Beruflich Dokumente
Kultur Dokumente
2 Power
excitation converter.
VAR
Brea ker Breaker Stato r
Synchronisation
Transformer Volt DCS
Ro to r
Distributed
Stator
6
Transformer 1
Stator
Transform er 2
7
Stator
8
Transform er 3
38 GMD
Others
protection for the cycloconverter inlet, over-voltage
E xcitation
Tran sformer
43 Supplier
protection system for the motor, basic charge system of
the cycloconverter.
44
23 25 26 27
33
21 14 15
E-House In the following, both control hardware and software are
42
Kn ife switche s
34
briefly described.
37
36
17
Ringmotor U
V W
MLCP
a) Control Hardware
Y 2x heat Motor Local Control
exchanger
M
P anel
29
20
Mill Lubrication System
35
32 The controller hardware used for the cycloconverters
belongs to the family of high speed processing controllers
41
(scope of mil l supp lier) Mill Brake
System
(scope of mil l supp lier)
18
called PSR 2, especially developed for the control of high
Figure 2. Overview of a Typical GMD System and Its Components power drives.
Figure 2 presents the power and control circuit of a The control system requires inputs signals in order to carry
cycloconverter fed synchronous motor. The synchronous motor out control, supervision and protection of the drive. The output
has one 3-phase winding in the stator. The current in each signals are triggering pulses to thyristors, excitation reference
phase is controlled by a 12-pulse cycloconverter. The 12-pulse current and digital outputs for control and supervision.
configuration is obtained by the wye-delta connection in the The processor (PPC322 AE) where the control program is
secondary winding of the three power transformers and reduces running, communicates with its analogue/digital input/output
the low frequency current harmonics in the load and at the cards (UAC326), digital input/output cards (UDA327) pulse
input side of the converter. The motor field is excited by a generation card (GDB021) and serial communications with the
separate controlled excitation system fed by its own excitation plant control system (PMA324) through a 16-bit parallel
transformer. communication bus B448. For command and supervision of the
1) Power Part of the Drive Systems equipment there are local and in-field control panels with direct
The power part of the system is composed of the following communication with the processor through the ARCNet
main components. Basic data of the GMD systems are given in network. This network also serves for control and supervision
Table 1. of the cooling system for the power part components
(thyristors, resistors).
• Three converter transformers with one primary and two
secondary windings with the same power and wye- Part of the hardware is also represented by the PSR input
delta connection in the secondary winding in order to signal modulation cards, the UGA 359 motor current cards,
achieve 12-pulse operation. It is fed from a 23 kV bus UUA 358 voltage reference adapting card, current-voltage
and connected through the main switchgear. signal converter for the motor air gap supervision and
cycloconverter output voltage measuring LEM sensors. The
thyristor supervision cards in the power part provide an optical
signal to the XV C513 receiver cards and through the XV C512 analysis, transient data recording, data trending and storage can
control card, they provide a PSR controller condition signal provide important information to the operation personnel. Such
through digital inputs. Also, there are analogue signal data allows detecting upcoming problems in an early stage.
supervision cards (CSA 463 motor over current supervision) Furthermore, such systems provide valuable information to
and digital signals (supervision of backplane cards B448, CSA analyze problems and therefore to solve them faster than
465), DDA 353 cycloconverter bridge control and pulse otherwise.
amplifying cards LT8951.
The operation of a GMD is based on the design of the drive
b) Control Software system and the process requirements. As long as there are no
Programming of the controller is done in a high-level abnormal operating conditions or process requirements, no
graphic or function block diagram language with application problems with the equipment (hardware or software
software called FUPLA 400. The program is divided into malfunctions or failures), misuse of the equipment or problems
CLUSTERS called INTERRUPTS. The clusters have a with the supply network, the GMD will work fine. The main
particularity that logic or part of the program on the cluster purpose of hardware and software protection systems of the
runs in a defined cycle time. Table 2 shows the cycle times for GMD is protecting the equipment to avoid under all
the clusters in the cycloconverter program. This permits circumstances any risk to the health and safety of the operation
incorporation of signals measured in the minor cycle time and maintenance personnel. Protecting the equipment means to
cluster and those fundamental activities and/or actions such as avoid any damage as far as possible or at least to limit the
commutation of the cycloconverter bridges, generation of damage to certain components and to eliminate the risk of more
sinusoidal current of the motor for internal control purposes, severe and serious damage of larger parts of the drive system.
protections, etc. The basic protection functions were developed more than
three decades ago and since then have worked without
TABLE II. CLUSTER CYCLE TIMES OR PROGRAM INTERRUPTS problems in many installations. These functions had been
continuously reviewed considering specific requirements and
Cluster Name Cycle Time Remarks special conditions.
Interrupt 0 833 µs The fastest cluster. It
(Voltage period / 24) = contains that logic or At the Minera Escondida the protection systems of the
for 50 Hz network; part of the program for installed GMDs have operated. However, there have also been
20 ms / 24 = 833.3 µs measurement and
phenomena that have triggered the need to review specific
communication with
the bridge protection functions and to improve them.
commutation card,
through digital card A. Protection Against Network Disturbances
UDA 327 mounted in
backplane B448. The drive has a protection against over- and under-voltage
Interrupt 1 1.667 ms (2x Int 0) as well as against over- and under-frequency. Specifically,
Interrupt 2 5.0 ms (3x Int 1) these protections are implemented in the PSR processor
Interrupt 3 20.0 ms (4x Int 2) program in the cluster called Interrupt 0.
Init - This cluster runs when
the processor is 1) Over-voltage protection at the network side
energized. The cycloconverter power part, as well the excitation
Int3-allen-bradl 20.0 ms (4x Int 2) Cycle time of this converter, are protected via surge arresters against high and
cluster is the same as
cluster Interrupt 3.
dynamic voltage peaks created by the network or by switching
Backgnd - The logic in the cluster the converter transformers. This over-voltage protection
background is executed especially protects the power semiconductor valves (thyristors)
in the time the against the “avalanche breakdown”.
processor is available.
PANEL-AFC094 Background 2) Line over- and under-voltage protection
LCB-AFC094 Background This protection function is realized inside the drive control
software. Information of the actual network voltage at the
high/medium voltage side is taken from the synchronizing
Inside the clusters the program is segmented according to
transformer installed in the feeding switchgear (incoming side),
the functionality and/or task developed in particular by this part
and read in by the analogue inputs of the drive control system.
of the program. The segment is named in accordance with the
The under-voltage and over-voltage detection immediately
task of function that it performs.
forces the blocking of all triggering pulses. Loosing the feeding
voltage for any reason while triggering is still on-going, the
II. PROTECTION OF THE GMD SYSTEM AND ITS BEHAVIOR emf voltage (electromagnetic force) of the motor as an
AT MINERA ESCONDIDA alternating voltage would change its polarity and the motor
The purpose of the different protection systems is to avoid would become a generator until it stops moving.
damage to the equipment in case of all possible mechanical and The emf voltage of the motor would drive a short circuit
electrical faults. Supervision systems that allow the current through the motor windings and the cycloconverter
visualization of all relevant analog and digital signals, handling thyristors. The transformer windings are not anymore in the
of status, alarm and fault information, fault tracing and loop to limit the current. At first, such a situation would lead to
a three-phase short circuit until the first phase will cross the this reason ABB was asked to study the possibility of the drive
zero current, then the short circuit would become a two-phase detecting this situation and generating a self-limitation so that
short circuit until the energy of the ringmotor is zero. the equipment does not end up out of service, but only limits
the speed generating minor impacts on operations.
Two- and three-phase short circuits at the motor terminals
create unfavorable high forces (several times of nominal For the aforementioned, the following modifications were
forces) acting on the motor and its foundation. Therefore, it is generated in the PSR control program, and at the same time, it
important that especially under-voltage is detected fast enough was decided to raise the secondary voltage of the power
to be able to react and to block the triggering pulses. If the transformers, by lowering their taps.
supply voltage has become too low then a controlled shutdown
of the GMD would not be possible any more. Trip levels are set
TABLE IV. PROTECTION SETTING FOR NETWORK VOLTAGE AND
in the drive control software and are 110 % of the rated value FREQUENCY
for over-voltage and 85 % for under-voltage.
Protection Adjustment Action Observations
3) Excitation under-voltage at the network side Under-voltage 95 % of rated voltage Alarm; INT 0,
This protection is realized in the drive controller as well as (Un) with a time Limitation of SEGMENT S07
delay of 15 ms speed
in the microprocessor of the stand-alone excitation converter
Under-voltage 95 % Un, 60 s Trip INT 0,
itself. It protects the converter module / thyristors against SEGMENT S07
damage in case of loosing the network. In the worst case Over-voltage 85 % Un, 30 ms Trip INT 0,
loosing the feeding voltage or an uncontrolled opening of the SEGMENT S07
feeding breaker during motor operation could destroy thyristors Over-voltage 110 % Un, 50 ms Trip INT 0,
and other parts of the power electronics. The rotor of the SEGMENT S07
ringmotor would feed energy back to the excitation converter, Under- 48 Hz, 100 ms Trip INT 0,
frequency SEGMENT S07
which would lead to very high current and voltage to the Under- 48.4 Hz, 100 ms Trip INT 0,
excitation power electronics. Trip levels set in the drive control frequency, SEGMENT S07
software are 110 % of the rated value for over-voltage and 85 Power system This level is
% for under-voltage. (SING) applicable for
requirement the ball mills
4) Line over- and under-frequency and is the option
In the same way the network frequency supervision is to select one of
the ball mills
working. If the frequency is out of the allowed range (95 % to
with this
105 % of nominal), then the system will trip. These trip levels adjustment.
are set in the drive control software. Over- 52 Hz, 100 ms Trip INT 0,
frequency SEGMENT S07
The protection settings originally established are given in
the following table.
Besides, a signal called “INTERN_Min-phase-volt” is
TABLE III. ORIGINAL GMD PROTECTION RELATED WITH UNDER- AND
generated by the program on cluster INT 0 / S07 for limiting
OVER -VOLTAGE AND UNDER- AND OVER-FREQUENCY the speed accordingly with the network voltage reduction.
Protection Adjustment Action Observations
Under-voltage 85 % of rated Trip INT 0, SEGMENT S07
voltage (Un) with
a delay time of 30
ms
Over-voltage 110 % Un, 50 ms Trip INT 0, SEGMENT S07
Under- 48 Hz, 100 ms Trip INT 0, SEGMENT S07
frequency
Over- 52 Hz, 100 ms Trip INT 0, SEGMENT S07
frequency
These over-voltage arrester modules have a circuit for Figure 4 shows the operation of the stator current unbalance
triggering the thyristors that sense the cycloconverter output protection.
voltage and, when reaching a certain level, trigger the thyristors
and connect the dissipating resistances.
In ball mill 2, the over-voltage arrester modules failed and
the dissipating resistances were connected during the operation
of the mill. This situation was not detected by the current
circulation sensors in the over-voltage arrester modules and the
equipment continued in service. The resistance reached the
limit of energy dissipation and started to destroy itself,
generating an increase in current that was finally detected by
the magnetic sensors and tripping of the mill. The incandescent
pieces of the resistance damaged some components of the
cycloconverter.
These over-voltage arrester modules were installed in many
previous GMD installations and never before similar problems
had been experienced. The burned components were replaced
and after a period of 4 days the drive was able to operate again.
Nevertheless, it became clear that this failure and its effects
needed to be analyzed in order to understand its root cause and
the conditions under which such malfunction could occur to Figure 4. Oscilogram captured by transient recorder : cycloconverter output
avoid similar problems in the future. currents unbalanced in ball mill 1, July 22nd, 2006
For implementing this protection some consideration were • Change the time delay trip in the over-current detection
taken into account: card, CSA 463
• The introduction of the “firing all release” has to take 5) Implementation and Testing
place without circulating currents via the This protection function was once activated and has
cycloconverter transformers. operated on one ball mill. The reason for triggering this
protection function was a so-called incomplete stop sequence.
Figure 5 shows the event captured by the transient recorder. It
can be seen that the current of phases R and S were zero when Figure 6 shows the signals of the nine air gap sensors
the trip occurred, but for phase T the current was still different installed in the motor. Three are mounted at the bottom (6
than zero, the pulse blocking signal was not active and o’clock), two at the right hand side (3 o’clock), one on the top
therefore the firing all release was triggered. of the motor (12 o’clock) and three at the left hand side (9
o’clock).
The air gap values from the sensors mounted at the left and
right hand sides show that the air gaps were reduced. At least
one pole is showing an air gap reduction on both sides. Thus,
the motor was definitely exposed to lateral forces, which in this
case were reduced and controlled by creating the three-phase
short circuit.
The root cause that triggered this event and activated the
protection was an overload of the equipment which demands
too high current from the cycloconverters resulting in a trip of
the drive system.
III. CONCLUSIONS
The protection functions of a GMD system are properly and
purposefully designed, fulfill a specific function and will
protect the drive system. The operator should take care of the
protection systems and make sure that they are set and working
correctly.
Figure 5. Motor currents when the trip signal occurred (the sum fault signal
from the PSR controller is used for triggering the transient recorder) However, specific needs and requirements may trigger the
development new or improved solutions. In the minerals
The maximum current was achieved on phase R with a industry, e.g. weak networks, sensitivity against under-voltage
value of about 7.9 kA. This value shows good agreement together with the need for high system availability resulted in
with the expected value obtained by the simulations and the desire for an improved protection functionality as described
also during the commissioning of the protection function. in this paper.
Furthermore, abnormal situations and very specific worst-
case scenarios may result in the need to address, review and
analyze these circumstances. Modifications of protection
schemes and settings should only be done with great care and
after thorough analysis and testing. Feedback from operation,
information about specific conditions and needs as well as an
open and close cooperation between customer and supplier are
the basis for improvements. Such a joint approach helped to
review, analyze and solve situations not experienced before.
Finally, it lead to a successful implementation and testing of
the modified protection functions.
REFERENCES
[1] Ahrens, M. and Gonser, J., “Protection and Supervision Systems for
Gearless Mill Drives”, SAG Conference, Vancouver, 2006
[2] Ahrens, M. and Gonser, J., “Technical and Commercial Benefits of
Gearless Mill Drives for Grinding Applications”, SME Conference,
Denver, 2007
Figure 6. Measured air gap values during a trip and after it, when the firing
all release was activated; the air gap numbering is given seeing the motor from
the feed end side