24 kV & 36 kV
AMTED306003EN.indd 1
LBSkit
24 kV & 36 kV
The Schneider Electric group’s experience extends over 30 years in SF6 technology
for Medium Voltage switchgear.
This gives you the advantage of unique experience, that of a world leader,
with over 2,000,000 SF6 Medium Voltage units installed throughout the world.
Putting this experience at your service and remaining attentive to your requirements
is the spirit of active partnership that we want to develop in offering you the LBSkit.
LBSkit is a product to let you develop harmonized functions equipped with SF6
breaking technology switchgear.
These functions allow you to produce all your Medium Voltage substation
requirements up to 36 kV.
The result of in-depth analysis of your requirements, both now and in the future,
LBSkit means that you can take advantage of all the features of both a modern
and proven technology.
Commercial references
PE56350
Iran
Tabesh tablou, Teheran utility
Russia
MEL, Moscow utility
Canada
AVAD, Ontario
Sweden
KL Industry, Eon utility, Fortum
Turkey
CIMTAV, Istanbul
ELTES, Ankara
AYSAN, Ankara
SELEN, Ankara
Algeria
EDIEL, Algier
Thailand
ASEFA, Bangkok
India
Telawne Power Equipments, Bombay
China
Beijing Tongzhou Switchgear
East China Electrical
Guangzhou South Power Group Electrical
2 AMTED306003EN.indd
LBSkit The product’s advantages
24 kV & 36 kV
Upgradability
61003N
Compactness
LBSkit, an optimised product
b Compact components, for reduced increment units
b Rationalised space requirement for switchboard installation.
Maintenance
LBSkit, a product with reduced maintenance
b The active parts (breaking and earthing) are integrated in an SF6-filled,
“sealed for life” unit
b The control mechanisms, are intented to function with reduced maintenance
under normal operating conditions
b Enhanced electrical endurance when breaking.
Ease of installation
LBSkit, a simple product to incorporate
b Reduced dimensions and weights
b A solution adapted to cable connection
b Simplified switchboard busbar connection.
AMTED306003EN.indd 3
LBSkit Technical characteristics
24 kV & 36 kV
16 630 A
12.5 630 A
Disconnector (kA/1 s) 25 630 - 1250 A 1250 A
20 630 - 1250 A
16 630 - 1250 A
12.5 630 - 1250 A
Maximum breaking capacity
Transformer off load (A) 16
Cables off load (A) 31.5 50
Switch and earthing switch 24 kV
Switch (A) 630
Fuse-switch ** (kA) 25 20
The making capacity is equal to 2.5 times the short-time withstand current.
(*) Equipped referring to installation guide, and setting up at an altitude below 1000 m.
(**) Depending on fuse characteristics, and on using of Merlin Gerin Fusarc CF fuses.
Endurance
PE56359
Standards
LBSkit units meet all the following recommendations:
b Switch:
IEC 60265: High voltage switches for rated voltages of 52 kV and above.
b Disconnector:
IEC 62271-102: High-voltage alternating current disconnectors and earthing
switches.
b Switch /disconnector:
IEC 62271-200: A.C. metal-enclosed switchgear and controlgear for rated voltage
above 1 kV and up to including 52 kV.
4 AMTED306003EN.indd
LBSkit Dimensions and weights
24 kV & 36 kV
LBSkit 24 kV
630 A switch - 630 A disconnector Weight: 50 kg
840
DE57151
DE57151
220 200 200 350
213
417,5
190
72
202
940 365
840
DE57151
DE57151
213
417,5
190
72
191
940 365
AMTED306003EN.indd 5
LBSkit Dimensions and weights
24 kV & 36 kV
LBSkit 36 kV
630 A switch - 630 A disconnector (width 750 mm) Weight: 75 kg
1342.5 720
DE58831
DE58832
95 352.5 350 350 700
307.6
136
395.5
207
290
1250 A disconnector (width 750 mm) Weight: 76 kg
1342.5 720
DE58833
DE58834
307.6
136
395.5
207
279
1342.5 970
DE58836
136
395.5
207
290
1342.5 970
DE58838
136
395.5
207
279
6 AMTED306003EN.indd
LBSkit Safety of people
24 kV & 36 kV By switchgear
b Gas tightness
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.4 bar (400 hPa) for LBSkit 24 kV and 1.5 bar (1500 hPa) for LBSkit 36 kV.
It satisfies “sealed pressure system” requirements and seal tightness is always
factory checked.
LBSkit 36 kV
AMTED306003EN.indd 7
LBSkit Safety of people
24 kV & 36 kV By operating mechanism safety
This device has integrated VPIS (Voltage Presence Indicating System) type lights,
in conformity with IEC standard 61958, enabling the presence (or absence) of voltage
to be checked on the cables.
8 AMTED306003EN.indd
LBSkit Operating mechanisms
24 kV & 36 kV
b Switch function
Independent-operation opening or closing by lever or motor.
b Earthing-switch function
Independent-operation opening or closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
b Auxiliary contacts
v switch (2 O + 2 C) *
v switch (2 O + 3 C) and earthing switch (1 O + 1 C).
b Motor option
b Switch function
v independent-operation closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to close.
v independent-operation opening by push-button (O) or trip units.
b Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
b Auxiliary contacts
v switch (2 O + 2 C)
v switch (2 O + 3 C) and earthing switch (1 O + 1 C).
b Opening releases
v shunt trip.
b Switch function
v independent-operation closing in two steps:
1 - operating mechanism recharging by lever or motor
2 - stored energy released by push-button (I) or trip unit.
v independent-operation opening by push-button (O) or trip unit.
b Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
b Auxiliary contacts
v switch (2 O + 2 C) *
v switch (2 O + 3 C) and earthing switch (1 O + 1 C).
b Opening release shunt trip
b Closing release shunt trip
b Motor option
AMTED306003EN.indd 9
LBSkit Auxiliaries
24 kV & 36 kV
Un DC AC (50/60 Hz)
Power supply (V) 24 48 110 220
Motor option
(W) 200
(VA) 200
Operating time for CIT (s) 1 to 2 1 to 2
and charging time for CI2 (s) 4 to 7 4 to 7
Opening releases
Shunt trip (W) 200 250 300
(VA) 750
Response time (ms) 35 35
Closing release
Shunt trip (W) 200 250 300
(VA) 750
Response time (ms) 55 55
10 AMTED306003EN.indd
LBSkit Interlocks
24 kV & 36 kV
Functional interlocks
These comply with IEC recommendation 62271-200.
In addition to the functional interlocks, each disconnector and switch include
built-in padlocking capacities (padlocks not supplied).
Key-type interlocks
O X b To prevent the closing of an earthing switch if the switch of the other unit
has not been locked in the “open” position.
X O
O
MT20240EN
AMTED306003EN.indd 11
LBSkit Installation Guides
24 kV & 36 kV
The Installation Guides have been written for “Panel Builders” who have to design,
realize, inspect and maintain own functions with LBSkit in compliance with
international standards of the International Electrotechnical Commission (IEC).
The Installation Guides are single documents covering the assembly of LBSkit and
related components and recommendations. They are intended for Panel Builders
who want to develop their own functions, then a range using LBSkit.
12 AMTED306003EN.indd
LBSkit 24 kV Selection Guide
Switch unit 1 to 24 kV, 630 A
Coil kits
Coil type: Without Without Without Opening Without Opening/closing Opening/closing
release release release
(included in
motorized
3730304B 3730305B switch)
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Operating mechanism One out of 51238920FA 51238920FB 51238920FB 51238920FE 51238920FE 51238920FE
cover 51238920FA (4 pieces) (4 pieces) (4 pieces) (4 pieces) (4 pieces) (4 pieces)
Metal cover Metal cover Metal cover Metal cover Metal cover Metal cover Metal cover
manufactured manufactured manufactured manufactured manufactured manufactured manufactured
by customer * by customer * by customer * by customer * by customer * by customer * by customer *
AMTED306003EN.indd 13
LBSkit 24 kV Selection Guide
Fuse-switch unit 1 to 24 kV, 630 A
48 VDC 3730109AZ
Coil kits
Coil type: Without Opening release Without Opening/closing release Opening/closing release
(included in motorized
switch)
3730304B 3730305B
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Capacitive divider (3 pieces per unit) 51238495FA (12 pieces) Included in earthing
switch kit (3 pieces)
3730351B 3730351B
Interlocking type: A3 + 3731440 + 3731640
3730352B 3730352B
P1 + 3731440 + 3731640
3730350B 3730350B
C4 + 3731438 + 3731638
+ 3731439 + 3731639
14 AMTED306003EN.indd
LBSkit 24 kV Selection Guide
Disconnector unit 1 to 24 kV
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B
AMTED306003EN.indd 15
LBSkit 24 kV Order form
Components
48 VDC+4AC 1 3730109AV 1
110 VDC+4AC 1 3730109AW 1
220 V 50 Hz+4AC 1 3730109AX 1
Motorized switch CI2 24 VDC+4AC+O/C coils 1 3730109AY 1
48 VDC+4AC+O/C coils 1 3730109AZ 1
110 VDC+4AC+O/C coils 1 3730109BA 1
220 V 50 Hz+4AC+O/C coils 1 3730109BB 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
16 AMTED306003EN.indd
LBSkit 24 kV Order form
Components (continued)
For disconnector
For CS1 4:2O-2C/Switch 1 3730300B 1
DE58843
Coil
For switch or fuse-switch without motor
Coil for CI1 24 VDC 1+1 3730304B + 3730332A 1+1
DE58844
AMTED306003EN.indd 17
LBSkit 24 kV Order form
Components (continued)
DE58848
Fig. 2
Fig. 3
Cable connection for field distributor 3736435 75
DE58850
6 to 8.9 kV VPI62405 14
9 to 17.9 kV VPI62407 14
18 to 24 kV VPI62408 14
3 2 1G
UP
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
18 AMTED306003EN.indd
LBSkit 24 kV Order form
Components (continued)
(complete with mimic 4 covers for switch unit with CI1 51238920FB 1
diagram and shutters) 4 covers for switch unit with CI2 51238920FE 1
4 covers for fuse-switch unit with CI1 51238920FC 1
4 covers for fuse-switch unit with CI2 51238920FF 1
4 covers for disconnector unit with CS1 51238920FD 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
AMTED306003EN.indd 19
20 AMTED306003EN.indd
LBSkit 36 kV Selection Guide
Switch unit 36 kV, 630 A
Coil kits
Coil type: Without Without Without Opening Without Opening/closing Opening/closing
release release release
(included in
motorized
3730304B 3730305B switch)
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
Operating mechanism
cover Metal cover Metal cover Metal cover Metal cover Metal cover Metal cover Metal cover
manufactured manufactured manufactured manufactured manufactured manufactured manufactured
by customer * by customer * by customer * by customer * by customer * by customer * by customer *
AMTED306003EN.indd 21
LBSkit 36 kV Selection Guide
Fuse-switch unit 36 kV, 630 A
48 VDC 51000162X
Coil kits
Coil type: Without Opening release Without Opening/closing release Opening/closing release
(included in motorized
switch)
3730304B 3730305B
Auxiliary voltage: 24 VDC + 3730332A + 3730337A
3730304B 3730305B
48 VDC + 3730333A + 3730338A
3730304B 3730305B
110 VDC-220 VAC + 3730335A + 3730340A
3730351B 3730351B
Interlocking type: A3 + 3731440 + 3731640
3730352B 3730352B
P1 + 3731440 + 3731640
3730350B 3730350B
C4 + 3731438 + 3731638
+ 3731439 + 3731639
22 AMTED306003EN.indd
LBSkit 36 kV Selection Guide
Disconnector unit 36 kV, 630-1250 A
Auxiliary contacts:
4 AC : 2O-2C switch 3730300B
AMTED306003EN.indd 23
LBSkit 36 kV Order form
Components
48 VDC+4AC 1 51000162T 1
110 VDC+4AC 1 51000162U 1
220 V 50 Hz+4AC 1 51000162V 1
Motorized switch CI2 24 VDC+4AC+O/C coils 1 51000162W 1
48 VDC+4AC+O/C coils 1 51000162X 1
110 VDC+4AC+O/C coils 1 51000162Y 1
220 V 50 Hz+4AC+O/C coils 1 51000162Z 1
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
24 AMTED306003EN.indd
LBSkit 36 kV Order form
Components (continued)
For disconnector
For CS1 4:2O-2C/Switch 3730300B 1
DE58843
Coil
For switch or fuse-switch without motor
Coil for CI1 24 VDC 3730304B + 3730332A 1+1
DE58844
AMTED306003EN.indd 25
LBSkit 36 kV Order form
Components (continued)
DE58848
Fig. 2
Fig. 3
Cable connection for field distributor 3736435 75
DE58850
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
26 AMTED306003EN.indd
LBSkit 36 kV Order form
Components (continued)
(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.
AMTED306003EN.indd 27
Notes
28 AMTED306003EN.indd
ART.819791 © Schneider Electric Industries SAS - All rights reserved
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35,rue Joseph Monier of the information given in this publication.
CS 30323
F - 92506 Rueil Malmaison Cedex This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 € Publishing: Schneider Electric Industries SAS
www.schneider-electric.com Design: Schneider Electric Industries SAS
Printing: Imprimerie du Pont de Claix/JPF - Made in France
AMTED306003EN 03-2009