Beruflich Dokumente
Kultur Dokumente
INTRODUCTION
The digital multimeters series EMM-R4e- allow to monitor all the
electrical parameters present on a distribution line .
The local display of 30 electrical parameters is carried out by 4 display
with red LED. A simple front panel completes the intuitive selection of
several electrical parameters, with a great information. On top of the
local measurement, these instruments display the Maximum value of
Voltage,Maximum demand, Active Power and Currents.
The presence of a serial communication port (optional) allows the
connection of various instruments in a network, even with the EMA
series Analysers in order to establish easily a centralised network of
measure.
Multimeters EMM-R4e.. replace in a unique device , all the functions of
voltmeters, ammeters,energy meters, cosphimeters, wattmeters,
varmeters, frequency meters permitting a great saving of energy,
overall dimensions and wiring.
AVAILABLE TYPES
They are available in 3 types all in flush mounted version for panel
DIN 96X96 and with internal CT (-t option) ;
-
EMM-R4e multimeter with energy counter
EMM-R4ep multimeter with energy counter and pulse output
EMM-R4e485 multimeter with energy counter and EIA485 serial port
MEASURED PARAMETERS
phase and system voltage [V-kV] VL1-N VL2-N VL3-N VL-N
phase to phase voltage [V-kV] VL1-L2 VL2-L3 VL3-L1 VL-L
phase and three phase current [A-kA] IL1 IL2 IL3 I
phase and three phase power factor PFL1 PFL2 PFL3 PF
phase and three phase active power. [W-kW-MW] PL1 PL2 PL3 P
phase and three phase reactive power. [VAr-kVAr-MVAr] QL1 QL2 QL3 Q
phase and three phase apparent power. [VA-kVA-MVA] AL1 AL2 AL3 A
frequency [Hz] Fl1
ENERGY METERS
Three-phase active energy [kWh] kWh
Three-phase reactive energy [kVArh] kVArh
STORED VALUES
Peak maximum value:
current IL1 MAX - IL2 MAX - IL3 MAX
power PL MAX - SL MAX
average current (in 15') IL1 MAX(AV.) - IL2 MAX(AV.) - IL3 MAX(AV.)
Average active power (15’ max.demand) PL MAX(AVERAGE)
EMM-R4 electrical multi meter
TECHNICAL DATA
MEASURES, ACCURACY
DIMENSIONS Voltage RMS value of phase to phase voltage and phase
voltage, Phase voltage and phase to phase
voltage of the system (average)
EMM-R4e..(t) Measures range: max 480V-rms phase to phase
290V rms phase to neutral
Visualisation 0,02÷50,0kV
Measures accuracy: ±0,5% ±1 digit
V. AUX:
Measures range: 0,02÷5A rms
! VL2 - VL3
Measures accuracy: ±0,5% ±1 digit
90
VL3 - N
MADE IN EU
OPTIONS:
INTERNAL CTs Visualisation 0,02÷9990A
s.n. ENERGY COUNTERS
CURRENT VOLTAGE
INPUTS
MAX 5A ac
S1 S2
INPUTS
MAX 440V ac ph-ph Frequency L1 phase frequency, measures range: 40÷500Hz
I1 I2 I3 C.I VL1 VL2 VL3 N
Accuracy: ±0,5% ±1 digit
90
AUXILIARY SUPPLY
Aux.supply shared with the inputs voltage
380-415V ±15% L2 - L3
96 9 56 14 Frequency 50-60Hz - absorption 2VA
(Other voltages on request)
from 1 to 400.
Panel flush mounting
According with DIN 43700 Current input from 0,02 to 5A; permanent overload 30%
(100% for EMM-...t - insulation 500V)
from external CT with 5 A secondary,
primary programmable from 5 to 10000A
92 Self-consumption <0,5VA (<0,2VA per EMM-...t)
GENERAL
Operational 4 display red LED 10mm, each one composed of
display 7 segments 3 digit; 3 keys for measure selection
and external transformers' transformation ratio
programming
For possible application and functional problems, which haven't been
seen in the present manual, please contact with our Technical Mechanical Protection degree: IP52 front
Assistance Department. IP20 enclosure and terminals
weight 0,5-kg approx.
The manufacturer declines any potential direct or consequential Connection through screw terminals for
damages to persons or things, derived form the use of the instruments. 2
2,5 mm cables
It is possible to customise multimeters, with different characteristics
Self-extinguishing plastic enclosure
of those covered in the present manual. Please call upon us with Flush mounting DIN 96x96mm, depth 60mm
your enquiry.
Environmental working temperature: -10÷60°C; humidity <90%
Storage temperature: -25÷80°C
Isolation test: 3 kV for 1 minute
Standards