- Proper cleaning by using water and a suitable Full cure is obtained in 8 – 12 hours after coating
detergent might be sufficient. application depending on thickness, temperature and
- Insulators that show an adhering pollution, such humidity.
like cement, other mineral or chemical pollution
layers should be cleaned by either "cob corn-" All spraying equipment should be cleaned with a
or carbon dioxide blasting. nonpolar solvent (e. g. Xylene or White Spirit)
- Any type of grease or fatty pollution is to be immediately after use.
removed by using a suitable solvent like benzine
or turpentine. Maintenance
- Residual contaminants should be removed by
thoroughly wiping. The product contains migratable matter that is able to
- Finish the cleaning just before spraying encapsulate contaminants and to provide a
POWERSIL® 567 with Isopropanol or an equivalent hydrophobic surface. Coated insulators may appear
Technical data sheet for POWERSIL® 567 / Version: 1.7 / Date of last alteration: 25.02.2015 1/3
dirty after some time in service. Nevertheless, washing on the product label.
and cleaning, especially with detergents and other
chemicals is not recommended. Storage beyond the date specified on the label does
not necessarily mean that the product is no longer
Inspection usable. In this case however, the properties required
for the intended use must be checked for quality
The water repellent appearance can be evaluated by assurance reasons.
spraying with water. IEC 62073, “Guidance on the
measurement of wettability of insulator surfaces”
provides further information. A partly lowering of the Safety notes
effect does not necessarily require immediate action.
Experience shows that the remaining parts of the POWERSIL® 567 contains a combustible solvent.
insulator will provide the necessary insulation ability. Explosion-proof equipment has to be used during
application.
Physical damage, such like scratching can be easily
repaired by brushing of fresh coating after partly Provide adequate ventilation during application and
cleaning with benzine. avoid prolonged exposure to vapours and repeated
skin contact.
To allow an instant replacement of broken insulators it
is recommendable to store a number of coated spare Comprehensive instructions are given in the
insulators. These should be stored in a protective corresponding Material Safety Data Sheets. They are
covering. available on request from WACKER subsidiaries or
may be printed via WACKER web site
http://www.wacker.com.
Storage
Product data
These figures are only intended as a guide and should not be used in preparing specifications.
Technical data sheet for POWERSIL® 567 / Version: 1.7 / Date of last alteration: 25.02.2015 2/3
The data presented in this medium are in accordance with the present state of our knowledge but The management system For technical, quality, or
do not absolve the user from carefully checking all supplies immediately on receipt. We reserve the has been certified product safety questions,
right to alter product constants within the scope of technical progress or new developments. The according to please contact:
recommendations made in this medium should be checked by preliminary trials because of DIN EN ISO 9001 and
conditions during processing over which we have no control, especially where other companies’ DIN EN ISO 14001 Wacker Chemie AG
raw materials are also being used. The information provided by us does not absolve the user from Hanns-Seidel-Platz 4
the obligation of investigating the possibility of infringement of third parties’ rights and, if necessary, WACKER® is a trademark 81737 München, Germany
clarifying the position. Recommendations for use do not constitute a warranty, either express or of info.silicones@wacker.com
implied, of the fitness or suitability of the product for a particular purpose. Wacker Chemie AG.
POWERSIL® is a www.wacker.com
trademark of
Wacker Chemie AG.
Technical data sheet for POWERSIL® 567 / Version: 1.7 / Date of last alteration: 25.02.2015 3/3