DATA SHEET ► Safety Precautions is for using the product safely and correctly in order to prevent
Related Manual
Read this data sheet carefully prior to any operation, mounting, installation or start-up of
2. Performance Specifications
the accidents and danger, so please go by them. the product. Item Performance specification
LS Programmable Logic Controller ► The precautions explained here only apply to this module. For safety precautions Name ode Number of channel 2 channels
on the PLC system, refer to User‟s manual. XGB analog 10310000920 Type Voltage Current
Analog Input Option Board ► The precautions are divided into 2 sections, „Warning‟ and „Caution‟. Each of the
XGK/XGB Instruction & Programming 10310000754 DC 0 ~ 10V DC 4 ~ 20㎃
XG5000 10310000512 Analog (input resistance: DC 0 ~ 20㎃
meanings is represented as follows. XGB Hardware 10310000926 input Range 1㏁ or above) (input resistance: 250Ω)
Input range can be see at user program or I/O
If you violate instructions, it can cause death, fatal injury or a parameter per each channel-Note1)
XGB XBO-AD02A Warning considerable loss of property Revision History
Form 12 bit binary data
Date Version Updated Information
Unsigned 0 ~ 4000
2011.01 V1.0 First Edition
If you violate instructions, it can cause a slight injury or a slight Digital Signed -2000 ~ 2000
2011.05 V1.1 CI changed
Caution loss of products
output Range Precise
value
0 ~ 1000 (DC 0 ~10V)
400~2000 (DC 4~20㎃)
0 ~ 2000 (DC 0~20㎃)
Applicable version Percentile 0 ~ 1000
► The symbols which are indicated in the PLC and User‟s Manual mean as follows. For system configuration, the following version is necessary. 1/4000 (DC 4~20㎃: 1/3200)
This symbol means paying attention because of danger of injury, fire, Segment Version Max. resolution 5㎂ (DC0~20㎃)
2.5mV (DC 0 ~10V)
or malfunction XGB E type V1.1 or above 6.25㎂ (DC 4~20㎃)
► This symbol means paying attention because of danger of electric shock. XGB S type V1.1 or above Precision ±1.0% or less
Store this datasheet in a safe place so that you can take it out and read XGB SU type V1.0 or above Max. conversion speed 1ms/channel + scan time
it whenever necessary. Always forward it to the end user XG5000 V3.61 or above Absolute max. input DC +12V / -10V DC ±25㎃
Additional Average function Count average (2~64,000 times)
Handling Precautions function Gain adjust Gain adjust (-40~40)
Non-insulation between analog input channels
► Don‟t drop or make impact. Insulation method Non-insulation between input terminal and PLC
► Don‟t detach PCB from case. It may cause problem. basic unit
► When wiring, let no foreign material go into the module. If it goes into the module, Input terminal 5-point terminal block
remove it. I/O points occupied Fixed type: 64 point
► Don‟t detach the module from slot while power is on 1EA(When using XBC-DR10E/DR14E “E” type)
Max. no. of installation 2EA (When using XBC-DR20E/DR30E “E” type)
2 EA(When using XBC-DxxxS/SU “S” type)
Supply power Internal DC5V
- When using LSIS equipment, thoroughly read this Warning Consumption current 50㎃
datasheet and associated manuals introduced in this Weight 20g
► Do not contact the terminals while the power is applied.
datasheet. Also pay careful attention to safety and handle Risk of electric shock and malfunction.
Remarks
the module properly. ► Protect the product from being gone into by foreign metallic matter.
Note1) Offset/gain value on the analog input range can be adjusted at XG5000 I/O
- Store this datasheet in a safe place so that you can take it Risk of fire, electric shock and malfunction.
parameter
out and read it whenever necessary. ► Risk of fire, electric shock and malfunction.
Risk of injury and fire by explosion and ignition.
1.General Specifications
HEAD OFFICE Caution
LS tower, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do No Item Specification Standard
1026-6, Korea http://eng.lsis.biz ► Be sure to check the rated voltage and terminal arrangement for the Operating
module before wiring work. 1 temperature
0 ~ 55℃ -
Tel: 82-2-2034-4870 Fax: (82-2)2034-4648 e-mail: cshwang@lsis.biz
Risk of electric shock, fire and malfunction. Storage
2 temperature
-25 ~ 70℃ -
LSIS(ME) FZE _ Dubai, U.A.E. ► Tighten the screw of terminal block with the specified torque range.
Operating
Tel: 971-4-886-5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz If the terminal screw is loose, it can cause fire and electric shock. 3 5 ~ 95%RH, non-condensing -
humidity
.
► Use the PLC in an environment that meets the general Storage
4 5 ~ 95%RH, non-condensing -
LSIS Tokyo Office _ Tokyo, Japan specifications contained in this datasheet. humidity
Risk of electrical shock, fire, erroneous operation and deterioration of the For discontinuous vibration - -
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz
PLC. Frequency Acceleration Amplitude times
10≤f∠57 Hz - 0.075 mm
LSIS Shanghai Office _ Shanghai, China ► Be sure that external load does not exceed the rating of output Vibration 57 ≤f≤150 Hz 9.8㎨ (1G) - 10 times in
module. 5 each
Tel: 86-21-5237-9977(609) Fax: 89-21-5237-7189 e-mail: liyong@lsis.com.cn resistance For continuous vibration IEC61131-2
direction
Risk of fire and erroneous operation. Frequency Acceleration Amplitude for
LSIS Beijing Office _ Beijing, China ► Do not use the PLC in the environment of direct vibration 10≤f∠57 Hz - 0.035 mm X, Y, Z
Risk of electrical shock, fire and erroneous operation. 57≤f≤150 Hz 4.9㎨(0.5G) -
Tel: 86-10-5825-6027(666) Fax: 86-10-5825-6028 e-mail: xunmj@lsis.com.cn
Max. impact acceleration : 147 ㎨ (15G)
► Do not disassemble, repair or modify the PLC. Shocks Authorized time : 11㎳
6 IEC61131-2
LSIS Guangzhou Office _ Guangzhou, China Risk of electrical shock, fire and erroneous operation resistance Pulse wave : Sign half-wave pulse
Tel: 86-20-8328-6754 Fax: 86-20-8326-6287 e-mail: chenxs@lsis.com.cn ► When disposing of PLC and battery, treat it as industrial waste. (Each 3 times in X,Y,Z directions)
Square wave AC: ±1,500V LSIS
Risk of poisonous pollution or explosion.
impulse noise DC: ±900V standard
LSIS Chengdu Office _ Chengdu, China Electrostatic IEC61131-2
Tel: 86-20-8328-6754 Fax: 86-20-8326-6287 e-mail: comysb@lsis.biz Voltage: 4kV (Contact discharge)
discharge IEC61000-4-2
Precautions for use Radiated
IEC61131-2
► Do not Install other places except PLC controlled place. Noise electromagnetic 80 ~ 1,000 MHz, 10 V/m
LSIS Qingdao Office _ Qingdao, China 7 IEC61000-4-3
► Make sure that the FG terminal is grounded with class 3 grounding which is resistance field noise
Tel: 86-532-8501-6068 Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn Digital/analog
dedicated to the PLC. Otherwise, it can cause disorder or malfunction of PLC Power
input/output
Fast transient Segment supply IEC61131-2
LSIS Europe B.V., Netherlands PLC Others PLC Others PLC Others /burst noise module
communication
IEC61000-4-4
Tel: +31 (0)20 654 1420 Fax: +31(0)20 654 1429 e-mail: junshickp@lsis.biz interface
Voltage 2 kV 1 kV
Ambient
A) Best B) Good C) Bad 8 No corrosive gas or dust -
conditions
► Connect expansion connector correctly when expansion module is needed. Operating
9 2000m or less -
height
► Do not detach PCB from the case of the module and do not modify the module.
Pollution
LS constantly endeavors to improve our products so that information in this ► Turn off power when attaching or detaching module. 10 2 or less -
degree
datasheet is subject to change without notice. ► Cellular phone or walkie-talkie should be farther than 30cm from the PLC. Cooling
11 Natural air cooling -
The date of issue: 2011. 5 ► Input signal and communication line should be farther than10cm from a high- type
10310001187 Ver 1.1 tension and a power line in order not to be affected by noise and magnetic field.
Remarks
*(a) In case of current input, connect V+ terminal and I+ terminal
*(b) Input resistance of current input circuit is 250 Ω (typ.)
*(c) Input resistance of voltage input circuit is 1 MΩ (min.)