Beruflich Dokumente
Kultur Dokumente
Abstract
A new scheme to classify between large current is drawn by the transformer from
internal fault current and inrush current of supply. Similar condition is encountered when a
power transformer is presented in this paper transformer is energised in parallel with another
conventionally this paper presents a novel transformer already in service, and this situation is
technique for three phase transformer protection, known as sympathetic inrush’. This large current
which the method effectively identify from the source results in the saturation of the
Magnetizing inrush currents from internal fault transformer core.
currents. This technique employs symmetrical
components. When transformer is switched, 1.1 Improved Protection Schemes:
inrush current happens. This current has some This paper proposes an analysis of the
Features, which it is enough for identify itself. In symmetrical components obtained during inrush and
this paper, by extract these features, a new during internal fault conditions, By introducing a
criterion is proposed to discriminate inrush symmetrical component conversion can decouple
currents from internal faults in power three-phase system into three independent sequence
transformers. In faulty time such as switching or equivalent networks, namely positive, negative and
short circuit, the value of negative sequence for zero sequence network. Therefore these three
differential current is different from positive sequence networks can be analyzed separately.
sequence value. Helping this feature, new
criterion is introduced. Simulations show this II. SYMMETRICAL COMPONENTS
criterion works properly in over-flux and CT APPROACH
saturation condition too. The simulated results Under symmetrical load condition fault
presented clearly, the proposed algorithm can absence is characterized by the absence of negative
accurately discriminate between an internal fault and zero sequence currents within the delta winding.
and a magnetizing inrush current in power Internal faults and inrush generate an asymmetrical
transformer protection in all cases. current demand from the supply source, due to the
unbalanced magnetization of the core. It is easier to
Keywords: inrush current, internal fault, analyze the performance of the damaged transformer
Symmetrical component, transformer protection, when it is delta-connected. An internal fault causes a
type of Faults, Transformer energizing, PSCAD distortion in the flux distribution in the locality of
the damaged turn. As a result, the coil e.m.f. when
I. INTRODUCTION damaged is also affected by the fault and thus a
Power transformer forms an important link different current distribution may be observed in the
between generation and transmission of power damaged winding. The voltage distortion in the
system. It is essential that a transformer gives a very damaged coil results in a zero sequence current
stable, reliable and efficient performance during which flows within the delta winding. It has been
normal service. Failure of power transformer found however, that the zero sequence current is not
completely disrupts the supply of area fed from it. due to load or source asymmetries. This zero
When transformer internal faults occur, immediate sequence current is in consequence an indicator of
disconnection of the faulted transformer is necessary the fault existence and the zero sequence current
to avoid extensive damage and preserve power within the delta winding leads to characteristic
system stability The magnetizing inrush occurs in positive and negative sequences values. Either
transformers whenever polarity and magnitude of unbalanced loads or internal faults do generate
residual flux do not agree with polarity and negative sequence currents and the zero sequence
magnitude of instantaneous value of flux. Whenever current within the delta winding implies the arising
there is a large and sudden change in the input of positive and negative sequences in the primary
terminal voltage of a transformer (either due to lines. Finally, line currents at the supply side are
switching-in or due to recovery from external fault), distorted, since the positive and negative sequences
1515 | P a g e
Mr. R.V.Katre, Prof.D.S.Chavan / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp. 1515-1518
found within the delta winding are to be translated in simultaneously during switching event.
the same line sequences. Another zero sequence Consequently, the negative component is not
generation is observed when the transformer is considerably changed in this case. On the other
energized. In such cases, there is an asymmetrical hand, faults are classified into symmetrical and
magnetization of the core, which yields also the asymmetrical parts. The major feature of these faults
circulation of a zero sequence current within the is the large value of the negative component, such
delta winding. As in the case of internal fault, the that there are the theoretical following cases-
instantaneous measurement and transformation of
currents shows that positive and negative currents For phase–ground fault
are also present and therefore faults and inrush may
be detected.
1516 | P a g e
Mr. R.V.Katre, Prof.D.S.Chavan / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp. 1515-1518
during the asymmetrical fault, the negative Main : Graphs
component of current increases and the value of R Ibb Icc Iaa
5.0
is much smaller than that before fault event. Thus, it
4.0
is enough that the threshold value be lower than at
3.0
the value of R in the normal state of the network.
2.0
V. Simulation 1.0
y
algorithm, a part of a distribution system shown in -1.0
Fig.1 is modeled; using the EMTDC/ PSCAD -2.0
package. The network parameter of the 2-bus -3.0
distribution system is illustrated in this figure. -4.0
Several nonfault events are applied to this system -5.0
along with some short circuit events at different time ...
0.000 0.050 0.100 0.150 0.200 0.250 0.300 0.350 0.400 0.450 0.500
times. The simulation results show that how the ...
proposed algorithm could help the overcurrent relay ...
to discriminate fault from nonfault events. The Fig 5.2 (a): Three-phase currents (L-L Fault
following cases are presented here:
• Transformer energizing;
1517 | P a g e
Mr. R.V.Katre, Prof.D.S.Chavan / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp. 1515-1518
Trans. Power Del., vol. 16, no. 2, pp. 281– Senior ion of Member, IEEE, and Reza
285, Apr. 2001. Iravani, Fellow, IEEE
[4] M. A. Rahman and B. Jeyasurya, “A state- [15] Overcurrent Protection Solution based on
of-the-art review of transformer protection symmetrical component Method; Mr. K. K.
algorithms,” IEEE Trans. Power Del., vol. Rajput, Mrs. K. D. Thakur Mrs. C. H.
3, no. 2, pp. 534–544, Apr. 1988. Chavan, Journal of Information ,knowledge
[5] P. Liu, O. P. Malik, C. Chen, G. S. Hope, and research in electronics and
and Y. Guo, “Improved operation of communication engineering, ISSN 0975-
differential protection of power 6779,Nov 10 toOct11,Vol-01,issue-0
transformers for internal faults,” IEEE
Trans. Power Del., vol. 7, no. 4, pp. 1912–
1919, Oct. 1992.
[6] T. S. Sidhu, M. S. Sachdev, H. C. Wood,
and M. Nagpal, “Design, implementation
and testing of a micro-processor-based
high-speed relay for detecting transformer
winding faults,” IEEE Trans. Power Del.,
vol. 7, no. 1, pp. 108–117, sJan. 1992, .
[7] K. Yabe, “Power differential method for
discrimination between fault and
magnetizing inrush current in
transformers,” IEEE Trans. Power Del.,
vol. 3, no. 3, pp. 1109–1117, Jul. 1997.
[8] P. Bastard, M. Meunier, and H. Regal,
“Neural network-based algorithm for power
transformer differential relays,” Proc. Inst.
Elect. Eng. C, vol. 142, no. 4, pp. 386–392,
1995.
[9] M. C. Shin, C. W. Park, and J. H. Kim,
“Fuzzy logic-based for large power
transformer protection,” IEEE Trans.
Power Del., vol. 18, no. 3, pp. 718–724,
Jul. 2003.
A. T. Johns and S. K. Salman, Digital
Protection for Power Systems. Stevenage,
U.K.: Peregrinus, 1995.
[10] S. Emmanouil, M. H. J. Bollen, and I. Y. H.
Gu, “Expert system for classification and
analysis of power system events,” IEEE
Trans. Power Del., vol. 17, no. 2, pp. 423–
428, Apr. 2002.
[11] W. A. Elmore, C. A. Kramer, and S. E.
Zocholl, “Effects of waveform distortion on
protective relays,” IEEE Trans. Ind. Appl.,
vol. 29, no. 2, pp. 404–411, Mar./Apr.
1993.
[12] J. F. Witte, F. P. Decesaro, and S. R.
Mendis, “Damaging long-term over
voltages on industrial capacitor banks due
to transformer energization inrush
currents,” IEEE Trans. Ind. Appl., vol. 30,
no. 4, pp. 1107–1115, Jul./Aug. 1994.
[13] R. Rudenberg, Transient Performance of
Electric Power System. Cambridge, MA:
MIT Press, 1965.
[14] Improved Overcurrent Protection Using
Symmetrical Components Saeed Lotfi-
fard, Student Member, IEEE, Jawad Faiz,
1518 | P a g e