CIRCUIT BREAKER & EARTH SWITCH

FAKOOR SANAT TEHRAN Commissioning Test Formats


Description: CIRCUIT BREAKER Record No. :
Equip. No.: U05B Drawing ref.: VII-1 Sheet : 1 of 1
Contractor : Contract no.: Substation No : 121

CIRCUIT BREAKER TIMING TEST

General Data and Information:

CB Type : Motor Spring


Rated Voltage: 33 KV rms
Manufacture : EATON

Time (m.sec)
Control Voltage
Opening and Closing
D.C (V)
R Y B

Close 125 53 53 52
OPEN 125 31 33 32
Close–Open (C-O) 125 85 82 83
SPRING CHARGE CURRENT 125 1.74 A-DC

CONTACT RESISTANCE INJECTED CURRENT VOLTAGE DROP RESISTANCE (µΩ)


R 100 6.6 mV 66 µΩ
S 100 6.6 mV 66 µΩ
T 100 6.5 mV 65 µΩ

Item Description Checked


1 Check tightness of all connections Yes N/A
2 Inspect for physical damage / defects Yes N/A
Panel condition, cleanliness, organization, labeling, readiness for service, panel doors,
3 Yes N/A
handles...etc.
4 Indications checked Yes N/A
5 Contact resistance Yes N/A
6 Check the ferrules as per specification Yes N/A
7 Confirm that each panel has been properly secured to the floor in its final service location. Yes N/A
8 Panel Earthing checked Yes N/A
9 Confirm that panels are constructed and wired as per SEC relevant specification. Yes N/A
10 Check case cover and gasket for proper seal against dust. Yes N/A

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: