Sie sind auf Seite 1von 1

1 2 3 4 5 6 7 8

E-Base Version: 6.7.0.1103


DB Version: SL-0.2-1/10/2012
Sheet Version: 0.2
=B10+S1

CB Q0 Trip coil
Intertrip send inbuilt in 7SD52

Lockout relay
66kV BF/BB trip relay K8710
PH13-5C-10-13-0010

Intertrip send inbuilt in P545


Annunciation to SCS/NCC
A A

CB Block close

Eqpt. Location
Group-A 86-1
Group-B 86-2

Device no.
Initiate BF

DC Group

Function
Description

Type
TC1
TC2
X610 S871 S871
B10CT1 7SD52 (87C1) F871 X
=B10+S1/AA 05.8 X X Optical fibre feeder differential protection Main-1
LINK-D
X710 IT SEND-1 X X X Back-up distance protection Main-1 / SOTF Trip
B106 VT_1
=B10+S1/AA 05.8
X X Inter Trip receive

PI-1 Fo box PI-2 X 87C/ Thermal O/L (49C) -stage-1


49C/
Fiber optic Fiber optic T1 RP 7SD52 F871
X 21C/ Thermal O/L (49C) -stage-2
Along side protn. ckt. Along side parallel ckt. 51
B B
X X X Backup overcurrent protection

X 110% O/C alarm


X620 S872 S872
B10CT2 P545 (87C2) F872
=B10+S1/AA 05.8 X X X Optical fibre feeder differential protection Main-2
LINK-E
X720
B106VT_2 IT SEND-2 X X X Back-up distance protection Main-2 / SOTF Trip
=B10+S1/AA 05.8
X X 87C/ Inter Trip receive
49C/
T2 RP P545 F872
PI-1 Fo box PI-2 X 21C/ Thermal O/L (49C) -stage-1
51
Fiber optic Fiber optic
X Thermal O/L (49C) -stage-2
Along side protn. ckt. Along side parallel ckt.
X X X Backup overcurrent protection

C C
Last Used by: z003nrbn

X 110% O/C alarm

X X X X X X 87B Busbar Protection


Time: h:40:05 tt
Date: M/d/2017

X X X Breaker fail protection (Stage-1)


S8710 LINK-C BBP1/
BBP 7SS52 50BF F8710
=BB+RP BF INITIATION X X X X BBP2 Breaker fail protection (Stage-2)

X X X EFP End fault protection


X610 S8710 7SS52 F8710 S8710
B10CT4 7PG15 K311(86-1)
=B10+S1/AA 05.8 X X X X X T1 RP 7PG15 86-1 K311 Group-A master trip relay (hand/electrical reset)
Bay unit for B10
X X X X X T2 RP 7PG15 86-2 K321 Group-B master trip relay (hand/electrical reset)
S8710

X X X X X BBP1/ BBP 7PG15 96BBP K87X Master trip relay BB/BF (hand/electrical reset)
7PG15 K321(86-2) BBP2
UEBYA, UMAM1, AHUMW, LUAIB 66kV Cable Fdr. Protn.scheme Sch.(P545 M2) B AA 06

D BBP 50BF X X T1 RP 7PG17 74-1 K312 Trip circuit -1 supervision relay R,Y,B D
Stage-2
Optical fibre X X T2 RP 7PG17 74-2 K322 Trip circuit -2 supervision relay R,Y,B
communication 7PG17 K312(74-1)
7PG15 K8710 7SS522 F870

Master Control Unit


7PG17 K322(74-2)
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

B100(-Q0)_1 LINK-A
=B10+S1/AA 05.8
CB TRIP COIL-1
B100(-Q0)_2 LINK-B
=B10+S1/AA 05.8
CB TRIP COIL-2 +Unit
Device type X X Device no.
X Ansi no.
F F
Date 11/7/2017 UEBYA, UMAM1, AHUMW, LUAIB 66kV Cable Fdr. Protn.scheme Sch.(P545 M2) PH13-5C-00-33-0050 B =B10+RP 1 mm. : 1 mm.
Drawn By PS Protection Logic Diagram GTC/735C/2015 AA 06
Chkd By PS Sh. 06 of 6
Revision-0 (3)-G719EA-JG9191-U3050
Version Remarks Date Name Appr MJU Orig.: Replaces: Replaced by: Overview Diagram <05 ->
1 2 3 4 5 6 7 8