Sie sind auf Seite 1von 57

SUBMITTAL

Project

UTECH Hospitality - Synergy


Date

Tuesday, April 02, 2013


Table Of Contents
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit 1 3
Unit Report 4
Performance Summary 5
Acoustic Summary 7
Certified Drawing 8
Guide Specifications 9
Unit Feature Sheet 12
Unit 5 14
Unit Report 15
Performance Summary 16
Acoustic Summary 18
Certified Drawing 19
Guide Specifications 20
Unit Feature Sheet 23
Unit 8 25
Unit Report 26
Performance Summary 27
Acoustic Summary 29
Certified Drawing 30
Guide Specifications 31
Unit Feature Sheet 34
Unit 9 36
Unit Report 37
Performance Summary 38
Acoustic Summary 40
Certified Drawing 41
Guide Specifications 42
Unit Feature Sheet 45
Unit 10 47
Unit Report 48
Performance Summary 49
Acoustic Summary 51
Certified Drawing 52
Guide Specifications 53
Unit Feature Sheet 56

Commercial Split Systems Builder 1.19o Page 2 of 57


Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit 1

Unit 1

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Unit Feature Sheet

Commercial Split Systems Builder 1.19o Page 3 of 57


Unit Report For Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit Report

Indoor Unit Parameters


Unit Quantity: 1
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz

System Parameter
System Quantity: 1
Compressor Type: N/A

Indoor Unit Dimensions and Weight


Unit Length: 4' 1.0''
Unit Width: 2' 4.2''
Unit Height: 4' 8.1''
Unit Shipping Weight: 381 lb
Unit Operating Weight: 390 lb

Warranty Information (Net Price Ea.)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity Unit Master Price

Base Unit - Indoor


40RUSA08A2A9-0A0A0 1 $4,352
Base Unit $4,352
Std Static, Std Motor / Medium Drive 1 $0
Cabinet Paint - None 1 $0

Commercial Split Systems Builder 1.19o Page 4 of 57


Performance Summary For Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Performance Summary

System: 40RUS008
System Quantity: 1
Altitude: 0.0 ft

Indoor Unit Parameters


Unit Quantity: 1
PartNumber: 40RUSA08A2A9-0A0A0
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz
Actual Airflow: 2968.0 CFM
Total Clg Cap.(Gross): 89.0 MBH
Sensible Clg Cap.(Gross): 69.3 MBH
Ent Air DB: 80.0 °F
Ent Air WB: 67.0 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 58.6 °F
Lvg Air WB: 57.6 °F
Lvg Enthalpy: 24.77 BTU/lb
Coil Bypass Factor: 0.092
Fluid Flow Rate: 14.1 gpm
Ent Fluid Temp: 44.0 °F
Lvg Fluid Temp: 56.7 °F
Fluid Rise: 12.7 °F
Fluid PD: 1.9 ft wg
Fluid Type: Fresh Water
Fluid Conc: 0 %

Indoor Unit External Static: 0.60 in wg


Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc Htg Loss: 0.00 in wg
Total External Static: 0.60 in wg

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Fan Speed: 736 RPM
Fan Power: 1.05 BHP
Fan Motor Max: 2.40 BHP
Fan Motor FLA: 2.6 Amps
Motor and Medium Static Drive Required.

Indoor Electrical Data


Unit Voltage: 400-3-50 V-Ph-Hz
Unit MCA: 3.3 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 400-3-50

Acoustics
Sound Power Levels, db re 10E-12 Watts

Commercial Split Systems Builder 1.19o Page 5 of 57


Performance Summary For Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level NA 88.4
63Hz NA 95.3
125Hz NA 91.3
250Hz NA 87.3
500Hz NA 86.3
1000Hz NA 82.3
2000Hz NA 80.3
4000Hz NA 76.3
8000Hz NA NA
Sound Message Sound for rms008

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

40RUS008withStandardCoil
3
1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

5.00BHP
800RPM SC

700RPM
3.70BHP
1
600RPM 2.90BHP
2.40BHP 3.00BHP
2.00BHP
500RPM RP
1.30BHP
1.00BHP
400RPM

0
0 1 2 3 4 5
Airflow(CFM-thousands)
RPM=736 BHP=1.05 MaximumRPM=1200 MaximumHP=3.70
SC-SystemCurve RP-RatedPoint MP-MinimumPoint

Commercial Split Systems Builder 1.19o Page 6 of 57


Acoustic Summary For Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Acoustic Summary

Indoor Unit Parameters:


Tag Name: Unit 1
Unit Model: 40RUS
Unit Size: 26.3 kW
System Type: Chilled Water
External Static Pressure: 0.60 in wg
Fan Speed: 736 RPM
Fan BHP: 1.05 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 95.3 91.3 87.3 86.3 82.3 80.3 76.3 NA 97.8
A-Weighted Sound Power, dBA NA 69.0 75.2 78.7 83.1 82.3 81.5 77.3 NA 88.4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Commercial Split Systems Builder 1.19o Page 7 of 57


Certified Drawing for Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Certified Drawing

Commercial Split Systems Builder 1.19o Page 8 of 57


Guide Specification for Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Guide Specifications

GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 2,400 to 6,000 Cfm (1150 to 5650 L/s), Nominal Airflow, 6 to 30 Tons (21 to 105 kW), Nominal Cooling
Carrier Model Numbers: 40RUA (Direct-Expansion Coil)
40RUS (Chilled Water Coil)
Part 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be capable of
horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with chilled water coil
shall be used in a chilled water circuit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation. Insulation shall
contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s recommendations.
Part 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical configuration.
Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm) disposable air filters, and condensate drain pans for
vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-registered
immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
3. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections
on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of
the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access shall be
from either the right or left side of the unit.
B. Coils:
DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and
Commercial Split Systems Builder 1.19o Page 9 of 57
Guide Specification for Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be
Puron® R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall have a factory-installed bypass
line and check valve assembly around the TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil
tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
C. Operating Characteristics:
Unit shall be capable of providing cfm (L/s) airflow at an external static pressure of in. wg (kPag).
D. Motor:
1. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and installed.
2. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at 5 hp (3.73
kW) shall be protected by a circuit breaker.
3. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload protection or
manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not have conventional
horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the “air-over” location downstream of the
cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors”
above that rating may be applied.
4. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy Policy Act of
1992 (EPACT), effective October 24, 1997.
E. Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static pressure
requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fins bonded to the tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 150 psig (1034 kPag).
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be
mounted in a galvanized steel housing and shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260°F (138 kPag at 126°C).
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz shall be factory-supplied for field installation as shown on the equipment
drawings. Electric heat assembly shall be ETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-point power wiring.
Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel.
Electric heaters shall not be used with air discharge plenum.

Commercial Split Systems Builder 1.19o Page 10 of 57


Guide Specification for Unit 1
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

6. Air Discharge Plenum:


Plenum shall be factory-supplied to provide free-blow air distribution for vertical floor-mounted units. A grille with moveable vanes for
horizontal or vertical airflow adjustment shall be included. Plenum shall be field-assembled and field-installed on the unit’s fan deck for
blow-thru air distribution. Plenum shall not be used with electric heaters.
7. Return-Air Grille:
Grille shall be factory-supplied for field installation on the unit’s return air opening.
8. Unit Subbase:
Subbase assembly shall be factory-supplied for field installation. Subbase shall elevate floor-mounted vertical units to provide access for
correct condensate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be factory provided for field installation on either return air opening of air handler.
For free cooling applications, economizer shall be compatible with separate thermostat; economizer dampers shall open when outdoor
air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2 sensor accessory; economizer dampers shall
open when indoor CO2 level rises above predetermined set point. Economizer shall include enthalpy control and damper actuator.
10. Thermostat Controls:
a. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, °F/°C capability, and
CCN (Carrier Comfort Network™) compatibility.
b. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD temperature
display.
11. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
12. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds the predetermined setpoint. Sensor
shall have the capability of being connected to Comfort System relay pack or to economizer using field-supplied and field-installed
Honeywell dc adapter no. Q769C1004.
13. Condensate Drain Trap:
Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for
connection to an alarm if desired.
14. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using a
45°F (7.2°C) airstream moving at not less than 400 fpm (189 liters/sec.) shall measure individual lamp output. Lamp output at 253.7
nm shall not be less than 10µW/cm2 per inch of arc length measured at a distance of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to the emitters and are capable of producing the
specified output intensity with an input power no more than 80 watts.
c. Emitters and fixtures shall be installed in sufficient quantity and arranged so as to provide an equal distribution of UV-C energy on
the coil and drain pan.
d. The minimum UV-C energy striking the leading edge of the coil fins shall be not less than 820 µW/cm2 at the closest point and
through placement, not less than 60% of that value at the farthest point. Equal amounts are to strike the drain pan, either directly or
indirectly through reflection.

GS40RU-02PD
10/09

Commercial Split Systems Builder 1.19o Page 11 of 57


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


40RUS CHILLED WATER PACKAGED AIR-HANDLING UNITS

The 40RUS units are compact chilled water packaged air-handling units offering the ultimate
in installation ease and flexibility. 40RUS units range from 7-1/2 to 15 tons in capacity. These
units may be installed in either the vertical or horizontal configuration with no modifications.
Powerful fan systems allow easy adaptation to existing ductwork. Heating capability is
provided by accessory electric heaters, hot water coils, or steam coils.

40RUS 7-1/2 TO 10 TON CHASSIS SHOWN

Commercial Split Systems Builder 1.19o Page 12 of 57


STANDARD FEATURES

1. Cleanable insulation treated with an anti-microbial agent.


2. Two sloped condensate pans on each unit for horizontal or vertical applications.
3. 2 inch filters.
4. Powerful belt-driven forward curved fans.
5. Factory-installed fan motor and contactor.
6. Easy maintenance -- removal of a single panel allows access to virtually all components.
7. Single blower on 08-12 sizes; dual blower on 14-16 sizes.
8. 24 volt terminal block for control wiring connections.
9. Standard one-year warranty.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.19o Page 13 of 57


Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit 5

Unit 5

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Unit Feature Sheet

Commercial Split Systems Builder 1.19o Page 14 of 57


Unit Report For Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit Report

Indoor Unit Parameters


Unit Quantity: 1
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz

System Parameter
System Quantity: 1
Compressor Type: N/A

Indoor Unit Dimensions and Weight


Unit Length: 4' 1.0''
Unit Width: 2' 4.2''
Unit Height: 4' 8.1''
Unit Shipping Weight: 381 lb
Unit Operating Weight: 390 lb

Warranty Information (Net Price Ea.)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity Unit Master Price

Base Unit - Indoor


40RUSA08A2A9-0A0A0 1 $4,352
Base Unit $4,352
Std Static, Std Motor / Medium Drive 1 $0
Cabinet Paint - None 1 $0

Commercial Split Systems Builder 1.19o Page 15 of 57


Performance Summary For Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Performance Summary

System: 40RUS008
System Quantity: 1
Altitude: 0.0 ft

Indoor Unit Parameters


Unit Quantity: 1
PartNumber: 40RUSA08A2A9-0A0A0
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz
Actual Airflow: 3232.0 CFM
Total Clg Cap.(Gross): 97.0 MBH
Sensible Clg Cap.(Gross): 75.1 MBH
Ent Air DB: 80.0 °F
Ent Air WB: 67.0 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 58.7 °F
Lvg Air WB: 57.6 °F
Lvg Enthalpy: 24.77 BTU/lb
Coil Bypass Factor: 0.101
Fluid Flow Rate: 17.0 gpm
Ent Fluid Temp: 45.0 °F
Lvg Fluid Temp: 56.4 °F
Fluid Rise: 11.4 °F
Fluid PD: 2.7 ft wg
Fluid Type: Fresh Water
Fluid Conc: 0 %

Indoor Unit External Static: 0.60 in wg


Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc Htg Loss: 0.00 in wg
Total External Static: 0.60 in wg

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Fan Speed: 768 RPM
Fan Power: 1.26 BHP
Fan Motor Max: 2.40 BHP
Fan Motor FLA: 2.6 Amps
Motor and Medium Static Drive Required.

Indoor Electrical Data


Unit Voltage: 400-3-50 V-Ph-Hz
Unit MCA: 3.3 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 400-3-50

Acoustics
Sound Power Levels, db re 10E-12 Watts

Commercial Split Systems Builder 1.19o Page 16 of 57


Performance Summary For Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level NA 88.4
63Hz NA 95.3
125Hz NA 91.3
250Hz NA 87.3
500Hz NA 86.3
1000Hz NA 82.3
2000Hz NA 80.3
4000Hz NA 76.3
8000Hz NA NA
Sound Message Sound for rms008

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

40RUS008withStandardCoil
3
1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

5.00BHP
800RPM
SC

700RPM
3.70BHP
1
600RPM 2.90BHP
2.40BHP 3.00BHP
2.00BHP
500RPM RP
1.30BHP
1.00BHP
400RPM

0
0 1 2 3 4 5
Airflow(CFM-thousands)
RPM=768 BHP=1.26 MaximumRPM=1200 MaximumHP=3.70
SC-SystemCurve RP-RatedPoint MP-MinimumPoint

Commercial Split Systems Builder 1.19o Page 17 of 57


Acoustic Summary For Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Acoustic Summary

Indoor Unit Parameters:


Tag Name: Unit 5
Unit Model: 40RUS
Unit Size: 26.3 kW
System Type: Chilled Water
External Static Pressure: 0.60 in wg
Fan Speed: 768 RPM
Fan BHP: 1.26 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 95.3 91.3 87.3 86.3 82.3 80.3 76.3 NA 97.8
A-Weighted Sound Power, dBA NA 69.0 75.2 78.7 83.1 82.3 81.5 77.3 NA 88.4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Commercial Split Systems Builder 1.19o Page 18 of 57


Certified Drawing for Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Certified Drawing

Commercial Split Systems Builder 1.19o Page 19 of 57


Guide Specification for Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Guide Specifications

GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 2,400 to 6,000 Cfm (1150 to 5650 L/s), Nominal Airflow, 6 to 30 Tons (21 to 105 kW), Nominal Cooling
Carrier Model Numbers: 40RUA (Direct-Expansion Coil)
40RUS (Chilled Water Coil)
Part 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be capable of
horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with chilled water coil
shall be used in a chilled water circuit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation. Insulation shall
contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s recommendations.
Part 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical configuration.
Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm) disposable air filters, and condensate drain pans for
vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-registered
immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
3. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections
on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of
the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access shall be
from either the right or left side of the unit.
B. Coils:
DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and
Commercial Split Systems Builder 1.19o Page 20 of 57
Guide Specification for Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be
Puron® R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall have a factory-installed bypass
line and check valve assembly around the TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil
tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
C. Operating Characteristics:
Unit shall be capable of providing cfm (L/s) airflow at an external static pressure of in. wg (kPag).
D. Motor:
1. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and installed.
2. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at 5 hp (3.73
kW) shall be protected by a circuit breaker.
3. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload protection or
manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not have conventional
horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the “air-over” location downstream of the
cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors”
above that rating may be applied.
4. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy Policy Act of
1992 (EPACT), effective October 24, 1997.
E. Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static pressure
requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fins bonded to the tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 150 psig (1034 kPag).
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be
mounted in a galvanized steel housing and shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260°F (138 kPag at 126°C).
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz shall be factory-supplied for field installation as shown on the equipment
drawings. Electric heat assembly shall be ETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-point power wiring.
Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel.
Electric heaters shall not be used with air discharge plenum.

Commercial Split Systems Builder 1.19o Page 21 of 57


Guide Specification for Unit 5
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

6. Air Discharge Plenum:


Plenum shall be factory-supplied to provide free-blow air distribution for vertical floor-mounted units. A grille with moveable vanes for
horizontal or vertical airflow adjustment shall be included. Plenum shall be field-assembled and field-installed on the unit’s fan deck for
blow-thru air distribution. Plenum shall not be used with electric heaters.
7. Return-Air Grille:
Grille shall be factory-supplied for field installation on the unit’s return air opening.
8. Unit Subbase:
Subbase assembly shall be factory-supplied for field installation. Subbase shall elevate floor-mounted vertical units to provide access for
correct condensate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be factory provided for field installation on either return air opening of air handler.
For free cooling applications, economizer shall be compatible with separate thermostat; economizer dampers shall open when outdoor
air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2 sensor accessory; economizer dampers shall
open when indoor CO2 level rises above predetermined set point. Economizer shall include enthalpy control and damper actuator.
10. Thermostat Controls:
a. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, °F/°C capability, and
CCN (Carrier Comfort Network™) compatibility.
b. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD temperature
display.
11. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
12. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds the predetermined setpoint. Sensor
shall have the capability of being connected to Comfort System relay pack or to economizer using field-supplied and field-installed
Honeywell dc adapter no. Q769C1004.
13. Condensate Drain Trap:
Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for
connection to an alarm if desired.
14. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using a
45°F (7.2°C) airstream moving at not less than 400 fpm (189 liters/sec.) shall measure individual lamp output. Lamp output at 253.7
nm shall not be less than 10µW/cm2 per inch of arc length measured at a distance of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to the emitters and are capable of producing the
specified output intensity with an input power no more than 80 watts.
c. Emitters and fixtures shall be installed in sufficient quantity and arranged so as to provide an equal distribution of UV-C energy on
the coil and drain pan.
d. The minimum UV-C energy striking the leading edge of the coil fins shall be not less than 820 µW/cm2 at the closest point and
through placement, not less than 60% of that value at the farthest point. Equal amounts are to strike the drain pan, either directly or
indirectly through reflection.

GS40RU-02PD
10/09

Commercial Split Systems Builder 1.19o Page 22 of 57


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


40RUS CHILLED WATER PACKAGED AIR-HANDLING UNITS

The 40RUS units are compact chilled water packaged air-handling units offering the ultimate
in installation ease and flexibility. 40RUS units range from 7-1/2 to 15 tons in capacity. These
units may be installed in either the vertical or horizontal configuration with no modifications.
Powerful fan systems allow easy adaptation to existing ductwork. Heating capability is
provided by accessory electric heaters, hot water coils, or steam coils.

40RUS 7-1/2 TO 10 TON CHASSIS SHOWN

Commercial Split Systems Builder 1.19o Page 23 of 57


STANDARD FEATURES

10. Cleanable insulation treated with an anti-microbial agent.


11. Two sloped condensate pans on each unit for horizontal or vertical applications.
12. 2 inch filters.
13. Powerful belt-driven forward curved fans.
14. Factory-installed fan motor and contactor.
15. Easy maintenance -- removal of a single panel allows access to virtually all components.
16. Single blower on 08-12 sizes; dual blower on 14-16 sizes.
17. 24 volt terminal block for control wiring connections.
18. Standard one-year warranty.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.19o Page 24 of 57


Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit 8

Unit 8

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Unit Feature Sheet

Commercial Split Systems Builder 1.19o Page 25 of 57


Unit Report For Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit Report

Indoor Unit Parameters


Unit Quantity: 1
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz

System Parameter
System Quantity: 1
Compressor Type: N/A

Indoor Unit Dimensions and Weight


Unit Length: 4' 1.0''
Unit Width: 2' 4.2''
Unit Height: 4' 8.1''
Unit Shipping Weight: 381 lb
Unit Operating Weight: 390 lb

Warranty Information (Net Price Ea.)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity Unit Master Price

Base Unit - Indoor


40RUSA08A2A9-0A0A0 1 $4,352
Base Unit $4,352
Std Static, Std Motor / Medium Drive 1 $0
Cabinet Paint - None 1 $0

Commercial Split Systems Builder 1.19o Page 26 of 57


Performance Summary For Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Performance Summary

System: 40RUS008
System Quantity: 1
Altitude: 0.0 ft

Indoor Unit Parameters


Unit Quantity: 1
PartNumber: 40RUSA08A2A9-0A0A0
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz
Actual Airflow: 2760.0 CFM
Total Clg Cap.(Gross): 82.8 MBH
Sensible Clg Cap.(Gross): 64.7 MBH
Ent Air DB: 80.0 °F
Ent Air WB: 67.0 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 58.5 °F
Lvg Air WB: 57.6 °F
Lvg Enthalpy: 24.77 BTU/lb
Coil Bypass Factor: 0.085
Fluid Flow Rate: 13.8 gpm
Ent Fluid Temp: 45.0 °F
Lvg Fluid Temp: 57.0 °F
Fluid Rise: 12.0 °F
Fluid PD: 1.8 ft wg
Fluid Type: Fresh Water
Fluid Conc: 0 %

Indoor Unit External Static: 0.60 in wg


Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc Htg Loss: 0.00 in wg
Total External Static: 0.60 in wg

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Fan Speed: 712 RPM
Fan Power: 0.91 BHP
Fan Motor Max: 2.40 BHP
Fan Motor FLA: 2.6 Amps
Motor and Medium Static Drive Required.

Indoor Electrical Data


Unit Voltage: 400-3-50 V-Ph-Hz
Unit MCA: 3.3 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 400-3-50

Acoustics
Sound Power Levels, db re 10E-12 Watts

Commercial Split Systems Builder 1.19o Page 27 of 57


Performance Summary For Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level NA 88.4
63Hz NA 95.3
125Hz NA 91.3
250Hz NA 87.3
500Hz NA 86.3
1000Hz NA 82.3
2000Hz NA 80.3
4000Hz NA 76.3
8000Hz NA NA
Sound Message Sound for rms008

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

40RUS008withStandardCoil
3
1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

5.00BHP
800RPM SC

700RPM
3.70BHP
1
600RPM 2.90BHP
2.40BHP 3.00BHP
2.00BHP
500RPM RP
1.30BHP
1.00BHP
400RPM

0
0 1 2 3 4 5
Airflow(CFM-thousands)
RPM=712 BHP=0.91 MaximumRPM=1200 MaximumHP=3.70
SC-SystemCurve RP-RatedPoint MP-MinimumPoint

Commercial Split Systems Builder 1.19o Page 28 of 57


Acoustic Summary For Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Acoustic Summary

Indoor Unit Parameters:


Tag Name: Unit 8
Unit Model: 40RUS
Unit Size: 26.3 kW
System Type: Chilled Water
External Static Pressure: 0.60 in wg
Fan Speed: 712 RPM
Fan BHP: 0.91 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 95.3 91.3 87.3 86.3 82.3 80.3 76.3 NA 97.8
A-Weighted Sound Power, dBA NA 69.0 75.2 78.7 83.1 82.3 81.5 77.3 NA 88.4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Commercial Split Systems Builder 1.19o Page 29 of 57


Certified Drawing for Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Certified Drawing

Commercial Split Systems Builder 1.19o Page 30 of 57


Guide Specification for Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Guide Specifications

GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 2,400 to 6,000 Cfm (1150 to 5650 L/s), Nominal Airflow, 6 to 30 Tons (21 to 105 kW), Nominal Cooling
Carrier Model Numbers: 40RUA (Direct-Expansion Coil)
40RUS (Chilled Water Coil)
Part 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be capable of
horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with chilled water coil
shall be used in a chilled water circuit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation. Insulation shall
contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s recommendations.
Part 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical configuration.
Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm) disposable air filters, and condensate drain pans for
vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-registered
immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
3. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections
on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of
the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access shall be
from either the right or left side of the unit.
B. Coils:
DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and
Commercial Split Systems Builder 1.19o Page 31 of 57
Guide Specification for Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be
Puron® R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall have a factory-installed bypass
line and check valve assembly around the TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil
tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
C. Operating Characteristics:
Unit shall be capable of providing cfm (L/s) airflow at an external static pressure of in. wg (kPag).
D. Motor:
1. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and installed.
2. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at 5 hp (3.73
kW) shall be protected by a circuit breaker.
3. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload protection or
manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not have conventional
horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the “air-over” location downstream of the
cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors”
above that rating may be applied.
4. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy Policy Act of
1992 (EPACT), effective October 24, 1997.
E. Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static pressure
requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fins bonded to the tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 150 psig (1034 kPag).
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be
mounted in a galvanized steel housing and shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260°F (138 kPag at 126°C).
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz shall be factory-supplied for field installation as shown on the equipment
drawings. Electric heat assembly shall be ETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-point power wiring.
Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel.
Electric heaters shall not be used with air discharge plenum.

Commercial Split Systems Builder 1.19o Page 32 of 57


Guide Specification for Unit 8
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

6. Air Discharge Plenum:


Plenum shall be factory-supplied to provide free-blow air distribution for vertical floor-mounted units. A grille with moveable vanes for
horizontal or vertical airflow adjustment shall be included. Plenum shall be field-assembled and field-installed on the unit’s fan deck for
blow-thru air distribution. Plenum shall not be used with electric heaters.
7. Return-Air Grille:
Grille shall be factory-supplied for field installation on the unit’s return air opening.
8. Unit Subbase:
Subbase assembly shall be factory-supplied for field installation. Subbase shall elevate floor-mounted vertical units to provide access for
correct condensate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be factory provided for field installation on either return air opening of air handler.
For free cooling applications, economizer shall be compatible with separate thermostat; economizer dampers shall open when outdoor
air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2 sensor accessory; economizer dampers shall
open when indoor CO2 level rises above predetermined set point. Economizer shall include enthalpy control and damper actuator.
10. Thermostat Controls:
a. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, °F/°C capability, and
CCN (Carrier Comfort Network™) compatibility.
b. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD temperature
display.
11. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
12. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds the predetermined setpoint. Sensor
shall have the capability of being connected to Comfort System relay pack or to economizer using field-supplied and field-installed
Honeywell dc adapter no. Q769C1004.
13. Condensate Drain Trap:
Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for
connection to an alarm if desired.
14. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using a
45°F (7.2°C) airstream moving at not less than 400 fpm (189 liters/sec.) shall measure individual lamp output. Lamp output at 253.7
nm shall not be less than 10µW/cm2 per inch of arc length measured at a distance of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to the emitters and are capable of producing the
specified output intensity with an input power no more than 80 watts.
c. Emitters and fixtures shall be installed in sufficient quantity and arranged so as to provide an equal distribution of UV-C energy on
the coil and drain pan.
d. The minimum UV-C energy striking the leading edge of the coil fins shall be not less than 820 µW/cm2 at the closest point and
through placement, not less than 60% of that value at the farthest point. Equal amounts are to strike the drain pan, either directly or
indirectly through reflection.

GS40RU-02PD
10/09

Commercial Split Systems Builder 1.19o Page 33 of 57


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


40RUS CHILLED WATER PACKAGED AIR-HANDLING UNITS

The 40RUS units are compact chilled water packaged air-handling units offering the ultimate
in installation ease and flexibility. 40RUS units range from 7-1/2 to 15 tons in capacity. These
units may be installed in either the vertical or horizontal configuration with no modifications.
Powerful fan systems allow easy adaptation to existing ductwork. Heating capability is
provided by accessory electric heaters, hot water coils, or steam coils.

40RUS 7-1/2 TO 10 TON CHASSIS SHOWN

Commercial Split Systems Builder 1.19o Page 34 of 57


STANDARD FEATURES

19. Cleanable insulation treated with an anti-microbial agent.


20. Two sloped condensate pans on each unit for horizontal or vertical applications.
21. 2 inch filters.
22. Powerful belt-driven forward curved fans.
23. Factory-installed fan motor and contactor.
24. Easy maintenance -- removal of a single panel allows access to virtually all components.
25. Single blower on 08-12 sizes; dual blower on 14-16 sizes.
26. 24 volt terminal block for control wiring connections.
27. Standard one-year warranty.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.19o Page 35 of 57


Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit 9

Unit 9

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Unit Feature Sheet

Commercial Split Systems Builder 1.19o Page 36 of 57


Unit Report For Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit Report

Indoor Unit Parameters


Unit Quantity: 1
Unit Model: 40RUS
Unit Size: 70.3 kW
No. of Splits: 2
Voltage: 400-3-50 V-Ph-Hz

System Parameter
System Quantity: 1
Compressor Type: N/A

Indoor Unit Dimensions and Weight


Unit Length: 7' 5.0''
Unit Width: 2' 4.2''
Unit Height: 4' 8.1''
Unit Shipping Weight: 670 lb
Unit Operating Weight: 683 lb

Warranty Information (Net Price Ea.)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity Unit Master Price

Base Unit - Indoor


40RUSA25A4A9-0A0A0 1 $8,428
Base Unit $8,428
Std Static, High Eff Motor/Std Drive 1 $0
Cabinet Paint - None 1 $0

Commercial Split Systems Builder 1.19o Page 37 of 57


Performance Summary For Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Performance Summary

System: 40RUS025
System Quantity: 1
Altitude: 0.0 ft

Indoor Unit Parameters


Unit Quantity: 1
PartNumber: 40RUSA25A4A9-0A0A0
Unit Model: 40RUS
Unit Size: 70.3 kW
No. of Splits: 2
Voltage: 400-3-50 V-Ph-Hz
Actual Airflow: 8068.0 CFM
Total Clg Cap.(Gross): 242.0 MBH
Sensible Clg Cap.(Gross): 182.5 MBH
Ent Air DB: 80.0 °F
Ent Air WB: 67.0 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 59.3 °F
Lvg Air WB: 57.6 °F
Lvg Enthalpy: 24.77 BTU/lb
Coil Bypass Factor: 0.149
Fluid Flow Rate: 43.4 gpm
Ent Fluid Temp: 45.0 °F
Lvg Fluid Temp: 56.1 °F
Fluid Rise: 11.1 °F
Fluid PD: 6.3 ft wg
Fluid Type: Fresh Water
Fluid Conc: 0 %

Indoor Unit External Static: 0.60 in wg


Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc Htg Loss: 0.00 in wg
Total External Static: 0.60 in wg

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Fan Speed: 827 RPM
Fan Power: 3.86 BHP
Fan Motor Max: 5.00 BHP
Fan Motor FLA: 7.6 Amps
Motor and Standard Drive Required.

Indoor Electrical Data


Unit Voltage: 400-3-50 V-Ph-Hz
Unit MCA: 9.5 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 400-3-50

Acoustics
Sound Power Levels, db re 10E-12 Watts

Commercial Split Systems Builder 1.19o Page 38 of 57


Performance Summary For Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level NA 96.4
63Hz NA 102.6
125Hz NA 98.6
250Hz NA 94.6
500Hz NA 95.6
1000Hz NA 89.6
2000Hz NA 87.6
4000Hz NA 83.6
8000Hz NA NA
Sound Message Sound for rms024

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

40RUS025withStandardcoil
4

1200RPM

3
1100RPM
Static Pressure (in. wg.)

1000RPM

2 900RPM
SC

800RPM

700RPM

1
600RPM

500RPM RP

400RPM
7.50BHP 10.00BHP
3.70BHP 5.00BHP

0
0 2 4 6 8 10 12 14
Airflow(CFM-thousands)
RPM=827 BHP=3.86 MaximumRPM=1200 MaximumHP=10.00
SC-SystemCurve RP-RatedPoint MP-MinimumPoint

Commercial Split Systems Builder 1.19o Page 39 of 57


Acoustic Summary For Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Acoustic Summary

Indoor Unit Parameters:


Tag Name: Unit 9
Unit Model: 40RUS
Unit Size: 70.3 kW
System Type: Chilled Water
External Static Pressure: 0.60 in wg
Fan Speed: 827 RPM
Fan BHP: 3.86 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 102.6 98.6 94.6 95.6 89.6 87.6 83.6 NA 105.3
A-Weighted Sound Power, dBA NA 76.3 82.5 86.0 92.4 89.6 88.8 84.6 NA 96.4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Commercial Split Systems Builder 1.19o Page 40 of 57


Certified Drawing for Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Certified Drawing

Commercial Split Systems Builder 1.19o Page 41 of 57


Guide Specification for Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Guide Specifications

GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 2,400 to 6,000 Cfm (1150 to 5650 L/s), Nominal Airflow, 6 to 30 Tons (21 to 105 kW), Nominal Cooling
Carrier Model Numbers: 40RUA (Direct-Expansion Coil)
40RUS (Chilled Water Coil)
Part 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be capable of
horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with chilled water coil
shall be used in a chilled water circuit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation. Insulation shall
contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s recommendations.
Part 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical configuration.
Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm) disposable air filters, and condensate drain pans for
vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-registered
immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
3. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections
on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of
the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access shall be
from either the right or left side of the unit.
B. Coils:
DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and
Commercial Split Systems Builder 1.19o Page 42 of 57
Guide Specification for Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be
Puron® R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall have a factory-installed bypass
line and check valve assembly around the TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil
tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
C. Operating Characteristics:
Unit shall be capable of providing cfm (L/s) airflow at an external static pressure of in. wg (kPag).
D. Motor:
1. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and installed.
2. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at 5 hp (3.73
kW) shall be protected by a circuit breaker.
3. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload protection or
manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not have conventional
horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the “air-over” location downstream of the
cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors”
above that rating may be applied.
4. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy Policy Act of
1992 (EPACT), effective October 24, 1997.
E. Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static pressure
requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fins bonded to the tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 150 psig (1034 kPag).
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be
mounted in a galvanized steel housing and shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260°F (138 kPag at 126°C).
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz shall be factory-supplied for field installation as shown on the equipment
drawings. Electric heat assembly shall be ETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-point power wiring.
Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel.
Electric heaters shall not be used with air discharge plenum.

Commercial Split Systems Builder 1.19o Page 43 of 57


Guide Specification for Unit 9
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

6. Air Discharge Plenum:


Plenum shall be factory-supplied to provide free-blow air distribution for vertical floor-mounted units. A grille with moveable vanes for
horizontal or vertical airflow adjustment shall be included. Plenum shall be field-assembled and field-installed on the unit’s fan deck for
blow-thru air distribution. Plenum shall not be used with electric heaters.
7. Return-Air Grille:
Grille shall be factory-supplied for field installation on the unit’s return air opening.
8. Unit Subbase:
Subbase assembly shall be factory-supplied for field installation. Subbase shall elevate floor-mounted vertical units to provide access for
correct condensate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be factory provided for field installation on either return air opening of air handler.
For free cooling applications, economizer shall be compatible with separate thermostat; economizer dampers shall open when outdoor
air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2 sensor accessory; economizer dampers shall
open when indoor CO2 level rises above predetermined set point. Economizer shall include enthalpy control and damper actuator.
10. Thermostat Controls:
a. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, °F/°C capability, and
CCN (Carrier Comfort Network™) compatibility.
b. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD temperature
display.
11. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
12. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds the predetermined setpoint. Sensor
shall have the capability of being connected to Comfort System relay pack or to economizer using field-supplied and field-installed
Honeywell dc adapter no. Q769C1004.
13. Condensate Drain Trap:
Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for
connection to an alarm if desired.
14. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using a
45°F (7.2°C) airstream moving at not less than 400 fpm (189 liters/sec.) shall measure individual lamp output. Lamp output at 253.7
nm shall not be less than 10µW/cm2 per inch of arc length measured at a distance of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to the emitters and are capable of producing the
specified output intensity with an input power no more than 80 watts.
c. Emitters and fixtures shall be installed in sufficient quantity and arranged so as to provide an equal distribution of UV-C energy on
the coil and drain pan.
d. The minimum UV-C energy striking the leading edge of the coil fins shall be not less than 820 µW/cm2 at the closest point and
through placement, not less than 60% of that value at the farthest point. Equal amounts are to strike the drain pan, either directly or
indirectly through reflection.

GS40RU-02PD
10/09

Commercial Split Systems Builder 1.19o Page 44 of 57


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


40RUS CHILLED WATER PACKAGED AIR-HANDLING UNITS

The 40RUS units are compact chilled water packaged air-handling units offering the ultimate
in installation ease and flexibility. 40RUS units range from 7-1/2 to 15 tons in capacity. These
units may be installed in either the vertical or horizontal configuration with no modifications.
Powerful fan systems allow easy adaptation to existing ductwork. Heating capability is
provided by accessory electric heaters, hot water coils, or steam coils.

40RUS 7-1/2 TO 10 TON CHASSIS SHOWN

Commercial Split Systems Builder 1.19o Page 45 of 57


STANDARD FEATURES

28. Cleanable insulation treated with an anti-microbial agent.


29. Two sloped condensate pans on each unit for horizontal or vertical applications.
30. 2 inch filters.
31. Powerful belt-driven forward curved fans.
32. Factory-installed fan motor and contactor.
33. Easy maintenance -- removal of a single panel allows access to virtually all components.
34. Single blower on 08-12 sizes; dual blower on 14-16 sizes.
35. 24 volt terminal block for control wiring connections.
36. Standard one-year warranty.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.19o Page 46 of 57


Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit 10

Unit 10

Submittal Cover Sheet


Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Guide Specifications
Unit Feature Sheet

Commercial Split Systems Builder 1.19o Page 47 of 57


Unit Report For Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Unit Report

Indoor Unit Parameters


Unit Quantity: 1
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz

System Parameter
System Quantity: 1
Compressor Type: N/A

Indoor Unit Dimensions and Weight


Unit Length: 4' 1.0''
Unit Width: 2' 4.2''
Unit Height: 4' 8.1''
Unit Shipping Weight: 381 lb
Unit Operating Weight: 390 lb

Warranty Information (Net Price Ea.)

NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity Unit Master Price

Base Unit - Indoor


40RUSA08A2A9-0A0A0 1 $4,352
Base Unit $4,352
Std Static, Std Motor / Medium Drive 1 $0
Cabinet Paint - None 1 $0

Commercial Split Systems Builder 1.19o Page 48 of 57


Performance Summary For Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Performance Summary

System: 40RUS008
System Quantity: 1
Altitude: 0.0 ft

Indoor Unit Parameters


Unit Quantity: 1
PartNumber: 40RUSA08A2A9-0A0A0
Unit Model: 40RUS
Unit Size: 26.3 kW
No. of Splits: 1
Voltage: 400-3-50 V-Ph-Hz
Actual Airflow: 2600.0 CFM
Total Clg Cap.(Gross): 78.0 MBH
Sensible Clg Cap.(Gross): 61.2 MBH
Ent Air DB: 80.0 °F
Ent Air WB: 67.0 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 58.5 °F
Lvg Air WB: 57.6 °F
Lvg Enthalpy: 24.77 BTU/lb
Coil Bypass Factor: 0.079
Fluid Flow Rate: 12.7 gpm
Ent Fluid Temp: 45.0 °F
Lvg Fluid Temp: 57.2 °F
Fluid Rise: 12.2 °F
Fluid PD: 1.5 ft wg
Fluid Type: Fresh Water
Fluid Conc: 0 %

Indoor Unit External Static: 0.60 in wg


Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc Htg Loss: 0.00 in wg
Total External Static: 0.60 in wg

Indoor Supply Fan


Indoor Unit External Static: 0.60 in wg
Economizer Loss: 0.00 in wg
Grille Loss: 0.00 in wg
Plenum Loss: 0.00 in wg
Acc. Heating Loss: 0.00 in wg
Total Ext Static: 0.60 in wg
Fan Speed: 693 RPM
Fan Power: 0.81 BHP
Fan Motor Max: 2.40 BHP
Fan Motor FLA: 2.6 Amps
Motor and Medium Static Drive Required.

Indoor Electrical Data


Unit Voltage: 400-3-50 V-Ph-Hz
Unit MCA: 3.3 Amps
Unit MOCP: 15.0 Amps
Notice: Indoor unit elect. data is based on 400-3-50

Acoustics
Sound Power Levels, db re 10E-12 Watts

Commercial Split Systems Builder 1.19o Page 49 of 57


Performance Summary For Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Outdoor Unit (dB) Indoor Unit


(dB,Ducted)
A-Weighted Total Level NA 88.4
63Hz NA 95.3
125Hz NA 91.3
250Hz NA 87.3
500Hz NA 86.3
1000Hz NA 82.3
2000Hz NA 80.3
4000Hz NA 76.3
8000Hz NA NA
Sound Message Sound for rms008

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

40RUS008withStandardCoil
3
1200RPM
1100RPM

1000RPM
Static Pressure (in. wg.)

2
900RPM

5.00BHP
800RPM SC

700RPM
3.70BHP
1
600RPM 2.90BHP
2.40BHP 3.00BHP
2.00BHP
500RPM RP
1.30BHP
1.00BHP
400RPM

0
0 1 2 3 4 5
Airflow(CFM-thousands)
RPM=693 BHP=0.81 MaximumRPM=1200 MaximumHP=3.70
SC-SystemCurve RP-RatedPoint MP-MinimumPoint

Commercial Split Systems Builder 1.19o Page 50 of 57


Acoustic Summary For Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Acoustic Summary

Indoor Unit Parameters:


Tag Name: Unit 10
Unit Model: 40RUS
Unit Size: 26.3 kW
System Type: Chilled Water
External Static Pressure: 0.60 in wg
Fan Speed: 693 RPM
Fan BHP: 0.81 BHP

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total


Sound Power,dB NA 95.3 91.3 87.3 86.3 82.3 80.3 76.3 NA 97.8
A-Weighted Sound Power, dBA NA 69.0 75.2 78.7 83.1 82.3 81.5 77.3 NA 88.4

Notes:
1. The above estimated duct sound power levels are based upon the ASHRAE calculation approach from the ASHRAE 1987 HVAC
Systems and Applications handbook, Chapter 52.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the units is located at the geometric center of the unit.

Acoustic Note:
1. The indoor duct sound power data is estimated based on the ASHRAE calculation approach from the ASHRAE handbook 1987
HVAC Systems & Applications, Chapter 52.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.

Commercial Split Systems Builder 1.19o Page 51 of 57


Certified Drawing for Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Certified Drawing

Commercial Split Systems Builder 1.19o Page 52 of 57


Guide Specification for Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

Guide Specifications

GUIDE SPECIFICATIONS
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 2,400 to 6,000 Cfm (1150 to 5650 L/s), Nominal Airflow, 6 to 30 Tons (21 to 105 kW), Nominal Cooling
Carrier Model Numbers: 40RUA (Direct-Expansion Coil)
40RUS (Chilled Water Coil)
Part 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multi-position design and shall be capable of
horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit. Unit with chilled water coil
shall be used in a chilled water circuit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada, standards and shall carry the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.) requirements for flame spread and smoke generation. Insulation shall
contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion and chilled water coils shall be burst and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s recommendations.
Part 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical configuration.
Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, pre-wired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. (51-mm) disposable air filters, and condensate drain pans for
vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in. (12.7-mm) fire-retardant material. Insulation shall contain an EPA-registered
immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM
standards G21 and 22 (U.S.A.).
3. Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections
on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of
the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. (51 mm) throwaway-type filters installed upstream from the cooling coil. Filter access shall be
from either the right or left side of the unit.
B. Coils:
DX coil is 4-row and consists of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and
Commercial Split Systems Builder 1.19o Page 53 of 57
Guide Specification for Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

liquid line connections or supply and discharge connections shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be
Puron® R-410A compatible and capable of external adjustment. Direct-expansion heat pump coils shall have a factory-installed bypass
line and check valve assembly around the TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil
tubing shall be internally rifled to maximize heat transfer.
2. Chilled water coils shall be rated for an operating pressure of not less than 300 psig (2069 kPag).
C. Operating Characteristics:
Unit shall be capable of providing cfm (L/s) airflow at an external static pressure of in. wg (kPag).
D. Motor:
1. Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and installed.
2. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload protection. Motors rated at 5 hp (3.73
kW) shall be protected by a circuit breaker.
3. Evaporator-fan motor shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload protection or
manual reset calibrated circuit breakers. Evaporator motors are designed specifically for Carrier and do not have conventional
horsepower (hp) ratings listed on the motor nameplate. Motors are designed and qualified in the “air-over” location downstream of the
cooling coil and carry a maximum continuous bhp rating that is the maximum application bhp rating for the motor; no “safety factors”
above that rating may be applied.
4. All evaporator-fan motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy Policy Act of
1992 (EPACT), effective October 24, 1997.
E. Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-static drive shall be available to meet the airflow and external static pressure
requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fins bonded to the tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 150 psig (1034 kPag).
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be
mounted in a galvanized steel housing and shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260°F (138 kPag at 126°C).
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz shall be factory-supplied for field installation as shown on the equipment
drawings. Electric heat assembly shall be ETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-point power wiring.
Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel.
Electric heaters shall not be used with air discharge plenum.

Commercial Split Systems Builder 1.19o Page 54 of 57


Guide Specification for Unit 10
Project: UTECH Hospitality - Synergy 04/03/2013
Prepared By: 08:28AM

6. Air Discharge Plenum:


Plenum shall be factory-supplied to provide free-blow air distribution for vertical floor-mounted units. A grille with moveable vanes for
horizontal or vertical airflow adjustment shall be included. Plenum shall be field-assembled and field-installed on the unit’s fan deck for
blow-thru air distribution. Plenum shall not be used with electric heaters.
7. Return-Air Grille:
Grille shall be factory-supplied for field installation on the unit’s return air opening.
8. Unit Subbase:
Subbase assembly shall be factory-supplied for field installation. Subbase shall elevate floor-mounted vertical units to provide access for
correct condensate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be factory provided for field installation on either return air opening of air handler.
For free cooling applications, economizer shall be compatible with separate thermostat; economizer dampers shall open when outdoor
air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2 sensor accessory; economizer dampers shall
open when indoor CO2 level rises above predetermined set point. Economizer shall include enthalpy control and damper actuator.
10. Thermostat Controls:
a. TEMP System programmable communicating multi-stage thermostat with fan switch, time clock, LCD display, °F/°C capability, and
CCN (Carrier Comfort Network™) compatibility.
b. Commercial Electronic Thermostat with 7-day time clock, auto-changeover, multi-stage capability, and large LCD temperature
display.
11. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
12. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds the predetermined setpoint. Sensor
shall have the capability of being connected to Comfort System relay pack or to economizer using field-supplied and field-installed
Honeywell dc adapter no. Q769C1004.
13. Condensate Drain Trap:
Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for
connection to an alarm if desired.
14. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using a
45°F (7.2°C) airstream moving at not less than 400 fpm (189 liters/sec.) shall measure individual lamp output. Lamp output at 253.7
nm shall not be less than 10µW/cm2 per inch of arc length measured at a distance of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to the emitters and are capable of producing the
specified output intensity with an input power no more than 80 watts.
c. Emitters and fixtures shall be installed in sufficient quantity and arranged so as to provide an equal distribution of UV-C energy on
the coil and drain pan.
d. The minimum UV-C energy striking the leading edge of the coil fins shall be not less than 820 µW/cm2 at the closest point and
through placement, not less than 60% of that value at the farthest point. Equal amounts are to strike the drain pan, either directly or
indirectly through reflection.

GS40RU-02PD
10/09

Commercial Split Systems Builder 1.19o Page 55 of 57


Unit Feature Sheet

COMMERCIAL SPLIT SYSTEMS


40RUS CHILLED WATER PACKAGED AIR-HANDLING UNITS

The 40RUS units are compact chilled water packaged air-handling units offering the ultimate
in installation ease and flexibility. 40RUS units range from 7-1/2 to 15 tons in capacity. These
units may be installed in either the vertical or horizontal configuration with no modifications.
Powerful fan systems allow easy adaptation to existing ductwork. Heating capability is
provided by accessory electric heaters, hot water coils, or steam coils.

40RUS 7-1/2 TO 10 TON CHASSIS SHOWN

Commercial Split Systems Builder 1.19o Page 56 of 57


STANDARD FEATURES

37. Cleanable insulation treated with an anti-microbial agent.


38. Two sloped condensate pans on each unit for horizontal or vertical applications.
39. 2 inch filters.
40. Powerful belt-driven forward curved fans.
41. Factory-installed fan motor and contactor.
42. Easy maintenance -- removal of a single panel allows access to virtually all components.
43. Single blower on 08-12 sizes; dual blower on 14-16 sizes.
44. 24 volt terminal block for control wiring connections.
45. Standard one-year warranty.

Certified to ISO 9001:2000

Commercial Split Systems Builder 1.19o Page 57 of 57