Sie sind auf Seite 1von 8

1826 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO.

3, JULY 2010

Modeling the EPRI-Wisconsin Power


and Light Broken Wire Tests
Alan B. Peabody, Member, IEEE, and Ghyslaine McClure

Abstract—In the late 1970s, the Electric Power Research Insti-


tute and Wisconsin Power and Light performed a series of tests to
measure the forces on a power transmission tower due to broken
conductors. Three of those tests have been modeled using ADINA, a
finite-element structural analysis program with the ability to per-
form nonlinear time history analyses of dynamic events. When a
wire breaks, the time history of the force on the tower typically has
two peaks. The first peaks were modeled accurately in time and
magnitude. The second peaks were modeled accurately in time;
however, the magnitudes were larger than those measured during
the tests. The simulated time histories contained high frequencies
due to the discretization of the real structure into the finite ele- Fig. 1. Test line profile (spans in meters).
ments. Numerical filtering was used to remove these modeling ar-
tifacts.
Index Terms—Conductors, finite-element methods, modeling, to analyze the same tests that were modeled here. The structures
power transmission lines, power transmission mechanical factors, were also modeled as simple spring-mass damper systems. The
power transmission testing.
cables were modeled by using the catenary cable element de-
scribed by Peyrot and Goulois [7]. Thomas settled on a three
I. INTRODUCTION span (half of the spans in the test section) with ten elements
in the first span, four in the second, and two in the third. Axial
damping of 20% was used. In the modeling described here, there
I N the late 1970s, the Electric Power Research Institute
(EPRI) and Wisconsin Power and Light performed 12
broken wire tests to measure the dynamic forces on a power
is a large improvement in the fit of the timing and magnitude of
the first peak. There is also a large improvement in the timing
transmission tower. These tests provide excellent “real world” of the second peak.
data to test the accuracy of a dynamic finite-element model McClure and Tinawi [8] reported good results simulating
of the tower-insulator-conductor system. The finite-element model broken wire tests performed by Mozer [9] using ADINA.
model was developed to investigate the effects of adding The model time histories agreed well with the experimental
hydraulic dampers to the tower insulator system [1]–[3]. The time histories, always within 20%. The Wisconsin tests are the
dampers were found to reduce the peak dynamic forces on a first full-scale tests modeled with ADINA.
tower during a broken wire event by 50 to 80% of the total
B. Current Practice
possible reduction. The three full-scale tests that were modeled
are the subject of this paper. In current design practice, rather than design for dynamic
loads, towers are typically designed for the residual static load
A. Background (loads at rest after a broken wire) with the expectation that three
Siddiqui [4], [5] wrote one of the first computer programs to four towers on either side of the broken wire will fail—with
to analyze broken wires. While multiple elements were used to their failures absorbing sufficient energy to prevent the failure
model the structures, the conductors were modeled as a single from propagating into a cascade [10], [11].
element with one degree of freedom. Thomas [6] also developed
a program to analyze broken wire loads. This program was used II. FULL-SCALE TESTS
The full-scale broken wire tests were performed on a double-
circuit 138-kV line owned by Wisconsin Power and Light. [12]
Manuscript received July 23, 2007; revised May 29, 2008. First published
March 08, 2010; current version published June 23, 2010. This work was sup-
The line had been slated for replacement with a new 345-kV
ported in part by the Natural Sciences and Engineering Research Council of line, making it available for destructive tests. The line was built
Canada, in part by Hydro-Québec and TransEnergie, in part by the Family of in 1931 using lattice steel towers with square bases. The two
Emil Nenniger, in part by the Joseph S. Stauffer Foundation, and in part by the
Friends of McGill University. Paper no. TPWRD-00471-2007.
shield wires were 7 No. 8 Copperweld; the left circuit used 397
A. B. Peabody is with the Construction Management Program, University of kcmil ACSR 26/7 conductor and the right circuit 7/3 copper/
Alaska Anchorage, Anchorage, AK 99508 USA (e-mail: apeabody@ieee.org). bronze. The test section had seven towers as shown in Fig. 1
G. McClure is with the Department of Civil Engineering and Applied Me- [12, Fig. 3.1].
chanics, McGill University, Montreal, QC H3A 2K6, Canada (e-mail: ghys-
laine.mcclure@mcgill.ca). The tower outline is shown in Fig. 2. Two tests to determine
Digital Object Identifier 10.1109/TPWRD.2010.2041559 the tower’s natural frequencies were performed, one with all of
0885-8977/$26.00 © 2010 IEEE
PEABODY AND MCCLURE: MODELING THE EPRI-WISCONSIN POWER AND LIGHT BROKEN WIRE TESTS 1827

TABLE I
BROKEN CONDUCTOR TESTS

Fig. 2. Test towers (all dimensions in meters). TABLE II


WISCONSIN TEST TOWER DEFLECTIONS AND STIFFNESSES

III. TOWERS

The towers were modeled as a pin-connected truss using


Fig. 3. Full-scale test time histories. ADINA [14]. Static analysis was performed with tension-only
members modeled by using a modulus of elasticity in compres-
sion of 1/1000 the modulus in tension.
the wires attached to the tower with their normal suspension In order to reduce the number of nodes and members in
hardware and one with the shield wires detached. the transmission-line model, a dynamically similar model
The tower was excited by tensioning a cable attached to the for the tower-attachment point was constructed. A two-de-
top of tower to approximately 9.8 kN (1000 kgf) and suddenly gree-of-freedom spring-mass system is needed in the hor-
releasing it. The approximate static deflection was 2 to 3 cm. izontal direction to model the combined longitudinal and
The motion of the tower top was measured by using an ac- torsional vibration characteristics of the tower and a single-de-
celerometer. The period of the first mode of the tower with the gree-of-freedom system is needed to model the vertical
shield wires detached was reported to be 0.25 s (4 Hz) with a vibration characteristics. The spring stiffnesses were selected
viscous damping ratio of 4%. With the shield wires attached, to match the stiffnesses at the tower attachment point with the
the period was reported to be 0.24 s (4.2 Hz) with a damping mass selected so that the spring-mass systems would have the
ratio of 7% [12]. same natural frequencies as the tower.
Twelve broken conductor tests were then performed as de- The static analyses included load cases to determine the at-
scribed in Table I. tachment stiffness in the vertical and longitudinal directions.
Tests IIIL1, 2 and 3 were modeled. These tests were per- The dead load of the tower was included in all load cases. The
formed at the top, center, and lower left crossarms with three first load case was a longitudinal load of 9807 N (1000 kgf)
different conductor tensions (see Table I). All of the tests were applied at the top-left phase attachment point to determine the
performed by using a 397 kcmil ACSR 26/7 conductor. Fig. 2 overall deflection of the attachment point. The second case was
shows the time histories of the tension force measured in the in- two longitudinal loads of 4903.5 N (500 kgf) applied at the two
sulator assembly. Test IIIL1 had a gap in the time history for the upper phase attachments. This case gives the longitudinal de-
second peak and its timing and magnitude were taken from the flection at the phase attachments without the torsional compo-
report in [12, Table 6-2]. The time history of test IIIL1 shows a nent of the deflection. In a separate load case, a 9807 N vertical
bifurcated first peak, which may be due to the incipient buckling load was applied to the attachment point to measure the vertical
of the crossarm noted by Kluge [13]. stiffness. These results are summarized in Table II.
1828 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

TABLE III
WISCONSIN TEST TOWER FREQUENCIES

TABLE IV
COMPARISON OF FREQUENCY ANALYSIS AND PLUCKING ANALYSIS

Fig. 4. Simplified tower model. (a) Plan view. (b) Transverse elevation.
The natural frequencies and mode shapes of the tower were
determined for two modeling assumptions. The first case as-
TABLE V
sumed that the tension-only cross bracing acted as tension-com- EQUIVALENT MASS, STIFFNESS, AND DAMPING
pression bracing; in the second, the modulus of elasticity of the
tension-only members was assumed to be one-half the modulus
of elasticity of steel. This latter case simulated the stiffness of a
tension-only system by giving the total stiffness of these mem-
bers equal to the stiffness of one of them. Changing the mod-
ulus rather than the area has the advantage of keeping the same
mass in the model. Table III compares the natural frequencies
obtained with the two tower models.
Note that there is very little difference in the first transverse
and longitudinal modes; however, there is a significant differ-
ence in the frequencies of the first torsional mode because the
bracing is the main contributor to the torsional stiffness. The mass associated with the linear longitudinal spring was
The natural frequencies of the numerical models were also calculated by using (1), where is the mass, is the spring
explored by plucking the tower with a 20-kN force released in stiffness, and is the natural frequency
0.005 s. This was applied in three directions, longitudinally with
a 10 downdrop angle (x and -z), transversely (y) and vertically (1)
(-z). Table IV compares the frequency analysis with the frequen-
cies determined from Fourier transforms of the plucking anal- The torsional spring constants and rotational moments of
ysis, which confirms the frequency of the tension-only bracing inertia were calculated by using (2) and (3) where is the
in Table III. applied load, is the moment arm, and is the resulting longi-
Plucking the arm vertically excites the tower in the first trans- tudinal deflection
verse mode with a frequency of 4.6 Hz.
In order to simplify the finite-element model for nonlinear (2)
dynamic analysis, the tower was modeled as a set of spring-
mass dampers. This was advantageous for the many runs needed
for the subsequent analysis of adding supplemental dampers (3)
[1]–[3]. The balanced longitudinal mode of vibration was mod-
eled as a linear translational spring-mass system. The torsional Viscous damping for the linear and torsional spring-mass sys-
mode was modeled as a torsional spring with a rotational iner- tems was calculated by using (4) and (5), respectively
tial mass. Both linear and torsional springs were connected to a
rigid massless arm with length L being equal to the horizontal (4)
distance from the center of the tower to the conductor attach- (5)
ment point. The vertical motion of the tower was also modeled
by using a torsional spring with a rotational inertial mass. The Table V shows the properties of the equivalent spring-mass
simplified model is shown in Fig. 4. systems.
PEABODY AND MCCLURE: MODELING THE EPRI-WISCONSIN POWER AND LIGHT BROKEN WIRE TESTS 1829

TABLE VI
IBIS 397.5 kcmil ACSR CONDUCTOR PROPERTIES

TABLE VII
Fig. 5. Longitudinal deflection at the upper left-phase comparison of full and COMPARISON OF FREQUENCIES (IN HERTZ) IBIS: 300-m SPAN, H = 14.4 kN
simplified tower models.

Fig. 6. Fourier spectra-tower model comparison.


conform to the theory. A second measure is how the frequencies
converge as the length of the elements is reduced. Table VII
Fig. 5 compares the time histories of the longitudinal dis- compares theoretical calculations of the natural frequencies of
placements of the full tower model and the simplified tower a typical 300-m span with the results of ADINA analyses for
model, described before, under a longitudinal plucking load that different numbers of elements in the span. There is little change
is inclined downwards at a 10 angle from horizontal. Fig. 6 in the natural frequencies for the higher modes when at least
shows the corresponding Fourier spectra for the full and sim- 60 elements 5 m long are used and practically no difference
plified tower models. The natural frequencies of the simplified between 120 elements 2.5 m long and 300 elements 1 m long.
tower model match well with those of the full tower model. The length of the wire elements used was approximately 2.5 m.

IV. INSULATOR ASSEMBLIES C. Conductor Damping


The insulator assembly for the tower next to the break was Damping of transmission conductors can be separated into in-
modeled as five pin-connected truss elements with stiffnesses ternal damping and aerodynamic damping. Internal damping is
commensurate with the swinging arm bracket, standard insula- a combination of hysteretic damping within the individual cable
tors, and a load cell. The insulators at the remaining towers were strands and damping due to the sliding friction between strands
modeled with four truss elements. as they move past one another during cable movement. Aerody-
namic damping arises from the motion of the cable through the
V. CONDUCTOR air.
1) Internal Damping: Much of the literature related to the
A. Properties damping of transmission conductors is focused on the energy
The properties of the conductor used in the tests that were dissipated by the cable when excited by vortex shedding in
modeled are shown in Table VI. smooth laminar winds. This motion is known as aeolian vibra-
The conductor was modeled as pin-connected truss elements tion. The results of tests of the self-damping capabilities of the
with additional internal and aerodynamic damping elements. conductor are usually stated in terms of the energy dissipated
per-unit length as a function of the vibration frequency. The
B. Length of Conductor Finite Elements peak-to-peak amplitude of vibration is very small, typically
Methods of calculating the natural frequencies of single spans less than the conductor diameter [18]. These measurements
of wire are described in [12] and [15]–[17]. One measure of the often do not distinguish between the internal damping and the
goodness of the finite-element model of a structure is how well aerodynamic damping, in some cases, describing the vortex
the natural frequencies calculated for the finite-element model excitation as negative aerodynamic damping. The internal
1830 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

TABLE VIII
AXIAL DAMPING RATIOS

Fig. 7. Conductor model.

damping due to friction between the strands is reduced as the


tension in the wire increases, and increases as the amplitude of
vibration increases. Diana et al. [19] indicate that the damping
coefficient for the ACSR conductor is in the range of 0.1 to
0.01% of critical for the frequencies and amplitudes of interest
for aeolian vibration. When discussing guys for vertical axis
wind turbines, Carne [20] reports damping of less than 0.2%
of critical. In Bachmann et al. [21], a value as low as 0.05% of
critical is suggested.
The internal damping can be divided into two parts: 1) axial Fig. 8. Insulator tension at tower T3-test IIIL3 versus the ADINA model.
damping that takes place due to changes in the conductor tension
and 2) damping due to bending of the conductor. The critical
axial viscous damping for an elastic rod is given in For smooth circular cylinders, is between approximately
0.9 and 1.2 for Reynolds numbers between 200 and 100 000
(6) (Binder 1973; Eisner 1931), which correspond to relative veloc-
ities for the Ibis conductor of 0.15 m/s and 73 m/s, respectively.
Note that the critical damping constant is independent of As the relative velocity is reduced below a Reynolds number of
the length of the rod. Table VIII shows some values of axial 200, steadily increases to more than 50 at a Reynolds number
damping used in previous time history analyses of conductor of 0.1. A of 1.25 was used.
motion. McClure and Tinawi [22], [23] did not use explicit
damping; however, some of the time history analysis algorithms D. Conductor Finite-Element Model
they investigated introduce some numerical damping which Fig. 7 shows the conductor model used in ADINA with axial
reduces high-frequency components of the response. An axial and aerodynamic damping. Although the aerodynamic damping
viscous damping ratio of 0.5% of critical was used in this study. should be applied normal to the direction of movement, this
Little information is available on the lateral damping of would be more difficult to model in ADINA. Instead, the aero-
ACSR conductors; Yu [26], however, presents results of some dynamic damping was applied to the vertical motion of the con-
tests performed on slack-stranded steel cables similar to those ductor by using the initial horizontal projected area.
used for shield wires and the steel core of ACSR. These tests
indicate there may be substantial lateral damping.
VI. TIME HISTORY ANALYSIS RESULTS
2) Aerodynamic Damping: ADINA has the capability of
modeling the aerodynamic damping directly. Aerodynamic Fig. 8 shows the load-cell tension at tower T3 from a time
damping is due to the motion of the conductor relative to the history analysis of test IIIL3 performed with ADINA [14] and
air. In still air, the aerodynamic damping force is given by [27] the load-cell tension reported in Peyrot et al. [12].
Fig. 9 shows the Fourier transforms of the ADINA time
(7) history and the test record for test IIIL3. The amplitudes of
frequencies above 8 to 10 Hz in the test record are very small
in comparison to the amplitudes from the ADINA model. An
where is the damping force, is the air density, and is
inverse Fourier transform of only the frequencies below 10 Hz
the velocity relative to the air, is the drag coefficient, and
in the test record could not be distinguished from the original,
is the projected area. depends on the Reynolds number (8),
while higher frequencies are obviously represented in the
where is the conductor diameter and is the viscosity of air
ADINA time history.
The test report indicates that “ the basic concern for the in-
(8) strumentation was within the low frequency to dc range for the
PEABODY AND MCCLURE: MODELING THE EPRI-WISCONSIN POWER AND LIGHT BROKEN WIRE TESTS 1831

Fig. 9. Frequency content of test IIIL3 and ADINA model.

Fig. 10. Insulator tension at tower T3, test IIIL3, and the ADINA model versus
basic vibrational characteristics.” The fundamental frequency of the ADINA model with a 10-Hz low-pass filter.
the tower was expected to be in the neighborhood of 5 Hz. The
load-cell signals were conditioned before recording with an os-
cillographic recorder. No detail is given about the extent of the
signal conditioning; however, it is likely that a low-pass analog
filter was used. Even though higher frequencies would be ex-
pected in model tests, Kempner [28] used a low-pass filter with
50-Hz cutoff in his 1/23.33 scale broken wire model tests. This
is roughly equivalent to a 10-Hz cutoff frequency at full scale.
Analog low-pass filters partially attenuate some of the frequen-
cies below the nominal cutoff frequency. It can be reasonably
inferred that any higher frequencies shown in Fig. 8 would, if
they occurred in the tests, have been filtered out or attenuated Fig. 11. Insulator tension, test IIIL1 versus the filtered ADINA model.
before recording the data.
The ADINA time history analysis can itself be expected
to introduce some higher frequencies in the response due
to breaking up the continuous elements in the real structure
into discrete pieces in the finite-element model. In some past
studies, damping has been increased to suppress these spurious
frequencies in transmission-line dynamic analysis [24]. Holmes
and Belytschko [29] discuss the problem in reference to wave
propagation problems and explore the use of numerical filters to
remove the spurious frequencies. Using unequal elements in the
mesh will also introduce spurious frequencies due to reflections
between elements [30]. For this reason, using equal-length Fig. 12. Insulator tension, test IIIL2 versus the filtered ADINA model.
elements to model the conductor is preferred. For convenience
in calculation, lengths were made equal in the horizontal
projection of the elements leading to small differences in the
lengths within a span. Since spans must be divided up into an
integral number of elements, there are also small differences
in the length of elements used in the different spans. Some of
the high-frequency content shown in Fig. 8 can reasonably be
attributed to the modeling.
Numerical filtering of the load-cell tensions from the ADINA
time history analysis is an effective way to remove the high-
frequency components for better comparison with the full-scale
test data. Fig. 10 shows the use of a 10-Hz low-pass filter. A Fig. 13. Insulator tension, test IIIL3 versus the filtered ADINA model.
filter with a sharp cutoff was used because it is extremely easy
to program once the Fourier coefficients have been determined.
Figs. 11–13 compare the filtered results of the time history Similarly, the much faster reduction in tension during the fall of
analyses for tests IIIL1, 2, and 3. In all three cases, there is a the first peak may be explained by a permanent set in the tower
very good fit in the timing, the rise in tension, and the peak caused by connections slipping. In a theoretical analysis of bolt
tension of the first peak. The unloading part of the first peak slippage in the connections of lattice towers, Kitipornchai et al.
does not have such a good fit. It appears to improve with the [31] report an increase in a deflection of 20% due to slippage in
lower conductor tensions in tests IIIL1 and IIIL2. The small the connections.
bumps on the rising part of the first peak may be explained by the The timing of the second peak due to bottoming out of the
bolted connections suddenly slipping during the loading cycle. fall of the first span of conductor is well predicted, but all three
1832 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 3, JULY 2010

models substantially overpredict the magnitude of the peak. [8] G. McClure and R. Tinawi, “Mathematical modeling of the transient
There is a small angle in line at tower T4 (1 31 ) which was response of electric transmission lines due to conductor breakage,”
Comput. Structures, vol. 26, pp. 41–56, 1987.
not included in the ADINA model. This may explain some of [9] J. D. Mozer, W. A. Wood, and J. A. Hribar, “Broken wire tests on a
the differences. Increased movement of the tower under the model transmission line system,” presented at the IEEE Power Eng.
impact due to slippage in the connections may also contribute Soc. Summer Meeting, Vancouver, BC, Canada, 1979.
[10] “Guidelines for Electrical Transmission Line Structural Loading,
to the difference. ASCE 74, June 2001 Draft Revision,” ASCE, 2001, Reston, VA:
The time history of the forces depends on the line character- Amer. Soc. Civil Eng.
istics. These results should not be extrapolated to other lines or [11] “Guidelines for Electrical Transmission Line Structural Loading,
ASCE 74,” ASCE, 1991, New York: Amer. Soc. Civil Eng.
line sections. If only three spans are modeled, the second peak [12] A. H. Peyrot, R. O. Kluge, and J. W. Lee, “Longitudinal loading tests
will occur earlier and both peaks will be smaller in magnitude. on a transmission line,” Elect. Power Res. Inst., Palo Alto, CA, EPRI
EL-905, 1978.
VII. CONCLUSION [13] R. O. Kluge, Comments on EPRI Wisconsin Tests (Private Correspon-
dence). A. B. Peabody, Ed., 2002.
Analog time histories from older tests can be digitized, an- [14] ADINA (Automatic Dynamic Incremental Nonlinear Analysis). ver.
8.0, ADINA R&D, Inc., Watertown, MA, 2003.
alyzed for their frequency content, and used to test numerical
[15] R. D. Blevins, Formulas for Natural Frequency and Mode Shape.
models. Numerical filtering is an effective way to remove the New York: Van Nostrand, 1979.
high frequencies introduced by breaking continuous systems up [16] M. Irvine, Cable Structures. Mineola, NY: Dover, 1992.
into finite-element models. [17] M. Shears, “Static and dynamic behaviour of guyed masts” Struct. Eng.
Lab., Univ. California Berkeley, Berkeley, CA, CA Rep. No. 68-6, Jun.
The ADINA time history analysis does a good job of pre- 1968.
dicting the first peak due to the snap from the sudden loss of [18] Transmission Line Reference Book: Wind-Induced Conductor Mo-
conductor tension on one side of the tower. The prediction of tion. Palo Alto, CA: Elect. Power Res. Inst., 1979, Gilbert/Com-
monwealth.
the magnitude of the second peak due to the retensioning of the [19] G. Diana, M. Falco, A. Cigada, and A. Manenti, “On the measurement
conductor at the bottom of its fall was not as good. For the pur- of over head transmission lines conductor self-damping,” IEEE Trans.
poses of the further research based on the model, the model was Power Del., vol. 15, no. 1, pp. 285–292, Jan. 2000.
[20] T. G. Carne, “Guy cable design and damping for vertical axis wind
adequate as the second peak was on the conservative side for turbines” Sandia National Labs. Albuquerque, NM, SAND80-2669,
evaluating the effect of measures introduced into the tower and 1980.
[21] H. Bachmann, W. J. Amman, F. Deischl, J. Eisenmann, I. Floegl, G.
insulator system to control the impact. Modeling of other more
H. HIrsch, G. K. Klein, G. J. Lande, O. Mahrenholtz, H. G. Natke,
recent broken wire tests has also shown good agreement with H. Nussbaumer, A. J. Pretlove, J. H. Rainer, E. U. Saemann, and
the test measurements [32]. L. Steinbeisser, Vibration Problems in Structures: Practical Guide-
lines. Boston, MA: Birkhauser Verlag, 1995.
ADINA may be used to model complete sections of existing
[22] G. McClure and R. Tinawi, “Comportement dynamique des lignes aéri-
or new transmission lines, and to simulate the effects of broken ennes de transport d’électricité dû aux bris de câbles. II. Problèmes
wires and other disturbances. For preliminary design, a simpli- numériques associés à la modélisation mathématique. (Dynamic Be-
fied model as discussed here would be appropriate. For analysis havior of Overhead Electric Transmission Lines Due to Broken Cables.
II Numerical Problems Associated with the Mathematical Modeling),”
of existing lines, the ADINA model may be made as detailed Can. J. Civil Eng., vol. 16, pp. 354–374, 1989.
as desired, even to the extent of modeling the foundations in a [23] G. McClure and R. Tinawi, “Comportement dynamique des lignes aéri-
manner similar to that used in some foundation design programs ennes de transport d’électricité dû aux bris de câbles. I. Modélisation
mathématique. (Dynamic Behavior of Overhead Electric Transmission
(for example, L-Pile). Lines Due to Broken Cables. I Mathematical Modeling),” Can. J. Civil
Eng., vol. 16, pp. 335–353, 1989.
ACKNOWLEDGMENT [24] M. R. Fekr, “Dynamic response of overhead transmission lines to ice
shedding,” M.Eng. degree, Civil Eng. Appl. Mechan. Dept., McGill
The authors would like to thank R. Kluge for lending a film Univ., Montreal, QC, Canada, 1995.
of the tests and providing additional information about the tests. [25] G. McClure and M. Lapointe, “Modeling the structural dynamic re-
sponse of overhead transmission lines,” Comput. Structures, vol. 81,
pp. 825–834, 2003.
REFERENCES [26] A. T. Yu, “Vibration damping of stranded cable,” Experiment. Stress
[1] A. B. Peabody, “Applying shock damping to the problem of transmis- Anal., vol. 9, pp. 141–158, 1952.
sion line cascades,” Ph.D. dissertation, Dept. Civil Eng. Appl. Mechan, [27] C. Dyrbye and S. O. Hansen, Wind Loads on Structures. Chichester,
McGill University, Montreal, QC, Canada, 2004. U.K.: Wiley, 1996.
[2] A. B. Peabody and G. McClure, “Modeling the overhead power line [28] L. J. Kempner, “Longitudinal impact loading on electrical transmission
post spring-damper using ADINA,” Computational Fluid and Solid line towers: A scale model study systems science: Civil engineering,”
Mechanics 2005. Cambridge, MA, 2005, pp. 1279–1283. Ph.D. degree, Portland State Univ., Portland, OR, 1997, p. 203.
[3] A. B. Peabody and G. McClure, “The effect on broken wire loads of [29] N. Holmes and T. Belytschko, “Postprocessing of finite element tran-
adding dampers to rotating crossarms,” in Proc. Electrical Transmis- sient response calculations by digital filters,” Comput. Structures, vol.
sion Conf., Birmingham, AL, 2006, pp. 81–89. 6, pp. 211–216, 1976.
[4] F. M. A. Siddiqui, “Methods of analysis for determining longitudinal [30] Z. P. Bazant, “Spurious reflection of elastic waves in nonuniform ele-
loads in electric transmission lines due to broken wires, state-of-the- ment grids,” Comput. Meth. Appl. Mechan. Eng., vol. 16, pp. 91–100,
art,” M.Sc. dissertation, Univ. Pittsburgh, Pittsburgh, PA, 1979, p. 115. 1978.
[5] F. M. A. Siddiqui, “Dynamic analysis and behavior of electric transmis- [31] S. Kitipornchai, F. G. A. Al-Bermani, and A. H. Peyrot, “Effect of bolt
sion line systems subjected to broken wires,” Ph.D. dissertation, Univ. slippage on ultimate behavior of lattice structures,” J. Struct. Eng., vol.
Pittsburgh, Pittsburgh, PA, 1981, p. 198. 120, pp. 2281–2287, 1994.
[6] M. B. Thomas, “Broken conductor loads on transmission line struc- [32] P. Vincent, C. Huet, M. Charbonneau, P. Guilbault, M. Lapoint, D.
tures,” Ph.D. dissertation, Dept. Civil Environment. Eng., Univ. Wis- Banville, and G. McClure, “Testing and numerical simulation of over-
consin-Madison, Madison, WI, 1981, p. 312. head transmission line dynamics under component failure conditions,”
[7] A. H. Peyrot, A. Goulois, and M. , “Analysis of flexible transmission in Proc. Int. Conf. Large High Voltage Electric Systems: CIGRE, 2004,
lines,” J. Structural Div., ASCE, vol. 104, pp. 763–779, 1978. p. B2-208.
PEABODY AND MCCLURE: MODELING THE EPRI-WISCONSIN POWER AND LIGHT BROKEN WIRE TESTS 1833

Alan B. Peabody (M’92) was born in New Haven, Ghyslaine McClure was born in St. Ger-
CT, in 1949. He received the B.S. degree in art and main-de-Grantham, QC, Canada, in 1957. She
design (architecture) from the Massachusetts Insti- received the B.Eng. degree in civil engineering from
tute of Technology in 1971, the M. Civil Eng. degree École Polytechnique de Montréal, Montréal, QC,
from the University of Alaska, Anchorage, in 1995, Canada, in 1980, the S.M. degree in civil engineering
and the Ph.D. degree from McGill University, Mon- from the Massachusetts Institute of Technology,
treal, QC. Canada, in 2004. Cambridge, in 1984, and the Ph.D. degree from
He has 35 years experience in transmission-line École Polytechnique de Montréal in 1989.
engineering. She joined McGill University as an Assistant
Dr. Peabody is Chairman of the ASCE 7 Subcom- Professor in 1991, after working a few years in
mittee on Atmospheric Icing of Structures and is a the Quebec transmission-line industry. The bulk
member of the International Advisory Committee for the International Work- of Professor McClure’s research relates to nonlinear structural dynamics
shops on Atmospheric Icing of Structures. problems, and more specifically, to cable dynamics and transient response of
transmission lines to shock loads.
Dr. McClure is an active contributor to the CIGRÉ Study Committee B2 on
Overhead Lines.

Das könnte Ihnen auch gefallen