Sie sind auf Seite 1von 4

CARBON DIOXIDE CONCENTRATION AS A MEASURE OF AIR

EXCHANGE IN ANIMAL HOUSING

J. J. R. Feddes, J. J. Leonard, and J. B. McQuitty


Department ofAgricultural Engineering, University ofAlberta, Edmonton, Alta. T6G 2H1
Received 5 January 1983, accepted 17January 1984

Feddes, J. J. R., J. J. Leonard, and J. B. McQuitty. 1984. Carbon dioxide concentration as a measure of air
exchange in animal housing. Can. Agric. Eng. 26: 53-56.
The quality of the air in animal housing is afunction of air exchange rates or air exchange per animal. Measuring
air exchange rates can be adifficult procedure with conventional methods and instrumentation. The use ofa commercial
tracer gas has been tried but the technique has limitations for application in most confined animal units because of
incomplete mixing. Carbon dioxide can also be considered as a tracer gas. This gas is generated by animals at rates
dependent on size of animal and rate of metabolism and is introduced uniformly throughout the building. Carbon dioxide
production rates were measured indairy, pig and broiler facilities. Results are presented which indicate that the con
centration ofcarbon dioxide in the exhaust air from such facilities can be aconvenient method ofestimating ventilation
rates and should be investigated further.

INTRODUCTION Bruce (1981) made use of the above locities in theductsweremeasured bysev
Measuring air exchange rates in animal homeothermic theory to develop an ap eral methods. In all cases, air-flow rates
housing can be very difficult when con proximate relationship between metabo in the ducts were monitored at 4-min in
sidering the number of air exhaust loca lism and C02 production for pigs. Esti tervals by thermistor anemometers
tions, lack of data on fan capacities, and mates of C02 production for various (Feddes and McQuitty 1980). These sen
the variation in negative pressures at liveweights andfeeding levelsweregiven. sors were calibrated against a hot-wire
which the exhaust fans are operating. To From this relationship, Bruce observed anemometer (Kurz Instruments, Carmel
determine ventilation rates accurately, air that ventilation rates could be estimated to Valley, Calif.) during the course of each
flow from each exhaust fan must be de maintain a given C02 concentration. study. This anemometer was also used to
termined using, for example, a hot-wire Owen (1982) also suggested that C02 con measure air velocities in a 25-point trav
anemometer. The sum of the flow rates centrations be used as a basis for estab erse of each duct cross-section. The av
would be assumed to be the ventilation lishing minimum ventilation rates. A fur erage of these measurements was com
rate. An alternative to this technique ther possibility, however, would be to use pared and related to that measured by each
would be to use the decay rate of tracer C02 concentration as a means of estimat thermistor anemometer, thus accounting
gas concentration in the ventilated space ing actual ventilation rates in confinement for any lack of uniformity in the air-flow
to determine ventilation rates. This housing. Accordingly, a study was under profile within the duct.
method may be of little practical signifi taken with the objectiveof ascertainingthe Carbon dioxide concentrations in the
cance, however, since the air in many an feasibility of this approach, the results of exhaust air at each fan location were mon
imalhousing unitsis notcompletelymixed which are reported here. itored in each of the animal units by a non-
(Barber and Ogilvie 1982). dispersive infrared gas analyzer (Beck-
A further alternative may be to make EXPERIMENTAL FACILITIES AND man, Model 315 A, Fullerton, Calif). Pre
use of the carbon dioxide (C02) produc METHODS liminary testing had indicated that the con
tion arising from the metabolism of the an This work was carried out concurrently centration of C02 measured in the exhaust
imals within a barn. Various factors are with other studies related to the animal en air was much less variable and more rep
known to influence the rate of metabolism vironment (Feddes et al. 1983, 1984; resentative of the mean C02 concentration
in animals. Food intake rate, work or ac Smith et al. 1980). As reported in these than that measured at prescribed locations
tivity, and environmental temperature are studies, the ventilation rates, tempera within a barn. Air-sampling lines used to
considered to be the most influential fac tures, and air quality parameters including monitor C02 were brought from each sam
tors. Metabolic rates vary directly with C02 concentrations were measured simul pling location into the mobile laboratory
food intake and muscular activity. Envi taneously over a 1- or 2-day period in each and connected to an automatic sequencing
ronmental temperature also can decrease animal unit studied. The data acquisition sampler (Feddes and McQuitty 1977).
or increase the rate of metabolism. Envi and recording system, developed at the This sampler, driven by a data logger,
ronmental temperature above and below a University of Alberta (Feddes and Mc drew an air sample twice each hour from
certain temperature range, defined by an Quitty 1977) and housed in a mobile lab each sampling location and delivered it to
upper and a lower critical value, causes an oratory, was used to collect these data. the C02 analyzer. Each air sample was
increase in the heat production of the In each instance, dry-bulb temperatures drawn for 4 min before the concentration
body. Within this range, the heat loss of were measured by thermistors (Fenwal was recorded.
the animal through radiation, conduction Electronics, Framingham, Mass.). Ven The output signals from the thermis
or convection is regulated so that the rate tilation rates were monitored in an insu tors, ventilation-related instrumentation,
of metabolism and the body temperature lated discharge duct constructed down and the C02 analyzer were received di
are not affected. This temperaturerange is stream from each operating exhaust fan. rectly by the data logger (Feddes and
defined as the thermoneutral zone where The sizingof the ducts and the monitoring McQuitty 1980). Production rates of C02
heatproduction of the animalis independ locations of the air flows in each duct were were calculated by subtracting the C02
ent of the temperature. as prescribed by Jorgenson (1961). Air ve concentrations in outside air from those

CANADIAN AGRICULTURAL ENGINEERING, VOL. 26, NO. 1, SUMMER 1984 53


measured in the barns. The mean hourly lerslie Research Station near Edmonton, broilers in each of the barns (Feddes et al.
values of C02, temperature and ventila Alberta. This facility was divided into four 1984). One of the units housed approxi
tion rates were calculated and plotted on a rooms having a similar air-supply and mately 7900 broilers, while the other hou
digital plotter. The raw data were pro waste-removal drain. The dimensions of sed 6800 broilers (Table III). In this study,
cessed and plotted within 2 days of being the rooms were the same and approxi the speed of each fan was also monitored
recorded; this short turn-around time was mated those of a finishing pen in a com at 4-min intervals by a Hall-effect sensor
considered essential to insure that good mercial pig enterprise, i.e., 2 m X 5 m in activated by a magnet attached to the fan
data were collected. plan. The 12 pigs in each of these pens shaft. The pulses obtained were integrated
were subjected to two levels of tempera and the output voltage was associated with
Dairy Cattle ture and lighting and two feeding meth a fan air-flow rate derived from a function
Four dairy barns located in central Al ods. The mean temperatures were 22 and developed for each fan relating shaft speed
berta were studied between January and 25°C for the two respective treatments. In and air-flow rates. In both the pig and
March of 1979. Environmental condi the feeding method treatment, the pigs broiler studies, the performance curves of
tions, including C02 concentrations in the were fed from the floor or from feeders. each exhaust fan (L/sec vs rpm) were
exhaust air, were monitored continuously The feed intake of the floor-fed pigs was measured indirectly with sulphur hexa-
over a 48-h period in two tie-stall and two restricted to 85% of that consumed by the floride (SF6) as a non-toxic tracer gas
free-stall dairy barns (Smith et al. 1980). feeder-fed pigs of the same weight to min (Leonard et al. 1984) or directly by the
The barns were relatively new and were of imise feed wastage. The two lighting hot-wire anemometer. The mean C02 con
wood frame construction. The number of levels consisted of normal lighting only centrations in the exhaust air for the two
cows and calves housed, C02 production during feeding or normal lighting during barns ranged from 1313 to 4001 ppm over
rates, and mean ambient temperatures are the day. The 48 pigs had a mean mass of the complete production cycles (Table III).
shown in Table I. Since some of these 55 kg and 81 kg at the beginning and end Barn ventilation rates ranged from 270 to
units had a significant number of calves, of the trial, respectively. Each treatment 4330 L/sec.
the calves were converted to cow equiv was replicated three times, i.e., over a 3-
alents. The ratio of C02 production of a wk period. The air flows through each RESULTS AND DISCUSSION
cow to that of a calf was assumed to be room were almost constant throughout the Dairy Cattle
similar to that of heat production rates trial. The mean C02 concentrations in the As shown in Table I, the variation in
(American Society of Agricultural Engi exhaust air ranged between 1600 and 2600 C02 production per cow among the four
neers (ASAE) 1983; Data:270.4). The av ppm for all the treatments, while the mean dairy units was found to be quite large. An
erage mass of the calves was estimated on ventilation rate for all treatments was 6.8 attempt was made to explain this variation
the basis of age (ASAE 1983; L/(s-pig_1). Carbon dioxide production through regression analysis. A high cor
Data:D321.1). The measured C02 con rates were calculated from the air ex relation occurred between temperature and
centrations ranged between 2300 and 4040 change rates and mean C02 concentrations C02 production rate (/?2 = 0.80). How
ppm and the ventilation rates between 17 for each respective treatment. These were ever, when considering the energy metab
and 46 L/(s-cow~')- The average hourly then expressed in terms of metabolic mass olism of an animal, a rise in temperature
production rates per cow equivalent over per pig, since the mass of the pigs changed should not result in a higher rate of me
a one-day period are given in Table I. during the course of the experiment (Table
tabolism, assuming that the cows in each
II). barn were in the thermoneutral range as
Pigs
they appear to have been. There could
In a study involving the influence of se Broilers have been a possible increase in C02 pro
lected management practices on heat, Two broiler barns located near Edmon duction over a short period of time due to
moisture and air quality in pig housing ton, Alberta were studied between Sep cows in Barns C and D acclimatizing to
(Feddes et al. 1983), C02 concentration tember 1981 and May 1982. Environmen higher ambient temperatures since the out
was one of the parameters measured in a tal conditions, including C02 door temperatures changed from approx
controlled-environment facility operated concentrations in the exhaust air, were imately - 20°C to 0°C immediately before
by the Department of Agricultural Engi monitored continuously 1 day a week dur monitoring these barns. However, the
neering, University of Alberta, at the El- ing a complete production cycle of the amount of additional C02 produced due to
cows acclimatizing to higher temperatures
TABLE I. EXPERIMENTAL DATA SUMMARY — DAIRY COWS apparently is not known. In any case, the
amount was considered most probably to
Barn At Barn Bt Barn Ct Barn Dt
be insignificant since the cows presum
Number of cows 46 48 57 84 ably would have lowered their feed intake
Number of calves 19 7 34 0 to reduce any possible heat stress. The
Number of cow equivalents 48.3 48.6 62 84
Mean ambient temperature (°C) 8.1 6.4 13.1 16.3
variation might also be explained in part
Mean ventilation rate§ (L/(sec-cow)) 17 28 43 46 by the increased rate in fermentation of the
Predicted ventilation ratet (L/(sec-cow)) 20 39 37 37 manure. Since the manure was removed
Mean COz production§ (L/(h-cow)) 217 181 294 318 on a daily basis, however, any increase in
Mean C02 concentration!I (ppm) 4040 2300 2400 2420
C02 production from this source would
Milk production, (kg/(daycow)) 16.4 17.5 18.5 14.2
Water Consumption§ (kg/(daycow)) 73.8 76.5 79.2 74.2
have to be negligible. Similarily, the fact
that silage feeding was practised in Barn
tTie-stall.
tFree-stall.
D only is most unlikely to account for the
§Cow-equivalent. relatively high rate of C02 production
tBased on overall mean production rate of 250 L/(h-cow)). found in this barn. Again, while the high
pncludes 500 ppm C02 in outside air. est level of milk production occurred in

54 CANADIAN AGRICULTURAL ENGINEERING. VOL. 26, NO. 1, SUMMER 1984


TABLE II. EXPERIMENTAL DATA SUMMARY — PIGS heat production (Mount 1979). The floor-
fed pigs also consumed less feed (2.26 kg/
Temperature Feeding method
day) than those on feeders (2.83 kg/day).
High Low
(24.8°C) (21.9°C) Feeder Floor
This also accounted for the lower C02 pro
duction rates.
Mean ventilation rate (L/(sec-pig)) 6.8 6.8 7.5 6.0 As shown in Table II, the air exchange
Predicted ventilationratet (L/(sec-pig)) 7.4 6.2 7.1 6.4
C02 concentration^ (ppm) 1850 2120 1920 2080
rates predicted from the measured C02
C02 production (L/(h-kg metabolic wt)) 1.40 1.65 1.59 1.47 concentrations, the number and weight of
Feed consumption, (kg/(pig-day)) 2.38 2.71 2.83 2.26 the pigs, and the overall mean C02 pro
Relative humidity (%) 64 73 68 69 duction rate of 1.53 L/(h-kg of metabolic
tBased on overall meanproduction rate of 1.53 L/(h-kg of metabolic wt)). mass) were in good agreement with those
^Includes500 ppm C02 in outside air. measured. The discrepancy ranged from
5.3 to 8.8%, with a mean of 7.4%. The
TABLE in. EXPERIMENTAL DATA SUMMARY — BROILERS
predicted ventilation rates agreed more
closely with those measured in the feeder
C02 Ventilation rate C02 and floor feeding treatment than those
Age concentrationt Measured Predicted production measured in the temperature treatment
(days) (ppm) L/(h-1000 birds)
I / (Table II). This accuracy is considered to
Barn A be adequate in predicting ventilation rates
2 1310 750 760 280 in growing/finishing barns, but further
9 2040 720 540 510 work would be desirable to obtain reliable
16 1960 1300 1250 870 C02 production data under commercial
23 1830 2350 2470 1460
30 2240 2930 2830
housing conditions.
2380
37 3170 2290 2390 2890
44 2260 4330 4240 3630 Broilers
Number of birds. The mean C02 concentrations ranged
Initial 7937 between 1310 and 4000 ppm for the entire
Final 7535
production cycles in each unit. As in the
Final bird weight (kg) 1.71
Feed consumption (kg/ 3.68
dairy and pig facilities, these concentra
(bird-cycle)) tions are considered to be very low in
BarnB terms of any potential animal and human
5 1820 270 380 190 health hazards resulting from exposure to
12 2020 710 670 570 this gas (Animal Manure Management
19 2980 730 840 960
Committee 1980). The hourly production
26 3340 1220 1220 1860
33 3600 1720 1570 2870
rates were further averaged to a mean pro
40 4000 1670 1730 3180 duction rate for each respective age. These
Number of birds. values are given in Fig. 1 and Table III.
Initial 6810 As shown in Fig. 1, the C02 production
Final 6635
rates were very similar in both barns. This
Final bird weight (kg) 1.71
Feed consumption (kg/ 3.47
was expected since the type of bird, feed,
(bird-cycle)) and management practices were very sim
ilar in both operations.
Includes 500 ppm C02 in outside air.
The best fit equation, used to relate C02
production rates and bird age, was a po
Barn C (Table I), the anticipated corre Pigs lynomial function or a sigmoid curve. This
sponding increase in C02 production An analysis of variance was used to curve was very similar to a typical growth
would be insufficient to explain ade evaluate the effects of temperature, feed curve of a broiler. This best fit equation
quately the discrepancy of 50% in C02 ing method, and lighting on C02 produc which has a high correlation (R2 —0.99) is
production levels over Barns A and B. tion rates. This indicated that temperature as follows:
More research is necessary to explain and feeding method had a significant ef
Y = 340-40.7X + 5.59X2-0.0683X3 (1)
the variation in C02 production rates found fect on C02 production. Carbon dioxide
in this study. Using the mean C02 pro production rates were lower for the higher where Y = C02 production rate, L/
duction rate for all four barns of 250 L/ temperature and the floor-feeding treat (h. 1000 birds" !),andX = age of the birds
(h-cow equivalent) to predict the ventila ments (Table II). in days.
tion rate in each barn (Table I) resulted in The pigs in the higher temperature treat The prediction equation appears incorrect
discrepancies ranging from 14 to 39% ment consumed less feed daily than those when bird age is less than 5 days. The C02
compared to the measured values. At best, in the lower temperature treatment. This production value measured during day two
a mean discrepancy of nearly 23% would would account for the decrease in C02 in Barn A appears to be much too high.
provide little more than a preliminary production. This suggests that the pigs in The reason for the high discrepancy in the
evaluation of the air exchange in a dairy the higher temperature treatment were value was due to the difficulty in meas
barn. However, in view of the ease with either hyperthermic or approaching this uring air exchange rates since none of the
which C02 concentration in exhaust air condition. When pigs are approaching hy exhaust fans were in operation during the
may be checked, even this may be helpful perthermia, they reduce feed intake to re first week.
on occasions. duce their difficulty in dissipating their If the age of the birds in a broiler unit

CANADIAN AGRICULTURAL ENGINEERING, VOL. 26, NO. 1, SUMMER 1984 55


400 r feeder pigs (50-75 kg) was 1.53 L/(h.kg
of metabolic mass-1). Mean C02 produc
tion rates ranged between 1.40 and 1.65
L/(h.kg of metabolic mass -1).

ACKNOWLEDGMENTS
The authors wish to acknowledge the finan
cial support for these studies of Agriculture
Canada, Alberta Agricultural Research Trust,
and the Alberta Pork Producers Marketing
Board. The producers involved in these studies
and the contribution of Mr. D. Travis, Tech
nician, Department of Agricultural Engineer
ing, University of Alberta, also are gratefully
acknowledged.

REFERENCES
ANIMAL MANURE MANAGEMENT
COMMITTEE. 1980. Canada animal man
ure management guide. Publ. 1534, Agri
culture Canada, Ottawa, Ont.
AMERICAN SOCIETY OF AGRICUL
TURAL ENGINEERS. 1983. Agricultural
Engineers Yearbook of Standards. Am. Soc.
Agric. Eng., St. Joseph, Mich.
BARBER, E. M. and J. R. OGILVIE. 1982.
Incomplete mixing in ventilated air spaces.
Part 1. Theoretical considerations. Can.
16 24 32 40 Agric. Eng. 24: 25-30.
Bird Age (days) BRUCE, J. M. 1981. Ventilation and temper
ature control criteria for pigs. Pages 197—
Figure 1. Carbon dioxide production of broiler chickens in Barns A and B during complete 216 in: J. A. Clark, ed. Environmental as
production cycles. pects of housing for animal production. But-
terworths, London.
FEDDES, J. J. R. and J. B. MCQUITTY.
is known, the C02 production rate may be birds less than 1 wk old were eliminated 1977. Data acquisition system for measuring
obtained from either Eq. 1 or Fig. 1. Us from consideration of both barns, the environmental variables within confinement
animal units. Can. Agric. Eng. 19: 75-77.
ing this production rate, the number of mean discrepancy is decreased to 7.0%.
FEDDES, J. J. R. and J. B. MCQUITTY.
birds, and the measured C02 concentra Thus, results overall suggest that ventila 1980. Design of an air-speed sensor system.
tion in the exhaust air, the estimated ven tion rates in broiler houses can be esti Can. Agric. Eng. 22: 97-99.
tilation rate may be calculated as follows: mated easily and accurately using this FEDDES, J. J. R., J. J. LEONARD, and J. B.
V = 0.278 YB/(D-E) (2)
method, the only equipment necessary MCQUITTY. 1983. The influence of se
being a relatively inexpensive C02 ana lected management practices on heat, mois
where V = ventilation rate (L/sec), B = lyzer. ture, and air quality parameters in swine
number of birds, D = C02 concentration housing. Can. Agric. Eng. 25: 175-179.
in broiler house (ppm) and E = outside CONCLUSIONS FEDDES, J. J. R., J. J. LEONARD, and J. B.
C02 concentration (ppm). Based on the results of this study, the MCQUITTY. 1984. Broiler heat and mois
As shown in Table III, the measured and ture production under commercial condi
following conclusions were made.
tions. Can. Agric. Eng. 26: 57-64.
predicted ventilation rates for the two (1) Carbon dioxide concentrations in the
JORGENSEN, R. 1961. Fan engineering. 6th
barns were in good agreement, the mean exhaust air from a broiler barn may be used ed. Buffalo Forge Company, Buffalo, N.Y.
discrepancy being 10.0%. Of interest is to predict ventilation rates accurately, with LEONARD, J. J., J. J. R. FEDDES, and J. B.
the fact that the highest percentage of dis a regression equation using bird age as the MCQUITTY. 1984. Measurement of ven
crepancies occurred during those periods dependent variable. tilation rates using a tracer gas. Can. Agric.
of the broiler production cycle in which air (2) Carbon dioxide appears to be a re Eng. 26: 49-51.
exchange in the barns depended on infil liable parameter for estimating ventilation MOUNT, L. E. 1979. Adaptation to thermal
tration and/or minimal fan operation. In rates with adequate accuracy for confined environment. Edward Arnold (Publishers)
such circumstances, accurate measure feeder pigs, but with only fair accuracy in Ltd., London, U.K.
ment of air exchange rates is very difficult OWEN, J. 1982. A design basis for ventilation
the case of dairy housing.
of pig buildings. Proceedings of the Second
to achieve. While the percentage discrep (3) The mean C02 production rate in Livestock Environment Symposium, Ames,
ancy between measured and predicted four dairy barns was 250 L/(h-cow equiv Iowa. pp. 406-410.
ventilation rates during these periods for alent-1). The production rates ranged be SMITH, R. A., J. B. MCQUITTY, and J. J.
both barns was high, the values were tween 181 and 318 L/(h-cow equiva R. FEDDES. 1980. Heat and moisture loads
nevertheless of the same order of magni lent-1) for the four barns. in dairy barns. Paper no. 80-208 presented
tude. If the predicted ventilation rates for (4) The mean C02 production rate for at CSAE Conference, Edmonton, Alta.

56 CANADIAN AGRICULTURAL ENGINEERING, VOL. 26, NO. 1, SUMMER 1984

Das könnte Ihnen auch gefallen