8. MAINTENANCE ................................................................................ 38
Maintenace Schedule................................................................... 39
Engine oil change ......................................................................... 40
Air cleaner service ........................................................................ 41
Fuel filter service .......................................................................... 43
Battery service .............................................................................. 44
Fuse replacement ......................................................................... 46
9. TRANSPORTING/STORAGE............................................................ 47
10. TROUBLESHOOTING....................................................................... 49
11. SPECIFICATIONS.............................................................................. 50
12. REMOTE CONTROL KIT ................................................................... 52
13. WIRING DIAGRAM ........................................................................... 57
14. MAJOR Honda DISTRIBUTOR ADDRESSES ................................. 61
3
Downloaded from www.Manualslib.com manuals search engine
Thank you for purchasing a Honda generator.
Honda Motor Co., Ltd. reserves the right to make changes at any time
without notice and without incurring any obligation.
No part of this publication may be reproduced without written
permission.
4
Downloaded from www.Manualslib.com manuals search engine
To ensure safe operation−
5
Downloaded from www.Manualslib.com manuals search engine
To ensure safe operation−
Always make a pre-operation inspection (page 19 ) before you start
the engine. You may prevent an accident or equipment damage.
Place the generator at least 1 m (3 ft) away from buildings or other
equipment during operation.
Operate the generator on a level surface.
If the generator is tilted, fuel spillage may result.
Exhaust gas contains poisonous carbon monoxide.
Never run the generator in an enclosed area.
Be sure to provide adequate ventilation.
Know how to stop the generator quickly and understand operation
of all the controls. Never permit anyone to operate the generator
without proper instructions.
Keep children and pets away from the generator when it is in
operation.
Keep away from rotating parts while the generator is running.
The generator is a potential source of electrical shocks when
misused; do not operate with wet hands.
Do not operate the generator in rain or snow and do not let it get
wet.
Diesel fuel is extremely flammable and explosive under certain
conditions.
Refuel in a well ventilated area with the engine stopped.
Connections for standby power to a building’s electrical system
must be made by a qualified electrician and must comply with all
applicable laws and electrical codes. Improper connections can
allow electrical current from the generator to back feed into the
utility lines. Such back feed may electrocute utility company
workers or others who contact the lines during a power outage,
and when utility power is restored, the generator may explode,
burn, or cause fires in the building’s electrical system.
6
Downloaded from www.Manualslib.com manuals search engine
2. SAFETY LABEL LOCATIONS
These labels warn you of potential hazards that can cause serious
injury. Read the labels and safety notes and precautions described in
this manual carefully.
FUEL CAUTION
HOT CAUTION
EXHAUST CAUTION
CONNECT CAUTION
7
Downloaded from www.Manualslib.com manuals search engine
CE mark and noise label locations
NOISE LABEL
CE MARK
Manufacturer and address
Performance
class
IP code
Maximum ambient Maximum Dry weight
temperature altitude
LIFTING HOOK
Record the frame serial number in the space below. You will need this
serial number when ordering parts.
9
Downloaded from www.Manualslib.com manuals search engine
EXT12D (F, G and GW Types)
PILOT LAMP
WARNING LAMPS
AC RECEPTACLES
(SINGLE PHASE) AMMETER
CIRCUIT PROTECTOR
ENGINE SWITCH
AC RECEPTACLES
(THREE PHASE) AUTOMATIC
THROTTLE
SWITCH
FUEL METER
HOUR METER
VOLT METER
VOLTAGE ADUSTMENT KNOB
ENGINE SWITCH
AUTO
THROTTLE
SWITCH
FUEL METER
AC RECEPTACLES
HOUR METER
10
Downloaded from www.Manualslib.com manuals search engine
4. CONTROLS
Engine Switch
Key position:
START: To start the engine. The starter motor rotates. Detach your
hand from the key when the engine is started. The engine
switch will automatically return to ON position.
Make sure the engine switch is set to OFF position when the engine is
stopped. The Charge warning light will come on if the switch is left in
ON position.
ON
OFF START ON START
KEY
OFF
ENGINE SWITCH
Pilot Lamp (Equipped type only)
PILOT LAMP
11
Downloaded from www.Manualslib.com manuals search engine
Circuit Protector
F, G and GW types
ON
ON
OFF
OFF
CIRCUIT PROTECTOR
B type
ON
ON
OFF OFF
CIRCUIT PROTECTOR
12
Downloaded from www.Manualslib.com manuals search engine
Automatic Throttle Switch (Equipped type only)
(F, G and GW types only) When using the lefthand receptacle, the
automatic throttle does not function. Turn the automatic throttle
switch OFF. Applying load at low engine speed may result in damage
to the generator and the equipment connected to it.
F, G and GW types
OFF
ON
OFF
13
Downloaded from www.Manualslib.com manuals search engine
Voltmeter (Equipped type only)
Turn the automatic throttle switch OFF for checking the voltage.
MIN
MAX MIN MAX
14
Downloaded from www.Manualslib.com manuals search engine
Ammeter (Equipped type only)
(F, G and GW types only) The ammeter indicates only three phase
loaded current.
AMMETER
Fuel Meter
Indicates the amount of fuel in the fuel tank when the engine switch
ON.
Refill the fuel tank when the LED starts lighting near the ‘‘E (EMPTY)’’
mark.
FUEL METER
‘‘E’’ MARK
EMPTY FULL
LED
15
Downloaded from www.Manualslib.com manuals search engine
Hour Meter
HOUR METER
Warning Lamps
Lights when the engine oil level is low or engine lubrication system is
faulty, and the engine automatically stops.
If this occurs;
Check the engine oil level, and add recommended oil if level is low
(see page 20 ).
See your authorized Honda dealer if the oil pressure warning lamp
comes on even though the engine oil is sufficient.
To restart the engine, set the engine switch to OFF once and start
according to the starting procedure.
Engine speed will decrease without load when the fuel tank become
empty. That causes oil pressure remaining low and the oil pressure
warning lamp may light. Refill the fuel tank.
OIL PRESSURE WARNING LAMP
16
Downloaded from www.Manualslib.com manuals search engine
Water Temperature Warning Lamp
If this occurs;
Check the coolant level, and add coolant if level is low (see page 23 ).
Check the cooling air intake openings and the radiator for clogged or
overload occurred when the warning lamp lights and the engine
stops.
To restart the engine, set the engine switch to OFF once and start
according to the starting procedure.
The water temperature warning lamp may not function if the coolant
in the radiator is insufficient.
The general warning lamp lights and engine will stop if generator
problem or overloading has occurred. Stop the engine immediately
and disconnect the appliance, and determine whether the problem is
due to an generator problem, or generator overloading.
If the warning lamp lights and engine stops;
1. Turn off the AC circuit breaker OFF.
2. Restart the engine.
3. Check the generator voltage at the voltmeter.
If the voltage is correct, check the appliance for good condition.
If the voltage is incorrect, see your authorized Honda dealer.
17
Downloaded from www.Manualslib.com manuals search engine
Charge Warning Lamp
18
Downloaded from www.Manualslib.com manuals search engine
5. PRE-OPERATION CHECKS
Check the generator on a firm, level surface with the engine stopped.
Be sure to block the wheel with the two wheel stoppers provided.
To open
1. Remove the flange bolt from the bottom of the maintenance lid.
2. Align the maintenance lid knob OPEN and pull up the lid.
3. Pull the stopper from the holder and set the stopper to the hook to
hold the lid.
To close
1. Lift the maintenance lid slightly to unhook the stopper.
2. Set the stopper in the holder on the maintenance lid and gently
lower the lid.
3. Align the maintenance lid knob with CLOSE and fix the lid.
Keep the maintenance lid closed while operating the generator, or the
cooling efficiency is reduced, resulting in a damaged generator.
MAINTENANCE LID
FLANGE BOLT
OPEN
CLOSE
KNOB
OPEN
CLOSE
STOPPER
HOOK
HOLDER
19
Downloaded from www.Manualslib.com manuals search engine
Engine Oil
UPPER
LEVEL
LOWER
LEVEL
Ambient temperature
DIP STICK
20
Downloaded from www.Manualslib.com manuals search engine
Fuel
The fuel meter will stop indicating if you leave the engine switch to ON
for more than 15 seconds. Turn the engine switch to OFF once and
then turn the switch to ON and check the fuel meter.
Refill the fuel tank to the upper level if necessary. Do not fill the fuel
tank above the upper level mark.
EMPTY FULL
FUEL METER
21
Downloaded from www.Manualslib.com manuals search engine
According to season and ambient temperature, a different grade of
diesel fuel should be used. The fuel might freeze and prevent the
engine from starting if summer fuel is used in winter. If winter fuel is
used in summer, it could result in a lack of power. Be sure to use the
proper grade of diesel fuel which complies with the ambient
temperature.
Refill the fuel frequently, especially in winter. Water could
accumulate if there is much air in the fuel tank. We recommend that
you refill after each use of the generator.
Air bleeding (Restart of the engine after the fuel has run out)
Light blue exhaust gas is seen while bleeding air. Keep the engine
running, and the exhaust smoke color leans and the engine speed
stabilizes after the air bleeding.
22
Downloaded from www.Manualslib.com manuals search engine
Coolant
RESERVE TANK
MAX (UPPER LEVEL)
Never remove the radiator cap when the engine is hot. The coolant
is under pressure and severe scalding could result.
Wait until the engine is cool, then turn the radiator cap
counterclockwise until stops. DO NOT PRESS DOWN WHILE
TURNING THE CAP. After any remaining pressure has been relieved,
remove the cap by pressing down and again turning it
counterclockwise. Add enough coolant to fill the radiator, and
reinstall the cap. Be sure to tighten it securely. Fill the reserve tank
up to the MAX mark with the engine cold.
23
Downloaded from www.Manualslib.com manuals search engine
Coolant Recommendation
The use of unsuitable antifreeze, hard water, or salt water may cause
corrosion damage that will shorten the life of the engine.
Fuel Filter
FUEL STRAINER
STRAINER ELEMENT
24
Downloaded from www.Manualslib.com manuals search engine
Battery
The electrolyte level must be kept between the UPPER and LOWER
level marks. If the electrolyte level is near the LOWER mark, remove
the battery filler caps and carefully add distilled water to the upper
level line (see page 44 ).
UPPER LEVEL
LOWER LEVEL
25
Downloaded from www.Manualslib.com manuals search engine
Warning Lamps
Turn the engine switch to ON position and check to see whether the
warning lamps come on.
If the warning lamp(s) does not come on, consult an authorized Honda
dealer.
WARNING LAMPS
ON
ON
ENGINE SWITCH
26
Downloaded from www.Manualslib.com manuals search engine
6. STARTING AND STOPPING THE ENGINE
Break-in (initial 50 hours)
An initial break-in period will result in longer engine life. Do not run at
high speed during break-in.
Before starting the engine disconnect any load from the AC receptacle.
1. Open the maintenance lid (see page 19 ) and turn the fuel vale to ON.
FUEL VALVE
ON
AC CIRCUIT PROTECTOR
OFF
AC CIRCUIT
BREAKER
OFF
OFF
OFF
B type
F, G and GW types
27
Downloaded from www.Manualslib.com manuals search engine
4. Turn the automatic throttle switch ON (Equipped type only).
ON
ON
5. Insert the engine switch key and turn the engine switch to ON
position and wait until the charge warning lamp goes off (for about
4 seconds).
6. Turn the engine switch to the START position and hold it there until
the engine starts.
Do not use the starter motor for more than 5 seconds. If the engine
fails to start, release the key, and wait at least 10 seconds before
operating the starter motor again.
ON START
ON START
ENGINE SWITCH
28
Downloaded from www.Manualslib.com manuals search engine
7. After the engine starts, let the engine switch return to the ON
position.
8. The pilot lamp comes on after the engine starts (Equipped type only).
Warm up the engine for 2 or 3 minutes.
When the duty is small (loading power less than 350 W), the automatic
throttle control system might not work. Even above 350 W, it might not
function properly, due to the switch components. In these case set the
automatic throttle switch to OFF.
29
Downloaded from www.Manualslib.com manuals search engine
Stopping the engine
In an emergency:
OFF
In normal use:
AC CIRCUIT PROTECTOR
OFF
OFF
OFF
AC CIRCUIT OFF
PROTECTOR
B type
F, G and GW types
30
Downloaded from www.Manualslib.com manuals search engine
3. Turn off the engine switch.
OFF
ENGINE SWITCH
OFF
4. Open the maintenance lid and turn the fuel valve to OFF.
FUEL VALVE
OFF
31
Downloaded from www.Manualslib.com manuals search engine
7. GENERATOR USE
GROUND
TERMINAL
32
Downloaded from www.Manualslib.com manuals search engine
Limit operation requiring maximum power (see page 50 ) to 30
minutes.
For continuous operation, do not exceed the rated power (see page
50 ).
In either case, the total wattage of all appliances connected must be
considered.
Most appliance motors require more than their rated wattage for
startup.
Do not exceed the current limit specified for any one receptacle.
Do not connect the generator to a household circuit. This could
cause damage to the generator or to electrical appliances in the
house.
When an extension cable is required, be sure to use a tough rubber
sheathed flexible cable (IEC 245 or equivalent).
Limit length of extension cables; 60 m for cables of 1.5 mm and 100
m for cables of 2.5 mm . Long extension cables will lower usable
power due to resistance in the extension cable.
Keep the generator away from other electric cables or wires such as
commercial power supply lines.
33
Downloaded from www.Manualslib.com manuals search engine
AC Applications
Make sure all appliances are in good working order before connecting
them to the generator. If an appliance begins to operate abnormally,
becomes sluggish, or stops suddenly, turn it off immediately.
Disconnect the appliance, and determine whether the problem is due
to an appliance problem, or generator overloading.
Most appliance and power tool motors require more than the rated
operating current for start-up. To match appliance power needs to
generator capability, allow enough generator power reserve to
accommodate motor start-up requirements.
An overload will trip (switch off) the circuit breaker. If this happens,
reduce the electrical load on the circuit. Wait a few minutes before
resetting the circuit breaker.
Operation:
1. Start the engine. Makes sure the pilot lamp comes on (Equipped
type only).
2. Make sure that the voltmeter indicates the specified voltage. If not
adjust with the voltage adjustment knob (Equipped type only).
Although voltage adjustment is usually not required, fine
adjustments may be made by turning the voltage adjustment knob.
Use the generator at the specified voltage.
34
Downloaded from www.Manualslib.com manuals search engine
3. Switch on the AC circuit protector.
CIRCUIT PROTECTOR
ON
ON
F, G and GW types
CIRCUIT PROTECTOR
ON
ON
B type
35
Downloaded from www.Manualslib.com manuals search engine
How to use the receptacle
When two or more receptacle are used, refer to the table below and
apply the load to each receptacle equally to prevent overloading.
With this receptacle, the automatic throttle does not function (See page 8).
THREE PHASE
36
Downloaded from www.Manualslib.com manuals search engine
EX10D
Receptacle 230 V 115 V
Case 32 A 16 A 32 A 16 A × 2
Using 230 V 7.4 kVA Max. 3.7 kVA Max.
Total 10 kVA
Using 115 V 3.7 kVA 1.8 kVA
Max. MAX.
at one
Total 7.4 kVA
Using both 230 V Total 2.5 kVA Total 7.4 kVA
and 115 V Total 5.0 kVA Total 5.0 kVA
Total 7.5 kVA Total 2.5 kVA
When both 230 V and 115 V receptacles are used, be sure to use with
the voltampere at each receptacle less than the specified capacity and
total voltampere less than 10 kVA.
115 V 16 A 230 V 16 A
115 V 32 A 230 V 32 A
EX10D
37
Downloaded from www.Manualslib.com manuals search engine
8. MAINTENANCE
Use only genuine Honda parts or their equivalent for maintenance and
repair. Parts of lower quality may damage the engine.
38
Downloaded from www.Manualslib.com manuals search engine
Maintenance Schedule
REGULAR SERVICE PERIOD EACH FIRST EVERY EVERY EVERY EVERY EVERY
USE 50 200 400 600 1000 4000
ITEM HRS(3) HRS(3) HRS(3) HRS(3) HRS(3) HRS(3)
Engine oil Check level
Change
Battery Check
electrolyte
Radiator Check
coolant Change Every 2 years
Fuel filter Check
Diesel fuel Check
Warning Check
lamp
Fan belt Check (2) (2)
Air cleaner Check (1)
element (Wet) Change (1)
Oil filter Change (2)
Fuel filter Change (2)
element
Carbon Check (2)
brush
Injection Check (2)
nozzle
Valve Check-adjust (2)
clearance
Timing belt Change (2)
Fuel line Check
(Replace if Every 2 years (2)
necessary)
39
Downloaded from www.Manualslib.com manuals search engine
Engine oil change
Drain the oil while the engine is still warm to assure rapid and
complete draining.
DRAIN PLUG
Wash your hands with soap and water after handling used oil.
40
Downloaded from www.Manualslib.com manuals search engine
Air cleaner service
If you operate the generator in very dusty areas, check and replace the
air cleaner more often than specified in the MAINTENANCE
SCHEDULE.
Operating the engine without the air cleaner will cause rapid engine
wear.
2. Unhook the clips and remove the air cleaner cover and inner cover.
AIR CLEANER COVER
INNER COVER
3. Remove the wing bolt and air cleaner element and check the
element. Replace the element with a new one if damaged.
WING BOLT
41
Downloaded from www.Manualslib.com manuals search engine
4. Install the element, inner cover and air cleaner cover in the reverse
order of removal.
Install the cover with the UP mark facing up and align the tabs of the
inner cover and air cleaner cover with cutout of the air cleaner case.
UP MARK
TABS
CUTOUT
ELEMENT
INNER COVER
AIR CLEANER CASE
CLIP
42
Downloaded from www.Manualslib.com manuals search engine
Fuel filter service
3. Loosen the ring nut and then remove the strainer cup, spring and
element.
Make sure that the O-ring is in good condition and set on the cup
properly.
STRAINER CUP
O-RING
ELEMENT
SPRING
RING NUT
43
Downloaded from www.Manualslib.com manuals search engine
Battery service
○
−
UPPER LEVEL ○
+
LOWER LEVEL
44
Downloaded from www.Manualslib.com manuals search engine
Battery cleaning
If the battery terminals are contaminated or corroded, remove the
battery and clean the terminals.
1. Remove battery set plate.
2. Disconnect the battery cable at the battery negative (−) terminal,
then at the battery positive (+) terminal.
BATTERY
3. Remove the battery and clean the battery terminals and battery
cable terminals with a wire brush or sand paper.
Clean the battery with a solution of baking soda and warm water,
taking care not to get the solution or water in the battery cells. Dry
the battery thoroughly.
4. Connect the battery positive (+) cable to the battery positive (+)
terminal, then the battery negative (−) cable to the battery negative
(−) terminal. Tighten the bolts and nuts securely.
5. Coat the battery terminals with grease.
6. Reinstall the battery set plate.
45
Downloaded from www.Manualslib.com manuals search engine
Fuse replacement
Turn the engine switch OFF and remove the key before checking or
replacing fuses to prevent accidental short-circuiting.
To replace the sub fuse pull the old fuse out of the clips with your
finger. Push a new fuse into the clips.
If the main fuse is blown out, see your authorized Honda dealer.
MAIN FUSE SUB FUSE
5A
50 A
70 A
10 A
If frequent fuse failure occurs, determine the cause and correct the
problem before attempting to operate the generator further.
Never use a fuse with a different rating from that specified. Serious
damage to the electrical system or fire may result.
46
Downloaded from www.Manualslib.com manuals search engine
9. TRANSPORTING/STORAGE
The engine becomes very hot during operation and remains hot for a
while after stopping. Allow the engine to cool before transporting or
storing indoors.
Transporting
When transporting the generator, turn the engine switch OFF and
keep the generator level to prevent fuel spillage. Fuel vapor or
spilled fuel may ignite.
Contact with a hot engine or exhaust system can cause serious
burns or fires. Let the engine cool before transporting or shorting
indoors.
LIFTING EYE
CARRYING HANDLE
FRAME PIPE
47
Downloaded from www.Manualslib.com manuals search engine
Storage
3. Replace the engine oil with fresh oil before operating the generator
after storage.
Refer to page 40 for engine oil replacement.
5. Disconnect the battery ground cable from the terminal and tape it.
While storing the battery, fully charge the battery once a month.
6. Cover the generator and place it in a well ventilated and dry area. If
the generator is still hot, wait until it cools down cover.
Remove the radiator cap and check the coolant level before operating
the generator after storage. If the coolant level is low see your
authorized Honda dealer.
48
Downloaded from www.Manualslib.com manuals search engine
10. TROUBLESHOOTING
49
Downloaded from www.Manualslib.com manuals search engine
11. SPECIFICATIONS
Engine
Model GD1100
Type 4-stroke, overhead valve, 3 cylinder diesel
Displacement 1,061 cm (64.7 cu-in)
Bore × Stroke 76 × 78 mm (3.0 × 3.1 in)
Rated output 20 PS/3,000 min (rpm)
Max. torque 55.9 N·m (5.7 kgf·m, 41.2 lbf·ft)
Cooling system Liquid cooled
Fuel Diesel fuel
Fuel tank capacity 38 (10.0 US gal , 8.4 Imp gal)
Oil capacity 4.7 (5.0 US qt , 4.1 Imp qt)
Generator
Model EXT12D EX10D
Type F, G, GW B
AC Rated Three- 12 kVA
output Output phase
Single- 3.2 kVA × 3 10 kVA
phase
Rated frequency 50 Hz 50 Hz
Rated Three- 400 V
voltage phase
Single- 230 V 115/230 V
phase
Rated Three- 17.3 A
Current phase
Single- 13.9 A × 3 43.5 A
phase
50
Downloaded from www.Manualslib.com manuals search engine
Noise
Model EXT12D EX10D
Type F, G, GW B
Sound pressure level (LpA) 79 dB
According to 98/37/EC
Microphone point
CONTROL
PANEL
Center
1.60 m
1.0 m
51
Downloaded from www.Manualslib.com manuals search engine
12. REMOTE CONTROL KIT
1. Remove the cap from the 7 pin connector on the generator cover,
and connect the 7 pin connector of the remote control switch box
cable there.
7 PIN CONNECTOR
CAP
GENERATOR SIDE
Be sure to install the cap on the connector when the remote control
kit is not used.
2. Connect the remote control cable to the remote control switch box 7
pin connector.
7 PIN CONNECTOR
Do not pull on the remote control cable with excessive force when
disconnecting it from the connector.
Do not leave tools, parts or other objects on the remote control
cable or move things over it.
Do not direct jet or water to the remote control switch box.
52
Downloaded from www.Manualslib.com manuals search engine
Starting the engine
Before starting the engine disconnect any load from the AC receptacle.
1. Be sure that the fuel valve lever is at the ON auto throttle switch
(equipped type only) is at the ON, and the generator engine switch is
at the OFF position respectively.
2. Turn off the AC circuit protector.
AC CIRCUIT PROTECTOR
OFF
OFF
OFF
AC CIRCUIT OFF
PROTECTOR
F, G and GW types B type
OFF
53
Downloaded from www.Manualslib.com manuals search engine
3. Turn the remote control switch on the generator cover to ON.
ON
ON
Be sure to turn the remote control switch to OFF when the starting
motor is operated by the engine switch on the generator control
panel with the remote control kit installed.
54
Downloaded from www.Manualslib.com manuals search engine
4. Turn the engine switch on the remote control switch box to ON.
5. Turn the engine switch to ON position and wait until the glow lamp
of starter button (with glow lamp) goes off (for about 4 seconds).
ON
ENGINE SWITCH
6. Push the start button and hold until the engine starts.
7. The pilot lamp comes on after the engine starts.
START
STARTER BUTTON
Do not use the starter motor for more than 5 seconds. If the engine
fails to start, release the starter button, and wait at least 10 seconds
before operating the starter motor again.
Generator use
55
Downloaded from www.Manualslib.com manuals search engine
Starter button (with glow lamp)
When a problem with the generator occurs or the generator is
overloaded, the warning lamp of the generator lights and the engine
stops. The glow lamp of starter button on the remote control box light,
too, simultaneously.
Stop the engine immediately and disconnect the appliance, and
determine whether the problem is due to an generator problem, or
generator overloading.
If the warning lamp lights and engine stops:
STARTER BUTTON
PILOT LAMP
In normal use.
1. Turn off the electrical appliance’s switch.
2. Turn off the AC circuit protector.
3. Turn off the engine switch.
ENGINE SWITCH
OFF
4. Open the maintenance lid and turn the fuel valve to OFF.
56
Downloaded from www.Manualslib.com manuals search engine
13. WIRING DIAGRAM
ACOR AC Output Receptacle Bl BLACK
AC, G AC Generator Y YELLOW
ATU Auto Throttle Unit Bu BLUE
ATSw Auto Throttle Switch G GREEN
AVR Automatic Voltage R RED
Regurator W WHITE
ATM Automatic Throttle Br BROWN
Motor O ORANGE
BAT Battery Lb LIGHT BLUE
CB Circuit Protector Lg LIGHT GREEN
CBxB Control Box block P PINK
CT Current Trans Gr GRAY
CBSw Combination Switch
D Diode
EgB Engine Block
ExW Exciter Winding
EgCU Engine Control Unit
FrB Frame Block
Fu Fuse
Fuu Fuel Unit
FuM Fuel Meter
FW Field Winding
GeB Generator Block
GT Ground Terminal
GP Glow Plug
GL Glow Lamp
HM Hour Meter
In Indicator
MSw Main Switch
OPSw Oil Pressure Switch
RcB Remote Control Block
RT Rectifier
RY Relay
RCC Remote Control Cable
RCK Remote Control Kit
SM Starter Motor
STs Stop Solenoid
SeSw Select Switch
TS Thermo Switch
VR Variable Resister
57
Downloaded from www.Manualslib.com manuals search engine
EXT12D (F, G and GW Types)
58
Downloaded from www.Manualslib.com manuals search engine
EX10D (B Type)
59
Downloaded from www.Manualslib.com manuals search engine
RECEPTACLE
Shape Type
F, G, GW
60
Downloaded from www.Manualslib.com manuals search engine
14. MAJOR Honda DISTRIBUTOR ADDRESSES IN EUROPE
61
Downloaded from www.Manualslib.com manuals search engine
NAME OF FIRM (COMPANY) ADDRESS TEL: FAX:
OY Brandt AB Tuupakantie 4 Tel: 90-895-501
SF-01740, Vantaa Fax: 90-878-5276
Finland
TIMA PRODUCTS A/S Tårnfalkevej 16, Postboks 511 Tel: 31-49-17-00
DK 2650 Hvidovre Fax: 36-77-16-30
Denmark
Greens Polig. Industrial Congost Tel: 93-871-84-50
08530, La Garriga Fax: 93-871-81-80
(Barcelona), Spain
Automocion Canarias S.A. Apartado de Correos, num 206 Tel: 922-61-13-50
(AUCASA) Santa Cruz de Tenerife Fax: 922-61-13-44
Canary Island
The Associated Motors Company Ltd. 148, Rue D’Argens, Msida Tel: 356-333001
Malta Fax: 356-340473
Two Wheels Ltd. Crosslands Business Park, Tel: 4602111
Ballymount Road, Dublin 12, Fax: 4566539
Ireland
General Automotive Co., S.A. P.O. Box 1200, 101 73 Athens Tel: 346-5321
Greece Fax: 346-7329
BG Technik s.r.o Radlická 117/520 Tel: 2-5694 573
158 01 Praha 5 Fax: 2-5694 571
Czech Republic
Aries Power Equipment Ltd. 01-493 Warszawa, ul Wroclawska Tel: 22-685 17 06
25a Fax: 22-685 16 03
Poland
MO. TOR. PEDO Ltd. 2040 Buda-rs, Kamaraerdei-t 3. Tel: 23-444-971
Hungary Fax: 23-444-972
62
Downloaded from www.Manualslib.com manuals search engine
GENERATOR
EXT12D/EX10D
OWNER'S MANUAL
MANUEL DE L'UTILISATEUR
oHonda Motor Co., Ltd. 2002 BEDIENUNGSANLEITUNG
efgsY1100.2006.04
6-6160 Printed in Japan MANUAL DE EXPLICACIONES