Thank you very much for giving us an opportunity to serve you. Please find
enclosed here with the Test Report of Condition Monitoring Tests on Two Nos. of
Transformers,. We have also enclosed Service Bill and the Bill No. is 0282, for the
above work. We request you to settle the same at the earliest.
Kindly arrange to send the “Cheque/DD” in the name of “M/s. Shanthala Power
Limited”, Hubli.
Thanking you.
Yours faithfully,
(Vinoda. N.)
Chief Executive Officer
Enclosures:
I. Test Report: Three Set
1. Transformers Test Report : 21+24=45 Pages
NABL Accredited Laboratory for Transformer Oil Testing (1) BDV (100kV) (2) Water Content
(3) Flash Point (4) Tan Delta (5) Resistivity (6) Sludge (7) Acidity (8) IFT (9) DGA (10) Furan Analysis
Customer’s Address :
Voltage : 132kV/6.9kV
Phase : 3
Oil Temperature : --
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
IR Values in G DC
SL Mode of Voltage PI Absorption
No. Test (kV) Ratio
30th Sec 60th Sec 600th Sec
HV-LV
1 5 3.8 4.0 4.5 1.12 1.05
2 HV-GND
5 2.0 2.1 2.2 1.04 1.05
60 Seconds IR Value
600 Seconds IR Value
DA = -------------------------------
PI = -------------------------------
30 Seconds IR Value
60 Seconds IR Value
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
Name Plate Mode of Test Voltage
Capacitance (pF) Tan Delta (Absolute)
(kV)
R 2.5 244.53 0.00669
Sl No. 51741
Make: CG 5.0 244.49 0.00668
R/V: 142kV 0.00668
YOM: 1999 7.5 244.49
Current: 800A
Type: Condenser 10.0 244.49 0.00668
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
OLTC Current (mA) Measurement of DC Winding Resistance in m
Position Phase (R-N) Phase (Y-N) Phase (B-N)
01 100 4207 3901 3886
02 100 4080 3850 3837
03 100 4040 3804 3789
04 100 4005 3765 3747
05 100 3770 3712 3701
06 100 3640 3660 3657
07 100 3611 3615 4016
08 100 3563 3568 3581
09 100 3516 3522 3537
10 100 3470 3470 3474
11 100 3421 3430 3425
12 100 3378 3380 3386
13 100 3331 3335 3339
14 100 3285 3290 3287
15 100 3235 3238 3259
16 100 3193 3199 3201
17 100 3145 3154 3197
Voltage : 132kV/6.9kV
TEST RESULTS
Tested Phase Applied Voltage Measured Current (mA)
(kV)
5.0
0.5
7.0
1.0
R-N
9.0
1.5
11.0
2.0
12.0
2.5
4.0
0.5
1.0 5.0
2.0 8.0
2.5 9.0
5.0
0.5
7.0
1.0
B-N
9.0
1.5
10.0
2.0
11.0
2.5
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
R 397 13.85
399 15.93
Y
B 399 15.95
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
TRANSFORMER DETAILS:
Voltage : 132kV/6.9kV
TEST RESULTS
Measurement of Turn Ratio
OLTC
Phase Meter
Position Correction Turns Ratio Ø Angle of
Reading
factor (CF) (MRxCF) Deviation
(MR)
R 21.16 1.000 21.16 0.02
01 Y 21.16 1.000 21.16 0.02
B 21.16 1.000 21.16 0.02
R 19.88 1.000 19.88 0.08
02 Y 19.88 1.000 19.88 0.01
B 19.88 1.000 19.88 0.01
R 19.64 1.000 19.64 0.01
03 Y 19.64 1.000 19.64 0.01
B 19.64 1.000 19.64 0.01
R 19.24 1.000 19.24 0.08
04 Y 19.24 1.000 19.24 0.08
B 19.24 1.000 19.24 0.08
R 19.12 1.000 19.12 0.04
05 Y 19.12 1.000 19.12 0.04
B 19.12 1.000 19.12 0.04
R 18.90 1.000 18.90 0.08
06 Y 18.90 1.000 18.90 0.08
B 18.90 1.000 18.90 0.08
Note: 1) for test conditions please refer page No. 24 of 24
2) *Average Temperature → (Winding + Atmospheric) =450+450≈450C
TRANSFORMER DETAILS:
Serial No. : 2698/2
Voltage : 132kV/6.9kV
TEST RESULTS
Measurement of Turn Ratio
OLTC
Phase Meter
Position Correction Turns Ratio Ø Angle of
Reading
factor (CF) (MRxCF) Deviation
(MR)
R 18.68 1.000 18.68 0.08
07 Y 18.68 1.000 18.68 0.08
B 18.68 1.000 18.68 0.08
R 18.46 1.000 18.46 0.08
08 Y 18.46 1.000 18.46 0.08
B 18.46 1.000 18.46 0.08
R 18.12 1.000 18.12 0.08
09 Y 18.12 1.000 18.12 0.08
B 18.12 1.000 18.12 0.08
R 17.90 1.000 17.90 0.08
10 Y 17.90 1.000 17.90 0.08
B 17.90 1.000 17.90 0.08
R 17.60 1.000 17.60 0.06
11 Y 17.60 1.000 17.60 0.06
B 17.60 1.000 17.60 0.06
R 17.42 1.000 17.42 0.06
12 Y 17.42 1.000 17.42 0.06
B 17.42 1.000 17.42 0.06
Note: 1) for test conditions please refer page No. 24 of 24
2) *Average Temperature → (Winding + Atmospheric) =450+450≈450C
TRANSFORMER DETAILS:
Serial No. : 2698/2
Voltage : 132kV/6.9kV
TEST RESULTS
Measurement of Turn Ratio
OLTC
Phase Meter
Position Correction Turns Ratio Ø Angle of
Reading
factor (CF) (MRxCF) Deviation
(MR)
R 17.22 1.000 17.22 0.06
13 Y 17.22 1.000 17.22 0.06
B 17.22 1.000 17.22 0.06
R 16.84 1.000 16.84 0.06
14 Y 16.84 1.000 16.84 0.06
B 16.84 1.000 16.84 0.06
R 16.70 1.000 16.70 0.06
15 Y 16.70 1.000 16.70 0.06
B 16.70 1.000 16.70 0.06
R 16.50 1.000 16.50 0.06
16 Y 16.50 1.000 16.50 0.06
B 16.50 1.000 16.50 0.06
R 16.28 1.000 16.28 0.06
17 Y 16.28 1.000 16.28 0.06
B 16.28 1.000 16.28 0.06
Customer’s Address :
Note:
1. The test results relate only to the sample(s) tested.
2. ND-Not Detected.
3. The Limits for DGA is valid from last date of filtration.
4. If the last date of filtration is not specified the limits for DGA is considered from the Year of
Installation.
5. Any Anomaly / Discrepancy in this test report / certificate should be brought to our notice
within 60 days from the date of issue.
6. The Test Report Not to be reproduced except in full, without written approval from the laboratory.
TRANSFORMER DETAILS:
Serial Number : 2698/2
Customer Identification : Power Transformer -2
Make : Bharath Bijilee
Capacity: : 15MVA
Voltage (HV/MV/LV) : 132kV/6.9kV
Year of Manufacture : 1985
Year of Installation : 1985
Last Date of Filtration : 2008
Our Reference No. : LT-0392/01 (Main Tank-Top)
Date of Sample Collection : 14th May 2009
Date of Receipt of the Sample : 25th May 2009
Sample Tested on : 27th to 30th 2009
Appearance of the Oil : Bright Yellow Colour
Top Oil Temperature : 450C
Winding Temperature : --
Weather Condition : Dry
Condition on Receipt : OK
OIL PARAMETERS:
Reference Standard
IS: 1866: 2000 For Oil in Service
SL Limits TEST
TEST PARAMETERS
NO. 72.5kV-170kV RESULT
Test Method
B-Class
IS: 6792-199250Hz±2Hz
1 Break Down Voltage (BDV)/ Di-
Electrode Type: Brass 70,72,76,6
Electric Strength) in kV, at a
Spherical, Electrode gap: >40kV 74,68=71
Temp: 27.90C, RH: 46%
2.5mm
2 Moisture Content (Water Content) in IS: 13567-1992 Karl Fisher ≤40 ppm 11
ppm, at a Temp: 27.7 0C , RH:47% Titration Method 230±10V
IS: 6262-1971 50Hz±2Hz
Tan Delta (Di–Electric Dissipation Max
Factor) in absolute, at a Temp: 900C, Three terminal cell 1.0 0.012
3 250Vrms\mm: Average voltage
RH: 47% Absolute
gradient in the sample 230±10V
IS: 6103-1971 Three terminal Min
4 Resistivity (Specific Resistance) in Ω- cell250Vrms\mm: Average 0.1 X 10 12
2 x 1012
cm, at a Temp: 900C, RH: 47% voltage gradient in the sample Ω-cm
230±10V
Acidity (Neutralization Number) in Max
5 IS: 1448(P: 2)-1967 0.04
mg KOH/g 0.3 mg KOH/g
IS: 6792-199250Hz±2Hz
1 Break Down Voltage (BDV)/ Di-
Electrode Type: Brass 68,70,78,72
Electric Strength) in kV, at a
Spherical, Electrode gap: >40kV 70=70.66≈7
Temp: 26.30C, RH: 45%
2.5mm
2 Moisture Content (Water Content) in IS: 13567-1992 Karl Fisher ≤40 ppm 11
ppm, at a Temp: 26.9 0C , RH:46% Titration Method 230±10V
IS: 6262-1971 50Hz±2Hz
Tan Delta (Di–Electric Dissipation Max
Factor) in absolute, at a Temp: 900C, Three terminal cell 1.0 0.0088
3 250Vrms\mm: Average voltage
RH: 46% Absolute
gradient in the sample 230±10V
IS: 6103-1971 Three terminal Min
4 Resistivity (Specific Resistance) in Ω- cell250Vrms\mm: Average 0.1 X 10 12
3 x 1012
cm, at a Temp: 900C, RH: 46% voltage gradient in the sample Ω-cm
230±10V
Acidity (Neutralization Number) in Max
5 IS: 1448(P: 2)-1967 0.12
mg KOH/g 0.3 mg KOH/g
IS: 6792-199250Hz±2Hz
1 Break Down Voltage (BDV)/ Di-
Electrode Type: Brass 38,34,42,3
Electric Strength) in kV, at a
Spherical, Electrode gap: >40kV 42,34=37
Temp: 26.80C, RH: 44%
2.5mm
2 Moisture Content (Water Content) in IS: 13567-1992 Karl Fisher ≤40 ppm 27
ppm, at a Temp: 26.6 0C , RH:46% Titration Method 230±10V
IS: 6262-1971 50Hz±2Hz
Tan Delta (Di–Electric Dissipation Max
Factor) in absolute, at a Temp: 900C, Three terminal cell 1.0 0.0081
3 250Vrms\mm: Average voltage
RH: 45% Absolute
gradient in the sample 230±10V
IS: 6103-1971 Three terminal Min
4 Resistivity (Specific Resistance) in Ω- cell250Vrms\mm: Average 0.1 X 10 12
8 x 1012
cm, at a Temp: 900C, RH: 45% voltage gradient in the sample Ω-cm
230±10V
Acidity (Neutralization Number) in Max
5 IS: 1448(P: 2)-1967 0.04
mg KOH/g 0.3 mg KOH/g
Analysis:
Tests on Solid Insulation:
The test results of IR Values, PI & DC absorption ratios are normal considering its age.
The variation of Capacitance values with respect to voltage is normal and the Tan Delta values are
within the permissible limits, i.e. <0.02absolute.
Tests On Core
Magnetization currents are normal.
Magnetic Balance test results are normal.
Test On Bushings:
The variation of Capacitance values with respect to voltage is normal and the Tan Delta values are
within the permissible limits, i.e. <0.007absolute for R&Y- phase. B-phase could not be balanced.
Oil Parameters:
The test parameters of the transformer oil samples are within permissible limits as per IS: 1866- 2000
“The maintenance of transformer oil in service”.
DGA:
The gases generated are within the permissible limits as per relevant Standards.
Furan Analysis:
The total of the Furanic compounds is in the low reliability range.
Conclusion:
Solid insulation is normal.
Conductor and core are normal.
The results of Oil & DGA indicate normal internal condition of the Transformer.
The total of the Furanic compounds is in low reliability range.
B-Phase Bushing could not be balanced.
Recommendation:
All the tests should be carried out after one year to establish the trend analysis of Transformer
& Oil.
All the test results may be retained as bench mark for further analysis.
One more furan test to be conducted within 6 months to know the increasing trend in the
furanic compounds.
B-Phase bushing is in good condition. For normal operation the condenser bushing test tap is
earthed by screw cap with a centre pin which presses on the test tap for test purpose. The Cap
was removed and test tap was connected to C and Tan Delta Bridge for measurement. Most
likely this test Cap is grounded even when Cap is removed. So, C and Tan Delta Bridge
could not be balanced. So, please refer these results to manufacturer for further action. In the
next shutdown one more Megger, Tan Delta and other tests has to be carried out on Bushings.
Customer:
M/s.
“Shanthala”, No-24, Priyadarshini Colony, Gokul Road, Hubli - 580 030. Karnataka (India)
Phone: +91-0836 - 2332540, 2335936, 2335934,Fax: 0836 – 2334908, Mobile: 94481-34362,
E-mail:mkadappa@sify.com,customercare@shanthalaindia.com. Website:
www.shanthalaindia.com
Ref: SPL/CMT-Off Line//2009/ Date:06-10-2009
To,
M/s.
Thank you very much for giving us an opportunity to serve you. Please find
enclosed here with the Test Report of Condition Monitoring Tests on Four Nos. of
Transformers. We have also enclosed Service Bill and the Bill No. is 0635, for the
above work. We request you to settle the same at the earliest.
Kindly arrange to send the “Cheque/DD” in the name of “M/s. Shanthala Power
Limited”, Hubli.
Thanking you.
Yours faithfully,
(Mr.Vinod. N.)
Chief Executive Officer
Enclosures:
I. Test Report:
2. Transformers Test Report : 17+17+17+22=73Pages
3. Calibration Certificates : Annexure
II Bill
4. Service Bill : 02 Page(In Duplicate)
5. Service Tax Certificate : 02 Page
6. Pan No Certificate : 01 Page
NABL Accredited Laboratory for Transformer Oil Testing (1) BDV (100kV) (2) Water Content
(3) Flash Point (4) Tan Delta (5) Resistivity (6) Sludge (7) Acidity (8) IFT (9) DGA (10) Furan Analysis
Voltage : 11000V/433V
Phase : 3
TRANSFORMER DETAILS:
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
TRANSFORMER DETAILS:
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
IR Values in G DC
SL Mode of Voltage PI Absorption
No. Test (kV) 30th Sec 60th Sec 600th Sec Ratio
60-Seconds IR Value
600- Seconds IR Value
DA = -------------------------------
PI = -------------------------------
30-Seconds IR Value
60-Seconds IR Value
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
Sl. No. Mode of Grounded Voltage IR in G
Test Winding (kV) At 60th Sec
0.5 1.2
1.0 1.4
1 HV-LV Nil 2.5 2.0
5.0 3.0
0.5 10.0
1.0 3.0
2 HV-GND LV 2.5 2.75
5.0 3.5
TRANSFORMER DETAILS:
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
Mode of Grounded Voltage Current Capacitance Tan Delta
Test Winding (kV) (mA) (pF) (Absolute)
2.11 04 4089.63 0.00654
HV-LV
Nil 4.23 09 4089.83 0.00658
(UST)
6.35 15 4089.94 0.00666
TRANSFORMER DETAILS:
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
Tested Phase Applied Voltage Measured Current (mA)
(kV)
0.5 10
1.0 15
R-Y 1.5 20
2.0 25
2.5 30
0.5 12
1.0 20
Y-B
1.5 27
2.0 33
2.5 39
0.5 12
1.0 20
B-R
1.5 27
2.0 33
2.5 39
Note: 1) For test conditions please refer page No. 17 of 17
2) *Average Temperature → (Winding + Oil + Atmospheric) =280+280+290≈28.30C
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
Voltage Ratio
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
LV (Neutral)-GND
R-Y Y-B B-R
*Average Temperature
(Winding +Oil+ Atmospheric) : ≈28.30C
Voltage : 11000V/433V
TEST RESULTS
Tap Position : 1
Measured winding
a) HV side: U-V, V-W, W-U
b) LV Side: n1-u1, n1-v1, n1-w1.
Note:
2. ND-Not Detected.
8. The limits for DGA are valid from the last date of filtration.
9. If the last date of filtration is not specified, the limits for DGA are considered from the year of installation.
10. Any Anomaly / Discrepancy in this test report / certificate should be brought to our notice within 60 days from
11. The Test Report not to be reproduced except in full, without written approval from the laboratory
OIL PARAMETERS:
SL Reference Standard-
NO. TEST PARAMETERS IS: 1866: 2000 TEST RESULTS
Limits
Test Method
Kinematic Viscosity (cStr), at 270C IS:1448(P:25)-1976 27cst 5
1
2 Pour Point in 0C IS:1448 (P:10)-1970 Max: -60C -18
3 3
Density in kg/cm at 29.5 C 0
IS:1448(P:16)1990 Max:0.89 g/cm 3 0.825
Tests on Core:
Magnetization Currents are normal.
Excitation current results are normal.
Frequency Response Analysis:
The test results of FRA should be compared with earlier results to arrive at a definite conclusion. How ever taking
present test results as benchmark any further changes can be noticed by conducting FRA test at a later date under
similar conditions.
Oil Parameters:
The tested parameters of the oil sample of this Transformer are within the permissible limits as per IS:1866-2000
“The parameter of Transformer Oil in service”.
DGA:
The gases generated are within the permissible limits as per relevant Standards.
Furan Analysis:
The total of the Furanic compounds is in the normal range.
Conclusion:
Step Voltage results have variation.
Core and Conductor are normal.
Oil and DGA results are normal.
The total of the Furanic compounds is in the normal range.
The test results of FRA may be retained as reference for future guidance.
Recommendation:
All the Condition Monitoring tests should be carried out after one year to establish the trend analysis of
Transformer & Oil.
All the test results may be retained as bench mark for further analysis.
Since the step voltage results have variation, one more test should be repeated within 6 months or as per
your convenience, to know the insulation condition.