Beruflich Dokumente
Kultur Dokumente
INSTRUCTIONS
For Operation and Adjustment
ITABLE OF CONTENTS I
Section
Number Page Number Section
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SWITCHING WITH UNI-RUPTER’”
OPERATING DESCRIPTION Installing and Closing the Fuse . . . . . . . . . . . . . . . . . . 1 9
Normal Condltions . . . . . . . . . . . . . . . . . . . . . . . . .3 A Note on Slngle-Pole Switching . . . . . . . . . . . . . . . .21
Transfer on Loss of Source Voltage . . . . . . . . . . . . . . . .3 Openmg and Removlng the Fuse . . . . . . . . . . . . . . . . .22
Ketransfer on Return of Source Voltage . . . . . . . . . . . . . .4 RE-FUSING
Transfer on Open-Phase Condltion . . . . . . . . . . . . . . . . .4 How to Detect and Replace a Blown Fuse . . . . . . . . . . . . 2 4
Overcurrent-LockoutCondition . . . . . . . . . . . . . . . . . .4 Installing the Fuse in the Mountlng. . . . . . . . . . . . . . . . 2 5
Kemot,eIndication . . . . . . . . . . . . . . . . . . . . . . . . . . .5 FINAL CHECKS BEFORE WALKING AWAY . . . . . . . . . . . . 2 6
COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 IN CASE OF DIFFIClJLTY . . . . . . . . . . . . . . . . . . . . . . .27
AEAJIJSTMENTS ANI) PROGRAMMING I F OPERATOR STALLS . . . . . . . . . . . . . . . . . . . . . . . .28
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ,10 MAINTENANCE
Preferred-Source Selection . . . . . . . . . . . . . . . . . . . . . 10 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Voltage-Sensor Slgnal AdJustments . . . . . . . . . . . . . . . . 1 0 Refinishing
Recommendations
Enclosure . . . . . . . . . . . .30
Tlmer Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . .10 APPENDIX A
on Operating-Mode . . . . . . . . . . . . . . . . . . . . . 11 E’relimmaryTryoutBeforeGear Is Energized-Optional.31. .
0I’E:KATIONAL TESTING APPENDIX B
Loss-of-Sourcc Testing . . . . . . . . . . . .Testlng.......... .12 Dielectric .......................... ,31
Overcurrent-1,ockoutTestlng . . . . . . . . . . . . . . . . . . .13 AI’PENUIX C
MINI-RUF’TER@ SWITCHES Ratmgs for S&C Mini-Rupter Switches . . . . . . . . . . . . . . 3 2
Decouplmg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Ratlngs for S&C Fuses wlth Unl-Kupter . . . . . . . . . . . . .33
Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 APPESDIX D
AutomaticSwitchOperatLon . . . . . . . . . . . . . . . . . . .14 Specifcations for
Nonautomatkc Swtch Operation . . . . . . . . . . . . . . . . .15 S&C Type AT-12 Source-Transfer Control . . . . . . . . . .34
Charging Operator (Nonelectrical) . . . . . . . . . . . . . . . . 1 5 Specifications for S&C Voltage Sensors . . . . . . . . . . . . .35
Front ............................ APPENDIX E
RJSING OptionalFeatures ......................... .36
Assembling the Fuse . . . . . . . . . . . . . . . . . . . . . . . . .18 APPENDIX F
Installing the Fuse m the Mounting . . . . . . . . . . . . . . . . 1 8 Current-Limiting Fuses for lJse in
Warranty Qualifications . . . . . . . . . . . . . . . . . . . . .18 S&C Pati-MountedGear .................... .39
1 INTRODUCTION
This equipment has been provided with comprehen- 6. Use suitable protective equipment suchas rubber
sive access control and operating features to minimizegloves, rubber mats, hard hats, safety glasses, and
hazards. However, since this equipment contains high flashclothing in accordancewithstandard
voltage, there are hazards inherently present such system-operatingprocedures,especiallywhen
that thefollowing precautions should be observedat handling fuses and barriers within high-voltage
all times. Failure to observe these precautions may compartments.
result in serious injury or death. 7. Make certain that the pad-mounted gear enclo-
1. Compartment doors must be securely closed and sure is properly grounded.
latched, with a padlock for each Penta-Latch@ 8. Make certainfusesaredisconnectedfrom all
Mechanism in place at all times unless work is power sources (including backfeed) before being
being performed inside the enclosure. inspected or replaced.
2. Optional key interlocks (if furnished) must be in 9. Alwaysconfirmopeniclosepositions ofMini-
place.Checktheoperatingsequence of key Rupter Switches by visually observing positions
interlocks to verify proper sequencing. After the of switch blades.
pad-mounted gear is installed, destroy all dupli-
cate keys ormakethemaccessibleonlyto 10. Test forvoltageusing proper high-voltage test
authorizedpersons so thatthe key-interlock equipment before touching any device that is to
scheme will not be compromised. Key interlocks be inspected, serviced, or repaired.
are not security locks and are not substitutes for 11. Installsuitablegroundingequipmentbefore
padlocks. touchingany device that is to beinspected,
3. Optionalmechanicalcableinterlocks (if fur- serviced, or repaired.
nished)preventoperation of switchwhen 12. Always assume that both terminals of any switch
associatedswitch-compartmentdoor is open. or fuse are energized unless proved otherwiseby
Periodically,verify thattheseinterlocksare test, by visual evidence of open circuit conditions
functional. onbothterminals,or by observing thatboth
4. Do not apply any undue force when attempting terminals are grounded.
to open a door.Theuse of undueforcemay These recommendations may differ from the user’s
damage the latching mechanism, or an interlock operatingandsafetyprocedures.Wheresuch
mechanism may be jammed. discrepancy exists, users should follow their oper-
5. Do not remove or obscure anyof the “CAUTION,” ating procedures.
“DANGER,” orotherprecautionarysignsand
labels.
663m502INSTRUCTIONSHEET
Page 4 of 39 ELECTRIC
S&C COMPANY Chicago
July 9, 1990 ELECTRIC
S&C CANADA LTD. Toronto
OPERATING DESCRIPTION - Continued
1
An overcurrent in excess of 480 amperes. detected If the overcurrent is due to a fault that is cleared
by a current sensorin any phaseof the preferred source by feeder fuses, no switching will occur since loss of
will “set up” the lockout circuit in the AT-12 control. source voltage is not of sufficient duration to initiate
The overcurrent-lockout indicating lampwill light. opening of the sourceMini-Rupter serving the load. In
If the overcurrent is due to a fault that is cleared this case, although the fault current initially sets up
by the source-side protective device, the prolonged loss thelockoutcircuitandtheovercurrent-lockout
of source voltage will cause the preferred-sourceMini- indicating lamp lights, the subsequent return of normal
Rupter to open, and the lockout circuit will prevent source voltage actuates the overcurrent-lockout-reset
the alternate-source Mini-Rupter fromclosing into the timer. After a preset period of time, the lockout circuit
fault. (Conversely, if the load is being served from the will automatically reset, theAT-12 control will restore
alternate source, theprolonged loss of source voltage to its previous “normal” state, and the lockout indicating
will cause the alternate-source switch to open, and the lamp will extinguish.
lockout circuitwill prevent the preferred-source switch
from closing intothefaultwhenpreferred-source Remote Indication
voltage becomes available.) After the fault has been Inclusion of the optional remote indication feature is
located and repaired, the manual/automatic operation signified bythe additionof the suffix “-Y4” to the catalog
selector switch on the AT-12 control must be placed number. This option includes isolated contacts wired,
in the “MANUAL”position, and the overcurrent-lockout through an output receptacle and plug, to a terminal
resetpushbuttonpressedtocancelthelockout blockforuser’sexternalconnectiontoremote
condition-and to extinguish the overcurrent-lockout indicating devices. Isolated contacts are provided for
indicatinglamp.Then,service totheloadcanbe remotely monitoring the presence of preferred- and
restored by means of t h ea p p r o p r i a t e “CLOSE” alternate-source voltage; the position of the manual/
pushbutton. After the switch has closed, the manual/ automatic operation selector switch; the status of the
automatic operation selector switchis to be turned to automatic-transfer “ready” indicatinglamp;and, if
the “AUTOMATIC”position. The“READY”lamp will light applicable, the statusof the overcurrent-lockout circuit.
if the preferred-source Mini-Rupter is closed and the Remote indicating devices and their control power are
.
alternate-source Mini-Rupter is open. to be provided by the user.
Figures 1 through 4 which follow illustrate many of the remainder of the instructions, it is recommended
the basic components and features of S&C Power- that these figures be reviewed to gain familiarity with
Operated Pad-Mounted Gear. Before proceeding with the various components and locations.
A Remote-control receptacle
(Catalog Number Suffix “-Cll”)
\
Dual-purpose
manual handle
I
II
I vpJrmrr.mvm,
selector
Terminal-block Decoupler
compartment
Bolted cover provides access to
the AT-12 control’s programming panel
Timer-adjustment dials
Remote-Indication Receptacle
(not visible) provided with
Voltage-sensor signal adjust- optional remote-indication fea-
ments and measurements for atalog Number Suffix
preferred and alternate
sources
Voltage-sensor signal-
adjustment screws and test
jacks
Operating-mode selector
switches for return transfer
Preferred-source and
Selector switch included with alternate-source connector
the optional open-phase plugs-interchangeable, to
detection feature (Catalog allow selection of either source
Number Suffix “-Yl” or “-Y3”) as preferred
Shorting receptacle
Input plug (signal-voltage,
control-voltage, and current-
sensing input circuits)
Figure 3. Source-transfer control programming panel witn Doltea cover removea, snowmg aafusrmenr, measuremenr, resung,
and programming features of the control.
/
Current sensors furnished for
attachment to each entrance cable
when optional overcurrent-lockout feature
(Catalog Number Suffix “-Y2” or “-Y3”)
is included
INSTRUCTIONSHEET 6631502
ELECTRIC
S&C COMPANY Chicago Page 13 of 39
ELECTRIC
S&C LTD.CANADA Toronto July 9, 1990
I
S&C Pad-Mounted Gear For Automatic Source Transfer
Power-Operated PMH Models Models with “ R 4 ’ Supplement to the Catalog Number
Outdoor Distribution (14.4 kv and 25 kv)
I MINI-RUPTER SWITCHES I
To prevent an automatic operation when decoupling indicates the open or closedposition of the Mini-
or coupling an operator to a switch, during manual Rupter Switch.Uponcompletion of an opening or
charging of an operator, or when manually operating closing operation, check to be sure that the following
a switch,placethemanual/automaticoperation conditions exist:
selector switch, located on the faceplate of the AT-12 The operator target (see Figure 1)signals “OPERA-
control, in the “MANUAL” position. TOR IN SWITCH-OPEN POSITION or “OPERATOR
Do notperformanyswitchingoperations if the IN SWITCH-CLOSED POSITION” to indicate that the
source-transfercontrol is in the lockoutmode as switchoperatorhas moved through a complete
indicated by illumination of the overcurrent-lockout operation.
indicatinglamp. See Figure 2. Forsuchcases,see Theswitch-positiontarget(see Figure 1) which
section on overcurrent lockout on page4. signals “SWITCH OPEN or “SWITCHCLOSED,”is
If the gear is energized, to avoid tempom? service in agreement with the operator target.
interruptions when manually operating the switch, Theswitchposition, as verified by visualcheck
decouple both stored-energy operators (see section on of the switch-blade position, is in agreement with
“Decoupling” below). Switching operations will result the switch-position target.
in temporary service interruptions if stored-aergy
The operator target (see Figure 1)signals “OPERA-
operators w e coupled.
TORCHARGED” to indicate that the operator is
Due to operating errors, the stored-energy operator’s ready for the next operation.
quick-makequick-breakmechanism will stall in a
partially discharged state. The conditions which will To prevent all electrical and mechanical operations,
cause the quick-make quick-break mechanism to stall, padlock the operation selectorin the “L0CK”position.
as well as instructions for restoring the operator to This will also prevent motor charging of the stored-
the normal latched-open condition after a stall, are energy operator if system operating procedures
listed under “IF OPERATOR STALLS . . . on page 28.
”
require that the quick-make quick-break mechanism
remain discharged-and source voltage is present.
Do not assume that the operator position necessarily
663402 INSTRUCTIONSHEET
Page 14 of 39 S&C ELECTRIC COMPANY Chicago
July 9, 1990 S&C ELECTRICCANADA LTD. Toronto
1 MINI-RUPTER SWITCHES - Continued I
operation, the manual/automatic operation selector If Control Po wer Is Lost and Operator Is Discharged:
switch on the AT-12 control must be in the “AUTO- Manually charge the stored-energy operator’s quick-
MATIC” position. See Figure 2. The AT-12 control will make quick-break mechanism as described under
not function automatically if one operator is coupled “Charging Operator (Nonelectrical)” below. Then
and the other is decoupled. Complete adjustment and proceed as just described under “If Control Power Is
programming of the AT-12 control for automatic switch Lost and Operator Is Charged.”
operation is covered beginning on page 10.
Charging Operator (Nonelectrical)
Nonautomatic Switch Operation For manually charging the stored-energy operator’s
If Control Power Is Available: To manually operate quick-make quick-break mechanism (required only in
the stored-energy operator’s quick-make quick-break the event that control power has been lost), a dual-
mechanism-and (if coupled) to open or close a Mini- purpose manual handle is provided. See Figure 7. Keep
Rupter Switch-place the manual/automatic operation the charging-shaft access port open by holding the
selector switch in the “MANUAL” position and depress operation selector in the “CHARGING” position. While
the associated open/close pushbutton. See Figure 1. the operation selector is in the “CHARGING” position,
After each trip operation, the quick-make quick-break the control circuit is disconnected to prevent manual
mechanism automatically charges when voltage is or automatic electrical operation (charging or tripping)
present on the associated source. in the event that control power is restored; and the
If Control Power Is Lost and Operator Is Charged: emergency-trip port is mechanically blocked to prevent
To manually operate the stored-energy operator’s a manual mechanical trip operation.
quick-make quick-break mechanism-and (if coupled) While holding the port open, insert the threaded end
to open or close a Mini-Rupter Switch-insert the keyed of the dual-purpose manual handle and secure it to
end of the dual-purpose manual handle into the groove the end of the charging shaft by turning the knurled
of the tripping shaft behind the cover labeled knob clockwise 14 to 16 turns until firm resistance is
“EMERGENCY TRIP” and turn in the direction indicated felt. To charge the mechanism, grasp the tubular
to effect desired operation. See Figure 6. portion of the handle and, while pivoting the handle
Figure 5. Decoupler being rotated Figure 6. Dual-purpose manual handle Figure 7. Dual-purpose manual handle
counterclockwise to decouple switch inserted in socket of shaft for emer- on the charging shaft.
from associated switch operator. gency manual switching if control
power is lost.
S&C Grappler in
storage position
Door holder -, I
Figure 13. Dual-purpose front barriers for fuses in their nor- Figure 14. Removing or replacing optional dual-purpose
mal, suspended positions. Note that door holder is in place. front barrier with the S&C Grappler.
Figure 15. Grappler, as positioned-for opening or closing stroke, with longer prong inserted in fuse pull ring. (Fuse shown
in closed position.) Inset is closeup of Uni-Rupter with fuse fully closed.
6. With the Grappler prongs pointed downward, insert 7. Use the Grappler to hang the optional dual-purpose
the longest prong into the pull ring of the fuse. See front barrier, if furnished, in its normal, suspended
Figure 15. Then with one’s face turned away, close position. See Figure 14. Also install the optional inner
the fuse with a swift, unhesitating stroke. See Fig- barrier panel, if furnished.
ure 20. 8. Close and latch the door(s) and install a padlock.
Release the Grappler from the pull ring. Use the (On double-door models, the captive screw in the
Grappler to push against the fuse to make sure that left-hand door must be tightened before the right-
complete fuse closure was attained. hand door can be latched.) Pull on the doors to verify
that they are securely latched.
Figure 16. inserting the optional dual-purpose front barrier Figure 17. Grappler positioned for fuse removal or
into the “slide-in” position using the Grappler. installation. (Fuse shown installed in its hinge.)
tgure 18. Removing or installing fuse using Grappler. Figure 19. Removing the optional dual-purpose front barrier
from the “slide-in” position using Grappler.
7. For all fuses except 25.kv Fault F&r Electronic 8. For 25.kv Fault Fiter Electronic Power Fuses, de-
Power Fuses, remove the fuse from its hinge as energize, test, and properly ground the mounting in
follows: accordance with local operating practices, and then
a. Grasp the universal pole with both hands remove the fuse from its mounting by hand using
(approximately 2 feet apart), with one hand at suitable protective equipment.
the opposite end of the pole from the Grappler.
b. Position the Grappler cone in the fuse pull ring 9. If furnished, hang the optional dual-purpose front
and cradle the fuse in the Grappler prongs. See barrier into position using the Grappler (see Figure
Figure 17. 14). Also install the optional inner barrier panel, if
furnished. Then close and latch the door(s), and
c. Stand in a normal, upright position facing the
padlock securely. (On double-door models, the
universal pole. Move the pole forward until
captive screw in the left-hand door must be tightened
resistance between the Grappler and the fuse is
before the right-hand door can be latched.) Pull on
felt (approximately 2 inches). Then remove the the doors to verify that they are securely latched.
fuse from its hinge with a forward and upward
lifting motion. See Figure 18.
Make sure that the fuse is kept away from the contacts fittings, holders, interrupting modules, or current-
of the Uni-Rupter during removal of the fuse from limiting fuses in the enclosure.
its hinge to prevent reestablishment of the circuit.
If optional dual-purpose front barriers are furnished,
it is recommended that the associated barrier be
placed in the “slide-in” position whenever a fuse is
open or is being removed from or installed into its
hinge.
For Current-Limiting Fuses carried the fault current should also be replaced. For
To find the blown fuse(s), remove each fuse in turn instructions on replacing the fuse, refer to the
from its mounting (the target cannot be seen while applicable S&C instruction sheet.
the fuse is in its mounting), following the instructions
found under “Opening and Removing the Fuse” on Installing the Fuse in the Mounting
page 22. Then inspect the fuse. Check for a blown-fuse Follow the instructions found under “Installing and
target. Note: Following a two- or three-phase fault at Closing the Fuse” on page 19.
a three-phase installation, any unblown fuses that
Fluorescent-orange target
Id appears in “BLOWN” indi-
:A cator window when fuse
.=
has operated (visible
through translucent
*a ,
Fault Fiter
SML-20 Power Fuse SML-42 Power Fuse Electronic Power Fuse
Figure 21. Blown-fuse target locations for the fuse types used in PMH Models of S&C Pad-Mounted Gear.
1 Push-to-test the "READY" lamp If It does not hght when pushed, replace the lamp Replace-
ment lamps, S&C Catalog Number 9931-033, are avallable from the nearest S&C Sales Offlce
2 Conflrm that the condltlons requlred to light the "READY" lamp are met These condltlons are
"READY" lamp does not llght llsted above the AT-I2 control,as well as under "FINAL CHECKS BEFORE WALKING
AWAY ." onpage 26
3 If dlfflculty perslsts, contact the nearest S&C Sales Offlce
1 Push-to-test the source-voltage mdlcator lamp If It does not hght when pushed, replace the
lamp Replacement lamps, S&C Catalog Number 9931-033, are avallable from the nearest S&C
Sales Offlce
2 Conftrm that the source IS energlred
3 Measure the voltage-sensor slgnal voltages and reset to 2 5 volts If necessary See "Voltage-
Sensor Slgnal Adjustments'' on page 10
Preferred-source or alternate-source
4 If the optlonal open-phase detection feature IS furnished, place the assocrated selector swltch
voltage lndlcator lamp does not llght
In the "OFF" posltlon The system IS probably unbalanced If the source-voltage indlcatmg lamp
hghts. Phase-to-phase voltage a.t the AT-12 control's programmtng panel should measure 40
to 4 7 volts If it does not, conflrm system phase-to-ground and phase-to-phase voltages at
another locatron on the system A voltage unbalance of 25% (30 volts on a 120-volt system) or
more, IS consldered loss of voltage by the AT-12 control See "Transfer on Open-Phase Condl-
tlon" on page 4
5 If dlfflculty perslsts, contact the nearest S&C Sales Offlce
1 Conflrm that the condltlons reqwredto llght the "READY" lamp are met These condltlons are
llsted above the AT-12 control,as well as under "FINAL CHECKS BEFORE WALKING
AWAY on page26
I'
Gear does not transfer on loss of 2 Conflrrn that the alternate-source voltage was good at the t m e of occurrence (greater than
preferred-source voltage 105 volts on a 120-volt basts or 2 19 volts on a 2 5-volt bass, and balanced wlthln25% )
3 Place the manual/automatlc selector swltch In the "MANUAL" posltlon, and check operatlon of
the preferred-source Mml-Rupter Swltch usmg the openklose pushbutttons
4 If dlfflculty perslsts, contact the nearest S&C Sales Offlce
Charglng tlme for stored-energy 1 If the gear IS belng energlzed wlth the S&C Test Accessory, Catalog NumberTA-1316, motor
operator exceeds 25 seconds (Nor- charglng may take twlceas long as normal See S&C lnstructlon Sheet 514-605.
mal charglng tlme IS 15 to 20 2. If the test accessory IS not being used and the difflculty perslsts, contact the nearest S&C
Sales
seconds) Offlce
Mlnl-Rupter Swltch stalls In partially 1 For posslble causes and lnstructlons on restorlng the stored-energy operator to Its normal
closed posltlon, and switch-posltlon condltlon. refer to "IF OPERATOR STALLS . on page 28 "
target appears sllghtly off center 2. If difflculty perslsts, contact the nearest S&C Sales Offlce
Time for operatlon IS greater than 1 If the gear IS belng tested wlth the S&C Test Accessory, Catalog NumberTA-1316, refer to
+20% of settlng on the "62P." "62A," S&C lnstructlon Sheet 514-605.
"2P," or optlonal "62 LR" tlmer-
adlustment dlal 2 If dtfflculty perslsts. contact the nearest SBC Sales Offlce
Normal Stalled
Figure 22. Switch-position indicator target appears slightly Figure 23. Dual-purpose manual handle positioned for
off-center if mechanism is stalled. reverse-driving the Mini-Rupter Switch and the operator’s
quick-make quick-break mechanism to recover from a stalled
condition.
* These recommrndatmns may dffer from the user's operating and safety procedures. Where a dlscrepancy exlsts, users should follow their procedures
INSTRUCTIONSHEET 6631502
S&C ELECTRIC COMPANY Chicago Page 29 of 39
S&C ELECTRIC CANADA LTD.
July Toronto 9, 1990
I
S&C Pad-Mounted Gear For Automatic SourceTransfer
Power-OperatedPMHModels Models with “ R 4 ’ Supplement to the Catalog Number
Outdoor Distribution (14.4 kv and 25 kv)
I MAINTENANCE - Continued I
When returningtheequipmenttoservice,the the enclosurelies with both the manufacturer and the
following procedures should be observed: user. S&C Pad-MountedGear is finishedwith S&C
1. Make sure that any grounding means is removed OutdoorFinish,thequalityfinishingsystemthat
before closing the associated Mini-Rupter Switch or provides lasting protection for the enclosure. To retain
power fuses. this protection, the user should take periodic corrective
action as follows:
2. Close each door permitting access to high voltage
andmakesurethattheassociatedPenta-Latch 1. Touch upanypenetration of the finish tobare
Mechanisms are securely latched before energizing metal-such as scratchesandabrasionsdueto
the circuit or operating any switching device. shippingor vandalism-to maintainthe original
integrity. S&C touch-up finish andprimerare
3. Make certain that the input plug is in the input
available in aerosol spray cans-order by Catalog
receptacle.
Number: 9999-058 for olive green finish, 9999-080
4. Make certain that the Mini-Rupter Switches are in forlight grayfinish,and 9999-061forred-oxide
the correct positions (open or closed) as dictated primer. No other finish or primer is approved. The
by system circumstances. area tobe touched up should be cleaned toremove
5.Referto “FINAL CHECKS BEFORE WALKING all oil and grease. Sand the area,
removing any traces
AWAY . . .” on page 26. of rust thatmay be present, and make sure all edges
6. Close both low-voltage compartmentdoorsand are featheredbefore applying primer.
make sure that the associated Penta-Latch Mech- 2. Provide an occasional simple washdown-such as
anism is completely latched. an automobile would be given-to remove surface
7. Padlock all doors beforeleaving the installation site, contaminants. Use anyordinary mild household
even momentarily. Observe this procedure even in detergent solution.
thosecaseswherethegear is accessibleonly to In those cases where the enclosure must be refinished
qualified persons. by theuserbeforethe finish has weathered-for
example,tomatchotherequipment-aspecial
Enclosure Refinishing precaution must be taken. The entire surface mustbe
Recommendations sanded to provide a tooth to bond the new coat to
The responsibility for ensuring that a finish protects the unusually tough and smooth S&C Outdoor Finish.
663-502 INSTRUCTIONSHEET
Page 30 of 39 ELECTRIC
S&C COMPANY Chicago
July 9, 1990 S&C
LTD.
CANADA
ELECTRIC 0 Toronto
IAPPENDIX A I
Is
Preliminary Tryout Before Gear MINGand “OPERATIONALTESTING” onpages10
Energized-Optional through 13 of this instruction sheet can be completed
Ideally, all adjustments and operational testing of the during the preliminary checkout.
S&C Type AT-12 Source-Transfer Control should be When the test accessory is used, the control power
deferreduntilthepad-mountedgear isenergized available to supply the charging motor of the stored-
because some adjustments cannot be made accurately energy operators and to maintain the charge on the
until high voltage is applied to the gear. However, the solenoid-tripping capacitors is less than that available
user may wish to perform a preliminary checkout so during normal three-phase operation. As a result, the
as to expeditefull service oncehigh voltage is available. time required f o r the motorsto charge the stored-energy
For this reason S&C an Test Accessory, Catalog Number operators will be longer than normal. Furthermore,
TA-1316, is available to permit checkoutof the source- it may take as long as two minutes after the stored-
transferoperation of the AT-12 control, using an energy operatorsare charged for the solenoid-tripping
external single-phase 120-volt ac source. capacitors to becomefully charged. Therefore, to ensure
If a preliminary checkout is to be performed, special accuracy when performing operational timing tests,
instructionsmustbefollowedtoensurecorrect wait at leasttwominutesafterthestored-energy
operation of the AT-12 control. These instructions are operators are chargedbeforeinitiating a transfer
set forth in S&C Instruction Sheet 514-605, furnished operation. Voltage-sensor signaladjustments cannot be
with the test accessory. The adjustments and testing finalized until high voltage has been applied to the gear.
describedunder “ADJUSTMENTS AND PROGRAM-
1 APPENDIX B I
Dielectric Testing the wiring diagrams furnished with the gear.
(a> Remove the input plug from the input receptacle
located below t,he AT-12 control’sprogramming
The testproceduresdescribedbelowmustbe panel. See Figures 1 and 3. Transfer the plug to
performed by qualified persons who are thoroughly theshortingreceptacle.Thisprocedureshort-
experienced withthis type of equipment and with the circuits and isolates the secondaries of the voltage
applicable codes and standards. sensorsand alsoisolates thecurrentsensors.
Beforeperformingdielectric tests, makecertain Current sensors (see Figure 4) are furnished when
thathigh-voltagecircuitsarede-energizedand theoptionalovercurrent-lockoutfeatureis
disconnected. Test for voltage, and tag and ground included-as signified by the additionof suffix “-Y2”
all circuits in accordance with establishedsystem- or “-Y3”to the catalog number.
operating safety procedures. In addition, disconnect (b) Performthedielectrictests in accordancewith
all surge arresters. user’s operating and safety procedures. Test values
which apply to S&C Voltage Sensors are shown in
When high-voltage ac dielectric tests are performed “Specifications for S&C Voltage Sensors” on page
on the gear, special precautionary measures must be 35.
taken to prevent damage to S&C the Type AT-12 Source- ( c ) Whendielectrictestinghasbeencompleted,
Transfer Control and to the S&C Voltage Sensors. I t transfer the input plugfrom theshorting raeptacle
is recommended that these precautions also be followed back to the input receptacle.
whenperforminghigh-voltagedcdielectrictests,
althoughtheapplication of rated dc dielectric test IJpon completion of all dielectric testing, remove all
voltages will notdamagethe voltagesensors.The grounds and reconnect allhigh-voltage circuits and
generalprecautionsarestated below. Precautions surge arresters.
specific to the unit involved are contained on one of
81602R2-A 95 50 14
364 17 O + 66 98 83
81603R2-A 25 29 11 8 14 4 16 7 60 70 125
@ For appl~catlonsInvolving othcr he-to-ground voltages, refer to the @ The column headed "Dc" 1s gwen as a reference only for those rnakmg
ncarest SMC Sales Office dc tests and represents values heheved to he approprlate and approx-
Added to
Item Pad-Mounted
Gear
Catalog No.
utdoor Gray
-A2 Light
green ohve of
-A10 finlsh green olwe Wlth
Stainless-Steel Enclosure@
Wlth
llght
gray
outdoor
flnlsh
Instead of green -AI2
I
Interlocks
Key to prevent
openmg
fuse-compartment
door
unless
both
swltches are locked
open
-C5A
Mechanlcal
Cable
Interlocks to prevent
operatlon of swltch
when
assoctated
swltch-compartment
door IS open
-C6A
swltch Swltches,
each
Auxlllary to coupled
4-PST, one 1 -C9A I
y to coupled one 4-PST,
Swltches,
Auxlllary
Remote-Control Receptacle for each stored-energy operator to perrnlt open/close operatlons from an adlacent
IOcatlOn
411
uslng the remote-control statlon (not Included)
Mountmg Provlslons for a fault lndlcator In each switch
compartment
Without vlewlng window In door -F1
(3 When thls ootionalfeature is sDecliied. theentreexterwrofthe @ Meets REAs requirements for “dead-front
enclosure w ~ l lbe-fabricated from 11-gauge T$pe 304 stamless steel. When
ordering optional hexhead actuator, auxiliarS
antl~parallellng, A When ordering optional feature ‘“~1.”*‘-EL,” “225” through “-clo.”
or
swltches, fault indicator wlth viewingwlndow In door, or base spacer, spec~fy
“-F2” for use wlth a stamless-steel enclosure, Increase the optlon suffix
deslgnatlon by 10, for example, speclfy“-HlI ” instead of “-H1
”
the correct sultix for use wlth a stainless-steel enclosure
@ Where t h e National Electnc Safety Code (ANSI Standard C2) apphes,
this optlonal feature may he mcluded to meet the requirements o f Sec-
tion 381G.
663-502 INSTRUCTIONSHEET
Page 36 of 39 ELECTRIC
S&C COMPANY Chicago
July 9, 1990 S&C ELECTRIC CANADA LTD. 0 Toronto
IAPPENDIX E - Continued ~~~~ ~~
1
OPTIONAL FEATURES-Continued
Suffix lo be
Added to
Item Pad-Mounted
Gear
Catalog No.
6 Inches -K1
12 Inches -K2
Carbon steel
18 Inches -K3
Base Spacer, compartmented to match enclosure, Increases I 24 Inches I -K4 I
cable-termmatlon helght I 6
inches I -K11 I
12 Inches
Stamless steel
18 inches
Inches
-K1424
I 6
inches I -K7 I
12 Inches
Carbon steel
18 Inches
Base Spacer, noncompartmented, Increases cable- 24 Inches
termlnatlon helght I 6
inches I -K17 I
I 12 inches I -K18 I
Stamless steel
I 18 Inches I -K19 I
24 inches -K20
Swltch-Termlnal Adapters-for connectlon of two cables (through750 kc mll) per termmal@
-M 1
to be Installed
Note Space llmltatlons prevent use of these adapters where surge arresters are
In swltch compartments For conductor sizes No. 2
through 1000 kc rnll
Cable Guldes, oneat each terminal@@
I n fuse compartments For conductor sues No. 2
through 4/0
Slllcon-carbide type
15 kv
18 kv -N5
Surge Arresters,@ base-mounted, at all swltch terminals 9 kv -N6
(removed for shlpment)
10 kv -N7
Metal-oxlde type I 12 kv I -N8 I
I 15 kv I -N9 I
I 18kv I -N10 I
0 When suffix ""1," ""2,"or ""3" specfied, cable-terminatton optlons
IS @ Surge arrestersarebase-mounted only (wlthout Isolator)Slllcon-
lsuff~xes"-U2"and "-113") cannot be accommodated. carbide tvpe arresters arefor application at altttudes of 6,000 feet or less;
metal-oxide type arresters arefor appllcatlon at altltudes of 12,000 feet
@ These demces extend base the "It Provide a or less. For hlgher-altltude apphcatlons,
refer to the nearest S&C Sales
or speclfya base spacerthat provldesa12-mch or greater Increase In Office
cable-terminatlon helght.
I Open-Phase
Detectlon to lnltlate
source
a transfer
source-slde
when
a open-phase
condltlon
occurs I -y1 I
ach
I
Overcurrent Lockout to prevent a source transfer that would close a swltch Into a fault-Includes adjustable-delay
automatlc-reset tlmer, lockout-indlcatlng lamp, manual-reset pushbutton, and SIX current-sensor assemblles (one per
phase for
Open-Phase
switch)@@
Detectlon
plus
Overcurrent
Lockout
Comblnes functions of
opttons " - Y l " and "-Y2" llsted above@@
II -y2
-y3
II
Remote lndlcatlon Feature-includes provlslons to perrnlt remote monltorlng of the presence or absence of preferred-
and alternate-source voltage, the operatlng mode of the source-transfer control (I e , automatic or manual), and thesta-
tus of the "ready" Indicator. Thls optlonal feature also Includes provlslons to permit remote lndlcation of overcurrent
lockout
@ Thest. provlswnsaccommodate Ohm Brass ' b e PDV (metaloxlde),
McCraw-Edlsun Type AZL19C (mcral oxlde), GeneralElectrlc TranqueIP swltch-termmal adapter optmn
1 -y4
@ The current-senstrr assemblles furnlshfd cannot beused with the
suffix "-Ml" for applkcatmnsmvolvmg two
1
(metal oxkde), o r McGraw-Edlson Type ES (slllcon carbtde) d ~ s t r ~ b u t ~ o n - source cmductors per phaw For such appllcatwns, refer tothenearest
class surge arrestcm Surge arresters must he base-mounted only (wlthout S8C Sales Office
Isolator)
@ For applicatlons where t h e pad-mounted gear feeders are connected
@ Thesedewces extend I~clow the base of the unit Provlde a cableplt to transformers with wye-grounded primary wmdings, refer to the nearest
baseor speclfy a spacer S&C Sales Office
Current-Limiting Fuse
- Rating
For use in PMH Models
Manufacturer Type Rated, Kv
Max, Kv Max Amperes, Rrns
83 30-1 12 14 4
6 15 5 30-100 25
22 25-65 25
Kearney
83 6- 100 14 4
0
15 5 6-1 00 14 4or 25
I McGraw-Edlson 1 NXS
83
15 5
2523
15C-100C
15C-100C
6C-40C I
14 4
14 4 or 25
I
J
83 3-50 14 4
RT E ELX 15 5 3-50 144or25
23 3-40 25
83 3.5C-40C 14.4
cx 15 5 4C-40C 144or25
Westmghouse
CXN 15 5 45C-60C 25