the fire performance of the LSF cables.

The materialshall possess following properties:

1.Good abrasion resistance

2.Excellent mechanical and electrical properties

3.Processed at High Extrusion Speed

4.Long-term reliability

5.Excellent flame retardancy and low smoke with low halogen.

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 11 / 75
ALSECURE - Technical Literature

6.Limiting Oxygen Index to BS 7682

7.Halogen Acid Gas Generation to IEC 60754-1

8.Flame Retardant to IEC 60332-3 and BS 4066

HALOGEN FREE FIRE RETARDANT SHEATHING COMPOUND

This material is a Zero Halogen, Low Smoke, Flame Retardant Thermoplastic Compound,

polyolefin based for Sheathing/Jacketing applications. The material shall be high Oxygen

Index, Temperature Index and thermal stress resistance.

The materialshall be consists of special thermoplastic polymers, inorganic filler and other

additives.

It shows good processing and physical properties.

The materialshall possess following properties:

1.Good abrasion resistance

2.High Oxygen Index and Temperature Index

3.Excellent mechanical properties

4.Long-term reliability and Good UV Stability

5.Excellent flame retardancy and low smoke

6.Smoke Density Rating to ASTM D 2843

7.Limiting Oxygen Index to ASTM D 2863

8.Halogen Acid Gas Generation to IEC 60754-1

9.Test on Gases Evolved During Combustion to IEC 60754-2

10.Flame Retardant to IEC 60331,2 and BS 4066

11.Smoke Emission IEC 61034

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 12 / 75
ALSECURE - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 13 / 75
ALSECURE - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 14 / 75
ALSECURE - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 15 / 75
ALSECURE - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 16 / 75
ALSECURE - Type Test

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 17 / 75
ALSECURE - Type Test

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 18 / 75
Contact
ALSECURE BS, Cu/XL-HFFR H07Z-R Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

BS 7211

450/750V halogen free, flame retardant cables

DESCRIPTION
Application:
Used in energy networks in refineries,mines,hotels,schools,tunnels,high
constructions,hospitals,power plants, data processing centers,business centers where
there is a risk of fire.

1. Conductor

Stranded bare copper class 2 to BS EN 60228

2. Insulation

Cross Linked Halogen Free "XL-HFFR"

Installation

In conduit, insulation support, ducts...in coverd and dry place.

Packing

The packing will be in coils with 91.4 m.


STANDARDS
Marking:
International EN 50525-3-41
450/750 V Cu/XL-FFR no. of cores x cable size H07Z-R EN 50525-3.41
BASEC Made in Qatar National BS 7211
Permissible current and voltage drop are given

For conductor laid alone in insulating tube on a wall Temperature = 30C.


Permanent operation If conditions are different, apply correction factors from IEC
60364-5-52 standard or other equivalent national standard Voltage drop Calculated
with cosj = 0,8

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Conductor flexibility Stranded class 2
Conductor shape Circular stranded (RM)

Conductor flexibility Halogen free Rated Voltage Uo/U Mechanical Cable flexibility Flame retardant Operating temp. Smoke density
Stranded class 2 Yes (Um) resistance to Rigid IEC 60332-1-2 -20 .. 60 C IEC 61034
450 / 750 V impacts
Low

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 19 / 75
Contact
ALSECURE BS, Cu/XL-HFFR H07Z-R Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

Construction characteristics
Insulation XL-HFFR
Halogen free Yes
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 450 / 750 V
Mechanical characteristics
Mechanical resistance to impacts Low
Cable flexibility Rigid
Usage characteristics
Flame retardant IEC 60332-1-2
Operating temperature, range -20 .. 60 C
Short-circuit max. conductor temperature 250 C
Smoke density IEC 61034
Gases toxicity No toxicity to IEC 60754-1
Gases corrosivity Low IEC 60754-2

CU/XL-HFFR "H07Z-R" BS 7211


Nom. outer Approx. Max. DC Resist. Cond. 20 Voltage
Length
Nexans ref. Name diam. weight C Drop
[m]
[mm] [kg/km] [Ohm/km] [V/A.km]
21002PHZOU000AD0 1x1.5 3.0 20 100 12.1 22.6
21003PHZOU000AD0 1x2.5 3.7 30 100 7.41 13.8
21004PHZOU000AD0 1x4 4.2 40 100 4.61 8.6
21006PHZOU000AD0 1x6 4.8 60 100 3.08 5.8
21010PHZOU000AD0 1x10 6.0 110 100 1.83 3.5
21016PHZOU000AD0 1x16 6.5 170 100 1.15 2.2
21025PHZOU000AD0 1x25 8.5 260 1000 0.727 1.4
21035PHZOU000AD0 1x35 9.5 360 1000 0.524 1.1
21050PHZOU000AD0 1x50 11.0 480 1000 0.387 0.8
21070PHZOU000AD0 1x70 13.0 650 1000 0.268 0.58
21095PHZOU000AD0 1x95 15.0 950 1000 0.193 0.44
21120PHZOU000AD0 1x120 16.0 1200 1000 0.153 0.37
21150PHZOU000AD0 1x150 18.0 1400 1000 0.124 0.32
21185PHZOU000AD0 1x185 20.0 1800 1000 0.099 0.27
21240PHZOU000AD0 1x240 23.0 2970 1000 0.075 0.23

Conductor flexibility Halogen free Rated Voltage Uo/U Mechanical Cable flexibility Flame retardant Operating temp. Smoke density
Stranded class 2 Yes (Um) resistance to Rigid IEC 60332-1-2 -20 .. 60 C IEC 61034
450 / 750 V impacts
Low

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 20 / 75
Contact
ALSECURE BS, Cu/XL-HFFR H07Z-R Nexans Qatar
Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. outer Approx. Max. DC Resist. Cond. 20 Voltage


Length
Nexans ref. Name diam. weight C Drop
[m]
[mm] [kg/km] [Ohm/km] [V/A.km]
21300PHZOU000AD0 1x300 26.0 3600 1000 0.0601 0.2
21400PHZOU000AD0 1x400 29.0 4600 1000 0.047 0.18
21500PHZOU000AD0 1x500 33.0 5970 1000 0.037 0.15
21630PHZOU000AD0 1x630 36.0 7350 1000 0.028 0.14
21800PHZOU000AD0 1x800 39.0 7600 1000 0.022 0.13

Conductor flexibility Halogen free Rated Voltage Uo/U Mechanical Cable flexibility Flame retardant Operating temp. Smoke density
Stranded class 2 Yes (Um) resistance to Rigid IEC 60332-1-2 -20 .. 60 C IEC 61034
450 / 750 V impacts
Low

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 21 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC 60502-1

Unarmoured LV cable, HFFR sheathed for fixed installations. Rated voltage 0.6/1 KV

DESCRIPTION
Application

These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant)

Design
STANDARDS
1. Conductor International IEC 60332-1;
Stranded bare copper class 2 acc. to IEC 60228 IEC 60502-1
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding
Lapped bedding or extruded HFFR
4. Outer Sheath
Halogen Free Flame retardant "HFFR".

Options:

- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

- Ozone resistant.

- Oil resistant.

- Anti termite

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Marking

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 22 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

no. of cores x conductor sizes mm2 Cu / XLPE / HFFR 600/1000 V IEC 60502-1
MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Unarmoured
Outer sheath Halogen free flame retardant
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 19 (xD)
Bending factor when installed 10 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1

IEC LV, XLPE INSULATION, UNARMOURED HFFR 1 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
21010BXZOUH30BD0 1x10 8.0 160 1.83 85 77 3.6
21016BXZOUH30BD0 1x16 9.0 220 1.15 113 100 2.3
21025BXZOUH30BD0 1x25 11.0 330 0.727 135 129 1.5

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 23 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
21035BXZOUH30BD0 1x35 12.0 425 0.524 169 155 1.1
21050BXZOUH30BD0 1x50 13.0 480 0.387 216 183 0.83
21070BXZOUH30BD0 1x70 15.0 670 0.268 279 225 0.6
21095BXZOUH30BD0 1x95 16.0 920 0.193 342 270 0.46
21120BXZOUH30BD0 1x120 18.0 1140 0.153 400 306 0.38
21150BXZOUH30BD0 1x150 20.0 1400 0.124 464 343 0.33
21185BXZOUH30BD0 1x185 22.0 1740 0.0991 533 387 0.28
21240BXZOUH30BD0 1x240 25.0 2250 0.0754 634 448 0.24
21300BXZOUH30BD0 1x300 27.0 2780 0.0601 736 502 0.21
21400BXZOUH30BD0 1x400 31.0 3530 0.047 868 717 0.18
21500BXZOUH30BD0 1x500 35.0 4570 0.0366 896 539 0.16
21630BXZOUH30BD0 1x630 39.0 5810 0.0283 1035 678 0.15
21800BXZOUH30BD0 1x800 43.0 7375 0.0221 1246 726 0.14

IEC LV, XLPE INSULATION, UNARMOURED HFFR 2 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002BXZOUH30BD0 2x1.5 11.0 300 12.1 23 21 22.8
22003BXZOUH30BD0 2x2.5 12.0 240 7.41 32 30 14.0
22004BXZOUH30BD0 2x4 13.0 190 4.61 42 39 8.7
22006BXZOUH30BD0 2x6 14.0 160 3.08 54 49 5.9
22010BXZOUH30BD0 2x10 16.0 440 1.83 75 65 3.5
22016BXZOUH30BD0 2x16 18.0 570 1.15 100 84 2.2
22025BXZOUH30BD0 2x25 21.0 840 0.727 127 107 1.5
22035BXZOUH30BD0 2x35 23.0 1070 0.524 158 129 1.1
22050BXZOUH30BD0 2x50 26.0 1400 0.387 192 153 0.81
22070BXZOUH30BD0 2x70 30.0 1950 0.268 246 188 0.58
22095BXZOUH30BD0 2x95 33.0 2610 0.193 298 226 0.44
22120BXZOUH30BD0 2x120 37.0 3240 0.153 346 257 0.37
22150BXZOUH30BD0 2x150 41.0 3960 0.124 399 287 0.31
22185BXZOUH30BD0 2x185 46.0 4980 0.0991 456 324 0.27

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 24 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE INSULATION, UNARMOURED HFFR 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002BXZOUH30BD0 3x1.5 12.0 180 12.1 23 21 22.8
23003BXZOUH30BD0 3x2.5 13.0 230 7.41 32 30 14.0
23004BXZOUH30BD0 3x4 14.0 290 4.61 42 39 8.7
23006BXZOUH30BD0 3x6 15.0 370 3.08 54 49 5.9
23010BXZOUH30BD0 3x10 17.0 520 1.83 75 65 3.5
23016BXZOUH30BD0 3x16 19.0 720 1.15 100 84 2.2
23025BXZOUH30BD0 3x25 22.0 1060 0.727 127 107 1.5
23050BXZOUH30BD0 3x50 23.0 1435 0.387 192 153 0.81
23035BXZOUH30BD0 3x35 25.0 1380 0.524 158 129 1.1
23070BXZOUH30BD0 3x70 27.0 2020 0.268 246 188 0.58
23095BXZOUH30BD0 3x95 30.0 2745 0.193 298 226 0.44
23120BXZOUH30BD0 3x120 33.0 3430 0.153 346 257 0.37
23150BXZOUH30BD0 3x150 37.0 4240 0.124 399 287 0.31
23185BXZOUH30BD0 3x185 41.0 5250 0.0991 456 324 0.27
23240BXZOUH30BD0 3x240 45.0 6730 0.0754 538 375 0.23
23300BXZOUH30BD0 3x300 51.0 8450 0.0601 621 419 0.2
23400BXZOUH30BD0 3x400 58.0 10800 0.047 765 468 0.18

IEC LV, XLPE INSULATION, UNARMOURED HFFR 4 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002BXZOUH30BD0 4x1.5 13.0 210 12.1 23 21 22.8
24003BXZOUH30BD0 4x2.5 14.0 270 7.41 32 30 14.0
24004BXZOUH30BD0 4x4 15.0 350 4.61 42 39 8.7
24006BXZOUH30BD0 4x6 16.0 440 3.08 54 49 5.9
24010BXZOUH30BD0 4x10 18.0 635 1.83 75 65 3.5
24016BXZOUH30BD0 4x16 20.0 890 1.15 100 84 2.2
24025BXZOUH30BD0 4x25 24.0 1330 0.727 127 107 1.5
24050BXZOUH30BD0 4x50 25.0 1860 0.387 192 153 0.81
24035BXZOUH30BD0 4x35 27.0 1730 0.524 158 129 1.1

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 25 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24070BXZOUH30BD0 4x70 29.0 2630 0.268 246 188 0.58
24095BXZOUH30BD0 4x95 33.0 2610 0.193 298 226 0.44
24120BXZOUH30BD0 4x120 37.0 4480 0.153 346 257 0.37
24150BXZOUH30BD0 4x150 41.0 5530 0.124 399 287 0.31
24185BXZOUH30BD0 4x185 46.0 6900 0.0991 456 324 0.27
24240BXZOUH30BD0 4x240 51.0 8980 0.0754 538 375 0.23
24300BXZOUH30BD0 4x300 58.0 11270 0.0601 621 419 0.2
24400BXZOUH30BD0 4x400 65.0 14370 0.047 765 468 0.18

IEC LV, XLPE INSULATION, UNARMOURED HFFR 5 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002BXZOUH30BD0 5x1.5 13.0 250 12.1 23 21 22.8
25003BXZOUH30BD0 5x2.5 15.0 310 7.41 32 30 14.0
25004BXZOUH30BD0 5x4 16.0 410 4.61 42 39 8.7
25006BXZOUH30BD0 5x6 17.0 530 3.08 54 49 5.9
25010BXZOUH30BD0 5x10 20.0 760 1.83 75 65 3.5
25016BXZOUH30BD0 5x16 22.0 1090 1.15 100 84 2.2
25025BXZOUH30BD0 5x25 27.0 1630 0.727 127 107 1.5
25035BXZOUH30BD0 5x35 30.0 2610 0.524 158 129 1.1
25050BXZOUH30BD0 5x50 33.0 2480 0.387 192 153 0.81
25070BXZOUH30BD0 5x70 39.0 3480 0.268 246 188 0.58

IEC LV, XLPE INSULATION, UNARMOURED HFFR 7 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2C002BXZOUH30BD0 7x1.5 15.0 340 12.1 23 21 22.8
2C003BXZOUH30BD0 7x2.5 17.0 450 7.41 32 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 26 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE INSULATION, UNARMOURED HFFR 9 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2K002BXZOUH30BD0 9x1.5 16.0 410 12.1 23 21 22.8
2K003BXZOUH30BD0 9x2.5 18.0 545 7.41 32 30 14.0

IEC LV, XLPE INSULATION, UNARMOURED HFFR 12 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2E002BXZOUH30BD0 12x1.5 18.0 480 12.1 23 21 22.8
2E003BXZOUH30BD0 12x2.5 19.0 640 7.41 32 30 14.0

IEC LV, XLPE INSULATION, UNARMOURED HFFR 19 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2F002BXZOUH30BD0 19x1.5 20.0 655 12.1 23 21 22.8
2F003BXZOUH30BD0 19x2.5 22.0 880 7.41 32 30 14.0

IEC LV, XLPE INSULATION, UNARMOURED HFFR 24 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2I002BXZOUH30BD0 24x1.5 23.0 860 12.1 23 21 22.8
2I003BXZOUH30BD0 24x2.5 26.0 1150 7.41 32 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 27 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
HFFR 0.6/1KV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE INSULATION, UNARMOURED HFFR 37 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2M002BXZOUH30BD0 37x1.5 26.0 1130 12.1 23 21 22.8
2M003BXZOUH30BD0 37x2.5 29.0 1550 7.41 32 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 19 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 28 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC 60502-1

Galvanized steel wire armoured LV cable, HFFR sheathed for fixed installations. Rated
voltage 0.6/1 KV

DESCRIPTION
Application

These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant)

Design STANDARDS
International IEC 60332-1;
1. Conductor IEC 60502-1
Stranded bare copper class 2 acc. to IEC 60228
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding
Lapped bedding or extruded HFFR
4. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Halogen Free Flame retardant "HFFR".

Options :

- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

- Ozone resistant.

- Oil resistant.

- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 8 (xD) 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 29 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / HFFR 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Galvanized steel wires
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 8 (xD)
Bending factor when installed 15 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 2 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002BXZHSB30BD0 2x1.5 13.0 300 12.1 25 23 22.8
22003BXZHSB30BD0 2x2.5 14.0 380 7.41 33 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 8 (xD) 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 30 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22004BXZHSB30BD0 2x4 15.0 450 4.61 44 39 8.7
22006BXZHSB30BD0 2x6 16.0 540 3.08 56 49 5.9
22010BXZHSB30BD0 2x10 18.0 700 1.83 78 65 3.5
22016BXZHSB30BD0 2x16 21.0 1045 1.15 99 84 2.2
22025BXZHSB30BD0 2x25 21.0 1080 0.727 131 107 1.65
22035BXZHSB30BD0 2x35 24.0 1510 0.524 162 129 1.15
22050BXZHSB30BD0 2x50 26.0 1900 0.387 197 153 0.89
22070BXZHSB30BD0 2x70 29.0 2130 0.268 251 188 0.6
22095BXZHSB30BD0 2x95 33.0 2890 0.193 304 226 0.45
22120BXZHSB30BD0 2x120 36.0 3460 0.153 353 257 0.37
22150BXZHSB30BD0 2x150 39.0 4110 0.124 406 287 0.3
22185BXZHSB30BD0 2x185 44.0 5330 0.0991 463 324 0.26

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002BXZHSB30BD0 3x1.5 13.0 330 12.1 25 23 22.8
23003BXZHSB30BD0 3x2.5 15.0 410 7.41 33 30 14.0
23004BXZHSB30BD0 3x4 16.0 510 4.61 44 39 8.7
23006BXZHSB30BD0 3x6 17.0 610 3.08 56 49 5.9
23010BXZHSB30BD0 3x10 20.0 930 1.83 78 65 3.5
23016BXZHSB30BD0 3x16 22.0 1240 1.15 99 84 2.2
23025BXZHSB30BD0 3x25 24.0 1640 0.727 131 107 1.65
23035BXZHSB30BD0 3x35 27.0 2030 0.524 162 129 1.15
23050BXZHSB30BD0 3x50 30.0 2520 0.387 197 153 0.89
23070BXZHSB30BD0 3x70 33.0 2860 0.268 251 188 0.6
23095BXZHSB30BD0 3x95 38.0 3940 0.193 304 226 0.45
23120BXZHSB30BD0 3x120 41.0 4760 0.153 353 257 0.37
23150BXZHSB30BD0 3x150 46.0 6070 0.124 406 287 0.3
23185BXZHSB30BD0 3x185 50.0 7310 0.0991 463 324 0.26
23240BXZHSB30BD0 3x240 55.0 9135 0.0754 546 375 0.21
23300BXZHSB30BD0 3x300 60.0 11015 0.0601 628 419 0.18

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 8 (xD) 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 31 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23400BXZHSB30BD0 3x400 67.0 13760 0.047 731 439 0.17

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 4 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002BXZHSB30BD0 4x1.5 14.0 370 12.1 25 23 22.8
24003BXZHSB30BD0 4x2.5 16.0 470 7.41 33 30 14.0
24004BXZHSB30BD0 4x4 17.0 580 4.61 44 39 8.7
24006BXZHSB30BD0 4x6 19.0 820 3.08 56 49 5.9
24010BXZHSB30BD0 4x10 21.0 1100 1.83 78 65 3.5
24016BXZHSB30BD0 4x16 24.0 1430 1.15 99 84 2.2
24025BXZHSB30BD0 4x25 27.0 1970 0.727 131 107 1.65
24035BXZHSB30BD0 4x35 29.0 2470 0.524 162 129 1.15
24050BXZHSB30BD0 4x50 33.0 3150 0.387 197 153 0.89
24070BXZHSB30BD0 4x70 38.0 3890 0.268 251 188 0.6
24095BXZHSB30BD0 4x95 42.0 4930 0.193 304 226 0.45
24120BXZHSB30BD0 4x120 47.0 6450 0.153 353 257 0.37
24150BXZHSB30BD0 4x150 51.0 7645 0.124 406 287 0.3
24185BXZHSB30BD0 4x185 56.0 9250 0.0991 463 324 0.26
24240BXZHSB30BD0 4x240 62.0 11680 0.0754 546 375 0.21
24300BXZHSB30BD0 4x300 67.0 14140 0.0601 628 419 0.18
24400BXZHSB30BD0 4x400 77.0 18510 0.047 731 439 0.17

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 5 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002BXZHSB30BD0 5x1.5 15.0 430 12.1 25 23 22.8
25003BXZHSB30BD0 5x2.5 17.0 533 7.41 33 30 14.0
25004BXZHSB30BD0 5x4 18.0 680 4.61 44 39 8.7
25006BXZHSB30BD0 5x6 20.0 950 3.08 56 49 5.9

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 8 (xD) 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 32 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25010BXZHSB30BD0 5x10 23.0 1270 1.83 78 65 3.5
25016BXZHSB30BD0 5x16 27.0 1900 1.15 99 84 2.2
25025BXZHSB30BD0 5x25 31.0 2550 0.727 131 107 1.65
25035BXZHSB30BD0 5x35 34.0 3170 0.524 162 129 1.15
25050BXZHSB30BD0 5x50 39.0 4390 0.387 197 153 0.89
25070BXZHSB30BD0 5x70 44.0 4980 0.268 251 188 0.6

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 7 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2C002BXZHSB30BD0 7x1.5 16.0 440 12.1 25 23 22.8
2C003BXZHSB30BD0 7x2.5 19.0 650 7.41 33 30 14.0

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 9 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2K002BXZHSB30BD0 9x1.5 18.0 630 12.1 25 23 22.8
2K003BXZHSB30BD0 9x2.5 20.0 770 7.41 33 30 14.0

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 12 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2E002BXZHSB30BD0 12x1.5 19.0 710 12.1 25 23 22.8
2E003BXZHSB30BD0 12x2.5 21.0 890 7.41 33 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 8 (xD) 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 33 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 19 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2F002BXZHSB30BD0 19x1.5 22.0 930 12.1 25 23 22.8
2F003BXZHSB30BD0 19x2.5 25.0 1300 7.41 33 30 14.0

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 24 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2I002BXZHSB30BD0 24x1.5 25.0 1250 12.1 25 23 22.8
2I003BXZHSB30BD0 24x2.5 28.0 1590 7.41 33 30 14.0

IEC LV, XLPE INSULATION, SWA, HFFR SHEATHING 37 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2M002BXZHSB30BD0 37x1.5 28.0 1610 12.1 25 23 22.8
2M003BXZHSB30BD0 37x2.5 32.0 2555 7.41 33 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 8 (xD) 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 34 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
AWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC 60502-1

Aluminum wire armoured LV cable, HFFR sheathed for fixed installations. Rated
voltage 0.6/1 KV

DESCRIPTION
Application

These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant)

Design STANDARDS
International IEC 60332-1;
1. Conductor IEC 60502-1
Stranded bare copper class 2 acc. to IEC 60228
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding
Lapped bedding or extruded HFFR
4. Armour
Aluminum Steel Wire Armour "AWA"
5. Outer Sheath
Halogen Free Flame retardant "HFFR".

Options :

- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

- Ozone resistant.

- Oil resistant.

- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 15 (xD) 8 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 35 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
AWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / AWA / HFFR 600/1000 V IEC
60502-1 MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Aluminium Wire
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 15 (xD) 8 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 36 / 75
ALSECURE IEC LV, XLPE Insulation, Contact
Nexans Qatar
AWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, XLPE INSULATION, AWA, HFFR SHEATHING


Nom. Max. DC Current
Approx. Perm. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open air single phase
diam. 20C buried
[kg/km] [A] [V/A.km]
[mm] [Ohm/km] [A]
21070BXZVAB09BD0 1x70 21.0 940 0.268 278 188 0.61
21095BXZVAB09BD0 1x95 23.0 1210 0.193 342 226 0.47
21120BXZVAB09BD0 1x120 25.0 1460 0.153 400 257 0.39
21150BXZVAB09BD0 1x150 26.0 1750 0.124 464 287 0.34
21185BXZVAB09BD0 1x185 28.0 2100 0.0991 533 324 0.29
21240BXZVAB09BD0 1x240 31.0 2660 0.0754 634 375 0.25
21300BXZVAB09BD0 1x300 33.0 3230 0.0601 736 419 0.22
21400BXZVAB09BD0 1x400 37.0 4110 0.047 868 717 0.19
21500BXZVAB09BD0 1x500 42.0 5225 0.0366 998 791 0.17
21630BXZVAB09BD0 1x630 46.0 6510 0.0283 1151 861 0.16
21800BXZVAB09BD0 1x800 50.0 8340 0.0221 1246 904 0.15

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 15 (xD) 8 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 37 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS 6724

Galvanized steel wire armoured LV cable, HFFR sheathed for fixed installations. Rated
voltage 0.6/1 KV

DESCRIPTION
Application

These power cables are used for electricity supply in low voltage installation
systems.

They are well adapted to underground use in industrial applications where


chemical and mechanical protections are needed (refinery areas, chemical
plant)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding STANDARDS
Halogen Free Flame Retardant "HFFR"
International IEC 60332-3 Cat.C
4. Armour
Galvanized Steel Wire Armour "SWA" National BS 6724
5. Outer Sheath
Halogen Free Flame Retardant "HFFR", to BS 4066 or equivalent.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Marking

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 20 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 38 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

no. of cores x conductor sizes mm2 Cu / XLPE / SWA / HFFR 600/1000 V Standard
MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Galvanized steel wires
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 20 (xD)
Bending factor when installed 10 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1

BS LV, XLPE INSULATION, SWA, HFFR 0.6/1 KV 2 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002SXZHSH30BD0 2x1.5 11.0 240 12.1 25 23 22.8
22003SXZHSH30BD0 2x2.5 12.0 280 7.41 33 30 14.0
22004SXZHSH30BD0 2x4 13.0 330 4.61 44 39 8.7

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 20 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 39 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22006SXZHSH30BD0 2x6 14.0 390 3.08 56 49 5.9
22010SXZHSH30BD0 2x10 16.0 600 1.83 78 65 3.5
22016SXZHSH30BD0 2x16 18.0 750 1.15 99 84 2.2
22025SXZHSH30BD0 2x25 21.0 1120 0.727 131 107 1.65
22035SXZHSH30BD0 2x35 23.0 1340 0.524 162 129 1.15
22050SXZHSH30BD0 2x50 26.0 1680 0.387 197 153 0.89
22070SXZHSH30BD0 2x70 30.0 2200 0.268 251 188 0.6
22095SXZHSH30BD0 2x95 34.0 3030 0.193 304 226 0.45
22120SXZHSH30BD0 2x120 37.0 3610 0.153 353 257 0.37
22150SXZHSH30BD0 2x150 40.0 4280 0.124 406 287 0.3
22185SXZHSH30BD0 2x185 46.0 5540 0.0991 463 324 0.26

BS LV, XLPE INSULATION, SWA, HFFR 0.6/1 KV 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002SXZHSH30BD0 3x1.5 12.0 280 12.1 25 23 22.8
23003SXZHSH30BD0 3x2.5 13.0 330 7.41 33 30 14.0
23004SXZHSH30BD0 3x4 14.0 400 4.61 44 39 8.7
23006SXZHSH30BD0 3x6 15.0 480 3.08 56 49 5.9
23010SXZHSH30BD0 3x10 17.0 740 1.83 78 65 3.5
23016SXZHSH30BD0 3x16 19.0 950 1.15 99 84 2.2
23025SXZHSH30BD0 3x25 23.0 1410 0.727 131 107 1.65
23035SXZHSH30BD0 3x35 25.0 1720 0.524 162 129 1.15
23050SXZHSH30BD0 3x50 25.0 2100 0.387 197 153 0.89
23070SXZHSH30BD0 3x70 30.0 2980 0.268 251 188 0.6
23095SXZHSH30BD0 3x95 33.0 3810 0.193 304 226 0.45
23120SXZHSH30BD0 3x120 36.0 4600 0.153 353 257 0.37
23150SXZHSH30BD0 3x150 41.0 5860 0.124 406 287 0.3
23185SXZHSH30BD0 3x185 44.0 7010 0.0991 463 324 0.26
23240SXZHSH30BD0 3x240 49.0 8730 0.0754 546 375 0.21
23300SXZHSH30BD0 3x300 53.0 10640 0.0601 628 419 0.18
23400SXZHSH30BD0 3x400 59.0 13190 0.047 731 439 0.17

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 20 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 40 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE INSULATION, SWA, HFFR 0.6/1 KV 4 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002SXZHSH30BD0 4x1.5 11.0 160 12.1 25 23 22.8
24003SXZHSH30BD0 4x2.5 13.0 350 7.41 33 30 14.0
24004SXZHSH30BD0 4x4 14.0 430 4.61 44 39 8.7
24006SXZHSH30BD0 4x6 16.0 620 3.08 56 49 5.9
24010SXZHSH30BD0 4x10 18.0 880 1.83 78 65 3.5
24016SXZHSH30BD0 4x16 21.0 1250 1.15 99 84 2.2
24025SXZHSH30BD0 4x25 25.0 1730 0.727 131 107 1.65
24035SXZHSH30BD0 4x35 27.0 2120 0.524 162 129 1.15
24050SXZHSH30BD0 4x50 27.0 2570 0.387 197 153 0.89
24070SXZHSH30BD0 4x70 32.0 3680 0.268 251 188 0.6
24095SXZHSH30BD0 4x95 35.0 4700 0.193 304 226 0.45
24120SXZHSH30BD0 4x120 40.0 6070 0.153 353 257 0.37
24150SXZHSH30BD0 4x150 44.0 7250 0.124 406 287 0.3
24185SXZHSH30BD0 4x185 48.0 8810 0.0991 463 324 0.26
24240SXZHSH30BD0 4x240 54.0 11140 0.0754 546 375 0.21
24300SXZHSH30BD0 4x300 60.0 13520 0.0601 628 419 0.18
24400SXZHSH30BD0 4x400 67.0 17690 0.047 731 439 0.17

BS LV, XLPE INSULATION, SWA, HFFR 0.6/1 KV 5 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002SXZHSH30BD0 5x1.5 13.0 380 12.1 25 23 22.8
25003SXZHSH30BD0 5x2.5 14.0 450 7.41 33 30 14.0
25004SXZHSH30BD0 5x4 16.0 640 4.61 44 39 8.7
25006SXZHSH30BD0 5x6 18.0 780 3.08 56 49 5.9
25010SXZHSH30BD0 5x10 20.0 1040 1.83 78 65 3.5
25016SXZHSH30BD0 5x16 23.0 1490 1.15 99 84 2.2
25025SXZHSH30BD0 5x25 27.0 2070 0.727 131 107 1.65
25035SXZHSH30BD0 5x35 29.0 2540 0.524 162 129 1.15
25050SXZHSH30BD0 5x50 34.0 3480 0.387 197 153 0.89

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 20 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 41 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25070SXZHSH30BD0 5x70 39.0 4670 0.268 251 188 0.6

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 20 (xD) 10 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 42 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
AWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS 6724

Aluminum wire armoured LV cable, HFFR sheathed for fixed installations. Rated
voltage 0.6/1 KV

DESCRIPTION
Application

These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding
Lapped bedding or extruded HFFR
4. Armour
Aluminum Steel Wire Armour "AWA"
5. Outer Sheath STANDARDS
Halogen Free Flame retardant "HFFR".
International IEC 60332-1
Options :
National BS 6724
- Flame retardant : "CAT A, CAT B, CAT C" to BS 4066 or equivalent.

- Ozone resistant.

- Oil resistant.

- Anti termite.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor installed
Yes Stranded class 2 (Um) service Yes laying 8 (xD)
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 43 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
AWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / XLPE / AWA / HFFR 600/1000 V BS 6724
MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Conductor shape Circular
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Aluminium Wire
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Dimensional characteristics
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor installed
Yes Stranded class 2 (Um) service Yes laying 8 (xD)
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 44 / 75
ALSECURE BS LV, XLPE Insulation, Contact
Nexans Qatar
AWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, XLPE INSULATION, AWA, HFFR 0.6/1 KV


Perm.
Nom. Max. DC Current Voltage
Cross Approx. current
outer Resist. Cond. rating, drop, single
Nexans ref. Name section weight rating open
diam. 20C buried phase
[mm] [kg/km] air
[mm] [Ohm/km] [A] [V/A.km]
[A]
21050SXZHAH30BD0 1x50 50 19.0 710 0.387 216 153 0.84
21070SXZHAH30BD0 1x70 70 21.0 950 0.268 278 188 0.61
21095SXZHAH30BD0 1x95 95 23.0 1220 0.193 342 226 0.47
21120SXZHAH30BD0 1x120 120 25.0 1470 0.153 400 257 0.39
21150SXZHAH30BD0 1x150 150 26.0 1770 0.124 464 287 0.34
21185SXZHAH30BD0 1x185 185 28.0 2130 0.0991 533 324 0.29
21240SXZHAH30BD0 1x240 240 31.0 2680 0.0754 634 375 0.25
21300SXZHAH30BD0 1x300 300 33.0 3260 0.0601 736 419 0.22
21400SXZHAH30BD0 1x400 400 37.0 4150 0.047 868 717 0.19
21500SXZHAH30BD0 1x500 500 29.0 5270 0.0366 998 791 0.17
21630SXZHAH30BD0 1x630 630 46.0 6580 0.0283 1151 861 0.16
21800SXZHAH30BD0 1x800 800 50.0 8420 0.0221 1246 904 0.15

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor temp.in Flame retardant Bending factor when Bending factor installed
Yes Stranded class 2 (Um) service Yes laying 8 (xD)
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 45 / 75
ALSECURE PLUS - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 46 / 75
ALSECURE PLUS - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 47 / 75
ALSECURE PLUS - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 48 / 75
ALSECURE PLUS - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 49 / 75
ALSECURE PLUS - Technical Literature

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 50 / 75
ALSECURE PLUS NX100 Approvals

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 51 / 75
ALSECURE PLUS NX300 Approvals

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 52 / 75
ALSECURE PLUS NX300 Approvals

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 53 / 75
ALSECURE PLUS NX300 Approvals

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 54 / 75
ALSECURE PLUS NX400 Approvals

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/20/17 www.nexans.qa Page 55 / 75
ALSECURE PLUS NX100 BS, Cu/Mica/ Contact
Nexans Qatar
XL-HFFR Phone: + 974 4467 3009
sales.qatar@nexans.com

BS 7211

600/1000V Fire resistant, halogen free, flame retardant earthing wires

DESCRIPTION
Application:
Used in energy networks in refineries,mines,hotels,schools,tunnels,high
constructions,hospitals,power plants, data processing centers,business centers where
there is a risk of fire.

1. Conductor

Stranded bare copper class 2 to BS EN 60228

2. Fire barrier

Mica Glass Tape

3. Insulation

Cross Linked Halogen Free "XL-HFFR"

Installation

In conduit, insulated support, ducts...in coverd and dry place.


STANDARDS
Packing
International EN 50525-3-41
The packing will be in coils with 91.4 m.
National BS 7211
Marking:
450/750 V Cu/Mica/XL-FFR no. of cores x cable size H07Z-R EN 50525-3.41
LPCB Made in Qatar

Permissible current and voltage drop are given

For conductor laid alone in insulating tube on a wall Temperature = 30C.


Permanent operation If conditions are different, apply correction factors from IEC
60364-5-52 standard or other equivalent national standard Voltage drop Calculated
with cosj = 0,8

Conductor flexibility Halogen free Mechanical Cable flexibility Flame retardant Operating temp. Smoke density Gases toxicity
Stranded class 2 Yes resistance to Rigid IEC 60332-1-2 -20 .. 60 C IEC 61034 No toxicity to IEC
impacts 60754-1
Low

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 56 / 75
ALSECURE PLUS NX100 BS, Cu/Mica/ Contact
Nexans Qatar
XL-HFFR Phone: + 974 4467 3009
sales.qatar@nexans.com

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Conductor flexibility Stranded class 2
Conductor shape Circular stranded (RM)
Insulation XL-HFFR
Halogen free Yes
Dimensional characteristics
Number of cores 1
Mechanical characteristics
Mechanical resistance to impacts Low
Cable flexibility Rigid
Usage characteristics
Flame retardant IEC 60332-1-2
Operating temperature, range -20 .. 60 C
Short-circuit max. conductor temperature 250 C
Smoke density IEC 61034
Gases toxicity No toxicity to IEC 60754-1
Gases corrosivity Low IEC 60754-2

CU/MICA/XL-HFFR "H07Z-R" BS 7211


Nom. outer Approx. Max. DC Resist. Cond. 20 Voltage
Length
Nexans ref. Name diam. weight C Drop
[m]
[mm] [kg/km] [Ohm/km] [V/A.km]
21002PHZOU000BD0 1x1.5 3.0 20 100 12.1 22.6
21003PHZOU000BD0 1x2.5 3.7 30 100 7.41 13.8
21004PHZOU000BD0 1x4 4.2 40 100 4.61 8.6
21006PHZOU000BD0 1x6 4.8 60 100 3.08 5.8
21010PHZOU000BD0 1x10 6.0 110 100 1.83 3.5
21016PHZOU000BD0 1x16 6.5 170 100 1.15 2.2
21025PHZOU000BD0 1x25 8.5 260 1000 0.727 1.4
21035PHZOU000BD0 1x35 9.5 360 1000 0.524 1.1
21050PHZOU000BD0 1x50 11.0 480 1000 0.387 0.8
21070PHZOU000BD0 1x70 13.0 650 1000 0.268 0.58
21095PHZOU000BD0 1x95 15.0 950 1000 0.193 0.44
21120PHZOU000BD0 1x120 16.0 1200 1000 0.153 0.37

Conductor flexibility Halogen free Mechanical Cable flexibility Flame retardant Operating temp. Smoke density Gases toxicity
Stranded class 2 Yes resistance to Rigid IEC 60332-1-2 -20 .. 60 C IEC 61034 No toxicity to IEC
impacts 60754-1
Low

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 57 / 75
ALSECURE PLUS NX100 BS, Cu/Mica/ Contact
Nexans Qatar
XL-HFFR Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. outer Approx. Max. DC Resist. Cond. 20 Voltage


Length
Nexans ref. Name diam. weight C Drop
[m]
[mm] [kg/km] [Ohm/km] [V/A.km]
21150PHZOU000BD0 1x150 18.0 1400 1000 0.124 0.32
21185PHZOU000BD0 1x185 20.0 1800 1000 0.099 0.27
21240PHZOU000BD0 1x240 23.0 2970 1000 0.075 0.23
21300PHZOU000BD0 1x300 26.0 3600 1000 0.06 0.2
21400PHZOU000BD0 1x400 29.0 4600 1000 0.047 0.18
21500PHZOU000BD0 1x500 33.0 5970 1000 0.037 0.15
21630PHZOU000BD0 1x630 36.0 7350 1000 0.028 0.14
21800PHZOU000BD0 1x800 39.0 7600 1000 0.022 0.13

Conductor flexibility Halogen free Mechanical Cable flexibility Flame retardant Operating temp. Smoke density Gases toxicity
Stranded class 2 Yes resistance to Rigid IEC 60332-1-2 -20 .. 60 C IEC 61034 No toxicity to IEC
impacts 60754-1
Low

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 58 / 75
ALSECURE PLUS IEC LV, Mica, XLPE, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC 60502-1 & IEC 60331-21

Galvanized steel wire armoured LV cable, HFFR sheathed for fixed installations. Rated
voltage 0.6/1 KV

DESCRIPTION
Application

Refineries, Mines, Hotels, Schools, Tunnels, High construction, Hospitals, Power


plants, Data processing centers, Business centers where there is concentration of
sensitive to fire

Design
STANDARDS
1. Conductor International IEC 60331-21 ;
Stranded bare copper class 2 acc. to IEC 60228 IEC 60332-3-24 Cat.C;
2. Fire Barrier IEC 60502-1
Mica Glass tape
3. Insulation
Cross Linked Polyethylene "XLPE"
4. Inner Sheath or Bedding
Lapped bedding or extruded HFFR
5. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Halogen Free Flame retardant "HFFR".

Options :

- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

- Ozone resistant.

- Oil resistant.

- Anti termite.

Fire test :
As per IEC 60331-21 which is 750 Deg for 90 mins.

Installation Conditions:

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 59 / 75
ALSECURE PLUS IEC LV, Mica, XLPE, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

1. Air Temperature : 30 Deg.


2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / Mica / XLPE / SWA / HFFR 600/1000 V IEC
60502-1 IEC 60331-21 MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Galvanized steel wires
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 10 (xD)
Bending factor when installed 20 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1
Fire resistant IEC 60331-21

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 60 / 75
ALSECURE PLUS IEC LV, Mica, XLPE, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 2 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002BXZHSB34BD0 2x1.5 14.0 330 12.1 25 23 22.8
22003BXZHSB34BD0 2x2.5 15.0 420 7.41 33 30 14.0
22004BXZHSB34BD0 2x4 17.0 500 4.61 44 39 8.7
22006BXZHSB34BD0 2x6 18.0 590 3.08 56 49 5.9
22010BXZHSB34BD0 2x10 20.0 780 1.83 78 65 3.5
22016BXZHSB34BD0 2x16 23.0 1150 1.15 99 84 2.2
22025BXZHSB34BD0 2x25 23.0 1190 0.727 131 107 1.65
22035BXZHSB34BD0 2x35 26.0 1660 0.524 162 129 1.15
22050BXZHSB34BD0 2x50 29.0 2090 0.387 197 153 0.89
22070BXZHSB34BD0 2x70 32.0 2350 0.268 251 188 0.6
22095BXZHSB34BD0 2x95 36.0 3180 0.193 304 226 0.45
22120BXZHSB34BD0 2x120 40.0 3810 0.153 353 257 0.37
22150BXZHSB34BD0 2x150 43.0 4520 0.124 406 287 0.3
22185BXZHSB34BD0 2x185 48.0 5870 0.0991 463 324 0.26

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002BXZHSB34BD0 3x1.5 14.0 360 12.1 25 23 22.8
23003BXZHSB34BD0 3x2.5 17.0 450 7.41 33 30 14.0
23004BXZHSB34BD0 3x4 18.0 560 4.61 44 39 8.7
23006BXZHSB34BD0 3x6 19.0 670 3.08 56 49 5.9
23010BXZHSB34BD0 3x10 22.0 1030 1.83 78 65 3.5
23016BXZHSB34BD0 3x16 24.0 1365 1.15 99 84 2.2
23025BXZHSB34BD0 3x25 26.0 1810 0.727 131 107 1.65
23035BXZHSB34BD0 3x35 30.0 2230 0.524 162 129 1.15
23050BXZHSB34BD0 3x50 33.0 2780 0.387 197 153 0.89
23070BXZHSB34BD0 3x70 36.0 3150 0.268 251 188 0.6
23095BXZHSB34BD0 3x95 42.0 4335 0.193 304 226 0.45
23120BXZHSB34BD0 3x120 45.0 5230 0.153 353 257 0.37

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 61 / 75
ALSECURE PLUS IEC LV, Mica, XLPE, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23150BXZHSB34BD0 3x150 51.0 6685 0.124 406 287 0.3
23185BXZHSB34BD0 3x185 55.0 8040 0.0991 463 324 0.26
23240BXZHSB34BD0 3x240 61.0 10040 0.0754 546 375 0.21
23300BXZHSB34BD0 3x300 66.0 12110 0.0601 628 419 0.18
23400BXZHSB34BD0 3x400 74.0 15140 0.047 731 439 0.17

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 4 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002BXZHSB34BD0 4x1.5 15.0 410 12.1 25 23 22.8
24003BXZHSB34BD0 4x2.5 18.0 520 7.41 33 30 14.0
24004BXZHSB34BD0 4x4 19.0 640 4.61 44 39 8.7
24006BXZHSB34BD0 4x6 21.0 900 3.08 56 49 5.9
24010BXZHSB34BD0 4x10 23.0 1210 1.83 78 65 3.5
24016BXZHSB34BD0 4x16 26.0 1570 1.15 99 84 2.2
24025BXZHSB34BD0 4x25 30.0 2170 0.727 131 107 1.65
24035BXZHSB34BD0 4x35 32.0 2720 0.524 162 129 1.15
24050BXZHSB34BD0 4x50 36.0 3460 0.387 197 153 0.89
24070BXZHSB34BD0 4x70 42.0 4280 0.268 251 188 0.6
24095BXZHSB34BD0 4x95 46.0 5430 0.193 304 226 0.45
24120BXZHSB34BD0 4x120 52.0 7100 0.153 353 257 0.37
24150BXZHSB34BD0 4x150 56.0 8410 0.124 406 287 0.3
24185BXZHSB34BD0 4x185 62.0 10185 0.0991 463 324 0.26
24240BXZHSB34BD0 4x240 68.0 12840 0.0754 546 375 0.21
24300BXZHSB34BD0 4x300 74.0 15560 0.0601 628 419 0.18
24400BXZHSB34BD0 4x400 85.0 20360 0.047 731 439 0.17

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 62 / 75
ALSECURE PLUS IEC LV, Mica, XLPE, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 5 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002BXZHSB34BD0 5x1.5 17.0 470 12.1 25 23 22.8
25003BXZHSB34BD0 5x2.5 19.0 580 7.41 33 30 14.0
25004BXZHSB34BD0 5x4 20.0 750 4.61 44 39 8.7
25006BXZHSB34BD0 5x6 22.0 1040 3.08 56 49 5.9
25010BXZHSB34BD0 5x10 25.0 1400 1.83 78 65 3.5
25016BXZHSB34BD0 5x16 30.0 2090 1.15 99 84 2.2
25025BXZHSB34BD0 5x25 34.0 2800 0.727 131 107 1.65
25035BXZHSB34BD0 5x35 37.0 3495 0.524 162 129 1.15
25050BXZHSB34BD0 5x50 43.0 4830 0.387 197 153 0.89
25070BXZHSB34BD0 5x70 48.0 5485 0.268 251 188 0.6

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 7 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2C002BXZHSB34BD0 7x1.5 18.0 490 12.1 25 23 22.8
2C003BXZHSB34BD0 7x2.5 21.0 725 7.41 33 30 14.0

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 9 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2K002BXZHSB34BD0 9x1.5 20.0 690 12.1 25 23 22.8
2K003BXZHSB34BD0 9x2.5 22.0 840 7.41 33 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 63 / 75
ALSECURE PLUS IEC LV, Mica, XLPE, Contact
Nexans Qatar
SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 12 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2E002BXZHSB34BD0 12x1.5 21.0 780 12.1 25 23 22.8
2E003BXZHSB34BD0 12x2.5 23.0 980 7.41 33 30 14.0

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 19 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2F002BXZHSB34BD0 19x1.5 24.0 1020 12.1 25 23 22.8
2F003BXZHSB34BD0 19x2.5 28.0 1430 7.41 33 30 14.0

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 24 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2I002BXZHSB34BD0 24x1.5 28.0 1370 12.1 25 23 22.8
2I003BXZHSB34BD0 24x2.5 31.0 1750 7.41 33 30 14.0

IEC LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 37 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2M002BXZHSB34BD0 37x1.5 31.0 1780 12.1 25 23 22.8
2M003BXZHSB34BD0 37x2.5 35.0 2810 7.41 33 30 14.0

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 64 / 75
ALSECURE PLUS NX300 BS LV, Mica, Contact
Nexans Qatar
XLPE Insulation, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS 6724

Unarmoured LV cable, HFFR sheathed for fixed installations. Rated voltage 0.6/1 KV

DESCRIPTION
Application

These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant)

Design

1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
2. Fire Barrier
Mica Glass tape
3. Insulation
Cross Linked Polyethylene "XLPE"
4. Outer Sheath
Halogen Free Flame retardant "HFFR".

Options : STANDARDS
- Flame retardant : "CAT A, CAT B, CAT C" to BS 4066 or equivalent. International IEC 60332-1
- Ozone resistant. National BS 6724
- Oil resistant.

- Anti termite.

Fire test :
As per BS 6387 :

C-Resistance to fire at 950 Deg for 180 mins.

W-Resistanace to fire and water at 650 Deg for 30 mins.

Z-Resistance to fire and mechanical shock at 950 Deg for 15 mins.

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Smoke density Gases corrosivity
Yes Stranded class 2 (Um) temp.in service Yes when laying IEC 61034 IEC 60754-2
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 65 / 75
ALSECURE PLUS NX300 BS LV, Mica, Contact
Nexans Qatar
XLPE Insulation, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / Mica / XLPE / HFFR 600/1000 V BS 6724
MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Armour type Unarmoured
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 15 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1
Fire resistant Yes
Bending factor when installed 8 (xD)

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Smoke density Gases corrosivity
Yes Stranded class 2 (Um) temp.in service Yes when laying IEC 61034 IEC 60754-2
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 66 / 75
ALSECURE PLUS NX300 BS LV, Mica, Contact
Nexans Qatar
XLPE Insulation, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

ALSECURE PLUS NX300 BS LV, MICA, XLPE INSULATION, HFFR 0.6/1 KV


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight single phase
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
21050RXZOUH34BD0 1x50 14.0 700 0.387 216 153 0.84
21070RXZOUH34BD0 1x70 16.0 900 0.268 278 188 0.61
21095RXZOUH34BD0 1x95 18.0 1160 0.193 342 226 0.47
21120RXZOUH34BD0 1x120 20.0 1400 0.153 400 257 0.39
21150RXZOUH34BD0 1x150 21.0 1700 0.124 464 287 0.34
21185RXZOUH34BD0 1x185 23.0 2050 0.0991 533 324 0.29
21500RXZOUH34BD0 1x500 24.0 5020 0.0366 998 791 0.17
21240RXZOUH34BD0 1x240 26.0 2550 0.0754 634 375 0.25
21340RXZOUH34BD0 1x300 28.0 3100 0.0601 736 419 0.22
21400RXZOUH34BD0 1x400 32.0 4000 0.047 868 717 0.19
21634RXZOUH34BD0 1x630 41.0 6200 0.0283 1151 861 0.16
21800RXZOUH34BD0 1x800 45.0 8000 0.0221 1246 904 0.15

ALSECURE PLUS NX300 BS LV, MICA, XLPE INSULATION, HFFR 0.6/1 KV 2C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight single phase
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002FXZOUB09BD0 2x1.5 10.0 265 12.1 23 21 22.8
22003FXZOUB09BD0 2x 2.5 11.0 215 7.41 32 30 14.0
22004FXZOUB09BD0 2x 4 12.0 170 4.61 42 39 8.7
22006FXZOUB09BD0 2x 6 13.0 140 3.08 54 49 5.9
22010FXZOUB09BD0 2x10 15.0 380 1.83 75 65 3.5
22016FXZOUB09BD0 2x16 17.0 500 1.15 100 84 2.2
22025FXZOUB09BD0 2x25 20.0 730 0.727 127 107 1.5
22035FXZOUB09BD0 2x35 22.0 940 0.524 158 129 1.1
22050FXZOUB09BD0 2x50 24.0 1220 0.387 192 153 0.81
22070FXZOUB09BD0 2x70 28.0 1700 0.268 246 188 0.58
22095FXZOUB09BD0 2x95 32.0 2280 0.193 298 226 0.44
22120FXZOUB09BD0 2x120 35.0 2830 0.153 346 257 0.37
22150FXZOUB09BD0 2x150 39.0 3465 0.124 399 287 0.31
22185FXZOUB09BD0 2x185 44.0 4350 0.0991 456 324 0.27

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Smoke density Gases corrosivity
Yes Stranded class 2 (Um) temp.in service Yes when laying IEC 61034 IEC 60754-2
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 67 / 75
ALSECURE PLUS NX300 BS LV, Mica, Contact
Nexans Qatar
XLPE Insulation, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

ALSECURE PLUS NX300 BS LV, MICA, XLPE INSULATION, HFFR 0.6/1 KV 3C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight single phase
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002FXZOUB09BD0 3x 1.5 11.0 160 12.1 23 21 22.8
23003FXZOUB09BD0 3x 2.5 12.0 200 7.41 32 30 14.0
23004FXZOUB09BD0 3x 4 13.0 250 4.61 42 39 8.7
23006FXZOUB09BD0 3x 6 14.0 320 3.08 54 49 5.9
23010FXZOUB09BD0 3x10 16.0 450 1.83 75 65 3.5
23016FXZOUB09BD0 3x16 18.0 635 1.15 100 84 2.2
23025FXZOUB09BD0 3x25 21.0 930 0.727 127 107 1.5
23050FXZOUB09BD0 3x50 22.0 1250 0.387 192 153 0.81
23035FXZOUB09BD0 3x35 23.0 1200 0.524 158 129 1.1
23070FXZOUB09BD0 3x70 25.0 1770 0.268 246 188 0.58
23095FXZOUB09BD0 3x95 29.0 2390 0.193 298 226 0.44
23120FXZOUB09BD0 3x120 32.0 3000 0.153 346 257 0.37
23150FXZOUB09BD0 3x150 35.0 3700 0.124 399 287 0.31
23185FXZOUB09BD0 3x185 39.0 4590 0.0991 456 324 0.27
23240FXZOUB09BD0 3x240 43.0 5880 0.0754 538 375 0.23
23300FXZOUB09BD0 3x300 48.0 7380 0.0601 621 419 0.2
23400FXZOUB09BD0 3x400 55.0 9440 0.047 765 468 0.18

ALSECURE PLUS NX300 BS LV, MICA, XLPE INSULATION, HFFR 0.6/1 KV 4C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight single phase
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002FXZOUB09BD0 4x 1.5 12.0 190 12.1 23 21 22.8
24003FXZOUB09BD0 4x 2.5 13.0 230 7.41 32 30 14.0
24004FXZOUB09BD0 4x 4 14.0 300 4.61 42 39 8.7
24006FXZOUB09BD0 4x 6 15.0 390 3.08 54 49 5.9
24010FXZOUB09BD0 4x10 17.0 550 1.83 75 65 3.5
24016FXZOUB09BD0 4x16 19.0 780 1.15 100 84 2.2
24025FXZOUB09BD0 4x25 23.0 1160 0.727 127 107 1.5
24050FXZOUB09BD0 4x50 24.0 1620 0.387 192 153 0.81
24035FXZOUB09BD0 4x35 25.0 1515 0.524 158 129 1.1

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Smoke density Gases corrosivity
Yes Stranded class 2 (Um) temp.in service Yes when laying IEC 61034 IEC 60754-2
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 68 / 75
ALSECURE PLUS NX300 BS LV, Mica, Contact
Nexans Qatar
XLPE Insulation, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight single phase
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24070FXZOUB09BD0 4x70 28.0 2300 0.268 246 188 0.58
24095FXZOUB09BD0 4x95 31.0 2280 0.193 298 226 0.44
24120FXZOUB09BD0 4x120 35.0 3910 0.153 346 257 0.37
24150FXZOUB09BD0 4x150 39.0 4830 0.124 399 287 0.31
24185FXZOUB09BD0 4x185 43.0 6030 0.0991 456 324 0.27
24240FXZOUB09BD0 4x240 49.0 7850 0.0754 538 375 0.23
24300FXZOUB09BD0 4x300 55.0 9850 0.0601 621 419 0.2
24400FXZOUB09BD0 4x400 61.0 12555 0.047 765 468 0.18

ALSECURE PLUS NX300 BS LV, MICA, XLPE INSULATION, HFFR 0.6/1 KV 5C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight single phase
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002FXZOUB09BD0 5x 1.5 13.0 220 12.1 23 21 22.8
25003FXZOUB09BD0 5x 2.5 14.0 270 7.41 32 30 14.0
25004FXZOUB09BD0 5x 4 15.0 350 4.61 42 39 8.7
25006FXZOUB09BD0 5x 6 16.0 465 3.08 54 49 5.9
25010FXZOUB09BD0 5x10 19.0 670 1.83 75 65 3.5
25016FXZOUB09BD0 5x16 21.0 955 1.15 100 84 2.2
25025FXZOUB09BD0 5x25 25.0 1425 0.727 127 107 1.5
25035FXZOUB09BD0 5x35 28.0 2280 0.524 158 129 1.1
25050FXZOUB09BD0 5x50 32.0 2170 0.387 192 153 0.81
25070FXZOUB09BD0 5x70 37.0 3050 0.268 246 188 0.58

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Smoke density Gases corrosivity
Yes Stranded class 2 (Um) temp.in service Yes when laying IEC 61034 IEC 60754-2
0.6/1 kV 90 C 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/20/17 www.nexans.qa Page 69 / 75
ALSECURE PLUS NX400 LV, Mica, Contact
Nexans Qatar
XLPE, SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS 7846 -F2 & BS 6387

Galvanized steel wire armoured LV cable, HFFR sheathed for fixed installations. Rated
voltage 0.6/1 KV

DESCRIPTION
Application

Refineries, Mines, Hotels, Schools, Tunnels, High construction, Hospitals, Power


plants, Data processing centers, Business centers where there is concentration of
sensitive to fire

Design

1. Conductor
Stranded bare copper class 2 acc. to EN 60228
2. Fire Barrier
Mica Glass tape
3. Insulation
Cross Linked Polyethylene "XLPE"
4. Inner Sheath or Bedding
Lapped bedding or extruded HFFR
5. Armour
Galvanized Steel Wire Armour "SWA" STANDARDS
5. Outer Sheath International IEC 60331-21
Halogen Free Flame retardant "HFFR".
National BS 6387 CWZ;
Options : BS 7846
- Flame retardant : "CAT A, CAT B, CAT C" to BS 4066 or equivalent.

- Ozone resistant.

- Oil resistant.

- Anti termite.

Fire test :
As per BS 6387 :

C-Resistance to fire at 950 Deg for 180 mins.

W-Resistanace to fire and water at 650 Deg for 30 mins.

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 70 / 75
ALSECURE PLUS NX400 LV, Mica, Contact
Nexans Qatar
XLPE, SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Z-Resistance to fire and mechanical shock at 950 Deg for 15 mins.

Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m

All dimensions have tolerance +- 7 %

Marking
no. of cores x conductor sizes mm2 Cu / Mica / XLPE / SWA / HFFR 600/1000 V BS
7846BS 6387 LPCBMADE IN QATAR QICC-Nexans Year Meters

Custom marking available

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath Halogen free flame retardant
Armour type Galvanized steel wires
Outer sheath HFFR (Halogene Free Flame Retardant)
Colour Black
Halogen free Yes
Conductor flexibility Stranded class 2
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Flame retardant Yes
Bending factor when laying 10 (xD)
Bending factor when installed 20 (xD)
Smoke density IEC 61034
Gases corrosivity IEC 60754-2
Gases toxicity No toxicity to IEC 60754-1

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 71 / 75
ALSECURE PLUS NX400 LV, Mica, Contact
Nexans Qatar
XLPE, SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Usage characteristics
Fire resistant IEC 60331-21

BS LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 2 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002RXZHSH34BD0 2x1.5 13.0 290 12.1 25 23 22.8
22003RXZHSH34BD0 2x2.5 14.0 340 7.41 33 30 14.0
22004RXZHSH34BD0 2x4 15.0 400 4.61 44 39 8.7
22006RXZHSH34BD0 2x6 17.0 470 3.08 56 49 5.9
22010RXZHSH34BD0 2x10 19.0 720 1.83 78 65 3.5
22016RXZHSH34BD0 2x16 21.0 900 1.15 99 84 2.2
22025RXZHSH34BD0 2x25 25.0 1350 0.727 131 107 1.65
22035RXZHSH34BD0 2x35 27.0 1610 0.524 162 129 1.15
22050RXZHSH34BD0 2x50 31.0 2010 0.387 197 153 0.89
22070RXZHSH34BD0 2x70 35.0 2640 0.268 251 188 0.6
22095RXZHSH34BD0 2x95 40.0 3630 0.193 304 226 0.45
22120RXZHSH34BD0 2x120 44.0 4330 0.153 353 257 0.37
22150RXZHSH34BD0 2x150 47.0 5140 0.124 406 287 0.3
22185RXZHSH34BD0 2x185 54.0 6650 0.0991 463 324 0.26

BS LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 3 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23002RXZHSH34BD0 3x1.5 14.0 340 12.1 25 23 22.8
23003RXZHSH34BD0 3x2.5 15.0 400 7.41 33 30 14.0
23004RXZHSH34BD0 3x4 17.0 480 4.61 44 39 8.7
23006RXZHSH34BD0 3x6 18.0 580 3.08 56 49 5.9
23010RXZHSH34BD0 3x10 20.0 890 1.83 78 65 3.5
23016RXZHSH34BD0 3x16 22.0 1150 1.15 99 84 2.2
23025RXZHSH34BD0 3x25 27.0 1700 0.727 131 107 1.65
23035RXZHSH34BD0 3x35 30.0 2070 0.524 162 129 1.15
23050RXZHSH34BD0 3x50 30.0 2520 0.387 197 153 0.89

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 72 / 75
ALSECURE PLUS NX400 LV, Mica, Contact
Nexans Qatar
XLPE, SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

Nom. Max. DC Perm. current Current


Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
23070RXZHSH34BD0 3x70 35.0 3570 0.268 251 188 0.6
23095RXZHSH34BD0 3x95 39.0 4570 0.193 304 226 0.45
23120RXZHSH34BD0 3x120 42.0 5520 0.153 353 257 0.37
23150RXZHSH34BD0 3x150 48.0 7030 0.124 406 287 0.3
23185RXZHSH34BD0 3x185 52.0 8410 0.0991 463 324 0.26
23240RXZHSH34BD0 3x240 58.0 10480 0.0754 546 375 0.21
23300RXZHSH34BD0 3x300 63.0 12770 0.0601 628 419 0.18
23400RXZHSH34BD0 3x400 70.0 15830 0.047 731 439 0.17

BS LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 4 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002RXZHSH34BD0 4x1.5 13.0 200 12.1 25 23 22.8
24003RXZHSH34BD0 4x2.5 15.0 420 7.41 33 30 14.0
24004RXZHSH34BD0 4x4 17.0 510 4.61 44 39 8.7
24006RXZHSH34BD0 4x6 19.0 750 3.08 56 49 5.9
24010RXZHSH34BD0 4x10 21.0 1060 1.83 78 65 3.5
24016RXZHSH34BD0 4x16 25.0 1500 1.15 99 84 2.2
24025RXZHSH34BD0 4x25 30.0 2070 0.727 131 107 1.65
24035RXZHSH34BD0 4x35 32.0 2550 0.524 162 129 1.15
24050RXZHSH34BD0 4x50 32.0 3080 0.387 197 153 0.89
24070RXZHSH34BD0 4x70 38.0 4420 0.268 251 188 0.6
24095RXZHSH34BD0 4x95 41.0 5650 0.193 304 226 0.45
24120RXZHSH34BD0 4x120 47.0 7280 0.153 353 257 0.37
24150RXZHSH34BD0 4x150 52.0 8700 0.124 406 287 0.3
24185RXZHSH34BD0 4x185 57.0 10570 0.0991 463 324 0.26
24240RXZHSH34BD0 4x240 64.0 13370 0.0754 546 375 0.21
24300RXZHSH34BD0 4x300 71.0 16230 0.0601 628 419 0.18
24400RXZHSH34BD0 4x400 79.0 21230 0.047 731 439 0.17

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 73 / 75
ALSECURE PLUS NX400 LV, Mica, Contact
Nexans Qatar
XLPE, SWA, HFFR 0.6/1 kV Phone: + 974 4467 3009
sales.qatar@nexans.com

BS LV, MICA, XLPE INSULATION, SWA, HFFR 0.6/1 KV 5 C


Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002RXZHSH34BD0 5x1.5 15.0 450 12.1 25 23 22.8
25003RXZHSH34BD0 5x2.5 17.0 540 7.41 33 30 14.0
25004RXZHSH34BD0 5x4 19.0 770 4.61 44 39 8.7
25006RXZHSH34BD0 5x6 21.0 940 3.08 56 49 5.9
25010RXZHSH34BD0 5x10 24.0 1250 1.83 78 65 3.5
25016RXZHSH34BD0 5x16 27.0 1780 1.15 99 84 2.2
25025RXZHSH34BD0 5x25 32.0 2490 0.727 131 107 1.65
25035RXZHSH34BD0 5x35 34.0 3040 0.524 162 129 1.15
25050RXZHSH34BD0 5x50 40.0 4180 0.387 197 153 0.89
25070RXZHSH34BD0 5x70 46.0 5600 0.268 251 188 0.6

Halogen free Conductor flexibility Rated Voltage Uo/U Max.conductor Flame retardant Bending factor Bending factor Smoke density
Yes Stranded class 2 (Um) temp.in service Yes when laying installed IEC 61034
0.6/1 kV 90 C 10 (xD) 20 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/20/17 www.nexans.qa Page 74 / 75
Distributed by

Nexans Qatar
Doha - Qatar
+ 974 4467 3009
sales.qatar@nexans.com