Focus 02-11
1. General Details:
Floor Area ........................................................... 155.0 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 5.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 155.0 ft² Area ..................................................................... 398.3 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
Focus 02-19
1. General Details:
Floor Area ........................................................... 141.0 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 4.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 141.0 ft² Area ..................................................................... 372.4 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
Focus 02-23
1. General Details:
Floor Area ........................................................... 141.0 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 5.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 141.0 ft² Area ..................................................................... 372.4 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
Focus 03-08
1. General Details:
Floor Area ........................................................... 136.7 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 3.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 136.7 ft² Area ..................................................................... 369.2 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
Focus 03-32
1. General Details:
Floor Area ........................................................... 138.9 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 3.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 138.9 ft² Area ..................................................................... 369.2 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
Focus02-27
1. General Details:
Floor Area ........................................................... 202.4 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 8.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 75.3 1 0 0
SW 95.8 0 1 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 202.4 ft² Area ..................................................................... 269.1 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.100
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
meeting02-03
1. General Details:
Floor Area ........................................................... 274.5 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ............................................................ 12.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 105.5 1 0 0
SE 95.8 0 1 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 274.5 ft² Area ..................................................................... 439.2 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.100
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
meeting02-18
1. General Details:
Floor Area ........................................................... 266.9 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 8.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 121.6 1 0 0
N 121.6 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 266.9 ft² Area ..................................................................... 256.2 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.100
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
meeting03-18
1. General Details:
Floor Area ........................................................... 258.3 ft²
Avg. Ceiling Height .................................................. 9.0 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 6.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 121.6 1 0 0
N 121.6 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 258.3 ft² Area ..................................................................... 371.4 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.100
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
meeting03-27
1. General Details:
Floor Area ........................................................... 209.9 ft²
Avg. Ceiling Height .................................................. 9.0 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 6.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 209.9 ft² Area ..................................................................... 457.5 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.100
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
MPR
1. General Details:
Floor Area ........................................................... 310.0 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ................................. Recessed (Vented) Occupancy ............................................................ 10.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ........................................ Medium Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 295.2
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 454.8
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 310.0 ft² Area ..................................................................... 531.7 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
1. General Details:
Floor Area ............................................................. 37.7 ft²
Avg. Ceiling Height .................................................. 9.0 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 1.0 Person
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ....................................................................... 37.7 ft² Area ..................................................................... 198.1 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.500
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F
Project02-13
1. General Details:
Floor Area ........................................................... 216.4 ft²
Avg. Ceiling Height .................................................. 7.9 ft
Building Weight ..................................................... 70.0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 0.0 CFM/person
OA Requirement 2 ................................................ 0.00 CFM/ft²
Space Usage Defaults ............. ASHRAE Std 62-2001
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy .............................................................. 8.0 People
Wattage ................................................................. 1.30 W/ft² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.25 Sensible ............................................................... 245.0
Schedule ............................................................. Micro .................................................................... BTU/hr/person
Latent .................................................................. 205.0
.................................................................... BTU/hr/person
Schedule ............................................................ Micro
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 CFM
Design Heating ...................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition Partition Type ........................................ Wall Partition
Area ..................................................................... 216.4 ft² Area ..................................................................... 472.5 ft²
U-Value ............................................................... 0.500 U-Value ............................................................... 0.100
.................................................................... BTU/(hr-ft²-°F) .................................................................... BTU/(hr-ft²-°F)
Uncondit. Space Max Temp .................................. 75.2 °F Uncondit. Space Max Temp .................................. 75.2 °F
Ambient at Space Max Temp .............................. 107.6 °F Ambient at Space Max Temp .............................. 107.6 °F
Uncondit. Space Min Temp ................................... 59.0 °F Uncondit. Space Min Temp ................................... 59.0 °F
Ambient at Space Min Temp ................................. 50.0 °F Ambient at Space Min Temp ................................. 50.0 °F