CALIBRATION PROCEDURE FOR TUC-6 (WF)

TUC DISPLAY ACCESS KEYS DESCRIPTION

X = 00,0 t/h Press & to enter the OFF LINE menu from the main
S1 = 6356,12 t program.

Press to enter the PASSWORD menu


Password

Password Enter 5 digit password and press to access the OFF LINE
Enter password : menu
X X X X X

Password If TUC shows “Y” the password is correct. Password is wrong


Enter password : Y it shows “N”. If password is wrong again go to password menu
to enter the correct password. If password is correct press
to go to CALIBRATION menu.

Analog Input
Press to proceed the calibration. If the calibration menu in
Calibration bottom

CALIBRATION_ MENU To proceed the calibrations press


RE-CALIBRATE? -> To terminate the calibration process press

DEAD-LOAD Initially TUC shows some counts w. r .t old calibration,


0790 accepting the DEAD – LOAD by pressing the counts are
become zero. Before proceed the calibration ensure the belt is
empty & the load cell mechanism repeatability is proper.
DEAD-LOAD
Press to precede the load calibration.
0000

CALIBRATION LOAD LHS counts (auto) w.r.t load cell mV & RHS counts determined
Keep the test
0000 => 0000 d the calibration percentage. LHS counts will increase w.r.t to
weight on the knife
increment of the mV from Tare mV. After study state of
edge.
counts enter the “d” counts in RHS w.r.t to calibration
CALIBRATION LOAD percentage. Press to complete the calibration & close the
2756 => 15000 d calibration menu.
Note: 1% calibration = 20 d counts

Press to go to main program.

SYSTEM DATA Press to run the main program, while main program
MAINPROGRAM menu in bottom line.

ISSUE: 1.0 - 10/03/17 Please go through below course of action for repeatability check & zero correction.
REPEATIBILITY CHECK IN STOP CONDITION

BB = 75 % Keep the test weight & ensure the “BB” value in line with
Ta = 0000 Hz calibration percentage. (Exp: here showing 75%)

BB = 00 % Remove the test weight & ensure the “BB” value Is 0%.
Ta = 0000 Hz

ZERO CORRECTION IN VOLUMETRIC RUNNING

BB = 00 % Remove the test weight. Run the weigh feeder in volumetric


Ta = 0000 Hz mode @calibration RPM

BB = 00 % While volumetric running press


Ta = 0500 Hz

ZERO CORRECTION TUC shows the Zero correction process.


0012421292

ZERO CORRECTION TUC display the zero correction error. It is auto accepted if
ERROR = -1.5% the error is less than the zero limit settings in configuration.

BB = 00 % Press any key to go the main program.


Ta = 0000 Hz

NOTE DOWN CALIBRATION COUNTS

BB = 00 % Press & to observe the “DL” & “Span” counts.


Ta = 0000 Hz

Password
Enter five digit password and press
Enter password :
X X X X X

Dl COUNT : 03567
Note down this values for future reference.
SPAN COUNT: 06538

BB = 00 % Press to go to main program & normal operation.


Ta = 0000 Hz

ISSUE: 1.0 - 10/03/17