Sie sind auf Seite 1von 5

Princess Noura Bint Abdulrahman University for Women Project Joint venture

Riyadh, Kingdom of Saudi Arabia El Seif/CCC


part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

CANTILEVER BRACKETS FOR DI PIPES

These brackets are adopted as beam welded to steel plate and anchored to concrete wall
using postdrilled HILTI anchor bolts.
The worst case is taken in to consideration and the designed details are applicable for the
same supports with DI pipes with less diameters and less distance from wall.

maximum pipe dimeters are: 100 mm and 200 mmm


maximum distance from the wall for 100 mm DI pipe: 900 mm
maximum distance from the wall for 200 mm DI pipe: 450 mm
Building / area: Utility Tunnel rev: UTILITY TUNNEL Sheet:
issued for: APPROVAL 0 pipe support 0 2 8

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

3.0 THE INPUT DATA FOR 200 mm DI pipe


The wieght of fluid……….………………………………………………… 10 kN/m3
The weight of pipe 200 mm dia……….………………………………….. 37 kg/m
Adopted steel grade……………..… ASTM A36 yield stren..Py= 245 N/mm2
The strength of the weld (Fexx=60% of Py)…….………….…..Pyw= 147 N/mm2
The distance between two supports horizontaly….……………L= 4 m
The pipe center line offset from the wall……….………………………… 0.45 m
The compressive strength of concrete after 28 days………....... fc'= 35 MPa
The density of the steel...……….………………………….……...γs= 7860 kg/m3
The earthquake zone, as per consultant instruction………......zone 0
The pipe diameter………………………………………………..…..D= 200 mm
The height of the structure (roof elevation)……………………………… NA m
The bracket elevation (the highest)………………………………………. NA m
Adopted bolts are steel grade… 8.8 GR, diameter………. 12 mm

4. LOADS ANALYSES
4.1 Dead load
The wieght of the pipe………………………………………………. 148 kg
The weight of the fluid……………………………………………….. 31.4 kg
The weight of the clamp...………………………………………….. 30 kg
total= 209.4 kg
Total weight without water including stiffeners, bolts, nuts……… 195.8 kg
total dead load G=…………….. 1.958 kN
Total weight including water weight (for seismic force required)… 227.2 kg
total dead load Gs=…………… 2.272 kN

4.2 Live load


Since the all lateral forces will be taken by anchor walls and trust blocks this support is
subject to dead load only, live load is 0.

5. THE CHECK OF STEEL BRACKET

Will be calculated in softwear STAAD PRO and the input / output files are shown on the
following pages.
The adopted design criteria is AISC ASD ad the torsion stress is included.
Building / area: Utility Tunnel rev: UTILITY TUNNEL Sheet:
issued for: APPROVAL 0 pipe support 0 3 0

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

5. THE LOAD DISTRIBUTION ON THE CLAMP/STEEL BRACKET LOCATION


Forces are:
dead load:
vertical force…………….2.272 kN
bending moment……… 0 kNm
live load:
vertical force……………. 0 kN
bending moment……… 0 kNm
seismic load horizontal
horizontal force…………. 0 kN
bending moment……… 0 kNm

6. THE CHECK OF U BOLT FOR TIGHTENING


Total dead load force……………… 2.272 kN
Adopted U bolt grade 4.6 diameter 12 mm total number of 2 pieces.
Tension capacity of the U bolt:
Ptcap=0.8*Aa*ptcap=…………….. 21.70368 kN
Ptcap=…………… 21.70368 > 1.136 kN-dead load tension force per one U bolt safe

7. THE CHECK OF THE STEEL BRACKET


Is calculated in softwear STAAD PRO 2006 and input/output files are shown on following
pages.
The deisgn criteria AISC ASD included, and the bracket is checked on the torsion stress.
Building / area: Potable tabk rev: POTABLE TANK Sheet:
issued for: APPROVAL 0 the pipe support 0 0 5

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

8.0 THE CHECK OF THE ANCHORING SYSTEM

The adopted is post drilled HILTI anchored system using galvanized HILTI bolts prior to
water's environment.
Due to water's environment the designed anchored system is not using grouting, the plate
will be directly tighten to the concrete wall. All other steel items, susch as beam, clamp and
connection bolts will be hot deep galvanized.

The calculations are based on maximum reaction forces assuming all types of loads:
dead load:
live load,
seismic load horizontal perpendicular,
seismic load horizontal longitudinal

Fx= 1.256 kN Mx= 0.595 kNm


Fy= 3.881 kN My= 0 kNm
Fz= 0.496 kN Mz= 1.507 kNm

Assuming safety factor of ……. 2

Fx= 2.512 kN Mx= 1.19 kNm


Fy= 7.762 kN My= 0 kNm
Fz= 0.992 kN Mz= 3.014 kNm
Building / area: Potable tabk rev: POTABLE TANK Sheet: