Sie sind auf Seite 1von 8

Type MVTP

Busbar Supervision Relay


Type MVTP
Busbar Supervision Relay

Figure 1:
Type MVTP relay
withdrawn from case

Features be used, or alternatively three connected in series with a high


single-phase units may be preferred. value resistor.
l Integral buswire shorting facility
In earth-fault only busbar protection The secondary output signal of this
l Low ac burden schemes, the single-phase relay is isolating transformer is fed into a
l No external resistors required employed. current to voltage converter, then
l Alarm contacts provided rectified for comparison with a pre-
Description set value.
Application MVTP relays have a setting range of The ac voltage input is continuously
The MVTP relay is available in two 1-16V in 1V steps, adjusted by monitored and when it exceeds the
types: means of a dual in line (DIL) switch level pre-set by means of the DIL
on the relay front panel. Relays are switch setting, the output relay is
l Type MVTP 11 - single phase actuated after a three second delay.
continuously rated at 600V rms and
relay. The hand reset contacts of the output
no external components are
l Type MVTP 31 - three phase required. relay are normally connected across
relay. the buswires of the busbar
The relays have a ventilated
protection thus short-circuiting the
The MVTP provides continuous enclosure fitted to the rear of each
busbar protection relay and
supervision of the buswires in high case to provide extra thermal
rendering the protection of the zone
impedance type busbar protection dissipation for the auxiliary supply
concerned inoperative. On the same
schemes such as those utilising components.
output relay are hand reset contacts
ALSTOM type MCAG 34 and
for alarm purposes.
MFAC 34 relays. It detects open- Operation
circuited buswires as well as open- Operation of the relay is indicated
Isolation from the main CTs is
circuited by a hand resettable mechanical
achieved by an internal transformer
main current transformers. In phase flag.
whose primary winding is
and earth fault busbar protection
schemes the three phase relay may

2
A

P1 S1 P1 S1 C B
Phase rotation
See note 3
S2 S2
P2 P2
a 1
b Power +
c supply 3 Vx
circuits –
n 23
RL1-1 1
VA 24
3
Alarm
RL1-2 2
25 contacts
87 87 87
A B C 4
v v v VB 26
Output RL1 RL1-3 5
Case earth t
27 >Vs circuits 6
RL1-4
1 2 VC 28 7
3 4
5 6 RL1-5 6
7 8 13
+ve
9 10 See note 3 Power 8
14
11 12 –ve supply RL1-6 9
13 14 22 circuits
15 16 11
17 18
19 20 Case earth connection
21 22
23 24
25 26
27 28
Notes
1 (a) CT shorting links make 2 Earthing connections as shown are typical only
Module terminal before (b) & (c) disconnect. 3 CT connections are typical only.
block viewed (b) Short terminals break before (c)
from rear (c) Long terminals

Figure 2:
Typical application diagram: static modular buswires voltage supervision relay, type MVTP 31, with 5 make contacts

Technical Data

Burdens
Measuring circuit – typical burdens
Applied voltage Vac 2 8 14 600
Burden VA 0.01x10 -3 0.7x10-3 2.2x10-3 4.0
Auxiliary supply – typical burdens at the upper rated voltage
Vx rated voltage Output relay Output relay
not energised energised
(V dc) mA W mA W
30/34 24 0.82 90 3.06
48/54 24 1.3 90 4.86
110/125 24 3.0 35 4.37
220/250 24 6.0 35 8.75

Settings
Setting range (VS) 1-16V rms adjusted by means of a
DIL switch in 1V equal steps.
2, 4, 6, 8, 10, 12, 14V

Auxiliary supplies (VX) Rating (V dc) Operative range (V dc)


24/27* 19.2-30.2
30/34 24 -37.5
48/54 37.5-60
110/125 87.5-137.5
220/250 175 -275
* Use a 30/34V relay with a separate
MSTZ 02 dc/dc converter. All relays
are rated continuously at the maximum
voltage in the operative range.

3
Frequency 50 and 60 Hz
Operative range 47-61 Hz
Operating time Fixed at 3 seconds
Contact disengaging time <150ms
Drop off/pick up ratio >85% after 3 second delay
>98% before 3 second delay

Accuracy
Setting ±5% under reference conditions.
Variation with frequency ±2% over operative range
Variation with temperature ±1%/5ºC change
Variation with auxiliary supply Nil

Timer ±5% under reference conditions.


Variation with frequency ±2% over operative range
Variation with temperature ±1%/5ºC change
Variation with auxiliary supply Nil

Contacts Hand reset


Contact combinations 5 make
4 make, 1 break
3 make, 2 break

Contact ratings
Make and carry Make and carry Break
continuously for 3 seconds
AC 1250VA with maxima 7500VA with maxima 1250VA with maxima
of 5 amps and of 30 amps and of 5 amps and
600V 600V 600V

DC 1250 watts with 7500 watts with 100 watts (resistive)


maxima of 5 amps maxima of 30 amps 50 watts (inductive)
and 600V and 600V and maxima of
5 amps and 600V
The hand-reset contacts will carry 150A rms for 0.5 seconds.
Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

Thermal rating
600V rms per phase on all three
phases simultaneously (at any
setting).

High voltage withstand


Dielectric withstand 2kV rms for 1 minute between all
IEC 60255-5: 1977 terminals and case earth.
2kV rms for 1 minute between all
terminals of independent circuits,
with terminals on each independent
circuit connected together.
1kV rms for 1 minute across normally
open contacts.

4
High voltage impulse Three positive and three negative
IEC 60255-5 : 1977 impulses of 5kV peak, 1.2/50µs,
0.5J between all terminals of the
same circuit (except output
contacts), between independent
circuits, and between all terminals
connected together and case earth.
Electrical environment
High frequency disturbance 2.5kV peak between independent
IEC 60255-22-1 : 1988 Class III circuits and between independent
circuits and case earth.
1.0kV peak across terminals of the
same circuit (except metallic
contacts).
1mhz burst decaying to 50% peak
value after 3 to 6 cycles.
Repetition rate: 400 per second.
EMC Compliance Compliance with the European
89/336/EEC Commission Directive on EMC is
claimed via the Technical
Construction File route.
EN 50081-2 : 1994 Generic standards were used to
EN 50082-2 : 1995 establish conformity.
Product safety
73/23/EEC Compliance with the European
Commission Low Voltage Directive.
EN 61010-1 : 1993/A2 : 1995 Compliance is demonstrated by EN
EN 60950 : 1992/A11 : 1997 reference to generic safety standards.

Atmospheric environment
Temperature
IEC 60255-6 : 1988 Storage and transit –25°C to +70°C
Operating –25°C to + 55°C
IEC 60068-2-1 : 1990 Cold
IEC 60068-2-2 : 1974 Dry heat
Humidity
IEC 60068-2-3 : 1969 56 days at 93% RH and 40°C
Enclosure protection
IEC 60529 : 1989 IP50 (dust protected)

Mechanical environment
Vibration
IEC 60255-21-1: 1988 Response class 1

5
Information Required with Order

MVTP 1 C B
Relay type:
Single phase relay 1 1 D
Three phase relay 3 1 F

Auxiliary voltage:
30/34V 0 2 5
48/54V 0 5 0
110/125V 0 7 5
220/250V 1 0 0

Contacts – hand reset:


5 make 1
4 make 1 break 2
3 make 2 break 3

Cases
52
Types MVTP 11 and MVTP 31 are 4 holes Ø4.4
97 23.5
supplied in size 4 and size 6 cases
respectively, as shown in Figures 3
and 4.
168 159
Additional Information
Service Manual R8023
MCAG R6035 Push button
projection 10 max. 99
MFAC R6007 Panel cut-out:
Flush mounting fixing details
High impedance busbar
protection application notes R6142
32 212 25 min.
MSTZO2 R6006

177 157 max.

Reset

103 Flush mounting 11


All dimensions in mm

Figure 3:
MVTP 11. Case outline size 4

6
103.6
149 4 holes 4.4 24

168 159

Push button
projection 10 max. 151
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

155 Flush mounting 11


All dimensions in mm

Figure 4:
MVTP 31. Case outline size 6

7
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: enquiries@pcs.alstom.co.uk Internet: www.alstom.com
©1998 ALSTOM T&D Protection & Control Ltd

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication R-6023I 129830 GSP Printed in England.