Sie sind auf Seite 1von 115

Engineering

Low Voltage
Protection Devices
Selectivity-Tables

Edition 06/2017 siemens.com/SIOS


table of contents
selectivity tables - product lines with global marketing

1 air circuit breaker ACB -

in combination with molded case circuit breaker MCCB


1.10 3WL1 - 3VA2
1.11 3WL1 - 3VA1
1.12 3WL1 - 3VL

in combination with motor starter protector MSP


1.20 3WL1 - 3RV

in combination with miniature circuit breaker MCB


1.30 3WL1 - 5SY
1.31 3WL1 - 5SL

2 molded case circuit breaker MCCB -

in combination with molded case circuit breaker MCCB


2.10 3VA2 - 3VA2
2.11 3VA2 - 3VA1
2.12 3VL - 3VA2
2.13 3VL - 3VA1

in combination with motor starter protector MSP


2.20 3VA2 - 3RV
2.21 3VA1 - 3RV
2.22 3VL - 3RV

in combination with miniature circuit breaker MCB


2.30 3VA2 - 5SY/5SP
2.31 3VA2 - 5SL
2.32 3VA1 - 5SY/5SP
2.33 3VA1 - 5SL
2.34 3VL - 5SY/5SP
2.35 3VL - 5SL

in combination with residual current protective device RCBO


2.40 3VA2 - 5SU1
2.41 3VA1 - 5SU1

in combination with fuse systems FUSES


2.50 3VA2 - 3NA / Neozed
2.51 3VA1 - 3NA / Neozed
2.52 3VA2 - Sitor
2.53 3VL - 3NA / Neozed

1 / 114
table of contents
selectivity tables - product lines with global marketing

3 fuse systems FUSES -

in combination with molded case circuit breaker MCCB


3.10 3NA - 3VA2
3.11 3NA - 3VA1

in combination with miniature circuit breaker MCB


3.30 3NA - 5SY/5SP
3.31 3NA - 5SL

in combination with fuse systems FUSES


3.40 3NA - 3NA

in combination with residual current protective device RCBO

3.50 3NA - 5SU1

2 / 114
SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150 55 / 66 / 80 / 85 / 100 / 130 / 150

2500

frame size
3200
trip unit

Icu [kA]

In [A]
630 800 1000 1250 1600 2000 2500 3200 4000 250 315 400 500 630 800 1000 1250 1600 2000 4000
5000
6300

25
40
100 A

8.5 11 17 32 90 T T T T 8.4 11 17 32 87 T T T T T T
63
ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

100

25
40
160 A
downstream molded case circuit breaker 3VA2

63 6.6 10 13 21 42 85 T T T 6.5 10 13 21 40 85 T T T T T
100
160
line protection

55 / 85 / 110

160
250 A

4.7 6.6 11 17 29 55 T T T 4.6 6.4 11 17 28 55 T T T T T


250

250
400 A

5 6.9 9.6 15 26 47 T T 5.5 6.9 9.6 15 26 47 T T T T


400

400
630 A

500 8.7 9.8 22 33 67 T 13 22 33 62 T T T


630

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G1.10 3WL1 - 3VA2 3 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU45B / ETU76B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

2500
250 630

frame size
3200
trip unit

Icu [kA]
315 800 1600

In [A]
4000
400 1000 2000
5000
500 1250
6300

25
40
100 A

T T T T
63
ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

100

25
40
160 A
downstream molded case circuit breaker 3VA2

63 T T T T
100
160
line protection

55 / 85 / 110

160
250 A

T T T T
250

250
400 A

T T T T
400

400
630 A

500 T T T T
630

*) for breakers with adjustable trip unit: the limit current with
selectivity Is [kA] apply to the maximum value Iimax

G1.10 3WL1 - 3VA2 4 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

frame size
2500 1000 2000 4000 250 500 1000 2000 4000
trip unit

Icu [kA]
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 1250 2500 5000 315 630 1250 2500 5000
4000 1600 3200 6300 400 800 1600 3200 6300

16
20
9.4 20 T T T T T 9.3 19 T T T T T T T T T T T T
25
32
16 / 25 / 36
TM 210

100 A

40
50
63 8.6 13 25 T T T T 8.5 13 25 T T T T T T T T T T T
80
100

16
20
line protection

9.4 20 44 T T T T 9.3 19 44 T T T T T T T T T T T
25
TM210 / TM220 / TM240

32
downstream molded case circuit breaker 3VA1

40
160 A

50
25 / 36 / 55 / 70

63 8.6 13 25 42 T T T 8.5 13 25 42 T T T T T T T T T T
80
100

125
7.2 12 19 40 70 T T 7.1 12 19 40 70 T T T T T T T T T
160

160
5.3 7.9 16 20 24 55 T 5.3 7.6 16 20 24 55 T T T T T T T T
200
TM 240

250 A

250 5.3 7.9 16 20 24 55 T 7.6 16 20 24 55 T T T T T T T T

32 9.4 20 44 T T T T 9.3 19 44 T T T T T T T T T T T

40
50
TM120M

160 A
starter protection

63 8.6 14 24 42 T T T 8.5 13 24 42 T T T T T T T T T T
80
55 / 70

100

125 7.2 14 19 40 T T T 7.1 14 19 40 T T T T T T T T T T


TM120M

160
250 A

5.3 7.9 16 20 24 55 T 5.3 7.6 16 20 24 55 T T T T T T T T


200

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G1.11 3WL1 - 3VA1 5 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

2500
3200
3200
trip unit

Icu [kA]
3200 4000
In [A] 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 4000
4000 5000
5000
6300
6300
downstream molded case circuit breaker 3VL

3VL6

800 10 13 17 28.5 17 24.1 40 69.5 T T T T T T T


line protection

55 / 70 / 100

1000 14.5 18.5 17.9 23.5 30 41.4 41.4 17.9 23.3 29.8 41.4
ETU
3VL7

1250 14.5 18.5 17.9 23.5 30 41.4 41.4 41.4 23.3 29.8 41.4
3VL8

1600 18.5 30 41.4 29.8 41.4

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G1.12 3WL1 - 3VL 6 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B
edition 06/2017
Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

1000
250
1250 1600
315
1600 2000
400
frame size
2500 2000 2500
trip unit

Icu [kA]
500
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
0.16 T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV1

0.4 T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T
0.63 T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T
motor protection

100

1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
TMTU

S00

1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
53

12 37.3 T T T T T T 34.9 T T T T T T T T

G1.20 3WL1 - 3RV 7 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B
edition 06/2017
Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

1000
250
1250 1600
315
1600 2000
400
frame size
2500 2000 2500
trip unit

Icu [kA]
500
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
0.16 T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T
0.4 T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV1

0.63 T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
100
motor protection

1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
TMTU

S0

2.5 T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
12.5 36.2 T T T T T T 35.6 T T T T T T T T
16 28.9 T T T T T T 28.3 T T T T T T T T
20 27.8 T T T T T T 27.3 T T T T T T T T
50

22 23.9 T T T T T T 23.4 T T T T T T T T
25 23 49.5 T T T T T 22.4 47.5 T T T T T T T

G1.20 3WL1 - 3RV 8 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B
edition 06/2017
Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

1000
250
1250 1600
315
1600 2000
400
frame size
2500 2000 2500
trip unit

Icu [kA]
500
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
16 21.4 37.3 49.6 T T T T 21.1 36.1 49.6 T T T T T T
20 17.2 27.3 43.5 T T T T 16.9 26.5 43.5 T T T T T T
25 13.7 22.7 38.7 T T T T 13.5 22 38.7 T T T T T T
32 10.4 18.2 29.4 T T T T 10.2 17.6 29.4 T T T T T T
S2

50

40 9.7 15.8 26.5 46.2 T T T 9.6 15.1 26.5 46.2 T T T T T


45 9.1 15.2 25.8 46.7 T T T 9 14.7 25.8 46.2 T T T T T
downstream motor starter protection 3RV1

50 9.3 14.8 29.2 46.3 T T T 9 14.4 25.8 46 T T T T T


16 27.2 T T T T T T 26.9 41.2 65 65 65 T T T T
20 16.6 29.3 61.1 T T T T 16.2 28.6 61.1 65 65 T T T T
25 11.8 19 29.3 56.9 T T T 11.7 18.3 29.3 56,9 65 T T T T
motor protection

32 10.7 15.5 26.4 35.2 76.4 T T 10.6 14.9 26.4 35.2 65 T T T T


TMTU

40 7.5 11.3 18.6 30.6 55.4 99 T 7.5 11.1 18.6 30.6 52.7 99 T T T
100

50 7.4 11.6 17.3 27.2 44.3 78.3 T 7.4 11.1 17.3 27.2 41.5 78.3 T T T
63 7.1 10.4 14.3 24.5 35.4 75.2 T 7 10.2 14.3 24.5 34.7 75.2 T T T
75 6.7 9.8 12.5 21.3 34 68.1 T 6.6 9.6 12.5 21.3 33.1 68.1 T T T
S3

90 6.3 9.4 12.4 20.8 32.7 62.6 93.8 6.3 9.1 12.4 20.8 32 62.6 93.8 T T
100 6.3 9.1 12.2 21 38 61.6 93.7 6.3 8.8 12.2 20.8 36.6 61.6 93.7 T T
40 7.5 11.3 18.6 30.6 T T T 7.5 11.1 18.6 30.6 52.7 99 T T T
50 7.4 11.6 17.3 27.2 44.3 T T 7.4 11.1 17.3 27.2 41.5 78.3 T T T
63 7.1 10.4 14.3 24.5 35.4 T T 7 10.2 14.3 24.5 34.7 75.2 T T T
50

75 6.7 9.8 12.5 21.3 34 T T 6.6 9.6 12.5 21.3 33.1 68.1 T T T
90 6.3 9.4 12.4 20.8 32.7 T T 6.3 9.1 12.4 20.8 32 62.6 93.8 T T
100 6.3 9.1 12.2 21 38 T T 6.3 8.8 12.2 20.8 36.6 61.6 93.7 T T

G1.20 3WL1 - 3RV 9 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B
edition 06/2017
Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

1000
250
1250 1600
315
1600 2000
400
frame size
2500 2000 2500
trip unit

Icu [kA]
500
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
0.16 T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T
0.4 T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV2

0.5 T T T T T T T T T T T T T T T T
0.63 T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
motor protection

1.25 T T T T T T T T T T T T T T T T
100
TMTU

S00

1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
12.5 39 T T T T T T 37 T T T T T T T T
16 24 T T T T T T 23 53 T T T T T T T
55

G1.20 3WL1 - 3RV 10 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B
edition 06/2017
Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

1000
250
1250 1600
315
1600 2000
400
frame size
2500 2000 2500
trip unit

Icu [kA]
500
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
0.63 T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV2

2 T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T
100

3.2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
motor protection

5 T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T
TMTU

S0

8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
12.5 39 T T T T T T 37 T T T T T T T T
16 24 T T T T T T 23 53 T T T T T T T
20 20 44 T T T T T 20 43 T T T T T T T
22 19 38 T T T T T 18 36 T T T T T T T
55

25 16 32 T T T T T 15 31 T T T T T T T
28 16 31 T T T T T 15 29 T T T T T T T
32 15 30 54 T T T T 15 29 54 T T T T T T
36 13 T T T T T T 13 T T T T T T T T
20

40 13 T T T T T T 12 T T T T T T T T

G1.20 3WL1 - 3RV 11 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU15B ETU25B / ETU27B ETU45B / ETU76B
edition 06/2017
Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150

1000
250
1250 1600
315
1600 2000
400
frame size
2500 2000 2500
trip unit

Icu [kA]
500
In [A] 630 800 1000 1250 1600 2000 3200 250 315 400 500 630 800 2500 3200
630
4000 3200 4000
800
4000 5000
1000
5000 6300
1250
6300
14 35 T T T T T T 35 T T T T T T T T
17 25 50 T T T T T 24 48 T T T T T T T
20 21 47 T T T T T 21 44 T T T T T T T
25 17 29 59 T T T T 17 28 59 T T T T T T
32 13 23 43 T T T T 13 22 43 T T T T T T
36 11 19 34 T T T T 11 18 34 T T T T T T
40 10 17 32 T T T T 10 17 32 T T T T T T
65
downstream motor starter protection 3RV2

45 9.9 16 29 57 T T T 9.8 16 29 57 T T T T T
52 9.7 15 28 53 T T T 9.5 15 28 53 T T T T T
59 8.6 13 24 44 T T T 8.5 13 24 44 T T T T T
65 8.3 13 24 37 T T T 8.5 12 20 37 T T T T T
motor protection

73 8.3 12 20 37 T T T 8.2 11 20 37 T T T T T
80 7.9 11 19 37 T T T 7.8 11 19 37 T T T T T
TMTU

S2

14 35 72 T T T T T 35 67 T T T T T T T
17 25 50 T T T T T 24 48 T T T T T T T
20 21 47 T T T T T 21 44 T T T T T T T
25 17 29 59 T T T T 17 28 59 T T T T T T
32 13 23 43 94 T T T 13 22 43 94 T T T T T
36 11 19 34 69 T T T 11 18 34 69 T T T T T
100

40 10 17 32 69 T T T 10 17 32 69 T T T T T
45 9.9 16 29 57 T T T 9.8 16 29 57 T T T T T
52 9.7 15 28 53 T T T 9.5 15 28 53 T T T T T
59 8.6 13 24 44 T T T 8.5 13 24 44 T T T T T
65 8.3 13 24 37 T T T 8.2 12 20 37 T T T T T
73 8.3 12 20 37 82 T T 8.2 11 20 37 77 T T T T
80 7.9 11 19 37 80 T T 7.8 11 19 37 75 T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G1.20 3WL1 - 3RV 12 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
resp. IEC 60947-2 trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1.6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
2 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
35

3 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
downstream miniature circuit breaker 5SY4

10
A

13 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
20

20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
25 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
line protection

32 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
40 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
50 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
15

63 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
35

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
13 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
20

20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
10
B

25 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
32 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
40 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
50 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
15

63 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

G1.30 3WL1 - 5SY 13 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
resp. IEC 60947-2 trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

0.3 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1.6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
2 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
2.5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
35

3 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
3.5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
13 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
10
C

15 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
20

20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
downstream miniature circuit breaker 5SY4

25 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
30 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
32 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
35 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
line protection

40 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
45 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
50 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
15

60 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
63 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
80 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
0.3 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1.6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
35

2 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
3 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
4 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
10
D

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
13 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
20

20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
25 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
32 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
40 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
50 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
15

63 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

G1.30 3WL1 - 5SY 14 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
resp. IEC 60947-2 trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
30

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
10 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
13 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
15
B

20 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
32 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
40 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
10

63 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
0,3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
0,5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
1 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
1.6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
30

3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
downstream miniature circuit breaker 5SY6

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
8 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
10 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
C

13 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
(except 5SY60)

line protection

15 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
15

20 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
30 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
32 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
40 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
10

63 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
0.3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
0.5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
1 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
1.6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
30

2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
4 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
8 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
D

10 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
13 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
15

20 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
32 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
40 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
10

63 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

G1.30 3WL1 - 5SY 15 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
resp. IEC 60947-2 trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
30 40

10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25
15
B

25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20

50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.3 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.5 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
1 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50

1.6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
2 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
3 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
4 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40

6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
downstream miniature circuit breaker 5SY7

8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

30
C

10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
line protection

20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25

25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.3 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.5 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
1 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50

1.6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
2 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
3 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
4 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40

6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

30
D

10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25

25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20

50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

80 T T T T T T T T T T T T T T T
downstream miniature circuit breaker

100 T T T T T T T T T T T T T T T
10

10
B

125 T T T T T T T T T T T T T T T
line protection

80 T T T T T T T T T T T T T T T
5SP4

100 T T T T T T T T T T T T T T T
10

10
C

125 T T T T T T T T T T T T T T T

80 T T T T T T T T T T T T T T T
10

10
D

100 T T T T T T T T T T T T T T T

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB
*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G1.30 3WL1 - 5SY 16 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


characteristic

Icn [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

6 T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
4.5
B

25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL3

50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
line protection

1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T
4.5
C

10 T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T

G1.31 3WL1 - 5SL 17 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


characteristic

Icn [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

1 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T
10
B

16 T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL4

2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T
line protection

10
C

10 T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T
10
D

10 T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T

G1.31 3WL1 - 5SL 18 / 114


SIEMENS AG upstream air circuit breaker 3WL1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU15B / ETU25B / ETU27B / ETU45B / ETU76B

edition 06/2017 Icu [kA] 55 / 66 / 80 / 85 / 100 / 130 / 150


characteristic

Icn [kA]
In [A] 250 315 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

2 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T
B

20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL6

40 T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T
line protection

0.5 T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T
C

13 T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G1.31 3WL1 - 5SL 19 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

edition 06/2017 frame size 250 A 400 A 630 A 1000 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110 55 / 85 / 110 55 / 85 / 110

frame size
trip unit

Icu [kA]
In [A] 160 250 250 400 400 500 630 630 800 1000 160 250 250 400 500 630 630 800 1000

25 55 55 T T T T T T T T 55 55 T T T T T T T
ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

40 55 55 T T T T T T T T 55 55 T T T T T T T
100 A

63 55 55 T T T T T T T T 55 55 T T T T T T T

100 55 55 T T T T T T T T 55 55 T T T T T T T

25 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
55
85
40 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
110
150
160 A

63 5.7 6 T T T T T T T T 5.7 6 T T T T T T T

100 5.7 6 T T T T T T T T 5.7 6 T T T T T T T


downstream molded case circit breaker 3VA2

160 6 T T T T T T T T 6 T T T T T T T

160 3.2 T T T T T T T T 3.2 T T T T T T T


250 A
line protection

250 T T T T T T T T T T T T

25 55 55 T T T T T T T T 55 55 T T T T T T T

40 55 55 T T T T T T T T 55 55 T T T T T T T
100 A

63 55 55 T T T T T T T T 55 55 T T T T T T T

100 55 55 T T T T T T T T 55 55 T T T T T T T

25 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
55
ETU340

85
40 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
110
150
160 A

63 5.7 6 T T T T T T T T 5.7 6 T T T T T T T

100 5.7 6 T T T T T T T T 5.7 6 T T T T T T T

160 6 T T T T T T T T 6 T T T T T T T

160 3.2 T T T T T T T T 3.2 T T T T T T T


250 A

250 T T T T T T T T T T T T

G2.10 3VA2 - 3VA2 20 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860 ETU340

edition 06/2017 frame size 250 A 400 A 630 A 1000 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110 55 / 85 / 110 55 / 85 / 110

frame size
trip unit

Icu [kA]
In [A] 160 250 250 400 400 500 630 630 800 1000 160 250 250 400 500 630 630 800 1000

25 5.7 6 T T T T T T T T 5.7 6 T T T T T T T

40 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
160 A

55 63 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
ETU350M

110

100 5.7 6 T T T T T T T T 5.7 6 T T T T T T T


250 A

160 3.8 4.8 T T T T T T 4.7 T T T T T T


motor protection

55
400 A

250 87 87 87 on request 87 87 87 on request


110
Nachgeschaltener Kompaktleistungsschalter 3VA2

25 5.7 6 T T T T T T T T 5.7 6 T T T T T T T

40 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
160 A

55 63 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
ETU860M

110

100 5.7 6 T T T T T T T T 5.7 6 T T T T T T T


250 A

160 3.8 4.8 T T T T T T 4.7 T T T T T T

55
400 A

250 87 87 87 on request 87 87 87 on request


110

25 5.7 6 T T T T T T T T 5.7 6 T T T T T T T

40 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
160 A
starter protection

63 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
ETU310M

110
100 5.7 6 T T T T T T T T 5.7 6 T T T T T T T
250 A

160 3.8 4.8 T T T T T T 4.7 T T T T T T


400 A

250 87 87 87 on request 87 87 87 on request

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.10 3VA2 - 3VA2 21 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110

frame size
trip unit

Icu [kA]
In [A] 100 160 160 250 250 400 400 500 630 630 800 1000

16 36 36 36 36 T T T T T T T T
20 36 36 36 36 T T T T T T T T
25 36 36 36 36 T T T T T T T T
16 / 25 / 36

32 36 36 36 36 T T T T T T T T
100 A

40 2.9 4.4 36 36 T T T T T T T T
50 2.9 4.4 36 36 T T T T T T T T
63 2.9 4.4 36 36 T T T T T T T T
80 4.4 36 36 T T T T T T T T
100 4.4 36 36 T T T T T T T T
TM210 / TM220 / TM240

16 36 36 36 36 T T T T T T T T
line protection
downstream molded case circuit breaker 3VA1

20 36 36 36 36 T T T T T T T T
25 36 36 36 36 T T T T T T T T
32 36 36 36 36 T T T T T T T T
40 2.9 4.4 36 36 T T T T T T T T
160 A

25 / 36 / 55 / 70

50 2.9 4.4 36 36 T T T T T T T T
63 2.9 4.4 36 36 T T T T T T T T
80 4.4 36 36 T T T T T T T T
100 4.4 36 36 T T T T T T T T
125 36 T T T T T T T T
160 36 T T T T T T T T
160 13 12 T T T T T T
250 A

200 12 T T T T T T
250 12 T T T T T T
32 T T T T T T T T T T
40 T T T T T T T T T T
50 T T T T T T T T T T
starter protection

160 A

63 T T T T T T T T T T
TM120M

55 / 70

80 T T T T T T T T T T
100 T T T T T T T T T T
125 T T T T T T T T T T
160 13 12 T T T T T T
250 A

200 12 T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.11 3VA2 - 3VA1 22 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60947-2
line protection

edition 06/2017 trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100

frame size
trip unit

Icu [kA]
1000
In [A] 800 1600
1250

25
55
40
85 22 T T
63
110
100
100 A
ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

25
40
150 13 36 78
63
100
25
55 40
85 63 16 55 T
110 100
160
160 A
line protection

25
40
150 63 13 36 78
100
160
55
85 160
250 A

13 36 78
110 250
downstream molded case circuit breaker 3VA2

150

55
250
85 7.8 18 33
400
400 A

110
250
150 7.8 18 33
400
55 400
630 A

85 500 7.4 16 27
110 630

25
40
160 A

16 55 T
63
ETU350M / ETU860M

100
motor protection

250 A

55 160 13 36 78
110
400 A

250 7.8 18 33
630 A

400 7.4 16 27

25
40
160 A

16 55 T
63
100
starter protection

ETU310M

250 A

160 13 36 78
110
400 A

250 7.8 18 33
630 A

400 7.4 16 27

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA]
apply to the maximum value Iimax

G2.12 3VL - 3VA2 23 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60947-2
line protection

edition 06/2017 trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 70 100

frame size
trip unit

Icu [kA]
In [A] 800 1000 1250 1600

16
20
T T T T T T
25
16 / 25 / 36

32
100 A

40
50
63 31 T T T T T
80
TM210 / TM220

100
16
line protection

20
downstream molded case circuit breaker 3VA1

T T T T T T
25
32
40
160 A

25 / 36 / 55 / 70

50
63 31 T T T T T
80
100

125
26 T T T T T
160

160
TM240

250 A

200 19 31 31 T 65 65
250

32 T T T T T T
40
50
starter protection

160 A

63 31 T T T T T
TM120M

55 / 70

80
100

125 26 T T T T T

160
250 A

19 31 31 T 65 65
200

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA]
apply to the maximum value Iimax

G2.13 3VL - 3VA1 24 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110

frame size
trip unit

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 500 630 630 800 1000

1 T T T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
100

2.5 1.4 T T T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T T T T
S00

4 0.9 T T T 2.8 T T T T T T T T T T T T T T
5 1.1 T T T 2.1 T T T T T T T T T T T T T T
6.3 0.7 10 T T 1.8 9.6 T T T T T T T T T T T T T
8 0.7 1.3 T T 1.3 3.1 T T T T T T T T T T T T T
10 0.6 3.1 4.3 T 1.1 3.3 11 T T T T T T T T T T T T
53

12 1 12 T 1.7 9.8 T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV1

2.5 T T T T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T T T T
100

4 T T T T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T T T T
S0
motor protection

6.3 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
TMTU

10 6.6 T T T 6.9 T T T T T T T T T T T T T T
12.5 T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
50

22 T T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T
32 25 25 25 T T T T T T T T T T
S2

50

40 25 25 25 T T T T T T T T T T
45 25 T T T T T T T T T T
50 25 25 25 T T T T T T T T
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 25 25 50 50 50 T T T T T T T T T T
32 25 25 25 T T T T T T T T T T
50 /100

40 2.4 2.7 25 T T T T T T T T T T
S3

50 25 25 25 T T T T T T T T
63 25 25 25 T T T T T T T T
75 25 T T T T T T T T
90 25 T T T T T T T T
100 25 T T T T T T T T

G2.20 3VA2 - 3RV 25 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110

frame size
trip unit

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 500 630 630 800 1000

0.16 T T T T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T T T T
0.4 T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T
0.63 T T T T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T T T
100
S00

1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV2

6.3 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
12.5 T T T T T T T T T T T T T T T T T
motor protection

16 T T T T T T T T T T T T T T T T T
55
TMTU

0.63 T T T T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T T T
100

3.2 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T T T T
6.3 T T T T T T T T T T T T T T T T T T T
S0

8 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
12.5 T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
22 T T T T T T T T T T T T T T T
55

25 T T T T T T T T T T T T T T T
28 T T T T T T T T T T T T T
32 T T T T T T T T T T T T T
36 T T T T T T T T T T T T T
20

40 T T T T T T T T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.20 3VA2 - 3RV 26 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit TM210 / TM220 TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70

16 16
frame size
trip unit

20 20

Icu [kA]
In [A] 40 50 63 80 100 40 50 63 80 100 125 160 160 200 250
25 25
32 32
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T
100

2.5 T T T T T T T T T
3.2 T T T T T T T
S00

4 T T T T T
5 T T T T
6.3 T T T
8 T T T
10 T T T
53

12 T T T
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T
downstream motor starter protection 3RV1

2.5 25 T T T T T 25 T T T T T T T T T T
3.2 16 22 T T 16 22 T T T T T T T
100

4 T T T T T T T T T
5 16 16 T T T T T
S0
motor protection

6.3 22 43 T T T
8 17 20 T T T
TMTU

10 T T T
12.5 T T T
16 T T T
20 T T T
50

22 T T T
25 T T T
16 T T T
20 T T T
25 T T T
32 T T T
S2

50

40 T T T
45 T T T
50 T T T
16 T T T
20 T T T
25 T T T
32 T T T
50 / 100

40 6.4 7.3 11
S3

50 5.8 6.6 11
63 4.7 5.6 6.8
75 5.2 6.4
90 5.4
100 5.1

G2.21 3VA1 - 3RV 27 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit TM210 / TM220 TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70

16 16
frame size
trip unit

20 20

Icu [kA]
In [A] 40 50 63 80 100 40 50 63 80 100 125 160 160 200 250
25 25
32 32

0.16 T T T T T T T T T T T T T T T T T
0.2 T T T T T T T T T T T T T T T T T
0.25 T T T T T T T T T T T T T T T T T
0.32 T T T T T T T T T T T T T T T T T
0.4 T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T
0.63 T T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
100
S00

1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T
3.2 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T
downstream motor starter protection 3RV2

5 T T T T T T T T T
6.3 T T T T T
8 T T T T T
10 11 T T T
12.5 T T T
motor protection

16 T T T
55
TMTU

0.63 T T T T T T T T T T T T T T T T T
0.8 T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T
1.25 T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T
100

3.2 T T T T T T T T T T T T T T T
4 T T T T T T T T T T T
5 T T T T T T T T T
6.3 T T T T T
S0

8 T T T T T
10 11 T T T
12.5 T T T
16 T T T
20 T T T
22 T T T
55

25 T T T
28 T T T
32 T T T
36 T T T
20

40 T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.21 3VA1 - 3RV 28 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60947-2
line protection
edition 06/2017
trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100

frame size
trip unit

Icu [kA]
In [A] 800 1000 1250 1600

1 T T T T
1.25 T T T T
1.6 T T T T
2 T T T T
100

2.5 T T T T
3.2 T T T T
S00

4 T T T T
5 T T T T
6.3 T T T T
8 50 50 50 50
10 50 50 50 50
53

12 40 50 50 50
1 T T T T
1.25 T T T T
1.6 T T T T
2 T T T T
2.5 T T T T
downstream motor starter protection 3RV1

3.2 T T T T
100

4 T T T T
5 T T T T
S0

6.3 T T T T
motor protection

8 T T T T
TMTU

10 T T T T
12.5 30 T T T
16 30 T T T
20 25 T T T
50

22 20 T T T
25 20 T T T
16 20 T T T
20 15 T T T
25 12 40 T T
32 10 30 T T
S2

50

40 10 30 T T
45 8 30 T T
50 8 30 T T
16 25 T T T
20 15 80 T T
25 12 30 50 50
32 10 25 40 50
50 /100

40 6 20 30 30
S3

50 6 20 30 30
63 6 15 25 30
75 6 15 25 25
90 6 12 25 25
100 6 12 25 25

*) for breakers with adjustable trip unit: the limit current with selectivity Is
[kA] apply to the maximum value Iimax

G2.22 3VL - 3RV 29 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

1 T T T T T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T T T T T
35

3 T T T T T T T T T T T T T T T T T T T T T T T
4 16 T T T 16 T T T T 16 T T T T T T T T T T T T T
6 16 T T T 16 T T T T 16 T T T T T T T T T T T T T
8 16 T T T 16 T T T T 16 T T T T T T T T T T T T T
downstream miniature circuit breaker 5SY4

10 9.4 T T T 12 T T T T 5.5 T T T T T T T T T T T T T
10
A

13 6.2 16 T T 6.8 T T T T 4.7 14 T T T T T T T T T T T T


16 5.4 16 T T 5.7 T T T T 4.3 13 T T T T T T T T T T T T
20

20 16 19 T 16 T T T 13 T T T T T T T T T T T T
line protection

25 14 19 T 15 T T T 10 T T T T T T T T T T T T
32 19 T T T T 18 T T T T T T T T T T T
40 8 T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T
15

63 T T T T T T T T T T T T T T
6 16 T T T 16 T T T T 8.1 T T T T T T T T T T T T T
35

10 5.7 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T


13 4.5 16 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
16 3.7 14 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
20

20 7.7 19 T 10 T T T 6.3 19 T T T T T T T T T T T
10
B

25 7.6 19 T 10 T T T 6.3 19 T T T T T T T T T T T
32 18 T T T T 18 T T T T T T T T T T T
40 8 T T T T 7 T T T T T T T T T T T
50 T T T T T T T T T T T T T T
15

63 T T T T T T T T T T T T T T

G2.30 3VA2 - 5SY 30 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T T T T T T T T
35

3 T T T T T T T T T T T T T T T T T T T T T T T
3.5 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
4 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
5 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
6 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
8 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
10 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
13 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
10
C

15 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T


16 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
20
downstream miniature circuit breaker 5SY4

20 6.3 19 T 10 T T T 6.3 19 T T T T T T T T T T T
25 6.3 19 T 10 T T T 6.3 19 T T T T T T T T T T T
30 18 T T T T 18 T T T T T T T T T T T
32 18 T T T T 18 T T T T T T T T T T T
35 7 T T T T 7 T T T T T T T T T T T
line protection

40 7 T T T T 7 T T T T T T T T T T T
45 T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T
15

60 T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T
80
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
35

2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
4 8.7 16 16 16 9.7 16 16 16 16 5.4 16 16 16 16 16 16 16 16 16 16 T T T
6 5.9 16 16 16 7.1 16 16 16 16 4.5 16 16 16 16 16 16 16 16 16 16 T T T
8 4.6 16 16 16 4.9 16 16 16 16 3.5 9.5 16 16 16 16 16 16 16 16 16 T T T
10
D

10 4.4 16 16 16 4.5 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 T T T


13 4.2 16 16 16 4.3 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 T T T
16 3.7 11 16 16 4 11 16 16 16 3 6.2 16 16 16 16 16 16 16 16 16 T T T
20

20 5.2 8 8 3.2 5.2 16 16 16 3.6 4.9 16 16 16 16 16 16 16 16 T T T


25 4.2 8 8 4.6 16 16 16 3.6 4.6 16 16 16 16 16 16 16 16 T T T
32 8 8 4.2 15 16 16 4.3 16 16 16 16 16 16 16 16 T T T
40 8 8 9 T T 3.6 5.5 T T T T T T T T T T
50 8 T T 5.5 T T T T T T T T T T
15

63 8 T 5.5 T T T T T T T T T T

G2.30 3VA2 - 5SY 31 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

2 T T T T T T T T T T T T T T T T T T T T T T T
4 16 T T T 16 T T T T 16 T T T T T T T T T T T T T
30

6 16 T T T 16 T T T T 8.1 T T T T T T T T T T T T T
10 5.7 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
13 4.5 16 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
16 3.7 14 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
15
B

20 7.7 T T 10 T T T 6.3 T T T T T T T T T T T T
25 7.6 T T 10 T T T 6.3 T T T T T T T T T T T T
downstream miniature circuit breaker 5SY6 (except 5SY60)

32 T T T T T T T T T T T T T T T T T
40 8 T T T T 7 T T T T T T T T T T T
50 T T T T T T T T T T T T T T
10

63 T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T T T T T
line protection

1.6 T T T T T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T T T T T
30

3 T T T T T T T T T T T T T T T T T T T T T T T
4 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
5 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
6 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
8 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
10 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
C

13 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T


15 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
16 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
15

20 6.3 T T 10 T T T 6.3 T T T T T T T T T T T T
25 6.3 T T 10 T T T 6.3 T T T T T T T T T T T T
30 T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T
40 7 T T T T 7 T T T T T T T T T T T
50 T T T T T T T T T T T T T T
10

63 T T T T T T T T T T T T T T

G2.30 3VA2 - 5SY 32 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
downstream miniature circuit breaker 5SY6

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
30

2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
4 8.7 16 16 16 9.7 16 16 16 16 5.4 16 16 16 16 16 16 16 16 16 16 T T T
(außer 5SY60)

line protection

6 5.9 16 16 16 7.1 16 16 16 16 4.5 16 16 16 16 16 16 16 16 16 16 T T T


8 4.6 T T T 4.9 T T T T 3.5 9.5 T T T T T T T T T T T T
D

10 4.4 T T T 4.5 T T T T 3.2 9.5 T T T T T T T T T T T T


13 4.2 T T T 4.3 T T T T 3.2 9.5 T T T T T T T T T T T T
16 3.7 11 T T 4 11 T T T 3 6.2 T T T T T T T T T T T T
15

20 5.2 8 8 3.2 5.2 T T T 3.6 4.9 T T T T T T T T T T T


25 4.8 8 8 4.6 T T T 3.6 4.6 T T T T T T T T T T T
32 8 8 T T T 4.3 T T T T T T T T T T T
40 8 8 9 T T 3.6 5.5 T T T T T T T T T T
50 8 T T 5.5 T T T T T T T T T T
10

63 8 T 5.5 T T T T T T T T T T

G2.30 3VA2 - 5SY 33 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

6 16 T T T 16 T T T T 8.1 T T T T T T T T T T T T T
30 40

10 5.7 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T


13 4.5 16 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
16 3.7 14 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
20 7.7 19 T 3.6 10 T T T 6.3 19 T T T T T T T T T T T
25
15
B

25 7.6 19 T 10 T T T 6.3 19 T T T T T T T T T T T
32 18 T 10 T T T 18 T T T T T T T T T T T
40 8 T T T T 7 T T T T T T T T T T T
20

50 T T T T T T T T T T T T T T T
15

63 T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T T T T T
50

1.6 T T T T T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T T T T T T
4 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
40
downstream miniature circuit breaker 5SY7

6 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T


8 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
15

30
C

10 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T


13 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
line protection

16 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T


20 6.3 19 T 10 T T T 6.3 19 T T T T T T T T T T T
25

25 6.3 19 T 10 T T T 6.3 19 T T T T T T T T T T T
32 18 T T T T 18 T T T T T T T T T T T
40 7 T T T T 7 T T T T T T T T T T T
50 T T T T T T T T T T T T T T
20

63 T T T T T T T T T T T T T T
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
50

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
3 16 16 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 16 16 T T T
4 8.7 16 16 16 9.7 16 16 16 16 5.4 16 16 16 16 16 16 16 16 16 16 T T T
40

6 5.9 16 16 16 7.1 16 16 16 16 4.5 16 16 16 16 16 16 16 16 16 16 T T T


8 4.6 16 16 16 4.9 16 16 16 16 3.5 9.5 16 16 16 16 16 16 16 16 16 T T T
30
15
D

10 4.2 16 16 16 4.5 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 T T T


13 4 16 16 16 4.3 16 16 16 16 3.2 9.5 16 16 16 16 16 16 16 16 16 T T T
16 3.7 11 16 16 4 11 16 16 16 3 6.2 16 16 16 16 16 16 16 16 16 T T T
20 5.2 8 8 5.2 16 16 16 5.8 4.9 16 16 16 16 16 16 16 16 T T T
25

25 4.6 8 8 4.8 16 16 16 5.5 4.6 16 16 16 16 16 16 16 16 T T T


32 8 8 16 16 16 4.3 16 16 16 16 16 16 16 16 T T T
40 8 8 9 16 16 3.6 5.5 16 16 16 16 16 16 16 T T T
20

50 8 T T 5.5 T T T T T T T T T T
15

63 8 T T 5.5 T T T T T T T T T T

G2.30 3VA2 - 5SY 34 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

0.3 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
0.5 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
1 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
70

1.6 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
2 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
3 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
4 14 40 40 40 15 40 40 40 40 7.7 40 40 40 40 40 40 40 40 40 40 T T T
50

6 5.6 40 40 40 9.8 40 40 40 40 5.6 40 40 40 40 40 40 40 40 40 40 T T T


8 4.9 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
N/A

40
C

10 4.7 T T T 6.4 T T T T 4.5 30 T T T T T T T T T T T T


13 3.9 14 T T 5 25 T T T 3.7 9.6 T T T T T T T T T T T T
16 3.7 10 T T 5 25 T T T 3.7 9.6 T T T T T T T T T T T T
downstream miniature circuit breaker 5SY8

20 6.3 19 8 10 T T T 6.3 19 T T T T T T T T T T T
30

25 6.3 19 8 10 T T T 6.3 19 T T T T T T T T T T T
32 18 8 T T T 18 T T T T T T T T T T T
40 8 8 T T T 7 T T T T T T T T T T T
line protection

50 8 T T T T T T T T T T T T T
25

63 8 20 20 20 20 20 20 T T T T T T T
0.3 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
0.5 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
1 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
70

1.6 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
2 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
3 40 40 40 40 40 40 40 40 40 15 40 40 40 40 40 40 40 40 40 40 T T T
4 8.7 40 40 40 9.7 40 40 40 40 5.4 40 40 40 40 40 40 40 40 40 40 T T T
50

6 5.9 40 40 40 7.1 40 40 40 40 4.5 40 40 40 40 40 40 40 40 40 40 T T T


8 4.6 T T T 4.9 T T T T 3.5 9.5 T T T T T T T T T T T T
N/A

40
D

10 4.2 T T T 4.5 T T T T 3.2 9.5 T T T T T T T T T T T T


13 4 28 T T 4.3 T T T T 3.2 9.5 T T T T T T T T T T T T
16 3.7 11 T T 4 11 T T T 3 6.2 T T T T T T T T T T T T
20 5.2 8 8 5.2 T T T 5.8 4.9 T T T T T T T T T T T
30

25 4.6 8 8 4.8 25 25 25 5.5 4.6 T T 25 25 T T T T T T T


32 8 8 20 25 25 4.3 25 25 25 25 T T T T T T T
40 8 8 9 20 20 3.6 5.5 20 20 20 T T T T T T T
25

50 8 15 15 5.5 15 15 15 15 15 15 15 T T T
20

63 8 15 15 5.5 15 15 15 15 15 15 15 T T T

G2.30 3VA2 - 5SY 35 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

80 T 2.3 T T T T T T T T T
downstream miniature circuit breaker

100 T 2.2 T T T T T T T T T
B

125 T T T T T T T T T
line protection

80 T 2.3 T T T T T T T T T
5SP4

10

10

100 T 2.2 T T T T T T T T T
C

125 T T T T T T T T T

80 T 2.2 T T T T T T T T T
D

100 T 2.2 T T T T T T T T T

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB
*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.30 3VA2 - 5SY 36 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1 T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
35

3 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
8 T T T T 6.8 T T T T T T T T T T T
downstream miniature circuit breaker 5SY4

10 T T T T 6.8 T T T T T T T T T T T
10
A

13 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
20

20 17 T T 11 T T T T T T T T T T
line protection

25 17 T T 11 T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
50 T T T T T T T T T T
15

63 T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
35

10 T T T T 6.8 T T T T T T T T T T T
13 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
20

20 17 T T 11 T T T T T T T T T T
10
B

25 17 T T 11 T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
50 T T T T T T T T T T
15

63 T T T T T T T T T T

G2.30 3VA2 - 5SY 37 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1
0.3 T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
2.5 T T T T T T T T T T T T T T T T
35

3 T T T T T T T T T T T T T T T T
3.5 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
8 T T T T 6.8 T T T T T T T T T T T
10 T T T T 6.8 T T T T T T T T T T T
13 7.1 T T T 5.4 T T T T T T T T T T T
10
C

15 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
20
downstream miniature circuit breaker 5SY4

20 17 T T 11 T T T T T T T T T T
25 17 T T 11 T T T T T T T T T T
30 T T T T T T T T T T T T
32 T T T T T T T T T T T T
35 T T T T T T T T T T T T
line protection

40 T T T T T T T T T T T T
45 T T T T T T T T T T
50 T T T T T T T T T T
15

60 T T T T T T T T T T
63 T T T T T T T T T T
80
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
35

2 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
3 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
4 9.7 16 16 16 5.4 16 16 16 16 16 16 16 16 T T T
6 7.1 16 16 16 4.5 16 16 16 16 16 16 16 16 T T T
8 4.9 16 16 16 3.5 9.5 16 16 16 16 16 16 16 T T T
10
D

10 4.5 16 16 16 3.2 9.5 16 16 16 16 16 16 16 T T T


13 4.3 16 16 16 3.2 9.5 16 16 16 16 16 16 16 T T T
16 4 11 16 16 3 6.2 16 16 16 16 16 16 16 T T T
20

20 3.2 5.2 16 16 3.6 4.9 16 16 16 16 16 16 T T T


25 4.6 16 16 3.6 4.6 16 16 16 16 16 16 T T T
32 4.2 15 16 4.3 16 16 16 16 16 16 T T T
40 9 T 3.6 5.5 T T T T T T T T
50 T 5.5 T T T T T T T T
15

63 5.5 T T T T T T T T

G2.30 3VA2 - 5SY 38 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1
2 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
30

6 T T T T T T T T T T T T T T T T
10 T T T T 6.8 T T T T T T T T T T T
13 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
15
B

20 T T T 11 T T T T T T T T T T
25 T T T 11 T T T T T T T T T T
downstream miniature circuit breaker 5SY6 (except 5SY60)

32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
50 T T T T T T T T T T
10

63 T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
line protection

1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
30

3 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
5 T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
8 T T T T 6.8 T T T T T T T T T T T
10 T T T T 6.8 T T T T T T T T T T T
C

13 7.1 T T T 5.4 T T T T T T T T T T T
15 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
15

20 T T T 11 T T T T T T T T T T
25 T T T 11 T T T T T T T T T T
30 T T T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
50 T T T T T T T T T T
10

63 T T T T T T T T T T

G2.30 3VA2 - 5SY 39 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
downstream miniature circuit breaker 5SY6

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
30

2 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
3 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
4 9.7 16 16 16 5.4 16 16 16 16 16 16 16 16 T T T
(außer 5SY60)

line protection

6 7.1 16 16 16 4.5 16 16 16 16 16 16 16 16 T T T
8 4.9 T T T 3.5 9.5 T T T T T T T T T T
D

10 4.5 T T T 3.2 9.5 T T T T T T T T T T


13 4.3 T T T 3.2 9.5 T T T T T T T T T T
16 4 11 T T 3 6.2 T T T T T T T T T T
15

20 3.2 5.2 T T 3.6 4.9 T T T T T T T T T


25 4.6 T T 3.6 4.6 T T T T T T T T T
32 T T 4.3 T T T T T T T T T
40 9 T 3.6 5.5 T T T T T T T T
50 T 5.5 T T T T T T T T
10

63 5.5 T T T T T T T T

G2.30 3VA2 - 5SY 40 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1
6 T T T T T T T T T T T T T T T T
30 40

10 24 T T T 6.8 T T T T T T T T T T T
13 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
20 17 T T 11 T T T T T T T T T T
25
15
B

25 17 T T 11 T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
20

50 T T T T T T T T T T
15

63 T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T
50

1.6 T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T
40
downstream miniature circuit breaker 5SY7

6 T T T T T T T T T T T T T T T T
8 24 T T T 6.8 T T T T T T T T T T T
15

30
C

10 24 T T T 6.8 T T T T T T T T T T T
13 7.1 T T T 5.4 T T T T T T T T T T T
line protection

16 7.1 T T T 5.4 T T T T T T T T T T T
20 17 T T 11 T T T T T T T T T T
25

25 17 T T 11 T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
50 T T T T T T T T T T
20

63 T T T T T T T T T T
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
1 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
50

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
2 16 16 16 16 16 16 16 16 16 16 16 16 16 T T T
3 16 16 16 16 15 16 16 16 16 16 16 16 16 T T T
4 9.7 16 16 16 5.4 16 16 16 16 16 16 16 16 T T T
40

6 7.1 16 16 16 4.5 16 16 16 16 16 16 16 16 T T T
8 4.9 16 16 16 3.5 9.5 16 16 16 16 16 16 16 T T T
30
15
D

10 4.5 16 16 16 3.2 9.5 16 16 16 16 16 16 16 T T T


13 4.3 16 16 16 3.2 9.5 16 16 16 16 16 16 16 T T T
16 4 11 16 16 3 6.2 16 16 16 16 16 16 16 T T T
20 5.2 16 16 5.8 4.9 16 16 16 16 16 16 T T T
25

25 4.8 16 16 5.5 4.6 16 16 16 16 16 16 T T T


32 T 16 4.3 16 16 16 16 16 16 T T T
40 9 16 3.6 5.5 16 16 16 16 16 T T T
20

50 T 5.5 T T T T T T T T
15

63 T 5.5 T T T T T T T T

G2.30 3VA2 - 5SY 41 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1
0.3 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
0.5 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
1 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
70

1.6 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
2 50 50 50 50 50 50 50 50 50 50 50 50 50 T T T
3 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
4 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
50

6 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
8 24 T T T 6.8 T T T T T T T T T T T
N/A

40
C

10 24 T T T 6.8 30 T T T T T T T T T T
13 7.1 25 T T 5.4 25 T T T T T T T T T T
16 7.1 25 T T 5.4 25 T T T T T T T T T T
downstream miniature circuit breaker 5SY8

20 17 T T 11 25 T T T T T T T T T
30

25 17 T T 11 25 T T T T T T T T T
32 T T 25 T T T T T T T T T
40 T T 20 T T T T T T T T T
line protection

50 T T T T T T T T T T
25

63 20 20 20 T T T T T T T
0.3 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
0.5 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
1 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
70

1.6 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
2 40 40 40 40 40 40 40 40 40 40 40 40 40 T T T
3 40 40 40 40 15 40 40 40 40 40 40 40 40 T T T
4 9.7 40 40 40 5.4 40 40 40 40 40 40 40 40 T T T
50

6 7.1 40 40 40 4.5 40 40 40 40 40 40 40 40 T T T
8 4.9 T T T 3.5 9.5 T T T T T T T T T T
N/A

40
D

10 4.5 T T T 3.2 9.5 T T T T T T T T T T


13 4.3 T T T 3.2 9.5 T T T T T T T T T T
16 4 11 T T 3 6.2 T T T T T T T T T T
20 5.2 T T 5.8 4.9 T T T T T T T T T
30

25 4.8 25 25 5.5 4.6 T 25 T T T T T T T


32 20 25 4.3 25 25 T T T T T T T
40 9 20 3.6 5.5 20 T T T T T T T
25

50 15 5.5 15 15 15 15 15 T T T
20

63 15 5.5 15 15 15 15 15 T T T

G2.30 3VA2 - 5SY 42 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340
resp. acc. to IEC 60947-2
frame size 160 A 250 A 400 A 630 A 1000 A
edition 06/2017
Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110
characteristic

Icn [kA]

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

1
80 T T T T T T T T
downstream miniature circuit breaker

100 T T T T T T T T
B

125 T T T T T T T T
line protection

80 T T T T T T T T
5SP4

10

10

100 T T T T T T T T
C

125 T T T T T T T T

80 T T T T T T T T
D

100 T T T T T T T T

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB
*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.30 3VA2 - 5SY 43 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110


characteristic

Icn [kA]

In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

6 T T T T T T T T T T T T T T T T T T
10 3.7 T T T 4 T T T T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T
4.5
B

25 T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL3

50 T T T T T T T T T T T T
63 T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T
line protection

1 T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T
8 4 T T T T T T T T T T T T T T T T T
4.5
C

10 3.7 T T T 4 T T T T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T
50 T T T T T T T T T T T T
63 T T T T T T T T T T T T

G2.31 3VA2 - 5SL 44 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110


characteristic

Icn [kA]

In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

1 T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T
13 5.5 T T T 5.9 T T T T T T T T T T T T T
10
B

16 4.4 T T T 4.9 T T T T T T T T T T T T T
20 T 8 8 T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL4

25 T 8 8 T T T T T T T T T T T T T
32 8 8 T T T T T T T T T T T T
40 8 8 T T T T T T T T T T T T
50 8 T T T T T T T T T T T
63 8 T T T T T T T T T T T
line protection

0.3 T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T
8 5.1 T T T 5.6 T T T T T T T T T T T T T
10
C

10 5.1 T T T 5.6 T T T T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T T T T
16 3.7 T T T 4 T T T T T T T T T T T T T
20 T 8 8 7.3 T T T T T T T T T T T T
25 T 8 8 7.3 T T T T T T T T T T T T
32 8 8 T T T T T T T T T T T T
40 8 8 T T T T T T T T T T T T
50 8 T T T T T T T T T T T
63 8 T T T T T T T T T T T

G2.31 3VA2 - 5SL 45 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110


characteristic

Icn [kA]

In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

0.3 T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL4

1.6 T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T
line protection

6 6.7 T T T 7.1 T T T T T T T T T T T T T
8 3.3 T T T 3.9 T T T T T T T T T T T T T
10
D

10 3.3 T T T 3.9 T T T T T T T T T T T T T
13 3.2 T T T 3.6 T T T T T T T T T T T T T
16 3.2 T T T 3.6 T T T T T T T T T T T T T
20 T 8 8 T T T T T T T T T T T T T
25 T 8 8 T T T T T T T T T T T T T
32 8 8 T T T T T T T T T T T T
40 8 8 T T T T T T T T T T T T
50 8 T T T T T T T T T T T
63 8 T T T T T T T T T T T

G2.31 3VA2 - 5SL 46 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 55 / 85 / 110


characteristic

Icn [kA]

In [A] 25 40 63 100 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

2 T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T
6 4.6 T T T 5 T T T T T T T T T T T T T
10 3.7 T T T 4 T T T T T T T T T T T T T
13 3.7 T T T 4 T T T T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T T T T
B

20 T T T T T T T T T T T T T T T T
25 5.3 T T 5.4 T T T T T T T T T T T T
downstream miniature circuit breaker 5SL6

32 T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T
50 T T T T T T T T T T T T
63 T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T
line protection

1 T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T
2 4.4 T T T 4.6 T T T T T T T T T T T T T
3 4 T T T 4.3 T T T T T T T T T T T T T
4 3.9 T T T 4.1 T T T T T T T T T T T T T
6 3.9 T T T 4.1 T T T T T T T T T T T T T
8 3.8 T T T 4.4 T T T T T T T T T T T T T
10 3.7 T T T 4 T T T T T T T T T T T T T
C

13 3.7 T T T 4 T T T T T T T T T T T T T
16 2.8 T T T 3.2 T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T
25 5.3 T T 5.4 T T T T T T T T T T T T
32 T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T
50 T T T T T T T T T T T T
63 T T T T T T T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.31 3VA2 - 5SL 47 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A
edition 06/2017
Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

1 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 15 16 T T T T T
1.6 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 15 16 T T T T T
2 16 16 16 16 16 16 16 15 16 16 16 16 16 16 16 16 15 16 T T T T T
35

3 1.4 1.4 1.4 1.4 2.3 3.8 5.9 16 16 1.4 1.4 1.4 1.4 2.3 3.8 5.9 16 16 T T T T T
4 1 1 1 1 1.7 2.5 3.3 8.6 16 1 1 1 1 1.7 2.5 3.3 8.6 16 16 16 T T T
6 0.8 0.8 0.8 0.8 1.2 1.8 2.3 4 5.3 0.8 0.8 0.8 0.8 1.2 1.8 2.3 4 5.3 16 16 T T T
8 0.8 0.8 0.8 0.8 1.2 1.7 2 3.1 4.1 0.8 0.8 0.8 0.8 1.2 1.7 2 3.1 4.1 14 16 T T T
downstream miniature circuit breaker 5SY4

10 0.7 0.7 0.7 0.7 0.9 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 0.9 1.4 1.7 2.7 3.2 6.9 9.4 T T T
10
A

13 0.6 0.6 0.6 0.9 1.2 1.5 2.4 2.8 0.6 0.6 0.6 0.9 1.2 1.5 2.4 2.8 5.6 7 T T T
16 0.6 0.6 0.9 1.2 1.5 2.3 2.7 0.6 0.6 0.9 1.2 1.5 2.3 2.7 5.2 6.3 T T T
20

20 0.6 0.8 1.1 1.3 2 2.4 0.6 0.8 1.1 1.3 2 2.4 4.5 5.5 T T T
line protection

25 0.8 1.1 1.3 2.1 2.4 0.8 1.1 1.3 2.1 2.4 4.5 5.6 T T T
32 0.9 1.1 1.7 2 0.9 1.1 1.7 2 3.5 4.3 T T T
40 1.1 1.8 2.1 1.1 1.8 2.1 3.6 4.3 T T T
50 1.6 1.9 1.6 1.9 3.1 3.8 T T T
15

63 1.7 1.7 2.9 3.6 12 14 T


6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 10 16 T T T
35

10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
20

20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
10
B

25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 T T T
50 1.4 1.7 1.4 1.7 2.8 3.4 13 T T
15

63 1.6 1.6 2.7 3.3 12 T T

G2.32 3VA1 - 5SY 48 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A
edition 06/2017
Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
0.5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
2.5 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 T T T T T
35

3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 T T T T T
3.5 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
5 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
10
C

15 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
20

20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
downstream miniature circuit breaker 5SY4

25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
30 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
35 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 T T T
line protection

40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 T T T


45 1.3 1.6 1.3 1.6 2.9 3.5 12 14 T
50 1.3 1.6 1.3 1.6 2.9 3.5 12 14 T
15

60 1.4 1.4 2.7 3.3 12 14 T


63 1.4 1.4 2.7 3.3 12 14 T
80
0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
35

2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 16 16 16
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 16 16 16
6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 16 16 16
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 16 16 16
10
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 16 16 16
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 16 16 16
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 16 16 16
20

20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 16 16 16
25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 16 16
32 1.2 1.5 1.2 1.5 2.5 3 12 14 16
40 1.1 1.4 1.1 1.4 2.4 2.9 9.6 12 14
50 1.2 1.2 2.1 2.7 9.1 11 14
15

63 1.1 1.1 1.9 2.5 8.8 10 13

G2.32 3VA1 - 5SY 49 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A
edition 06/2017
Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
30

6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 10 16 T T T
10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
15
B

20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 T T T
50 1.4 1.7 1.4 1.7 2.8 3.4 T T T
10

63 1.6 1.6 2.7 3.3 T T T


0,3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
0,5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
30

3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
5 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
downstream miniature circuit breaker 5SY6

6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
C

13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
(except 5SY60)

line protection

15 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
15

20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
30 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 T T T
50 1.3 1.6 1.3 1.6 2.9 3.5 T T T
10

63 1.4 1.4 2.7 3.3 T T T


0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
30

2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 16 16 16
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 16 16 16
6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 16 16 16
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 T T T
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 T T T
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 T T T
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 T T T
15

20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 T T T
25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 T T
32 1.2 1.5 1.2 1.5 2.5 3 12 14 T
40 1.1 1.4 1.1 1.4 2.4 2.9 T T T
50 1.2 1.2 2.1 2.7 9.1 T T
10

63 1.1 1.1 1.9 2.5 8.8 T T

G2.32 3VA1 - 5SY 50 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A
edition 06/2017
Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 10 T T T T
30 40

10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
25
15
B

25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 17 T T
50 1.4 1.7 1.4 1.7 2.9 3.5 13 T T
20

63 1.6 1.6 2.7 3.2 12 T T


0.3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
0.5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
50

1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 T T T T T
3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
40
downstream miniature circuit breaker 5SY7

6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 10 14 T T T
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
15

30
C

10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
line protection

16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
25

25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 17 T T
50 1.3 1.6 1.3 1.6 2.9 3.5 13 T T
20

63 1.4 1.4 2.7 3.2 12 14 T


0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
50

1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 16 16 16
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 16 16 16
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 16 16 16
40

6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 16 16 16
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 16 16 16
30
15
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 16 16 16
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 16 16 16
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 16 16 16
20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 16 16 16
25

25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 16 16
32 1.2 1.5 1.2 1.5 2.5 3 12 14 16
40 1.1 1.4 1.1 1.4 2.4 2.9 9.6 12 14
20

50 1.2 1.2 2.1 2.7 9.1 11 14


15

63 1.1 1.1 1.9 2.5 8.8 10 13

G2.32 3VA1 - 5SY 51 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240
resp. acc. to IEC 60947-2
frame size 100 A 160 A 250 A
edition 06/2017
Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

Icu [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
0.5 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
1 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
70

1.6 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
2 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 1.2 1.2 1.2 1.2 1.8 2.7 3.4 6.9 11 50 50 50 50 50
3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 0.9 0.9 0.9 0.9 1.3 1.9 2.4 4.4 6.3 40 40 40 40 40
4 0.7 0.7 0.7 0.7 1 1.5 1.8 3 3.9 0.7 0.7 0.7 0.7 1 1.5 1.8 3 3.9 10 14 40 40 40
50

6 0.7 0.7 0.7 0.7 0.9 1.3 1.6 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.3 1.6 2.6 3.1 10 14 40 40 40
8 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.1 2.6 5.3 6.5 T T T
k.A.

40
C

10 0.6 0.6 0.6 0.6 0.8 1 1.3 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.3 2.1 2.6 5.3 6.5 T T T
13 0.5 0.5 0.5 0.7 0.9 1.2 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.2 1.8 2.3 4.3 5.4 T T T
16 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.3 5.4 T T T
downstream miniature circuit breaker 5SY8

20 0.4 0.6 0.8 1 1.6 1.9 0.4 0.6 0.8 1 1.6 1.9 3.5 4.4 T T T
30

25 0.6 0.8 1 1.6 1.9 0.6 0.8 1 1.6 1.9 3.5 4.4 T T T
32 0.8 1 1.6 1.9 0.8 1 1.6 1.9 3.4 4.1 T T T
40 0.9 1.5 1.7 0.9 1.5 1.7 3.1 3.7 T T T
line protection

50 1.4 1.6 1.4 1.6 2.9 3.5 13 T T


25

63 1.5 1.5 2.7 3.2 12 14 20


0.3 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
0.5 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
1 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
70

1.6 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
2 1 1 1 1 1.5 2.2 2.7 5.1 6.9 1 1 1 1 1.5 2.2 2.7 5.1 6.9 16 16 40 40 40
3 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 0.8 0.8 0.8 0.8 1.2 1.7 2.1 3.4 4.6 16 16 40 40 40
4 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 0.7 0.7 0.7 0.7 1 1.4 1.7 2.7 3.2 7.1 9.8 40 40 40
50

6 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.2 1.5 2.3 2.7 5.6 7.6 40 40 40
8 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 0.5 0.5 0.5 0.5 0.7 0.9 1.2 1.9 2.3 4.4 5.4 T T T
k.A.

40
D

10 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4 4.9 T T T
13 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 0.4 0.4 0.4 0.6 0.9 1.1 1.8 2.2 4.1 5.1 T T T
16 0.6 0.8 1 1.7 2.1 0.6 0.8 1 1.7 2.1 3.7 4.5 T T T
20 0.5 0.7 1 1.6 1.9 0.5 0.7 1 1.6 1.9 3.1 3.8 T T T
30

25 0.5 0.7 0.9 1.5 1.8 0.5 0.7 0.9 1.5 1.8 3 3.9 14 T T
32 1.2 1.5 1.2 1.5 2.5 3 12 14 25
40 1.1 1.4 1.1 1.4 2.4 2.9 9.6 12 14
25

50 1.2 1.2 2.1 2.7 9.1 11 14


20

63 1.1 1.1 1.9 2.5 8.8 10 13

80 1.8 5.7 6.4 7.1


downstream miniature circuit breaker

100 1.7 4.5 5.3 6.2


B

125 5.3 6.2


line protection

80 1.8 5.7 6.4 7.1


5SP4

10

10

100 1.7 4.5 5.3 6.2


C

125 5.3 6.2

80 4.4 5.3 6.3


D

100 3.8 5 6.2

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB
*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.32 3VA1 - 5SY 52 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

6 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 T T T T T
10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 T T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 T T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
4.5
B

25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T
downstream miniature circuit breaker 5SL3

50 1.2 1.4 1.2 1.4 2.5 3 T T T


63 1.3 1.3 2.4 2.9 T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
line protection

1 2.1 2.1 2.1 2.1 T T T T T 2.1 2.1 2.1 2.1 T T T T T T T T T T


1.6 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T T T T T T
2 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 T T T T T
3 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 T T T T T
6 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 T T T T T
8 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 4 T T T T
4.5
C

10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 T T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 T T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T
50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 1.3 2.4 2.9 T T T

G2.33 3VA1 - 5SL 53 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

1 T T T T T T T T T T T T T T T T T T T T T T T
2 5.5 5.5 5.5 5.5 T T T T T 5.5 5.5 5.5 5.5 T T T T T T T T T T
3 1.1 1.1 1.1 1.1 2.3 4.5 T T T 1.1 1.1 1.1 1.1 2.3 4.5 T T T T T T T T
4 0.8 0.8 0.8 0.8 1.1 1.7 2.2 5 6.5 0.8 0.8 0.8 0.8 1.1 1.7 2.2 5 6.5 T T T T T
6 0.7 0.7 0.7 0.7 0.9 1.4 1.7 3.2 4.2 0.7 0.7 0.7 0.7 0.9 1.4 1.7 3.2 4.2 T T T T T
8 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.7 3.3 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.7 3.3 8.9 T T T T
10 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.3 2.7 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.3 2.7 6.6 9.3 T T T
13 0.5 0.5 0.5 0.7 1 1.3 2.1 2.5 0.5 0.5 0.5 0.7 1 1.3 2.1 2.5 5.2 6.8 T T T
10
B

16 0.5 0.5 0.7 0.9 1.1 1.9 2.2 0.5 0.5 0.7 0.9 1.1 1.9 2.2 4.2 5.4 T T T
20 0.4 0.6 0.8 1 1.6 2 0.4 0.6 0.8 1 1.6 2 4 5.2 T T T
downstream miniature circuit breaker 5SL4

25 0.6 0.8 1 1.6 2 0.6 0.8 1 1.6 2 3.6 4.6 T T T


32 0.7 0.9 1.4 1.7 0.7 0.9 1.4 1.7 3.1 3.9 T T T
40 0.8 1.4 1.7 0.8 1.4 1.7 3.2 4 T T T
50 1.2 1.5 1.2 1.5 2.6 3.1 T T T
63 1.4 1.4 2.5 3 T T T
line protection

0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T T T T T
1.6 1.7 1.7 1.7 1.7 3.6 T T T T 1.7 1.7 1.7 1.7 3.6 T T T T T T T T T
2 0.9 0.9 0.9 0.9 1.5 2.3 3.3 8.6 T 0.9 0.9 0.9 0.9 1.5 2.3 3.3 8.6 T T T T T T
3 0.8 0.8 0.8 0.8 1.1 1.5 2 4.5 6 0.8 0.8 0.8 0.8 1.1 1.5 2 4.5 6 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.4 1.8 3.4 4.2 0.7 0.7 0.7 0.7 0.9 1.4 1.8 3.4 4.2 T T T T T
6 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.4 2.9 0.6 0.6 0.6 0.6 0.8 1.1 1.4 2.4 2.9 7.2 T T T T
8 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 4.7 6.1 T T T
10
C

10 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.8 1 1.6 2 4.7 6.1 T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.4 0.6 0.8 1 1.6 2 3.6 4.5 T T T
16 0.4 0.4 0.6 0.8 1 1.6 2 0.4 0.4 0.6 0.8 1 1.6 2 3.6 4.5 T T T
20 0.5 0.7 0.9 1.4 1.7 0.5 0.7 0.9 1.4 1.7 3.1 4 T T T
25 0.5 0.7 0.9 1.4 1.7 0.5 0.7 0.9 1.4 1.7 3.1 4 T T T
32 0.7 0.8 1.2 1.5 0.7 0.8 1.2 1.5 2.9 3.5 T T T
40 0.8 1.2 1.5 0.8 1.2 1.5 2.8 3.6 T T T
50 1.1 1.4 1.1 1.4 2.8 3.3 T T T
63 1.4 1.4 2.8 3.3 T T T

G2.33 3VA1 - 5SL 54 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

0.3 T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 2.5 2.5 2.5 2.5 T T T T T 2.5 2.5 2.5 2.5 T T T T T T T T T T
downstream miniature circuit breaker 5SL4

1.6 1.1 1.1 1.1 1.1 1.7 2.6 3.8 T T 1.1 1.1 1.1 1.1 1.7 2.6 3.8 T T T T T T T
2 0.8 0.8 0.8 0.8 1.3 1.9 2.6 6.3 7.6 0.8 0.8 0.8 0.8 1.3 1.9 2.6 6.3 7.6 T T T T T
3 0.7 0.7 0.7 0.7 1 1.4 1.8 3.3 4.4 0.7 0.7 0.7 0.7 1 1.4 1.8 3.3 4.4 T T T T T
4 0.6 0.6 0.6 0.6 0.8 1.1 1.5 2.7 3.3 0.6 0.6 0.6 0.6 0.8 1.1 1.5 2.7 3.3 7.8 T T T T
line protection

6 0.5 0.5 0.5 0.5 0.7 1 1.2 2.2 2.7 0.5 0.5 0.5 0.5 0.7 1 1.2 2.2 2.7 6.2 8.6 T T T
8 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.3 4.6 T T T
10
D

10 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.3 4.6 T T T
13 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.2 3.9 T T T
16 0.5 0.7 0.8 1.3 1.7 0.5 0.7 0.8 1.3 1.7 3.2 3.9 T T T
20 0.5 0.6 0.8 1.2 1.5 0.5 0.6 0.8 1.2 1.5 2.9 3.7 T T T
25 0.5 0.6 0.8 1.2 1.5 0.5 0.6 0.8 1.2 1.5 2.9 3.7 T T T
32 0.6 0.8 1.3 1.6 0.6 0.8 1.3 1.6 3 3.8 T T T
40 1.1 1.4 1.4 2.7 3.2 T T T
50 2.2 2.7 T T T
63 2.2 2.7 T T T

G2.33 3VA1 - 5SL 55 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

2 2.2 2.2 2.2 2.2 T T T T T 2.2 2.2 2.2 2.2 T T T T T T T T T T


4 0.6 0.6 0.6 0.6 0.8 1.1 1.4 3.3 4.2 0.6 0.6 0.6 0.6 0.8 1.1 1.4 3.3 4.2 T T T T T
6 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.2 4.5 T T T T
10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 4.7 T T T
13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 4.7 T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
B

20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
downstream miniature circuit breaker 5SL6

40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T


50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 2.4 2.9 T T T
0.3 T T T T T T T T T T T T T T T T T T T T T T T
line protection

0.5 T T T T T T T T T T T T T T T T T T T T T T T
1 2.1 2.1 2.1 2.1 5.2 T T T T 2.1 2.1 2.1 2.1 5.2 T T T T T T T T T
1.6 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T 0.9 0.9 0.9 0.9 1.4 2.2 2.9 T T T T T T T
2 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 0.7 0.7 0.7 0.7 1 1.5 1.8 3.1 3.6 T T T T T
3 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 T T T T T
4 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 T T T T T
6 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 0.7 0.7 0.7 0.7 0.9 1.2 1.4 2.5 2.9 T T T T T
8 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 0.5 0.5 0.5 0.5 0.7 0.9 1.1 1.7 2.1 4 5 T T T
10 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 0.4 0.4 0.4 0.4 0.6 0.9 1 1.6 2 3.7 4.7 T T T
C

13 0.4 0.4 0.4 0.6 0.8 1 1.5 2 0.4 0.4 0.4 0.6 0.8 1 1.5 2 3.6 4.7 T T T
16 0.4 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.4 0.5 0.7 0.9 1.3 1.6 3 3.7 T T T
20 0.4 0.5 0.7 0.9 1.3 1.6 0.4 0.5 0.7 0.9 1.3 1.6 3 3.6 T T T
25 0.5 0.7 0.9 1.3 1.6 0.5 0.7 0.9 1.3 1.6 2.9 3.5 T T T
32 0.7 0.9 1.3 1.5 0.7 0.9 1.3 1.5 2.5 3 T T T
40 0.9 1.3 1.6 0.9 1.3 1.6 2.9 3.4 T T T
50 1.2 1.4 1.2 1.4 2.5 3 T T T
63 1.3 2.4 2.9 T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.33 3VA1 - 5SL 56 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
3VL6 3VL7 3VL8
for 230 / 400V AC
acc. to IEC 60898 line protection
resp. acc. to IEC 60947-2 trip unit ETU

Icu [kA] 55 / 70 / 100


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 800 1000 1250 1600

6 10 10 10 10
35

10 10 10 10 10
13 10 10 10 10
16 10 10 10 10
20

20 10 10 10 10
10
B

25 10 10 10 10
32 10 10 10 10
40 10 10 10 10
50 10 10 10 10
15

63 10 10 10 10
0.3 10 10 10 10
0.5 10 10 10 10
downstream miniature circuit breaker 5SY4

1 10 10 10 10
1.6 10 10 10 10
2 10 10 10 10
2.5 10 10 10 10
35

3 10 10 10 10
line protection

3.5 10 10 10 10
4 10 10 10 10
5 10 10 10 10
6 10 10 10 10
8 10 10 10 10
10 10 10 10 10
13 10 10 10 10
10
C

15 10 10 10 10
16 10 10 10 10
20

20 10 10 10 10
25 10 10 10 10
30 10 10 10 10
32 10 10 10 10
35 10 10 10 10
40 10 10 10 10
45 10 10 10 10
50 10 10 10 10
15

60 10 10 10 10
63 10 10 10 10
80

G2.34 3VL - 5SY 57 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
3VL6 3VL7 3VL8
for 230 / 400V AC
acc. to IEC 60898 line protection
resp. acc. to IEC 60947-2 trip unit ETU

Icu [kA] 55 / 70 / 100


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 800 1000 1250 1600

2 6 6 6 6
4 6 6 6 6
30

6 6 6 6 6
10 6 6 6 6
13 6 6 6 6
16 6 6 6 6
15
B

20 6 6 6 6
25 6 6 6 6
downstream miniature circuit breaker 5SY6 (except 5SY60)

32 6 6 6 6
40 6 6 6 6
50 6 6 6 6
10

63 6 6 6 6
0.3 6 6 6 6
0.5 6 6 6 6
1 6 6 6 6
line protection

1.6 6 6 6 6
2 6 6 6 6
30

3 6 6 6 6
4 6 6 6 6
5 6 6 6 6
6 6 6 6 6
8 6 6 6 6
10 6 6 6 6
C

13 6 6 6 6
15 6 6 6 6
16 6 6 6 6
15

20 6 6 6 6
25 6 6 6 6
30 6 6 6 6
32 6 6 6 6
40 6 6 6 6
50 6 6 6 6
10

63 6 6 6 6

G2.34 3VL - 5SY 58 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
3VL6 3VL7 3VL8
for 230 / 400V AC
acc. to IEC 60898 line protection
resp. acc. to IEC 60947-2 trip unit ETU

Icu [kA] 55 / 70 / 100


edition 06/2017 characteristic

Icn [kA]

Icu [kA]
In [A] 800 1000 1250 1600

6 15 15 15 15
30 40

10 15 15 15 15
13 15 15 15 15
16 15 15 15 15
20 15 15 15 15
25
15
B

25 15 15 15 15
32 15 15 15 15
40 15 15 15 15
20
downstream miniature circuit breaker 5SY7

50 14.5 15 15 15
15

63 13.5 15 15 15
0.3 15 15 15 15
0.5 15 15 15 15
line protection

1 15 15 15 15
50

1.6 15 15 15 15
2 15 15 15 15
3 15 15 15 15
4 15 15 15 15
40

6 15 15 15 15
8 15 15 15 15
15

30
C

10 15 15 15 15
13 15 15 15 15
16 15 15 15 15
20 15 15 15 15
25

25 15 15 15 15
32 15 15 15 15
40 15 15 15 15
50 15 15 15 15
20

63 12.5 15 15 15

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value
Iimax
Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB

G2.34 3VL - 5SY 59 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60898
line protection

edition 06/2017 trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100


characteristic

trip unit

Icn [kA]

In [A] 800 1000 1250 1600

6 T T T T
10 T T T T
13 T T T T
16 T T T T
20 T T T T
4,5
B

25 T T T T
32 T T T T
40 T T T T
downstream miniature circuit breaker 5SL3

50 T T T T
63 T T T T
0,3 T T T T
0,5 T T T T
line protection

1 T T T T
1,6 T T T T
2 T T T T
3 T T T T
4 T T T T
6 T T T T
8 T T T T
4,5
C

10 T T T T
13 T T T T
16 T T T T
20 T T T T
25 T T T T
32 T T T T
40 T T T T
50 T T T T
63 T T T T

G2.35 3VL - 5SL 60 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60898
line protection

edition 06/2017 trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100


characteristic

trip unit

Icn [kA]

In [A] 800 1000 1250 1600

1 T T T T
2 T T T T
3 T T T T
4 T T T T
6 T T T T
8 T T T T
10 T T T T
13 T T T T
10
B

16 T T T T
20 T T T T
25 T T T T
32 T T T T
40 T T T T
50 T T T T
63 T T T T
0.3 T T T T
0.5 T T T T
1 T T T T
1.6 T T T T
downstream miniature circuit breaker 5SL4

2 T T T T
3 T T T T
4 T T T T
6 T T T T
8 T T T T
line protection

10
C

10 T T T T
13 T T T T
16 T T T T
20 T T T T
25 T T T T
32 T T T T
40 T T T T
50 T T T T
63 T T T T
0.3 T T T T
0.5 T T T T
1 T T T T
1.6 T T T T
2 T T T T
3 T T T T
4 T T T T
6 T T T T
8 T T T T
10
D

10 T T T T
13 T T T T
16 T T T T
20 T T T T
25 T T T T
32 T T T T
40 T T T T
50 T T T T
63 T T T T

G2.35 3VL - 5SL 61 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60898
line protection

edition 06/2017 trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100


characteristic

trip unit

Icn [kA]

In [A] 800 1000 1250 1600

2 T T T T
4 T T T T
6 T T T T
10 T T T T
13 T T T T
16 T T T T
B

20 T T T T
25 T T T T
32 T T T T
downstream miniature circuit breaker 5SL6

40 T T T T
50 T T T T
63 T T T T
0.3 T T T T
line protection

0.5 T T T T
1 T T T T
1.6 T T T T
2 T T T T
3 T T T T
4 T T T T
6 T T T T
8 T T T T
10 T T T T
C

13 T T T T
16 T T T T
20 T T T T
25 T T T T
32 T T T T
40 T T T T
50 T T T T
63 T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value
Iimax

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB

G2.35 3VL - 5SL 62 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU320 / ETU330 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 / 150 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110


characteristic

Icn [kA]
In [A] 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250 250 400 400 630 630 800 1000

6 T T T T T T T T T 8.1 T T T T T T T T T T T T T
10 5.7 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
downstream residual current device (RCBO)

13 4.5 T T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T


16 3.7 T T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
10
B

20 7.7 T T T T T T 6.3 T T T T T T T T T T T T
25 7.6 T T T T T T 6.3 T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T
line protection
5SU1, 10kA

40 T T T T T 7 T T T T T T T T T T T
6 5.6 T T T 9.8 T T T T 5.6 T T T T T T T T T T T T T
8 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
10 4.5 T T T 6.4 T T T T 4.5 T T T T T T T T T T T T T
13 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
16 3.7 9.6 T T 5 T T T T 3.7 9.6 T T T T T T T T T T T T
10
C

20 6.3 T T T T T T 6.3 T T T T T T T T T T T T
25 6.3 T T T T T T 6.3 T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T
40 T T T T T 7 T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T T T T T
10 5.7 T T T T T T T T 4.5 T T T T T T T T T T T T T
downstream residual current device (RCBO)

13 4.5 T T T 5 T T T T 3.7 T T T T T T T T T T T T T
4,5 / 6

16 3.7 T T T 5 T T T T 3.7 T T T T T T T T T T T T T
B

20 T T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T
5SU1, 4.5/6kA

line protection

40 T T T T T 7 T T T T T T T T T T T
6 5.6 T T T T T T T T 5.6 T T T T T T T T T T T T T
8 4.5 T T T T T T T T 4.5 T T T T T T T T T T T T T
10 4.5 T T T T T T T T 4.5 T T T T T T T T T T T T T
13 3.7 T T T 5 T T T T 3.7 T T T T T T T T T T T T T
4,5 / 6

16 3.7 T T T 5 T T T T 3.7 T T T T T T T T T T T T T
C

20 T T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T
40 T T T T T 7 T T T T T T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.40 3VA2 - 5SU1 63 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit ETU340

edition 06/2017 frame size 160 A 250 A 400 A 630 A 1000 A

Icu [kA] 55 / 85 / 110 150 55 / 85 / 110 / 150 55 / 85 / 110


characteristic

Icn [kA]
In [A] 25 40 63 100 25 40 63 100 160 250 400 500 630 630 800 1000

6 T T T T T T H T T T T T T T T T
10 T T T T 6.8 T T T T T T T T T T T
downstream residual current device (RCBO)

13 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
10
B

20 T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T
32 T T T T T T T T T T T T
line protection
5SU1, 10kA

40 T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
8 T T T T 6.8 T T T T T T T T T T T
10 T T T T 6.8 T T T T T T T T T T T
13 7.1 T T T 5.4 T T T T T T T T T T T
16 7.1 T T T 5.4 T T T T T T T T T T T
10
C

20 T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
downstream residual current device (RCBO)

13 T T T T 5.4 T T T T T T T T T T T
4,5 / 6

16 T T T T 5.4 T T T T T T T T T T T
B

20 T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T
32 T T T T T T T T T T T T
5SU1, 4.5/6kA

line protection

40 T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T
13 T T T T 5.4 T T T T T T T T T T T
4,5 / 6

16 T T T T 5.4 T T T T T T T T T T T
C

20 T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T
32 T T T T T T T T T T T T
40 T T T T T T T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.40 3VA2 - 5SU1 64 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60898
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70 25 / 36 / 55 / 70
characteristic

Icn [kA]
In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 T T T T T
10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 6.7 T T T
downstream residual current device (RCBO)

13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
10
B

20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
line protection
5SU1, 10kA

40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 T T T


6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 T T T T T
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 6.5 T T T
13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
10
C

20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.4 4.1 T T T
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 T T T
6 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 0.8 0.8 0.8 0.8 1 1.5 1.9 3.1 4.2 T T T T T
10 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 0.6 0.6 0.6 0.6 0.9 1.2 1.5 2.3 2.6 5.3 T T T T
downstream residual current device (RCBO)

13 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 0.6 0.6 0.6 0.8 1.1 1.3 2.1 2.5 4.5 5.5 T T T
4,5 / 6

16 0.5 0.5 0.8 1 1.3 2 2.3 0.5 0.5 0.8 1 1.3 2 2.3 4.3 5.4 T T T
B

20 0.5 0.7 1 1.2 1.8 2.2 0.5 0.7 1 1.2 1.8 2.2 3.8 4.8 T T T
25 0.6 0.9 1.1 1.7 2 0.6 0.9 1.1 1.7 2 3.5 4.4 T T T
32 0.9 1 1.6 1.9 0.9 1 1.6 1.9 3.4 4.1 T T T
5SU1, 4.5/6kA

line protection

40 1 1.5 1.8 1 1.5 1.8 3.1 3.9 T T T


6 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 0.7 0.7 0.7 0.7 0.9 1.2 1.5 2.6 3.1 T T T T T
8 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 T T T T
10 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 0.6 0.6 0.6 0.6 0.8 1 1.2 2.1 2.6 5.3 T T T T
13 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
4,5 / 6

16 0.5 0.5 0.7 0.9 1.1 1.8 2.3 0.5 0.5 0.7 0.9 1.1 1.8 2.3 4.3 5.4 T T T
C

20 0.4 0.6 0.8 0.9 1.5 1.9 0.4 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
25 0.6 0.8 0.9 1.5 1.9 0.6 0.8 0.9 1.5 1.9 3.5 4.4 T T T
32 0.8 0.9 1.5 1.9 0.8 0.9 1.5 1.9 3.4 4.1 T T T
40 0.9 1.4 1.7 0.9 1.4 1.7 3.1 3.7 T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.41 3VA1 - 5SU1 65 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860
edition 06/2017 frame size 100 A 160 A 250 A

55 55 55
Icu [kA] 85 150 85 150 85 150
110 110 110

Un [V] fuse

frame size
Icu [kA]

160
In [A] 25 40 63 100 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250
250

2, 4, 6, 10, 16, 20 T T T T T T T T T T T T T T T T T T T T T
25,32 T T T T T T T T T T T T T T T T T
35, 40, 50 T T T T T T T T T T T T T
000

63, 80 T T T T T T T T T
100 T T T T
125 T T 2.7 5.3
160 2.3
35, 40, 50 T T T T T T T T T T T T T
63,80 T T T T T T T T T
00

100, 125 T T T T
160 85
6, 10, 16, 20 T T T T T T T T T T T T T T T T T T T T T
25, 32 T T T T T T T T T T T T T T T T T
35, 40, 50 T T T T T T T T T T T T T
63 T T T T T T T T T
0

80 T T T T T T
100, 125 T T T T
160 85
downstream NH-fuse 3NA

utilization category gG

16, 20 T T T T T T T T T T T T T T T T T T T T T
400 / 500 / 690

25 T T T T T T T T T T T T T T T T T
35, 40, 50 T T T T T T T T T T T T T
120

63 T T T T T T T T T
80 T T T T T T T
1

100, 125 T T T T
160 85
200 85
224, 250
35, 50 T T T T T T T T T T T T T
63, 80 T T T T T T T T T
100, 125 T T T T
160, 200 85
2

224, 250
300, 315
355
400
200 85
224, 250
300, 315
3

355, 400
425
500
500
4a

G2.50 3VA2 - 3NA/Neozed 66 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A 250 A

55 55 55
Icu [kA] 85 150 85 150 85 150
110 110 110

Un [V] fuse

frame size
Icu [kA]

160
In [A] 25 40 63 100 25 40 63 100 25 40 63 100 160 25 40 63 100 160 160 250
250
utilization cat. gG
downstream fuse

35 T T T T T T T T T T T T T
D01 / D02 / D03
5SE2 (Neozed)

40 T T T T T T T T T T
400
50

50 T T T T T T T T T

63 T 2.3 T T 2.3 T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.50 3VA2 - 3NA/Neozed 67 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit
edition 06/2017 frame size 400 A 630 A 1000 A

55 55 55
Icu [kA] 85 150 85 85
110 110 110

Un [V] fuse

frame size
630
Icu [kA]

In [A] 250 400 250 400 400 500 630 800


1000

2, 4, 6, 10, 16, 20 T T T T T T T T
25,32 T T T T T T T T
35, 40, 50 T T T T T T T T
000

63, 80 T T T T T T T T
100 T T T T T T T T
125 T T T T T T T T
160 T T T T T T T T
35, 40, 50 T T T T T T T T
63,80 T T T T T T T T
00

100, 125 T T T T T T T T
160 T T T T T T T T
6, 10, 16, 20 T T T T T T T T
25, 32 T T T T T T T T
35, 40, 50 T T T T T T T T
63 T T T T T T T T
0

80 T T T T T T T T
100, 125 T T T T T T T T
160 T T T T T T T T
downstream NH-fuse 3NA

utilization category gG

16, 20 T T T T T T T T
400 / 500 / 690

25 T T T T T T T T
35, 40, 50 T T T T T T T T
120

63 T T T T T T T T
80 T T T T T T T T
1

100, 125 T T T T T T T T
160 T T T T T T T T
200 T T T T T T T
224, 250 T T T T T
35, 50 T T T T T T T T
63, 80 T T T T T T T T
100, 125 T T T T T T T T
160, 200 T T T T T T T T
2

224, 250 T T T T T
300, 315 T T T T
355 T T T
400 T T T on request
200 T T T T T T T T
224, 250 T T T T T T
300, 315 T T T T
3

355, 400 T T
425 T
on request
500 59
500 33
4a

G2.50 3VA2 - 3NA/Neozed 68 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit
edition 06/2017 frame size 400 A 630 A 1000 A

55 55 55
Icu [kA] 85 150 85 85
110 110 110

Un [V] fuse

frame size
630
Icu [kA]

In [A] 250 400 250 400 400 500 630 800


1000
utilization cat. gG
downstream fuse

35 T T T T T T T T
D01 / D02 / D03
5SE2 (Neozed)

40 T T T T T T T T
400
50

50 T T T T T T T T

63 T T T T T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply
to the maximum value Iimax

G2.50 3VA2 - 3NA/Neozed 69 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70

Un [V] fuse
25 25

frame sze
Icu [kA]

In [A] 16 20 32 50 63 80 100 16 20 32 50 63 80 100 125 160 160 200 250


40 40

2, 4, 6, 10 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T
32 T T T T T T T T T T T
000

35, 40 T T T T T T T T T
50, 63 T T T T T
80, 100 T T T
125 6.3 9 T
160 3.5
35 T T T T T T T T T
50, 63 T T T T T
00

80, 100, 125 T T T


downstream NH-fuse 3NA

6, 10 T T T T T T T T T T T T T T T T T T T
utilization category gG

16 T T T T T T T T T T T T T T T T T
400 / 500 / 690

20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T
120

32 T T T T T T T T T
0

35 T T T T T T T T T
40 T T T T T T T
50, 63 T T T T T
80, 100, 125 T T T
16 T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T
35 T T T T T T T T T
1

40 T T T T T T T T T
50, 63 T T T T T
80, 100, 125 T T T
35 T T T T T T T T T
50 T T T T T
63 T T T T
2

80, 100, 125 T T T


160 T

G2.51 3VA1 - 3NA/Neozed 70 / 114


SIEMENS AG upstream molded case circuit breaker 3VA1 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit TM210 / TM220 / TM240

edition 06/2017 frame size 100 A 160 A 250 A

Icu [kA] 16 / 25 / 36 25 / 36 / 55 / 70

Un [V] fuse
25 25

frame sze
Icu [kA]

In [A] 16 20 32 50 63 80 100 16 20 32 50 63 80 100 125 160 160 200 250


40 40
downstream fuse 5SE2 (Neozed)

utilization category gG

D01 / D02 / D03

35
40
400

on request T T T
50

50
63

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.51 3VA1 - 3NA/Neozed 71 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 100 A 160 A

55 55
Icu [kA] 85 150 85 150
110 110
Un [V] fuse

frame size

Icu [kA]
In [A] 25 40 63 100 25 40 63 100 25 40 63 100 160 25 40 63 100 160

20 T T T T 120 120 120 120 T T T T T 120 120 120 120 120


25 T T T T 120 120 120 120 T T T T T 120 120 120 120 120
32 T T T T 120 120 120 120 T T T T T 120 120 120 120 120
000

200

40 T T T T 120 120 120 120 T T T T T 120 120 120 120 120


50 T T T T 120 120 120 120 T T T T T 120 120 120 120 120
63 T T T T 120 120 120 120 T T T T T 120 120 120 120 120
690

25 T T T T T T T T T T T T T
35 T T T T T T T T T T T T T
utilization category gR

50 T T T T T T T T T T
63 T T T T T T
00

80 T T T T T T
100 T
125 T
downstream semiconductor-fuse 3NE

32 T T T T T T T T T T T T T T
100
1000

40 T T T T T T T T T T
0

50 T T T T T T T T T T
(NH-frame size)

160
200
1

250
690

350
400
2

500
16 T T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T
000

35 T T T T T T T T T T T T T T
40 T T T T T T T T T T
utilization category gS

63 T T T T T T
80 T T T T T T
690

100

100 T
00

125 T
160
200
1

250
350
400
2

500

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.52 3VA2 - 3NE 72 / 114


SIEMENS AG upstream molded case circuit breaker 3VA2 *)
Limit current with selectivity Is [kA]
for 230 / 400V AC line protection
acc. to IEC 60947-2
trip unit ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

edition 06/2017 frame size 250 A 400 A 630 A 1000 A

55 55 55 55
Icu [kA] 85 150 85 150 85 85
110 110 110 110
Un [V] fuse

frame size

Icu [kA]
In [A] 160 250 160 250 250 400 250 400 400 500 630 630 800 1000

20 T T 120 120 T T 120 120 T T T T T T


25 T T 120 120 T T 120 120 T T T T T T
32 T T 120 120 T T 120 120 T T T T T T
000

200

40 T T 120 120 T T 120 120 T T T T T T


50 T T 120 120 T T 120 120 T T T T T T
63 T T 120 120 T T 120 120 T T T T T T
690

25 T T T T T T T T T T T T T T
35 T T T T T T T T T T T T T T
utilization category gR

50 T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T
00

80 T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T
125 T T T T T T T T T T T T T T
downstream semiconductor-fuse 3NE

32 T T T T T T T T T T T T T T
100
1000

40 T T T T T T T T T T T T T T
0

50 T T T T T T T T T T T T T T
(NH-frame size)

160 85 T T T T T T T T T T
200 85 T T T T T T T T T T
1

250 T T T T T T T
690

350 T T T T T T
400 T T T T T
2

500 T T T T
16 T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T
000

35 T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T
utilization category gS

63 T T T T T T T T T T T T T T
80 T T T T T T T T T T T T T T
690

100

100 T T T T T T T T T T T T T T
00

125 T T T T T T T T T T T T T T
160 85 T T T T T T T T T T
200 85 T T T T T T T T T T
1

250 T T T T T T T
350 T T T T T T
400 T T T T T
2

500 T T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value Iimax

G2.52 3VA2 - 3NE 73 / 114


SIEMENS AG upstream molded case circuit breaker 3VL *)
Limit current with selectivity Is [kA]
for 230 / 400V AC 3VL6 3VL7 3VL8
acc. to IEC 60947-2
line protection

edition 06/2017 trip unit ETU ETU ETU

Icu [kA] 55 / 70 / 100 55 / 70 / 100 55 / 70 / 100

Un [V] fuse

frame size
Icu [kA]

In [A] 800 1000 1250 1600

2 T T T T
4 T T T T
6 T T T T
10 T T T T
16 T T T T
20 T T T T
25 T T T T
32 T T T T
35 T T T T
downstream NH-fuse 3NA

40 T T T T
000 / 00 / 0 / 1 / 2 / 3 / 4
utilization category gG

50 T T T T
400 / 500 / 690

63 60 T T T
80 31 T T T
120

100 12 T T T
125 5 52 T T
160 2.8 26 64 77
200 1.6 15 39 48
224 0.8 7.8 21 25
250 0.6 5.6 14 17
300 0.25 2.4 6 7.5
315 0.25 2.4 6 7.5
355 0.24 2 4.8 5.6
400 1.2 2.6 3.2
425 1 2 2.4
500 0.6 1.4 1.6
630 0.6 0.8
16 T T T T
downstream fuse 5SE2

utilization category gG

20 T T T T
D01 / D02 / D03

25 T T T T
(Neozed)

32 T T T T
400
50

35 T T T T
40 T T T T
50 T T T T
63 35 T T T

*) for breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to the maximum value
Iimax

G2.53 3VL - 3NA/Neozed 74 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60947-2
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 1 2 3 4 4a

frame size
trip unit

Icu [kA]
In [A] 200 224 250 200 224 250 300 315 355 400 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

25
55
40
85 3.3 4.1 5.6 3.3 4.1 5.6 17 19 72 T 3 4 5.7 17 19 72 T T T T T T T T T T T T T
63
110
100
100 A
ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

25
40
150 2.9 2.9 3.4 3.5 4.1 4.9 2.9 3.4 3.5 4.1 4.9 T T T T T T T T T T T T
63
100
downstream molded case circuit breaker 3VA2

25
55 40
85 63 3 3.5 4.1 3 3.5 4.1 5.8 5.9 10 12 3.4 4.2 5.8 5.9 10 12 T T T T T T T T T T T T
110 100
160
160 A
line protection

25
40
150 63 2.9 2.9 3.4 3.5 4.1 4.9 2.9 3.4 3.5 4.1 4.9 T T T T T T T T T T T T
100
160

55
160 2.9 2.9 3.4 3.5 4.1 4.9 2.9 3.4 3.5 4.1 4.9 T T T T T T T T T T T T
85
250 A

110
250 3.4 3.5 4.1 4.9 3.4 3.5 4.1 4.9 T T T T T T T T T T T T
150

55
85 250
400 A

7.8 13 T T T T T 8.4 T T T T
110 400
150

55 400
630 A

85 500 6.8 8.4 T T T 8.4 T T T


110 630

G3.10 3NA - 3VA2 75 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60947-2
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 1 2 3 4 4a

frame size
trip unit

Icu [kA]
In [A] 200 224 250 200 224 250 300 315 355 400 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

25
40
160 A

3 3.5 4.1 3 3.5 4.1 5.8 5.9 10 12 3.4 4.2 5.8 5.9 10 12 T T T T T T T T T T T T
63
ETU350M / ETU860M

100
motor protection

250 A
downstream molded case circuit breaker 3VA2

55 160 2.9 2.9 3.4 3.5 4.1 4.9 2.9 3.4 3.5 4.1 4.9 T T T T T T T T T T T T
110
400 A

250 7.8 13 T T T T T 8.4 T T T T


630 A

400 6.8 8.4 T T T 8.4 T T T

25
40
160 A

3 3.5 4.1 3 3.5 4.1 5.8 5.9 10 12 3.4 4.2 5.8 5.9 10 12 T T T T T T T T T T T T
63
100
starter protection

ETU310M

250 A

110 160 2.9 2.9 3.4 3.5 4.1 4.9 2.9 3.4 3.5 4.1 4.9 T T T T T T T T T T T T
400 A

250 7.8 13 T T T T T 8.4 T T T T


630 A

400 6.8 8.4 T T T 8.4 T T T

G3.10 3NA - 3VA2 76 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60947-2
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 000 00 0 1 2 3 4 4a

frame size
trip unit

Icu [kA]
In [A] 160 125 160 125 160 125 160 200 224 250 125 160 200 224 250 300 315 355 400 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

16
20
3.8 2.4 3.7 2.4 3.8 2.4 3.8 7.9 9.1 35 2.4 3.8 7.9 9.1 T T T T T 7.5 8.9 T T T T T T T T T T T T T T T T T
25
16 / 25 / 36

32
100 A

40
50
63 3.1 3 3.1 3.1 5.4 7.2 11 3.1 5.4 7.2 11 T T T T 5 6.9 11 T T T T T T T T T T T T T T T T
80
TM210 / TM220

100
16
downstream molded case circuit breaker 3VA1

line protection

20
3.8 2.4 3.7 2.4 3.8 2.4 3.8 7.9 9.1 36 2.4 3.8 7.9 9.1 36 T T T T 7.5 8.9 43 T T T T T T T T T T T T T T T T
25
32
40
160 A

25 / 36 / 55 / 70

50
63 3.1 3 3.1 3.1 5.4 7.2 11 3.1 5.4 7.2 11 36 41 T T 5 6.9 11 36 41 T T T T T T T T T T T T T T
80
100
125
5.4 6.2 7.4 5.4 6.2 7.4 16 17 56 T 5 6.1 7.6 16 17 56 T T T T T T T T T T T T T
160
160
TM240

250 A

200 4.7 4.9 6.6 9.5 4.7 4.9 6.6 9.5 19 28 T T T T T 19 T T T T


250
32 3.8 2.4 3.8 2.4 3.8 2.4 3.8 7.9 9.1 35 2.4 3.8 7.9 9.1 35 T T T T 7.5 8.9 43 T T T T T T T T T T T T T T T T
40
50
starter protection

160 A / 250 A

63 3.1 3.1 3.1 3.1 5.4 7.2 11 3.1 5.4 7.2 11 33 41 T T 4.9 6.9 11 33 41 T T T T T T T T T T T T T T
TM120M

55 / 70

80
100
125 5.4 6.2 7.4 5.4 6.2 7.4 16 17 56 T 5 6.1 7.6 16 17 56 T T T T T T T T T T T T T
160
4.7 4.9 6.6 9.5 4.7 4.9 6.6 9.5 19 28 T T T T T 19 T T T T
200

G3.11 3NA - 3VA1 77 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

1 0.2 0.4 3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 0.3 0.4 3 16 16 16 16 16 16 16 16 16


1.6 0.2 0.4 3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 0.3 0.4 3 16 16 16 16 16 16 16 16 16
2 0.2 0.4 3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 0.3 0.4 3 16 16 16 16 16 16 16 16 16
35

3 0.2 0.3 1 2.2 4.6 7.4 16 16 16 16 16 16 4.6 16 16 16 16 16 16 0.3 0.4 1 2.2 4.6 7.4 16 16 16 16 16 16
4 0.1 0.3 0.8 1.6 2.7 4.1 6.8 16 16 16 16 16 2.7 7.2 16 16 16 16 16 0.2 0.3 0.8 1.6 2.7 4.1 6.7 9.6 16 16 16 16
6 0.1 0.3 0.7 1.2 1.9 2.5 3.5 5 9.9 16 16 16 1.9 3.7 5 9.9 16 16 16 0.2 0.3 0.7 1.2 1.9 2.5 3.5 4.5 9.5 16 16 16
8 0.1 0.3 0.6 1.1 1.6 2.1 2.8 3.9 8.1 16 16 16 1.6 2.9 3.9 8.1 16 16 16 0.2 0.3 0.6 1.1 1.6 2.1 2.8 3.4 7.3 16 16 16
downstream miniature circit breaker 5SY4

10 0.1 0.2 0.6 0.9 1.4 1.7 2.3 3.1 5 13 16 16 1.4 2.4 3.1 5 13 16 16 0.2 0.3 0.6 0.9 1.4 1.7 2.3 2.8 4.8 11 16 16
10
A

13 0.1 0.2 0.5 0.9 1.2 1.5 2 2.7 4.2 8.4 10 16 1.2 2.1 2.7 4.2 8.2 12 16 0.2 0.3 0.5 0.9 1.2 1.5 2 2.4 4.1 7.8 12 16
16 0.2 0.5 0.8 1.2 1.5 1.9 2.5 3.9 7.7 10 16 1.2 2 2.5 3.9 7.5 12 16 0.3 0.5 0.8 1.2 1.5 1.9 2.3 3.8 7.1 11 16
20

20 0.5 0.8 1.1 1.3 1.7 2.1 3.3 6.4 9 16 1.1 1.7 2.1 3.3 6.3 10 16 0.5 0.8 1.1 1.3 1.7 1.9 3.2 5.9 10 16
line protection

25 0.8 1.1 1.3 1.7 2.2 3.3 6.3 8.3 15 1.1 1.7 2.2 3.3 6.2 9.6 15 0.8 1.1 1.3 1.7 2 3.3 5.9 9.6 15
32 1.1 1.4 1.8 2.7 4.6 5.6 10 1.4 1.8 2.7 4.5 6.4 10 1.1 1.4 1.6 2.6 4.4 6.4 10
40 1.4 1.8 2.8 4.6 5.5 11 1.5 1.8 2.8 4.5 6.2 10 1.4 1.7 2.7 4.4 6.2 11
50 1.6 2.4 4.1 4.9 9.7 1.6 2.4 4 5.4 9.4 1.5 2.3 3.9 5.4 9.7
15

63 2.2 3.8 4.7 7.8 2.2 3.8 5.3 7.7 2.1 3.6 5.2 7.9
6 0.1 0.2 0.6 1 1.5 2 2.7 3.9 7.1 16 16 16 1.5 2.8 3.9 7.1 16 16 16 0.2 0.3 0.6 1 1.5 2 2.7 3.4 6.9 16 16 16
35

10 0.1 0.2 0.5 0.9 1.2 1.4 1.9 2.4 3.9 8.3 11 16 1.2 1.9 2.4 3.9 8.1 14 16 0.2 0.3 0.5 0.9 1.2 1.4 1.8 2.2 3.7 7.6 14 16
13 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.4 6 7.7 16 1.1 1.8 2.2 3.4 5.9 8.8 16 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2 3.3 5.7 8.8 16
16 0.2 0.4 0.7 1 1.2 1.6 2 3.1 5.4 6.8 15 1 1.6 2 3.1 5.3 8 14 0.2 0.4 0.7 1 1.2 1.6 1.9 3 5.1 7.9 15
20

20 0.4 0.7 1 1.2 1.5 1.9 2.9 5.2 6.4 11 1 1.5 1.9 2.9 5.1 7.1 10 0.4 0.7 1 1.2 1.5 1.7 2.8 4.9 7.1 11
10
B

25 0.6 0.9 1.1 1.3 1.7 2.5 4.7 5.8 9.9 0.9 1.4 1.7 2.5 4.6 6.5 9.6 0.6 0.9 1.1 1.3 1.6 2.5 4.4 6.5 9.9
32 1.1 1.3 1.6 2.5 4.4 5.3 8.5 1.3 1.6 2.5 4.4 5.8 8.3 1.1 1.3 1.5 2.4 4.2 5.8 8.5
40 1.2 1.5 2.3 4.7 6 8.6 1.3 1.5 2.3 4.6 6.5 8.5 1.2 1.4 2.2 4.4 6.4 8.6
50 1.4 2.1 3.7 4.5 7.8 1.4 2.1 3.6 5 7.6 1.3 2 3.5 5 7.9
15

63 2.1 3.4 4.2 7 2.1 3.3 4.7 6.9 2.1 3.2 4.7 7.1

G3.30 3NA - 5SY 78 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

0.3 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
0.5 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
1 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
1.6 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
2 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
2.5 0.1 0.3 0.7 1.2 1.7 2.2 2.9 4.2 8.2 16 16 16 1.7 3 4.2 8.2 16 16 16 0.2 0.3 0.7 1.2 1.7 2.2 2.9 3.7 7.9 16 16 16
35

3 0.1 0.3 0.7 1.2 1.7 2.2 2.9 4.2 8.2 16 16 16 1.7 3 4.2 8.2 16 16 16 0.2 0.3 0.7 1.2 1.7 2.2 2.9 3.7 7.9 16 16 16
3.5 0.1 0.2 0.6 1 1.5 1.9 2.6 3.6 6 16 16 16 1.5 2.7 3.6 6 16 16 16 0.2 0.3 0.6 1 1.5 1.9 2.6 3.2 5.8 16 16 16
downstream miniature circit breaker 5SY4

4 0.1 0.2 0.6 1 1.5 1.9 2.6 3.6 6 16 16 16 1.5 2.7 3.6 6 16 16 16 0.2 0.3 0.6 1 1.5 1.9 2.6 3.2 5.8 16 16 16
5 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 9.3 13 16 1.2 2 2.6 4.1 9 15 16 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 8.4 15 16
6 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 9.3 13 16 1.2 2 2.6 4.1 9 15 16 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 8.4 15 16
8 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.5 7 9.8 16 1.1 1.8 2.2 3.5 6.8 12 16 0.2 0.3 0.5 0.8 1.1 1.3 1.7 2 3.4 6.3 12 16
line protection

10 0.2 0.4 0.7 1.1 1.3 1.7 2.2 3.4 6.6 8.7 16 1.1 1.7 2.2 3.4 6.4 10 16 0.2 0.4 0.7 1.1 1.3 1.7 2 3.3 6.1 10 16
13 0.2 0.4 0.6 1 1.1 1.4 1.8 2.8 4.8 5.9 12 1 1.5 1.8 2.8 4.8 6.8 11 0.2 0.4 0.6 1 1.1 1.4 1.7 2.7 4.6 6.7 12
10
C

15 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 6.6 15 1 1.5 1.9 3 5.2 7.7 14 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 7.7 15
16 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 6.6 15 1 1.5 1.9 3 5.2 7.7 14 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 7.7 15
20

20 0.6 0.9 1 1.3 1.6 2.5 4.3 5.1 10 0.9 1.3 1.6 2.5 4.2 5.8 9.9 0.6 0.9 1 1.3 1.5 2.4 4 5.7 10
25 0.6 0.9 1.1 1.3 1.6 2.5 4.5 5.6 10 0.9 1.3 1.6 2.5 4.4 6.3 9.9 0.6 0.9 1.1 1.3 1.5 2.4 4.3 6.3 10
30 1.1 1.4 1.7 2.5 4.2 5.2 9.9 1.4 1.7 2.5 4.1 6 9.6 1.1 1.4 1.6 2.4 3.9 5.9 9.9
32 1.1 1.4 1.7 2.5 4.2 5.2 9.9 1.4 1.7 2.5 4.1 6 9.6 1.1 1.4 1.6 2.4 3.9 5.9 9.9
35 1.2 1.5 2.2 3.9 4.8 8.6 1.2 1.5 2.2 3.8 5.4 8.4 1.2 1.3 2.1 3.7 5.3 8.6
40 1.2 1.5 2.2 3.9 4.8 8.6 1.2 1.5 2.2 3.8 5.4 8.4 1.2 1.3 2.1 3.7 5.3 8.6
45 1.4 2 3.7 4.5 7.7 1.4 2 3.6 5.1 7.6 1.3 2 3.4 5 7.8
50 1.4 2 3.7 4.5 7.7 1.4 2 3.6 5.1 7.6 1.3 2 3.4 5 7.8
15

60 1.9 3.4 4.1 7.1 1.9 3.3 4.7 7 1.8 3.2 4.6 7.1
63 1.9 3.4 4.1 7.1 1.9 3.3 4.7 7 1.8 3.2 4.6 7.1
80

G3.30 3NA - 5SY 79 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

0.3 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
0.5 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
1 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
downstream miniature circit breaker 5SY4

1.6 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
35

2 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
3 0.1 0.2 0.6 1.1 1.6 2.1 2.9 4.4 8.9 16 16 16 1.6 2.9 4.4 8.9 16 16 16 0.2 0.3 0.6 1.1 1.6 2.1 2.8 3.8 8.6 16 16 16
4 0.1 0.2 0.6 1 1.4 1.7 2.3 3.1 5.1 15 16 16 1.4 2.4 3.1 5.1 14 16 16 0.2 0.3 0.6 1 1.4 1.7 2.3 2.8 4.9 12 16 16
line protection

6 0.1 0.2 0.5 0.8 1.2 1.5 1.9 2.5 4.1 9.5 13 16 1.2 2 2.5 4.1 9.2 16 16 0.2 0.2 0.5 0.8 1.2 1.5 1.9 2.3 4 8.6 16 16
8 0.4 0.7 1 1.2 1.6 2 3.2 6.1 7.7 16 1 1.6 2 3.2 5.9 8.8 16 0.1 0.4 0.7 1 1.2 1.5 1.8 3.1 5.7 8.7 16
10
D

10 0.3 0.6 0.9 1.1 1.5 1.9 3 5.3 7.1 16 0.9 1.5 1.9 3 5.2 8.8 16 0.3 0.6 0.9 1.1 1.5 1.7 2.9 5 8.7 16
13 0.6 0.9 1.1 1.5 1.9 3 5.6 7.6 16 0.9 1.5 1.9 3 5.5 9.1 16 0.6 0.9 1.1 1.5 1.7 2.9 5.3 9.1 16
16 0.5 0.8 1.1 1.4 1.8 2.8 4.8 5.9 12 0.8 1.4 1.8 2.8 4.8 6.9 11 0.5 0.8 1.1 1.4 1.6 2.8 4.6 6.8 12
20

20 1 1.2 1.6 2.4 4 4.8 10 1.3 1.6 2.4 4 5.4 10 1 1.2 1.4 2.3 3.8 5.4 10
25 0.5 0.7 1 1.2 1.5 2.3 4.2 5.1 9.8 0.7 1.2 1.5 2.3 4.1 5.8 9.6 0.5 0.7 1 1.2 1.4 2.2 3.9 5.8 9.9
32 1 1.2 1.8 3.3 4 7.1 1 1.2 1.8 3.2 4.5 7 1 1.1 1.8 3.1 4.5 7.2
40 0.9 1.1 1.7 3.1 3.5 5.5 0.9 1.1 1.7 3 3.9 5.4 0.9 1 1.7 3 3.8 5.5
50 1.5 3 3.5 5.8 1.5 2.9 3.9 5.7 1.4 2.8 3.9 5.9
15

63 1.3 2.7 3.3 5.4 1.3 2.7 3.6 5.3 1.2 2.5 3.6 5.5

G3.30 3NA - 5SY 80 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

2 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
4 0.1 0.2 0.6 1 1.5 1.9 2.6 3.6 6 16 16 16 1.5 2.7 3.6 6 16 16 16 0.2 0.3 0.6 1 1.5 1.9 2.6 3.2 5.8 16 16 16
30

6 0.1 0.2 0.6 1 1.5 2 2.7 3.9 7.1 16 16 16 1.5 2.8 3.9 7.1 16 16 16 0.2 0.3 0.6 1 1.5 2 2.7 3.4 6.9 16 16 16
10 0.1 0.2 0.5 0.9 1.2 1.4 1.9 2.4 3.9 8.3 11 16 1.2 1.9 2.4 3.9 8.1 14 16 0.2 0.3 0.5 0.9 1.2 1.4 1.8 2.2 3.7 7.6 14 16
13 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.4 6 7.7 16 1.1 1.8 2.2 3.4 5.9 8.8 16 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2 3.3 5.7 8.8 16
16 0.2 0.4 0.7 1 1.2 1.6 2 3.1 5.4 6.8 15 1 1.6 2 3.1 5.3 8 14 0.2 0.4 0.7 1 1.2 1.6 1.9 3 5.1 7.9 15
15
B

20 0.4 0.7 1 1.2 1.5 1.9 2.9 5.2 6.4 11 1 1.5 1.9 2.9 5.1 7.1 10 0.4 0.7 1 1.2 1.5 1.7 2.8 4.9 7.1 11
25 0.6 0.9 1.1 1.3 1.7 2.5 4.7 5.8 9.9 0.9 1.4 1.7 2.5 4.6 6.5 9.6 0.6 0.9 1.1 1.3 1.6 2.5 4.4 6.5 9.9
32 1.1 1.3 1.6 2.5 4.4 5.3 8.5 1.3 1.6 2.5 4.4 5.8 8.3 1.1 1.3 1.5 2.4 4.2 5.8 8.5
40 1.2 1.5 2.3 4.7 6 8.6 1.3 1.5 2.3 4.6 6.5 8.5 1.2 1.4 2.2 4.4 6.4 8.6
50 1.4 2.1 3.7 4.5 7.8 1.4 2.1 3.6 5 7.6 1.3 2 3.5 5 7.9
10
downstream miniature circit breaker 5SY6

63 2.1 3.4 4.2 7 2.1 3.3 4.7 6.9 2.1 3.2 4.7 7.1
0,3 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
0,5 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
1 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
(except 5SY60)

line protection

1.6 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
2 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
30

3 0.1 0.3 0.7 1.2 1.7 2.2 2.9 4.2 8.2 16 16 16 1.7 3 4.2 8.2 16 16 16 0.2 0.3 0.7 1.2 1.7 2.2 2.9 3.7 7.9 16 16 16
4 0.1 0.2 0.6 1 1.5 1.9 2.6 3.6 6 16 16 16 1.5 2.7 3.6 6 16 16 16 0.2 0.3 0.6 1 1.5 1.9 2.6 3.2 5.8 16 16 16
5 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 9.3 13 16 1.2 2 2.6 4.1 9 15 16 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 8.4 15 16
6 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 9.3 13 16 1.2 2 2.6 4.1 9 15 16 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 8.4 15 16
8 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.5 7 9.8 16 1.1 1.8 2.2 3.5 6.8 12 16 0.2 0.3 0.5 0.8 1.1 1.3 1.7 2 3.4 6.3 12 16
10 0.2 0.4 0.7 1.1 1.3 1.7 2.2 3.4 6.6 8.7 16 1.1 1.7 2.2 3.4 6.4 10 16 0.2 0.4 0.7 1.1 1.3 1.7 2 3.3 6.1 10 16
C

13 0.2 0.4 0.6 1 1.1 1.4 1.8 2.8 4.8 5.9 12 1 1.5 1.8 2.8 4.8 6.8 11 0.2 0.4 0.6 1 1.1 1.4 1.7 2.7 4.6 6.7 12
15 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 6.6 15 1 1.5 1.9 3 5.2 7.7 14 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 7.7 15
16 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 6.6 15 1 1.5 1.9 3 5.2 7.7 14 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 7.7 15
15

20 0.6 0.9 1 1.3 1.6 2.5 4.3 5.1 10 0.9 1.3 1.6 2.5 4.2 5.8 9.9 0.6 0.9 1 1.3 1.5 2.4 4 5.7 10
25 0.6 0.9 1.1 1.3 1.6 2.5 4.5 5.6 10 0.9 1.3 1.6 2.5 4.4 6.3 9.9 0.6 0.9 1.1 1.3 1.5 2.4 4.3 6.3 10
30 1.1 1.4 1.7 2.5 4.2 5.2 9.9 1.4 1.7 2.5 4.1 6 9.6 1.1 1.4 1.6 2.4 3.9 5.9 9.9
32 1.1 1.4 1.7 2.5 4.2 5.2 9.9 1.4 1.7 2.5 4.1 6 9.6 1.1 1.4 1.6 2.4 3.9 5.9 9.9
40 1.2 1.5 2.2 3.9 4.8 8.6 1.2 1.5 2.2 3.8 5.4 8.4 1.2 1.3 2.1 3.7 5.3 8.6
50 1.4 2 3.7 4.5 7.7 1.4 2 3.6 5.1 7.6 1.3 2 3.4 5 7.8
10

63 1.9 3.4 4.1 7.1 1.9 3.3 4.7 7 1.8 3.2 4.6 7.1

G3.30 3NA - 5SY 81 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

0.3 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
0.5 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
1 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
downstream miniature circit breaker 5SY6

1.6 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
30

2 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 15 16 16 16 2.2 4.5 6.5 15 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
3 0.1 0.2 0.6 1.1 1.6 2.1 2.9 4.4 8.9 16 16 16 1.6 2.9 4.4 8.9 16 16 16 0.2 0.3 0.6 1.1 1.6 2.1 2.8 3.8 8.6 16 16 16
4 0.1 0.2 0.6 1 1.4 1.7 2.3 3.1 5.1 15 16 16 1.4 2.4 3.1 5.1 14 16 16 0.2 0.3 0.6 1 1.4 1.7 2.3 2.8 4.9 12 16 16
(except 5SY60)

line protection

6 0.1 0.2 0.5 0.8 1.2 1.5 1.9 2.5 4.1 9.5 13 16 1.2 2 2.5 4.1 9.2 16 16 0.2 0.2 0.5 0.8 1.2 1.5 1.9 2.3 4 8.6 16 16
8 0.4 0.7 1 1.2 1.6 2 3.2 6.1 7.7 16 1 1.6 2 3.2 5.9 8.8 16 0.1 0.4 0.7 1 1.2 1.5 1.8 3.1 5.7 8.7 16
D

10 0.3 0.6 0.9 1.1 1.5 1.9 3 5.3 7.1 16 0.9 1.5 1.9 3 5.2 8.8 16 0.3 0.6 0.9 1.1 1.5 1.7 2.9 5 8.7 16
13 0.6 0.9 1.1 1.5 1.9 3 5.6 7.6 16 0.9 1.5 1.9 3 5.5 9.1 16 0.6 0.9 1.1 1.5 1.7 2.9 5.3 9.1 16
16 0.5 0.8 1.1 1.4 1.8 2.8 4.8 5.9 12 0.8 1.4 1.8 2.8 4.8 6.9 11 0.5 0.8 1.1 1.4 1.6 2.8 4.6 6.8 12
15

20 1 1.2 1.6 2.4 4 4.8 10 1.3 1.6 2.4 4 5.4 10 1 1.2 1.4 2.3 3.8 5.4 10
25 0.5 0.7 1 1.2 1.5 2.3 4.2 5.1 9.8 0.7 1.2 1.5 2.3 4.1 5.8 9.6 0.5 0.7 1 1.2 1.4 2.2 3.9 5.8 9.9
32 1 1.2 1.8 3.3 4 7.1 1 1.2 1.8 3.2 4.5 7 1 1.1 1.8 3.1 4.5 7.2
40 0.9 1.1 1.7 3.1 3.5 5.5 0.9 1.1 1.7 3 3.9 5.4 0.9 1 1.7 3 3.8 5.5
50 1.5 3 3.5 5.8 1.5 2.9 3.9 5.7 1.4 2.8 3.9 5.9
10

63 1.3 2.7 3.3 5.4 1.3 2.7 3.6 5.3 1.2 2.5 3.6 5.5

G3.30 3NA - 5SY 82 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

6 0.1 0.2 0.6 1 1.5 2 2.7 3.9 7.1 16 16 16 1.5 2.8 3.9 7.1 16 16 16 0.2 0.3 0.6 1 1.5 2 2.7 3.4 6.9 16 16 16
30 40

10 0.1 0.2 0.5 0.9 1.2 1.4 1.9 2.4 3.9 8.3 11 16 1.2 1.9 2.4 3.9 8.1 14 16 0.2 0.3 0.5 0.9 1.2 1.4 1.8 2.2 3.7 7.6 14 16
13 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.4 6 7.7 16 1.1 1.8 2.2 3.4 5.9 8.8 16 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2 3.3 5.7 8.8 16
16 0.2 0.4 0.7 1 1.2 1.6 2 3.1 5.4 6.8 T 1 1.6 2 3.1 5.3 8 14 0.2 0.4 0.7 1 1.2 1.6 1.9 3 5.1 7.9 15
20 0.4 0.7 1 1.2 1.5 1.9 2.9 5.2 6.4 11 1 1.5 1.9 2.9 5.1 7.1 10 0.4 0.7 1 1.2 1.5 1.7 2.8 4.9 7.1 11
25
15
B

25 0.6 0.9 1.1 1.3 1.7 2.5 4.7 5.8 9.9 0.9 1.4 1.7 2.5 4.6 6.5 9.6 0.6 0.9 1.1 1.3 1.6 2.5 4.4 6.5 9.9
32 1.1 1.3 1.6 2.5 4.4 5.3 8.5 1.3 1.6 2.5 4.4 5.8 8.3 1.1 1.3 1.5 2.4 4.2 5.8 8.5
40 1.2 1.5 2.3 4.7 6 8.6 1.3 1.5 2.3 4.6 6.5 8.5 1.2 1.4 2.2 4.4 6.4 8.6
downstream miniature circit breaker 5SY7

50 1.4 2.1 3.7 4.5 7.8 1.4 2.1 3.6 5 7.6 1.3 2 3.5 5 7.9
20

63 2.1 3.4 4.2 7 2.1 3.3 4.7 6.9 2.1 3.2 4.7 7.1
0.3 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
0.5 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
line protection

1 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
50

1.6 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
2 0.1 0.3 0.8 1.4 2.1 2.8 4.1 5.8 16 16 16 16 2.1 4.2 5.8 16 16 16 16 0.2 0.3 0.8 1.4 2.1 2.8 4 5.1 16 16 16 16
3 0.1 0.3 0.7 1.2 1.7 2.2 2.9 4.2 8.2 16 16 16 1.7 3 4.2 8.2 16 16 16 0.2 0.3 0.7 1.2 1.7 2.2 2.9 3.7 7.9 16 16 16
4 0.1 0.2 0.6 1 1.5 1.9 2.6 3.6 6 16 16 16 1.5 2.7 3.6 6 16 16 16 0.2 0.3 0.6 1 1.5 1.9 2.6 3.2 5.8 16 16 16
40

6 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 9.3 13 16 1.2 2 2.6 4.1 9 T 16 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 8.4 15 16
8 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.5 7 9.8 16 1.1 1.8 2.2 3.5 6.8 12 16 0.2 0.3 0.5 0.8 1.1 1.3 1.7 2 3.4 6.3 12 16
15

30
C

10 0.2 0.4 0.7 1.1 1.3 1.7 2.2 3.4 6.6 8.7 16 1.1 1.7 2.2 3.4 6.4 10 16 0.2 0.4 0.7 1.1 1.3 1.7 2 3.3 6.1 10 16
13 0.4 0.6 1 1.1 1.4 1.8 2.8 4.8 5.9 12 1 1.5 1.8 2.8 4.8 6.8 11 0.2 0.4 0.6 1 1.1 1.4 1.7 2.7 4.6 6.7 12
16 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 6.6 T 1 1.5 1.9 3 5.2 7.7 14 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 7.7 15
20 0.6 0.9 1 1.3 1.6 2.5 4.3 5.1 10 0.9 1.3 1.6 2.5 4.2 5.8 9.9 0.6 0.9 1 1.3 1.5 2.4 4 5.7 10
25

25 0.6 0.9 1.1 1.3 1.6 2.5 4.5 5.6 10 0.9 1.3 1.6 2.5 4.4 6.3 9.9 0.6 0.9 1.1 1.3 1.5 2.4 4.3 6.3 10
32 1.1 1.4 1.7 2.5 4.2 5.2 9.9 1.4 1.7 2.5 4.1 6 9.6 1.1 1.4 1.6 2.4 3.9 5.9 9.9
40 1.2 1.5 2.2 3.9 4.8 8.6 1.2 1.5 2.2 3.8 5.4 8.4 1.2 1.3 2.1 3.7 5.3 8.6
50 1.4 2 3.7 4.5 7.7 1.4 2 3.6 5.1 7.6 1.3 2 3.4 5 7.8
20

63 1.9 3.4 4.1 7.1 1.9 3.3 4.7 7 1.8 3.2 4.6 7.1

G3.30 3NA - 5SY 83 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

0.3 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 T 16 16 16 2.2 4.5 6.5 T 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
0.5 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 T 16 16 16 2.2 4.5 6.5 T 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
1 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 T 16 16 16 2.2 4.5 6.5 T 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
50
downstream miniature circit breaker 5SY7

1.6 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 T 16 16 16 2.2 4.5 6.5 T 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
2 0.2 0.3 0.8 1.4 2.2 2.9 4.3 6.5 T 16 16 16 2.2 4.5 6.5 T 16 16 16 0.2 0.3 0.8 1.4 2.2 2.9 4.3 5.5 15 16 16 16
3 0.1 0.2 0.6 1.1 1.6 2.1 2.9 4.4 8.9 16 16 16 1.6 2.9 4.4 8.9 16 16 16 0.2 0.3 0.6 1.1 1.6 2.1 2.8 3.8 8.6 16 16 16
4 0.1 0.2 0.6 1 1.4 1.7 2.3 3.1 5.1 T 16 16 1.4 2.4 3.1 5.1 14 16 16 0.2 0.3 0.6 1 1.4 1.7 2.3 2.8 4.9 12 16 16
40
line protection

6 0.1 0.2 0.5 0.8 1.2 1.5 1.9 2.5 4.1 9.5 13 16 1.2 2 2.5 4.1 9.2 16 16 0.2 0.2 0.5 0.8 1.2 1.5 1.9 2.3 4 8.6 16 16
8 0.4 0.7 1 1.2 1.6 2 3.2 6.1 7.7 16 1 1.6 2 3.2 5.9 8.8 16 0.1 0.4 0.7 1 1.2 1.5 1.8 3.1 5.7 8.7 16
30
15
D

10 0.3 0.6 0.9 1.1 1.5 1.9 3 5.3 7.1 16 0.9 1.5 1.9 3 5.2 8.8 16 0.3 0.6 0.9 1.1 1.5 1.7 2.9 5 8.7 16
13 0.6 0.9 1.1 1.5 1.9 3 5.6 7.6 16 0.9 1.5 1.9 3 5.5 9.1 16 0.6 0.9 1.1 1.5 1.7 2.9 5.3 9.1 16
16 0.5 0.8 1.1 1.4 1.8 2.8 4.8 5.9 12 0.8 1.4 1.8 2.8 4.8 6.9 11 0.5 0.8 1.1 1.4 1.6 2.8 4.6 6.8 12
20 1 1.2 1.6 2.4 4 4.8 10 1.3 1.6 2.4 4 5.4 10 1 1.2 1.4 2.3 3.8 5.4 10
25

25 0.5 0.7 1 1.2 1.5 2.3 4.2 5.1 9.8 0.7 1.2 1.5 2.3 4.1 5.8 9.6 0.5 0.7 1 1.2 1.4 2.2 3.9 5.8 9.9
32 1 1.2 1.8 3.3 4 7.1 1 1.2 1.8 3.2 4.5 7 1 1.1 1.8 3.1 4.5 7.2
40 0.9 1.1 1.7 3.1 3.5 5.5 0.9 1.1 1.7 3 3.9 5.4 0.9 1 1.7 3 3.8 5.5
20

50 1.5 3 3.5 5.8 1.5 2.9 3.9 5.7 1.4 2.8 3.9 5.9
15

63 1.3 2.7 3.3 5.4 1.3 2.7 3.6 5.3 1.2 2.5 3.6 5.5

G3.30 3NA - 5SY 84 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

40 0.8 1 1.5 2.8 3.6 6.9 0.8 1 1.5 2.8 4.2 6.8 0.8 0.9 1.5 2.6 4.2 7
50 0.9 1.5 2.8 3.3 5.3 0.9 1.5 2.8 3.7 5.2 0.8 1.4 2.7 3.6 5.3
63 1.1 2 2.5 4.5 1.1 2 2.8 4.4 1.1 1.9 2.8 4.5
B

80 1.6 1.9 3.5 1.6 2.2 3.4 1.5 2.2 3.5


downstream miniature circit breaker

100 1.8 3.2 2 3.1 2 3.2


125 4.1 4 4.1
40 0.8 1 1.5 2.8 3.6 6.9 0.8 1 1.5 2.8 4.2 6.8 0.8 0.9 1.5 2.6 4.2 7
line protection

50 0.9 1.5 2.8 3.3 5.3 0.9 1.5 2.8 3.7 5.2 0.8 1.4 2.7 3.6 5.3
5SP4

63 1.1 2 2.5 4.5 1.1 2 2.8 4.4 1.1 1.9 2.8 4.5
10

10
C

80 1.6 1.9 3.5 1.6 2.2 3.4 1.5 2.2 3.5


100 1.8 3.2 2 3.1 2 3.2
125 4.1 4 4.1
40 0.9 1.4 2.5 3.1 5.7 0.9 1.4 2.5 3.5 5.5 0.9 1.4 2.4 3.5 5.7
50 0.9 1.4 2.6 3.3 5.6 0.9 1.4 2.6 3.6 5.5 1.3 2.5 3.6 5.6
63 1 1.6 1.9 4 1 1.5 2.2 3.9 1 1.5 2.2 4
D

80 3 2.9 3
100 2.6 2.6 2.6

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB

G3.30 3NA - 5SY 85 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1 0.2 0.4 3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1.6 0.2 0.4 3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 0.2 0.4 3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35

3 0.2 0.4 1 3.8 5.3 16 16 16 16 16 16 16 16 16 4.4 16 16 16 16 16 16 16 16 16 16 16 16 16


4 0.1 0.3 0.8 2.4 3 6.7 9.6 16 16 16 16 16 16 16 2.6 6.7 12 16 16 16 16 16 16 16 16 16 16 16
6 0.1 0.3 0.7 1.7 2 3.5 4.5 9.5 16 16 16 16 16 16 1.8 3.5 4.7 9.5 16 16 16 16 16 16 16 16 16 16
8 0.1 0.3 0.6 1.5 1.8 2.8 3.4 7.3 16 16 16 16 16 16 1.6 2.8 3.6 7.3 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY4

10 0.1 0.2 0.6 1.2 1.4 2.3 2.8 4.8 11 16 16 16 16 16 1.3 2.3 2.9 4.8 11 16 16 16 16 16 16 16 16 16
10
A

13 0.1 0.2 0.5 1.1 1.3 2 2.4 4.1 7.8 12 16 16 16 16 1.2 2 2.5 4.1 7.6 12 16 16 16 16 16 16 16 16
16 0.2 0.5 1.1 1.3 1.9 2.3 3.8 7.1 11 16 16 16 16 1.2 1.9 2.4 3.8 6.9 11 16 16 16 16 16 16 16 16
20

20 0.5 1 1.1 1.7 1.9 3.2 5.9 10 16 16 16 16 1.1 1.7 2 3.2 5.7 10 16 16 16 16 16 16 16 16
line protection

25 1 1.1 1.7 2 3.3 5.9 9.6 15 16 16 16 1.1 1.7 2 3.3 5.7 9.4 15 16 16 16 16 16 16 16
32 1 1.4 1.6 2.6 4.4 6.4 10 16 16 16 1.4 1.7 2.6 4.3 6.2 10 16 16 16 16 16 16 16
40 1.4 1.7 2.7 4.4 6.2 11 15 15 15 1.4 1.7 2.7 4.3 6.1 11 15 15 15 15 15 15 15
50 1.5 2.3 3.9 5.4 9.7 15 15 15 1.5 2.3 3.8 5.3 9.6 15 15 15 15 15 15 15
15

63 2.1 3.6 5.2 7.9 13 15 15 2.1 3.5 5.2 7.8 13 15 15 15 15 15 15


6 0.1 0.2 0.6 1.4 1.6 2.7 3.4 6.9 16 16 16 16 16 16 1.5 2.7 3.6 6.9 16 16 16 16 16 16 16 16 16 16
35

10 0.1 0.2 0.5 1.1 1.2 1.8 2.2 3.7 7.6 14 16 16 16 16 1.2 1.8 2.3 3.7 7.3 13 16 16 16 16 16 16 16 16
13 0.1 0.2 0.5 1 1.1 1.7 2 3.3 5.7 8.8 16 16 16 16 1.1 1.7 2.1 3.3 5.5 8.6 16 16 16 16 16 16 16 16
16 0.2 0.4 1 1.1 1.6 1.9 3 5.1 7.9 15 16 16 16 1 1.6 1.9 3 5 7.8 15 16 16 16 16 16 16 16
20

20 0.4 0.9 1 1.5 1.7 2.8 4.9 7.1 11 16 16 16 1 1.5 1.8 2.8 4.8 7 11 16 16 16 16 16 16 16
10
B

25 0.8 1 1.3 1.6 2.5 4.4 6.5 9.9 16 16 16 0.9 1.3 1.6 2.5 4.3 6.4 9.8 16 16 16 16 16 16 16
32 1 1.3 1.5 2.4 4.2 5.8 8.5 16 16 16 1.3 1.6 2.4 4.1 5.7 8.4 16 16 16 16 16 16 16
40 1.2 1.4 2.2 4.4 6.4 8.6 15 15 15 1.2 1.5 2.2 4.2 6.4 8.6 15 15 15 15 15 15 15
50 1.3 2 3.5 5 7.9 14 15 15 1.4 2 3.4 4.9 7.8 14 15 15 15 15 15 15
15

63 2.1 3.2 4.7 7.1 12 15 15 2.1 3.1 4.6 7 12 15 15 15 15 15 15

G3.30 3NA - 5SY 86 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
0.3 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
0.5 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
1 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
1.6 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
2 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
2.5 0.1 0.3 0.7 1.5 1.8 2.9 3.7 7.9 16 16 16 16 16 16 1.6 2.9 3.9 7.9 16 16 16 16 16 16 16 16 16 16
35

3 0.1 0.3 0.7 1.5 1.8 2.9 3.7 7.9 16 16 16 16 16 16 1.6 2.9 3.9 7.9 16 16 16 16 16 16 16 16 16 16
3.5 0.1 0.2 0.6 1.3 1.6 2.6 3.2 5.8 16 16 16 16 16 16 1.4 2.6 3.3 5.8 15 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY4

4 0.1 0.2 0.6 1.3 1.6 2.6 3.2 5.8 16 16 16 16 16 16 1.4 2.6 3.3 5.8 15 16 16 16 16 16 16 16 16 16
5 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 8.4 15 16 16 16 16 1.2 2 2.4 3.9 8.1 15 16 16 16 16 16 16 16 16
6 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 8.4 15 16 16 16 16 1.2 2 2.4 3.9 8.1 15 16 16 16 16 16 16 16 16
8 0.1 0.2 0.5 1 1.2 1.7 2 3.4 6.3 12 16 16 16 16 1.1 1.7 2.1 3.4 6.1 11 16 16 16 16 16 16 16 16
line protection

10 0.2 0.4 1 1.1 1.7 2 3.3 6.1 10 16 16 16 16 1 1.7 2.1 3.3 5.9 9.9 16 16 16 16 16 16 16 16
13 0.4 0.9 1 1.4 1.7 2.7 4.6 6.7 12 16 16 16 0.9 1.4 1.7 2.7 4.5 6.6 12 16 16 16 16 16 16 16
10
C

15 0.2 0.4 0.9 1 1.5 1.8 2.9 5 7.7 15 16 16 16 1 1.5 1.8 2.9 4.8 7.5 15 16 16 16 16 16 16 16
16 0.2 0.4 0.9 1 1.5 1.8 2.9 5 7.7 15 16 16 16 1 1.5 1.8 2.9 4.8 7.5 15 16 16 16 16 16 16 16
20

20 0.8 0.9 1.3 1.5 2.4 4 5.7 10 16 16 16 0.8 1.3 1.6 2.4 4 5.6 10 16 16 16 16 16 16 16
25 0.8 0.9 1.3 1.5 2.4 4.3 6.3 10 16 16 16 0.8 1.3 1.6 2.4 4.2 6.2 10 16 16 16 16 16 16 16
30 0.9 1.4 1.6 2.4 3.9 5.9 9.9 16 16 16 1.4 1.7 2.4 3.8 5.8 9.9 16 16 16 16 16 16 16
32 0.9 1.4 1.6 2.4 3.9 5.9 9.9 16 16 16 1.4 1.7 2.4 3.8 5.8 9.9 16 16 16 16 16 16 16
35 1.2 1.3 2.1 3.7 5.3 8.6 15 15 15 1.2 1.4 2.1 3.6 5.2 8.6 15 15 15 15 15 15 15
40 1.2 1.3 2.1 3.7 5.3 8.6 15 15 15 1.2 1.4 2.1 3.6 5.2 8.6 15 15 15 15 15 15 15
45 1.3 2 3.4 5 7.8 14 15 15 1.3 2 3.4 5 7.7 14 15 15 15 15 15 15
50 1.3 2 3.4 5 7.8 14 15 15 1.3 2 3.4 5 7.7 14 15 15 15 15 15 15
15

60 1.8 3.2 4.6 7.1 12 14 15 1.8 3.1 4.6 7.1 12 14 15 15 15 15 15


63 1.8 3.2 4.6 7.1 12 14 15 1.8 3.1 4.6 7.1 12 14 15 15 15 15 15
80

G3.30 3NA - 5SY 87 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
0.3 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
0.5 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
1 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY4

1.6 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
35

2 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16


3 0.1 0.3 0.6 1.5 1.8 2.8 3.8 8.6 16 16 16 16 16 16 1.6 2.8 4 8.6 16 16 16 16 16 16 16 16 16 16
4 0.1 0.2 0.6 1.3 1.5 2.3 2.8 4.9 12 16 16 16 16 16 1.3 2.3 2.9 4.9 11 16 16 16 16 16 16 16 16 16
line protection

6 0.1 0.2 0.5 1.1 1.2 1.9 2.3 4 8.6 16 16 16 16 16 1.1 1.9 2.4 4 8.3 16 16 16 16 16 16 16 16 16
8 0.4 0.9 1 1.5 1.8 3.1 5.7 8.7 16 16 16 16 1 1.5 1.9 3.1 5.6 8.6 16 16 16 16 16 16 16 16
10
D

10 0.3 0.8 1 1.5 1.7 2.9 5 8.7 16 16 16 16 0.9 1.5 1.8 2.9 4.9 8.5 16 16 16 16 16 16 16 16
13 0.8 1 1.5 1.7 2.9 5.3 9.1 16 16 16 16 0.9 1.5 1.8 2.9 5.1 8.8 16 16 16 16 16 16 16 16
16 0.7 0.9 1.4 1.6 2.8 4.6 6.8 12 16 16 16 0.8 1.4 1.7 2.8 4.5 6.7 12 16 16 16 16 16 16 16
20

20 0.9 1.2 1.4 2.3 3.8 5.4 10 16 16 16 1.2 1.5 2.3 3.8 5.3 10 16 16 16 16 16 16 16
25 0.7 0.8 1.2 1.4 2.2 3.9 5.8 9.9 14 16 16 0.7 1.2 1.4 2.2 3.8 5.7 9.8 14 16 16 16 16 16 16
32 1 1.1 1.8 3.1 4.5 7.2 12 15 16 1 1.2 1.8 3 4.4 7.1 12 15 16 16 16 16 16
40 0.9 1 1.7 3 3.8 5.5 10 12 15 0.9 1.1 1.7 2.9 3.8 5.5 10 12 15 15 15 15 15
50 1.4 2.8 3.9 5.9 10 12 15 1.4 2.7 3.8 5.8 10 12 15 15 15 15 15
15

63 1.2 2.5 3.6 5.5 10 11 14 1.2 2.5 3.6 5.4 10 11 14 15 15 15 15

G3.30 3NA - 5SY 88 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
2 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
4 0.1 0.2 0.6 1.3 1.6 2.6 3.2 5.8 16 16 16 16 16 16 1.4 2.6 3.3 5.8 15 16 16 16 16 16 16 16 16 16
30

6 0.1 0.2 0.6 1.4 1.6 2.7 3.4 6.9 16 16 16 16 16 16 1.5 2.7 3.6 6.9 16 16 16 16 16 16 16 16 16 16
10 0.1 0.2 0.5 1.1 1.2 1.8 2.2 3.7 7.6 14 16 16 16 16 1.2 1.8 2.3 3.7 7.3 13 16 16 16 16 16 16 16 16
13 0.1 0.2 0.5 1 1.1 1.7 2 3.3 5.7 8.8 16 16 16 16 1.1 1.7 2.1 3.3 5.5 8.6 16 16 16 16 16 16 16 16
16 0.2 0.4 1 1.1 1.6 1.9 3 5.1 7.9 15 16 16 16 1 1.6 1.9 3 5 7.8 15 16 16 16 16 16 16 16
15
B

20 0.4 0.9 1 1.5 1.7 2.8 4.9 7.1 11 16 16 16 1 1.5 1.8 2.8 4.8 7 11 16 16 16 16 16 16 16
25 0.8 1 1.3 1.6 2.5 4.4 6.5 9.9 16 16 16 0.9 1.3 1.6 2.5 4.3 6.4 9.8 16 16 16 16 16 16 16
32 1 1.3 1.5 2.4 4.2 5.8 8.5 16 16 16 1.3 1.6 2.4 4.1 5.7 8.4 16 16 16 16 16 16 16
40 1.2 1.4 2.2 4.4 6.4 8.6 15 15 15 1.2 1.5 2.2 4.2 6.4 8.6 15 15 15 15 15 15 15
50 1.3 2 3.5 5 7.9 14 15 15 1.4 2 3.4 4.9 7.8 14 15 15 15 15 15 15
10
downstream miniature circit breaker 5SY6

63 2.1 3.2 4.7 7.1 12 15 15 2.1 3.1 4.6 7 12 15 15 15 15 15 15


0,3 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
0,5 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
1 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
(except 5SY60)

line protection

1.6 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16


2 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
30

3 0.1 0.3 0.7 1.5 1.8 2.9 3.7 7.9 16 16 16 16 16 16 1.6 2.9 3.9 7.9 16 16 16 16 16 16 16 16 16 16
4 0.1 0.2 0.6 1.3 1.6 2.6 3.2 5.8 16 16 16 16 16 16 1.4 2.6 3.3 5.8 15 16 16 16 16 16 16 16 16 16
5 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 8.4 15 16 16 16 16 1.2 2 2.4 3.9 8.1 15 16 16 16 16 16 16 16 16
6 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 8.4 15 16 16 16 16 1.2 2 2.4 3.9 8.1 15 16 16 16 16 16 16 16 16
8 0.1 0.2 0.5 1 1.2 1.7 2 3.4 6.3 12 16 16 16 16 1.1 1.7 2.1 3.4 6.1 11 16 16 16 16 16 16 16 16
10 0.2 0.4 1 1.1 1.7 2 3.3 6.1 10 16 16 16 16 1 1.7 2.1 3.3 5.9 9.9 16 16 16 16 16 16 16 16
C

13 0.4 0.9 1 1.4 1.7 2.7 4.6 6.7 12 16 16 16 0.9 1.4 1.7 2.7 4.5 6.6 12 16 16 16 16 16 16 16
15 0.2 0.4 0.9 1 1.5 1.8 2.9 5 7.7 15 16 16 16 1 1.5 1.8 2.9 4.8 7.5 15 16 16 16 16 16 16 16
16 0.2 0.4 0.9 1 1.5 1.8 2.9 5 7.7 15 16 16 16 1 1.5 1.8 2.9 4.8 7.5 15 16 16 16 16 16 16 16
15

20 0.8 0.9 1.3 1.5 2.4 4 5.7 10 16 16 16 0.8 1.3 1.6 2.4 4 5.6 10 16 16 16 16 16 16 16
25 0.8 0.9 1.3 1.5 2.4 4.3 6.3 10 16 16 16 0.8 1.3 1.6 2.4 4.2 6.2 10 16 16 16 16 16 16 16
30 0.9 1.4 1.6 2.4 3.9 5.9 9.9 16 16 16 1.4 1.7 2.4 3.8 5.8 9.9 16 16 16 16 16 16 16
32 0.9 1.4 1.6 2.4 3.9 5.9 9.9 16 16 16 1.4 1.7 2.4 3.8 5.8 9.9 16 16 16 16 16 16 16
40 1.2 1.3 2.1 3.7 5.3 8.6 15 15 15 1.2 1.4 2.1 3.6 5.2 8.6 15 15 15 15 15 15 15
50 1.3 2 3.4 5 7.8 14 15 15 1.3 2 3.4 5 7.7 14 15 15 15 15 15 15
10

63 1.8 3.2 4.6 7.1 12 14 15 1.8 3.1 4.6 7.1 12 14 15 15 15 15 15

G3.30 3NA - 5SY 89 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
0.3 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
0.5 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
1 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY6

1.6 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
30

2 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16


3 0.1 0.3 0.6 1.5 1.8 2.8 3.8 8.6 16 16 16 16 16 16 1.6 2.8 4 8.6 16 16 16 16 16 16 16 16 16 16
4 0.1 0.2 0.6 1.3 1.5 2.3 2.8 4.9 12 16 16 16 16 16 1.3 2.3 2.9 4.9 11 16 16 16 16 16 16 16 16 16
(except 5SY60)

line protection

6 0.1 0.2 0.5 1.1 1.2 1.9 2.3 4 8.6 16 16 16 16 16 1.1 1.9 2.4 4 8.3 16 16 16 16 16 16 16 16 16
8 0.4 0.9 1 1.5 1.8 3.1 5.7 8.7 16 16 16 16 1 1.5 1.9 3.1 5.6 8.6 16 16 16 16 16 16 16 16
D

10 0.3 0.8 1 1.5 1.7 2.9 5 8.7 16 16 16 16 0.9 1.5 1.8 2.9 4.9 8.5 16 16 16 16 16 16 16 16
13 0.8 1 1.5 1.7 2.9 5.3 9.1 16 16 16 16 0.9 1.5 1.8 2.9 5.1 8.8 16 16 16 16 16 16 16 16
16 0.7 0.9 1.4 1.6 2.8 4.6 6.8 12 16 16 16 0.8 1.4 1.7 2.8 4.5 6.7 12 16 16 16 16 16 16 16
15

20 0.9 1.2 1.4 2.3 3.8 5.4 10 16 16 16 1.2 1.5 2.3 3.8 5.3 10 16 16 16 16 16 16 16
25 0.7 0.8 1.2 1.4 2.2 3.9 5.8 9.9 14 16 16 0.7 1.2 1.4 2.2 3.8 5.7 9.8 14 16 16 16 16 16 16
32 1 1.1 1.8 3.1 4.5 7.2 12 15 16 1 1.2 1.8 3 4.4 7.1 12 15 16 16 16 16 16
40 0.9 1 1.7 3 3.8 5.5 10 12 15 0.9 1.1 1.7 2.9 3.8 5.5 10 12 15 15 15 15 15
50 1.4 2.8 3.9 5.9 10 12 15 1.4 2.7 3.8 5.8 10 12 15 15 15 15 15
10

63 1.2 2.5 3.6 5.5 10 11 14 1.2 2.5 3.6 5.4 10 11 14 15 15 15 15

G3.30 3NA - 5SY 90 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
6 0.1 0.2 0.6 1.4 1.6 2.7 3.4 6.9 16 16 16 16 16 16 1.5 2.7 3.6 6.9 16 16 16 16 16 16 16 16 16 16
30 40

10 0.1 0.2 0.5 1.1 1.2 1.8 2.2 3.7 7.6 14 16 16 16 16 1.2 1.8 2.3 3.7 7.3 13 16 16 16 16 16 16 16 16
13 0.1 0.2 0.5 1 1.1 1.7 2 3.3 5.7 8.8 16 16 16 16 1.1 1.7 2.1 3.3 5.5 8.6 16 16 16 16 16 16 16 16
16 0.2 0.4 1 1.1 1.6 1.9 3 5.1 7.9 15 16 16 16 1 1.6 1.9 3 5 7.8 15 16 16 16 16 16 16 16
20 0.4 0.9 1 1.5 1.7 2.8 4.9 7.1 11 16 16 16 1 1.5 1.8 2.8 4.8 7 11 16 16 16 16 16 16 16
25
15
B

25 0.8 1 1.3 1.6 2.5 4.4 6.5 9.9 16 16 16 0.9 1.3 1.6 2.5 4.3 6.4 9.8 16 16 16 16 16 16 16
32 1 1.3 1.5 2.4 4.2 5.8 8.5 16 16 16 1.3 1.6 2.4 4.1 5.7 8.4 16 16 16 16 16 16 16
40 1.2 1.4 2.2 4.4 6.4 8.6 16 16 16 1.2 1.5 2.2 4.2 6.4 8.6 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY7

50 1.3 2 3.5 5 7.9 14 15 15 1.4 2 3.4 4.9 7.8 14 15 15 15 15 15 15


20

63 2.1 3.2 4.7 7.1 12 15 15 2.1 3.1 4.6 7 12 15 15 15 15 15 15


0.3 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
0.5 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
line protection

1 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16


50

1.6 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16


2 0.2 0.3 0.8 1.9 2.3 4 5.1 16 16 16 16 16 16 16 2.1 4 5.3 16 16 16 16 16 16 16 16 16 16 16
3 0.1 0.3 0.7 1.5 1.8 2.9 3.7 7.9 16 16 16 16 16 16 1.6 2.9 3.9 7.9 16 16 16 16 16 16 16 16 16 16
4 0.1 0.2 0.6 1.3 1.6 2.6 3.2 5.8 16 16 16 16 16 16 1.4 2.6 3.3 5.8 15 16 16 16 16 16 16 16 16 16
40

6 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 8.4 15 16 16 16 16 1.2 2 2.4 3.9 8.1 15 16 16 16 16 16 16 16 16
8 0.1 0.2 0.5 1 1.2 1.7 2 3.4 6.3 12 16 16 16 16 1.1 1.7 2.1 3.4 6.1 11 16 16 16 16 16 16 16 16
15

30
C

10 0.2 0.4 1 1.1 1.7 2 3.3 6.1 10 16 16 16 16 1 1.7 2.1 3.3 5.9 9.9 16 16 16 16 16 16 16 16
13 0.4 0.9 1 1.4 1.7 2.7 4.6 6.7 12 16 16 16 0.9 1.4 1.7 2.7 4.5 6.6 12 16 16 16 16 16 16 16
16 0.2 0.4 0.9 1 1.5 1.8 2.9 5 7.7 15 16 16 16 1 1.5 1.8 2.9 4.8 7.5 15 16 16 16 16 16 16 16
20 0.8 0.9 1.3 1.5 2.4 4 5.7 10 16 16 16 0.8 1.3 1.6 2.4 4 5.6 10 16 16 16 16 16 16 16
25

25 0.8 0.9 1.3 1.5 2.4 4.3 6.3 10 16 16 16 0.8 1.3 1.6 2.4 4.2 6.2 10 16 16 16 16 16 16 16
32 0.9 1.4 1.6 2.4 3.9 5.9 9.9 16 16 16 1.4 1.7 2.4 3.8 5.8 9.9 16 16 16 16 16 16 16
40 1.2 1.3 2.1 3.7 5.3 8.6 16 16 16 1.2 1.4 2.1 3.6 5.2 8.6 16 16 16 16 16 16 16
50 1.3 2 3.4 5 7.8 14 15 15 1.3 2 3.4 5 7.7 14 15 15 15 15 15 15
20

63 1.8 3.2 4.6 7.1 12 14 15 1.8 3.1 4.6 7.1 12 14 15 15 15 15 15

G3.30 3NA - 5SY 91 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
0.3 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
0.5 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
1 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
50
downstream miniature circit breaker 5SY7

1.6 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
2 0.2 0.3 0.8 2 2.4 4.3 5.5 15 16 16 16 16 16 16 2.1 4.3 5.8 15 16 16 16 16 16 16 16 16 16 16
3 0.1 0.3 0.6 1.5 1.8 2.8 3.8 8.6 16 16 16 16 16 16 1.6 2.8 4 8.6 16 16 16 16 16 16 16 16 16 16
4 0.1 0.2 0.6 1.3 1.5 2.3 2.8 4.9 12 16 16 16 16 16 1.3 2.3 2.9 4.9 11 16 16 16 16 16 16 16 16 16
40
line protection

6 0.1 0.2 0.5 1.1 1.2 1.9 2.3 4 8.6 16 16 16 16 16 1.1 1.9 2.4 4 8.3 16 16 16 16 16 16 16 16 16
8 0.4 0.9 1 1.5 1.8 3.1 5.7 8.7 16 16 16 16 1 1.5 1.9 3.1 5.6 8.6 16 16 16 16 16 16 16 16
30
15
D

10 0.3 0.8 1 1.5 1.7 2.9 5 8.7 16 16 16 16 0.9 1.5 1.8 2.9 4.9 8.5 16 16 16 16 16 16 16 16
13 0.8 1 1.5 1.7 2.9 5.3 9.1 16 16 16 16 0.9 1.5 1.8 2.9 5.1 8.8 16 16 16 16 16 16 16 16
16 0.7 0.9 1.4 1.6 2.8 4.6 6.8 12 16 16 16 0.8 1.4 1.7 2.8 4.5 6.7 12 16 16 16 16 16 16 16
20 0.9 1.2 1.4 2.3 3.8 5.4 10 16 16 16 1.2 1.5 2.3 3.8 5.3 10 16 16 16 16 16 16 16
25

25 0.7 0.8 1.2 1.4 2.2 3.9 5.8 9.9 14 16 16 0.7 1.2 1.4 2.2 3.8 5.7 9.8 14 16 16 16 16 16 16
32 1 1.1 1.8 3.1 4.5 7.2 12 15 16 1 1.2 1.8 3 4.4 7.1 12 15 16 16 16 16 16
40 0.9 1 1.7 3 3.8 5.5 10 12 16 0.9 1.1 1.7 2.9 3.8 5.5 10 12 16 16 16 16 16
20

50 1.4 2.8 3.9 5.9 10 12 15 1.4 2.7 3.8 5.8 10 12 15 15 15 15 15


15

63 1.2 2.5 3.6 5.5 10 11 14 1.2 2.5 3.6 5.4 10 11 14 15 15 15 15

G3.30 3NA - 5SY 92 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn[kA]

Icu [kA]
In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
40 0.8 0.9 1.5 2.6 4.2 7 T T T 0.8 0.9 1.5 2.6 4.1 6.9 T T T T T T T
50 0.8 1.4 2.7 3.6 5.3 9.8 T T 0.9 1.4 2.6 3.6 5.3 9.8 T T T T T T
63 1.1 1.9 2.8 4.5 9 T T 1.1 1.8 2.8 4.5 9 T T T T T T
B

80 1.5 2.2 3.5 6.6 7.5 T 1.5 2.1 3.5 6.6 7.5 T T T T T
downstream miniature circit breaker

100 2 3.2 5.6 6.7 8.8 2 3.2 5.6 6.7 8.8 T T T T


125 4.1 7.4 9.1 T 4.1 7.4 9.1 T T T T T
40 0.8 0.9 1.5 2.6 4.2 7 T T T 0.8 0.9 1.5 2.6 4.1 6.9 T T T T T T T
line protection

50 0.8 1.4 2.7 3.6 5.3 9.8 T T 0.9 1.4 2.6 3.6 5.3 9.8 T T T T T T
5SP4

63 1.1 1.9 2.8 4.5 9 T T 1.1 1.8 2.8 4.5 9 T T T T T T


10

10
C

80 1.5 2.2 3.5 6.6 7.5 T 1.5 2.1 3.5 6.6 7.5 T T T T T
100 2 3.2 5.6 6.7 8.8 2 3.2 5.6 6.7 8.8 T T T T
125 4.1 7.4 9.1 T 4.1 7.4 9.1 T T T T T
40 0.9 1.4 2.4 3.5 5.7 9.5 T T 0.9 1.4 2.3 3.4 5.7 9.5 T T T T T T
50 1.3 2.5 3.6 5.6 9.7 T T 1.3 2.4 3.6 5.6 9.7 T T T T T T
63 1 1.5 2.2 4 6.9 8.2 T 1 1.5 2.1 4 6.9 8.2 T T T T T
D

80 3 5.6 6.7 8.8 3 5.6 6.7 8.8 T T T T


100 2.6 5.3 6.4 8.2 2.6 5.3 6.4 8.2 T T T T

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB

G3.30 3NA - 5SY 93 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35

3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY4

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
10
A

13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
line protection

25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
10
B

25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 11 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

G3.30 3NA - 5SY 94 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35

3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY4

4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
line protection

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
10
C

15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
45 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

60 11 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
63 11 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
80

G3.30 3NA - 5SY 95 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY4

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
35

2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
line protection

6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
10
D

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25 13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 11 15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 10 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 9.6 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 9.3 11 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

G3.30 3NA - 5SY 96 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30

6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
15
B

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
10
downstream miniature circit breaker 5SY6

63 11 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0,3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0,5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
(except 5SY60)

line protection

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30

3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
C

13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
15

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
10

63 11 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

G3.30 3NA - 5SY 97 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY6

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30

2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
(except 5SY60)

line protection

6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
D

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
15

20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25 13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 11 15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 10 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
50 9.6 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
10

63 9.3 11 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

G3.30 3NA - 5SY 98 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30 40

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25
15
B

25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
downstream miniature circit breaker 5SY7

50 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20

63 11 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
line protection

1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
50

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40

6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
15

30
C

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25

25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 14 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
50 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20

63 11 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

G3.30 3NA - 5SY 99 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
0.3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
0.5 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
1 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
50
downstream miniature circit breaker 5SY7

1.6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
2 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
3 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
4 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40
line protection

6 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
30
15
D

10 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
25

25 13 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
32 11 15 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
40 10 12 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
20

50 9.6 12 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
15

63 9.3 11 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

G3.30 3NA - 5SY 100 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120
resp. acc. to IEC 60947-2
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn[kA]

Icu [kA]
In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
40 T T T T T T T T T T T T T T T T T T T
50 9 T T T T T T T T T T T T T T T T T T
63 7.6 T T T T T T T T T T T T T T T T T T
B

80 6.3 7.3 T T T T T T T T T T T T T T T T T
downstream miniature circit breaker

100 5.2 6.5 9 T T T T T T T T T T T T T T T T


125 6.8 8.8 T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
line protection

50 9 T T T T T T T T T T T T T T T T T T
5SP4

63 7.6 T T T T T T T T T T T T T T T T T T
10

10
C

80 6.3 7.3 T T T T T T T T T T T T T T T T T
100 5.2 6.5 9 T T T T T T T T T T T T T T T T
125 6.8 8.8 T T T T T T T T T T T T T T T T T
40 8.8 T T T T T T T T T T T T T T T T T T
50 9 T T T T T T T T T T T T T T T T T T
63 6.5 7.9 T T T T T T T T T T T T T T T T T
D

80 5.2 6.5 9 T T T T T T T T T T T T T T T T
100 4.7 6.3 8.6 T T T T T T T T T T T T T T T T

Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB

G3.30 3NA - 5SY 101 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn [kA]

In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

1 6.9 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
2 2.4 T T T T T T T T T T T T T T T T 2.4 T T T T T T T T T
3 2.3 5.4 T T T T T T T 5.4 T T T T T T 2.3 5.4 T T T T T T T
4 1.2 1.9 2.6 4.3 6.3 T T T T 1.9 4.5 6.3 T T T T 1.2 1.9 2.6 4.2 5.5 T T T T
6 1.5 2 2.8 4.1 8.7 T T T 1.5 2.9 4.1 8.6 T T T 1.5 2 2.8 3.6 8.1 T T T
8 1.3 1.7 2.4 3.2 5.8 T T T 1.3 2.4 3.2 5.8 T T T 1.3 1.7 2.3 2.9 5.6 T T T
10 1.2 1.5 2 2.6 4.6 T T T 1.2 2 2.6 4.6 T T T 1.2 1.5 2 2.4 4.4 T T T
13
10

1.1 1.4 1.8 2.3 3.9 8.6 T T 1.1 1.9 2.3 3.9 8.3 T T 1.1 1.4 1.8 2.1 3.8 7.7 T T
B

16 1.2 1.6 2.1 3.2 6.3 8.2 T 1.7 2.1 3.2 6.2 T T 1.2 1.6 1.9 3.2 6 T T
20 1.1 1.5 1.9 2.9 6.1 7.2 T 1.5 1.9 2.9 6 8.5 T 1.1 1.4 1.7 2.9 5.7 8.5 T
downstream miniature circuit breaker 5SL4

25 1.1 1.4 1.8 2.8 5.5 6.7 T 1.4 1.8 2.8 5.4 7.4 T 1.1 1.4 1.6 2.7 5.1 7.4 T
32 1.2 1.6 2.4 4.5 5.9 T 1.3 1.6 2.4 4.4 6.5 T 1.2 1.5 2.3 4.2 6.5 T
40 1.2 1.6 2.4 4.5 5.1 T 1.2 1.6 2.4 4.5 5.5 T 1.2 1.4 2.3 4.3 5.4 T
50 1.4 2 3.6 4.6 8.6 1.4 2 3.5 5.3 8.3 1.3 2 3.4 5.3 8.6
63 1.9 3.3 4.1 7.1 1.9 3.3 4.7 7 1.8 3.1 4.7 7.2
line protection

0.3 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1 1 3.3 T T T T T T T T T T T T T T T T 1.1 3.3 T T T T T T T T T
1.6 1.1 3.2 T T T T T T T T T T T T T T T 1.1 3.2 T T T T T T T T
2 1.5 2.5 3.9 5.8 T T T T T 2.5 6 T T T T T 1.5 2.5 3.9 5.7 9.4 T T T T
3 1.1 1.7 2.4 3.7 5.7 T T T T 1.7 3.9 5.7 T T T T 1.1 1.7 2.4 3.6 4.9 T T T T
4 1.5 2 2.9 4.1 7.8 T T T 1.5 3 4.1 7.8 T T T 1.5 2 2.9 3.7 7.4 T T T
6 1.2 1.5 2.1 2.8 5.2 T T T 1.2 2.1 2.8 5.2 T T T 1.2 1.5 2 2.5 5 T T T
8 1.1 1.4 1.8 2.8 7.1 9.9 T 1.4 1.8 2.8 7 T T 1.1 1.4 1.7 2.7 6.7 T T
10
C

10 1.1 1.4 1.8 2.8 7.1 9.9 T 1.4 1.8 2.8 7 T T 1.1 1.4 1.7 2.7 6.7 T T
13 1.1 1.4 1.8 2.8 5.9 7 T 1.4 1.8 2.8 5.7 8.3 T 1.1 1.4 1.7 2.7 5.2 8.2 T
16 1.1 1.4 1.8 2.8 5.9 7 T 1.4 1.8 2.8 5.7 8.3 T 1.1 1.4 1.7 2.7 5.2 8.2 T
20 1.2 1.6 2.4 4.6 6 T 1.3 1.6 2.4 4.5 6.6 T 1.2 1.4 2.3 4.3 6.6 T
25 1.2 1.6 2.4 4.6 6 T 1.3 1.6 2.4 4.5 6.6 T 1.2 1.4 2.3 4.3 6.6 T
32 1.1 1.4 2.1 4.1 5.3 T 1.1 1.4 2.1 4 6.1 9.9 1.1 1.3 2.1 3.8 6.1 T
40 1.1 1.4 2.1 4.2 5.3 9.7 1.1 1.4 2.1 4.1 6 9.4 1 1.3 2.1 3.9 6 9.7
50 1.2 2 3.6 4.3 7.1 1.2 2 3.6 4.9 7 1.1 1.9 3.4 4.9 7.1
63 2 3.6 4.3 7.1 2 3.6 4.9 7 1.9 3.4 4.9 7.1

G3.31 3NA - 5SL 102 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn [kA]

In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

0.3 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1
downstream miniature circuit breaker 5SL4

1.4 4.7 T T T T T T T T T T T T T T T 1.4 4.7 T T T T T T T T


1.6 1.6 2.7 4.2 7.4 T T T T T 2.7 9.5 T T T T T 1.6 2.7 4.2 7.3 T T T T T
2 1.3 2.1 2.7 4.1 7.1 T T T T 2.1 4.2 7.1 T T T T 1.3 2.1 2.7 4 6.5 T T T T
3 1 1.5 2 2.8 4.1 8.4 T T T 1.5 2.9 4.1 8.4 T T T 1 1.5 2 2.8 3.6 7.8 T T T
4 1.3 1.7 2.3 3.2 5.6 T T T 1.3 2.4 3.2 5.6 T T T 1.3 1.7 2.3 2.8 5.5 T T T
line protection

6 1 1.3 1.9 2.5 4.2 T T T 1 1.9 2.5 4.2 T T T 1 1.3 1.8 2.3 4.1 T T T
8 1.1 1.5 2.4 5.4 7.2 T 1.2 1.5 2.4 5.3 9.6 T 1.1 1.4 2.3 5 9.5 T
10
D

10 1.1 1.5 2.4 5.4 7.2 T 1.2 1.5 2.4 5.3 9.6 T 1.1 1.4 2.3 5 9.5 T
13 1.1 1.5 2.4 4.6 6.1 T 1.2 1.5 2.4 4.5 6.8 T 1.1 1.4 2.3 4.3 6.7 T
16 1.1 1.5 2.4 4.6 6.1 T 1.2 1.5 2.4 4.5 6.8 T 1.1 1.4 2.3 4.3 6.7 T
20 1 1.4 2.2 4.3 5.5 T 1.1 1.4 2.2 4.2 6.2 T 1 1.3 2.1 4 6.2 T
25 1 1.4 2.2 4.3 5.5 T 1.1 1.4 2.2 4.2 6.2 T 1 1.3 2.1 4 6.2 T
32 1.1 1.5 2.3 4.4 5.5 T 1.1 1.5 2.3 4.3 6.2 T 1.1 1.3 2.2 4.1 6.2 T
40 1.2 1.9 3.7 4.7 8.8 1.2 1.9 3.6 5.5 8.5 1.1 1.9 3.5 5.5 8.8
50 1.6 2.9 3.7 6.6 1.6 2.8 4.3 6.5 1.6 2.7 4.3 6.6
63 1.6 2.9 3.7 6.6 1.6 2.8 4.3 6.5 1.6 2.7 4.3 6.6

G3.31 3NA - 5SL 103 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 000 00 0
characteristic

Icn [kA]

In [A] 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 16 20 25 32 35 40 50 63 80 100 125 160

2 1 1.2 1.6 2 3.2 T T T 1 1.6 2 3.2 T T T 1 1.2 1.6 1.9 3.1 T T T


4 1 1.2 1.6 2 3.2 T T T 1 1.6 2 3.2 T T T 1 1.2 1.6 1.9 3.1 T T T
6 1 1.2 1.6 2 3.2 T T T 1 1.6 2 3.2 T T T 1 1.2 1.6 1.9 3.1 T T T
10 1.1 1.4 1.8 2.9 5.4 T T 1.4 1.8 2.9 5.2 T T 1.1 1.4 1.7 2.8 5 T T
13 1.1 1.4 1.8 2.8 5.7 T T 1.4 1.8 2.8 5.5 T T 1.1 1.4 1.6 2.8 5.2 T T
16 1.2 1.5 2.3 4.2 5 T 1.2 1.5 2.3 4.1 5.5 T 1.2 1.4 2.2 4 5.5 T
B

20 1.2 1.5 2.2 4 4.9 T 1.2 1.5 2.2 4 5.5 T 1.1 1.3 2.2 3.8 5.5 T
25 1.1 1.4 2.2 3.9 4.8 T 1.2 1.4 2.2 3.8 5.3 T 1.1 1.3 2.1 3.7 5.3 T
32
downstream miniature circuit breaker 5SL6

1.1 1.4 1.9 3.2 3.9 T 1.1 1.4 1.9 3.2 4.4 T 1.1 1.3 1.9 3.1 4.3 T
40 1.2 1.5 2.2 3.9 4.7 T 1.2 1.5 2.2 3.8 5.5 T 1.2 1.4 2.2 3.7 5.4 T
50 1.3 1.9 3.3 4 T 1.3 1.9 3.2 4.6 T 1.2 1.8 3.1 4.5 T
63 1.8 3.1 3.8 T 1.8 3 4.3 T 1.7 2.9 4.3 T
0.3 1.5 T T T T T T T T T T T T T T T T T 1 1.8 T T T T T T T T T T
line protection

0.5 1.5 T T T T T T T T T T T T T T T T T 1 1.8 T T T T T T T T T T


1 1.4 4.9 T T T T T T T T T T T T T T T 1.4 4.9 T T T T T T T T
1.6 1.3 2.3 3.4 T T T T T T 2.3 T T T T T T 1.3 2.3 3.4 T T T T T T
2 1 1.5 2 2.7 3.5 5.8 T T T 1.5 2.8 3.5 5.8 T T T 1 1.5 2 2.7 3.2 5.6 T T T
3 1.3 1.6 2.2 2.9 4.9 T T T 1.3 2.2 2.9 4.9 T T T 1.3 1.6 2.2 2.6 4.8 T T T
4 1.2 1.6 2.1 2.8 4.6 T T T 1.2 2.2 2.8 4.6 T T T 1.2 1.6 2.1 2.5 4.4 T T T
6 1.2 1.6 2.1 2.8 4.6 T T T 1.2 2.2 2.8 4.6 T T T 1.2 1.6 2.1 2.5 4.4 T T T
8 1.1 1.5 1.9 3 5.8 T T 1.5 1.9 3 5.7 T T 1.1 1.5 1.8 2.9 5.4 T T
10 1.1 1.4 1.8 2.9 5.4 T T 1.4 1.8 2.9 5.2 T T 1.1 1.4 1.7 2.8 5 T T
C

13 1.1 1.4 1.8 2.8 5.7 T T 1.4 1.8 2.8 5.5 T T 1.1 1.4 1.6 2.8 5.2 T T
16 1.2 1.5 2.3 4.2 5 T 1.2 1.5 2.3 4.1 5.5 T 1.2 1.4 2.2 4 5.5 T
20 1.2 1.5 2.2 4 4.9 T 1.2 1.5 2.2 4 5.5 T 1.1 1.3 2.2 3.8 5.5 T
25 1.1 1.4 2.2 3.9 4.8 T 1.2 1.4 2.2 3.8 5.3 T 1.1 1.3 2.1 3.7 5.3 T
32 1.1 1.4 1.9 3.2 3.9 T 1.1 1.4 1.9 3.2 4.4 T 1.1 1.3 1.9 3.1 4.3 T
40 1.2 1.5 2.2 3.9 4.7 T 1.2 1.5 2.2 3.8 5.5 T 1.2 1.4 2.2 3.7 5.4 T
50 1.3 1.9 3.3 4 T 1.3 1.9 3.2 4.6 T 1.2 1.8 3.1 4.5 T
63 1.8 3.1 3.8 T 1.8 3 4.3 T 1.7 2.9 4.3 T

G3.31 3NA - 5SL 104 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn [kA]

In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1 9 T T T T T T T T T T T T T T T T T T T T T T T T T T T
2 2.4 T T T T T T T T T T T T T T T T T T T T T T T T T
3 4.4 7.1 T T T T T T T T T 5.1 T T T T T T T T T T T T T
4 1.7 2.1 4.2 5.5 T T T T T T T 1.8 4.2 5.8 T T T T T T T T T T T
6 1.4 1.7 2.8 3.6 8.1 T T T T T T 1.5 2.8 3.8 8.1 T T T T T T T T T T
8 1.2 1.4 2.3 2.9 5.6 T T T T T T 1.3 2.3 3 5.6 T T T T T T T T T T
10 1.1 1.3 2 2.4 4.4 T T T T T T 1.1 2 2.5 4.4 T T T T T T T T T T
13
10

1 1.2 1.8 2.1 3.8 7.7 T T T T T 1.1 1.8 2.2 3.8 7.4 T T T T T T T T T
B

16 1 1.6 1.9 3.2 6 T T T T T 1.6 2 3.2 5.8 T T T T T T T T T


20 1 1.4 1.7 2.9 5.7 8.5 T T T T 1.4 1.8 2.9 5.5 8.2 T T T T T T T T
downstream miniature circuit breaker 5SL4

25 1.4 1.6 2.7 5.1 7.4 T T T T 1.4 1.7 2.7 4.9 7.3 T T T T T T T T
32 1.2 1.5 2.3 4.2 6.5 T T T T 1.2 1.5 2.3 4.1 6.4 T T T T T T T T
40 1.2 1.4 2.3 4.3 5.4 T T T T 1.2 1.5 2.3 4.2 5.4 T T T T T T T T
50 1.3 2 3.4 5.3 8.6 T T T 1.3 2 3.3 5.2 8.6 T T T T T T T
63 1.8 3.1 4.7 7.2 T T T 1.8 3.1 4.6 7.1 T T T T T T T
line protection

0.3 T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1 1 3.3 T T T T T T T T T T T T T T T T T T T T T T T T T
1.6 1.1 T T T T T T T T T T T T T T T T T T T T T T T T T
2 2.2 2.8 5.7 9.4 T T T T T T T 2.4 5.7 T T T T T T T T T T T T
3 1.5 1.9 3.6 4.9 T T T T T T T 1.6 3.6 5.2 T T T T T T T T T T T
4 1.3 1.6 2.9 3.7 7.4 T T T T T T 1.4 2.9 3.8 7.4 T T T T T T T T T T
6 1.1 1.3 2 2.5 5 T T T T T T 1.1 2 2.6 5 T T T T T T T T T T
8 1.4 1.7 2.7 6.7 T T T T T 1.4 1.7 2.7 6.5 T T T T T T T T T
10
C

10 1.4 1.7 2.7 6.7 T T T T T 1.4 1.7 2.7 6.5 T T T T T T T T T


13 1.4 1.7 2.7 5.2 8.2 T T T T 1.4 1.7 2.7 5 7.9 T T T T T T T T
16 1.4 1.7 2.7 5.2 8.2 T T T T 1.4 1.7 2.7 5 7.9 T T T T T T T T
20 1.2 1.4 2.3 4.3 6.6 T T T T 1.2 1.5 2.3 4.2 6.5 T T T T T T T T
25 1.2 1.4 2.3 4.3 6.6 T T T T 1.2 1.5 2.3 4.2 6.5 T T T T T T T T
32 1.1 1.3 2.1 3.8 6.1 T T T T 1.1 1.3 2.1 3.7 6 T T T T T T T T
40 1 1.3 2.1 3.9 6 9.7 T T T 1 1.3 2.1 3.8 5.9 9.6 T T T T T T T
50 1.1 1.9 3.4 4.9 7.1 T T T 1.2 1.9 3.4 4.8 7.1 T T T T T T T
63 1.9 3.4 4.9 7.1 T T T 1.9 3.4 4.8 7.1 T T T T T T T

G3.31 3NA - 5SL 105 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn [kA]

In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
0.3 T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1
downstream miniature circuit breaker 5SL4

1.4 T T T T T T T T T T T T T T T T T T T T T T T T T
1.6 2.4 3 7.3 T T T T T T T T 2.6 7.3 T T T T T T T T T T T T
2 1.9 2.2 4 6.5 T T T T T T T 2 4 6.7 T T T T T T T T T T T
3 1.4 1.7 2.8 3.6 7.8 T T T T T T 1.5 2.8 3.8 7.8 T T T T T T T T T T
4 1.1 1.4 2.3 2.8 5.5 T T T T T T 1.2 2.3 3 5.5 T T T T T T T T T T
line protection

6 1 1.1 1.8 2.3 4.1 T T T T T T 1 1.8 2.4 4.1 T T T T T T T T T T


8 1.1 1.4 2.3 5 9.5 T T T T 1.1 1.4 2.3 4.9 9.1 T T T T T T T T
10
D

10 1.1 1.4 2.3 5 9.5 T T T T 1.1 1.4 2.3 4.9 9.1 T T T T T T T T


13 1.1 1.4 2.3 4.3 6.7 T T T T 1.1 1.4 2.3 4.2 6.6 T T T T T T T T
16 1.1 1.4 2.3 4.3 6.7 T T T T 1.1 1.4 2.3 4.2 6.6 T T T T T T T T
20 1 1.3 2.1 4 6.2 T T T T 1 1.3 2.1 3.9 6.1 T T T T T T T T
25 1 1.3 2.1 4 6.2 T T T T 1 1.3 2.1 3.9 6.1 T T T T T T T T
32 1.1 1.3 2.2 4.1 6.2 T T T T 1.1 1.4 2.2 4 6.1 T T T T T T T T
40 1.1 1.9 3.5 5.5 8.8 T T T 1.2 1.9 3.4 5.4 8.8 T T T T T T T
50 1.6 2.7 4.3 6.6 T T T 1.6 2.6 4.2 6.6 T T T T T T T
63 1.6 2.7 4.3 6.6 T T T 1.6 2.6 4.2 6.6 T T T T T T T

G3.31 3NA - 5SL 106 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 1 2
characteristic

Icn [kA]

In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

1
2 1 1.6 1.9 3.1 T T T T T T 1.6 1.9 3.1 5.9 T T T T T T T T T
4 1 1.6 1.9 3.1 T T T T T T 1.6 1.9 3.1 5.9 T T T T T T T T T
6 1 1.6 1.9 3.1 T T T T T T 1.6 1.9 3.1 5.9 T T T T T T T T T
10 1 1.4 1.7 2.8 5 T T T T T 1.4 1.7 2.8 4.9 T T T T T T T T T
13 1 1.4 1.6 2.8 5.2 T T T T T 1.4 1.7 2.8 5 T T T T T T T T T
16 1.2 1.4 2.2 4 5.5 T T T T 1.2 1.4 2.2 3.9 5.4 T T T T T T T T
B

20 1.1 1.3 2.2 3.8 5.5 T T T T 1.1 1.4 2.2 3.7 5.4 T T T T T T T T
25 1.1 1.3 2.1 3.7 5.3 T T T T 1.1 1.4 2.1 3.6 5.2 T T T T T T T T
32
downstream miniature circuit breaker 5SL6

1.1 1.3 1.9 3.1 4.3 T T T T 1.1 1.3 1.9 3 4.3 T T T T T T T T


40 1.2 1.4 2.2 3.7 5.4 T T T T 1.2 1.4 2.2 3.6 5.3 T T T T T T T T
50 1.2 1.8 3.1 4.5 T T T T 1.2 1.8 3.1 4.5 T T T T T T T T
63 1.7 2.9 4.3 T T T T 1.7 2.9 4.2 T T T T T T T T
0.3 1.6 T T T T T T T T T T T T T T T T T T T T T T T T T T
line protection

0.5 1.6 T T T T T T T T T T T T T T T T T T T T T T T T T T
1 1.4 T T T T T T T T T T T T T T T T T T T T T T T T T
1.6 2 2.5 T T T T T T T T T 2.2 T T T T T T T T T T T T T
2 1.4 1.7 2.7 3.2 5.6 T T T T T T 1.5 2.7 3.3 5.6 T T T T T T T T T T
3 1.2 1.4 2.2 2.6 4.8 T T T T T T 1.3 2.2 2.7 4.8 T T T T T T T T T T
4 1.1 1.3 2.1 2.5 4.4 T T T T T T 1.2 2.1 2.6 4.4 T T T T T T T T T T
6 1.1 1.3 2.1 2.5 4.4 T T T T T T 1.2 2.1 2.6 4.4 T T T T T T T T T T
8 1 1.5 1.8 2.9 5.4 T T T T T 1.5 1.8 2.9 5.3 T T T T T T T T T
10 1 1.4 1.7 2.8 5 T T T T T 1.4 1.7 2.8 4.9 T T T T T T T T T
C

13 1 1.4 1.6 2.8 5.2 T T T T T 1.4 1.7 2.8 5 T T T T T T T T T


16 1.2 1.4 2.2 4 5.5 T T T T 1.2 1.4 2.2 3.9 5.4 T T T T T T T T
20 1.1 1.3 2.2 3.8 5.5 T T T T 1.1 1.4 2.2 3.7 5.4 T T T T T T T T
25 1.1 1.3 2.1 3.7 5.3 T T T T 1.1 1.4 2.1 3.6 5.2 T T T T T T T T
32 1.1 1.3 1.9 3.1 4.3 T T T T 1.1 1.3 1.9 3 4.3 T T T T T T T T
40 1.2 1.4 2.2 3.7 5.4 T T T T 1.2 1.4 2.2 3.6 5.3 T T T T T T T T
50 1.2 1.8 3.1 4.5 T T T T 1.2 1.8 3.1 4.5 T T T T T T T T
63 1.7 2.9 4.3 T T T T 1.7 2.9 4.2 T T T T T T T T

G3.31 3NA - 5SL 107 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn [kA]

In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
13
10

T T T T T T T T T T T T T T T T T T T
B

16 T T T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T T T T
downstream miniature circuit breaker 5SL4

25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T T
line protection

0.3 T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10
C

10 T T T T T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T T

G3.31 3NA - 5SL 108 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn [kA]

In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
0.3 T T T T T T T T T T T T T T T T T T T
0.5 T T T T T T T T T T T T T T T T T T T
1
downstream miniature circuit breaker 5SL4

T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
line protection

6 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10
D

10 T T T T T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T T

G3.31 3NA - 5SL 109 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with
selectivity Is [kA] utilization category gG
for 230 / 400V AC
Icu [kA] 120
acc. to IEC 60898
Un fuse [V] 400 / 500 / 690
edition 06/2017
frame size 3 4 4a
characteristic

Icn [kA]

In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

1
2 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T T T
B

20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32
downstream miniature circuit breaker 5SL6

T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T T
0.3 T T T T T T T T T T T T T T T T T T T
line protection

0.5 T T T T T T T T T T T T T T T T T T T
1 T T T T T T T T T T T T T T T T T T T
1.6 T T T T T T T T T T T T T T T T T T T
2 T T T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
C

13 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T T T
20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T T

G3.31 3NA - 5SL 110 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60947-2
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 000 / 00 / 0 / 1 / 2 / 3 / 4 / 4a

Un [V] fuse

frame size
Icu [kA]

In [A] 4 6 10 16 20 25 32 35 40 50 63 80 100 125 160 200 224 250 300 315 355 400 425 500 630 800 1000 1250

2 T T T T T T T T T T T T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T T T T T T T
16 0.81 T T T T T T T T T T T T T T T T T T T T T T T
20 1.09 T T T T T T T T T T T T T T T T T T T T T T
25 1.48 T T T T T T T T T T T T T T T T T T T T T
32 1.73 2 T T T T T T T T T T T T T T T T T T T
35 2 2.44 T T T T T T T T T T T T T T T T T T
40 2.44 2.77 T T T T T T T T T T T T T T T T T
50 2.77 T T T T T T T T T T T T T T T T T
000 / 00 / 0 / 1 / 2 / 3 / 4 / 4a
downstream NH-fuse 3NA

utilization category gG

63 3.46 T T T T T T T T T T T T T T T T
400 / 500 / 690

80 4.89 T T T T T T T T T T T T T T T
100 6 T T T T T T T T T T T T T T
120

125 7.61 T T T T T T T T T T T T T
160 10.72 12.04 T T T T T T T T T T T
200 14.31 19 19 T T T T T T T T
224 14.31 19 19 T T T T T T T T
250 19 21 21 25.49 28.01 T T T T
300 19 21 21 25.49 28.01 T T T T
315 21 23 25.49 28.01 T T T T
355 28.01 T T T T
400 28.01 T T T T
425 28.01 T T T T
500 43.58 T T T
630 58.99 T T
800 88.99 T
1000 109

G3.40 3NA - 3NA 111 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 000 00 0


characteristic

Icn [kA]

In [A] 6 10 16 20 25 32 35 40 50 63 80 100 125 160 35 50 63 80 100 125 160 6 10 16 20 25 32 35 40 50 63 80 100 125 160

6 0.1 0.2 0.6 1 1.5 2 2.7 3.9 7.1 T T T 1.5 2.8 3.9 7.1 T T T 0.2 0.3 0.6 1 1.5 2 2.7 3.4 6.9 T T T
10 0.1 0.2 0.5 0.9 1.2 1.4 1.9 2.4 3.9 8.3 T T 1.2 1.9 2.4 3.9 8.1 T T 0.2 0.3 0.5 0.9 1.2 1.4 1.8 2.2 3.7 7.6 T T
downstream residual current device (RCBO)

13 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.4 6 7.7 T 1.1 1.8 2.2 3.4 5.9 8.8 T 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2 3.3 5.7 8.8 T
16 0.2 0.4 0.7 1 1.2 1.6 2 3.1 5.4 6.8 T 1 1.6 2 3.1 5.3 8 T 0.2 0.4 0.7 1 1.2 1.6 1.9 3 5.1 7.9 T
10
B

20 0.4 0.7 1 1.2 1.5 1.9 2.9 5.2 6.4 T 1 1.5 1.9 2.9 5.1 7.1 T 0.4 0.7 1 1.2 1.5 1.7 2.8 4.9 7.1 T
25 0.6 0.9 1.1 1.3 1.7 2.5 4.7 5.8 9.9 0.9 1.4 1.7 2.5 4.6 6.5 9.6 0.6 0.9 1.1 1.3 1.6 2.5 4.4 6.5 9.9
32 1.1 1.3 1.6 2.5 4.4 5.3 8.5 1.3 1.6 2.5 4.4 5.8 8.3 1.1 1.3 1.5 2.4 4.2 5.8 8.5
line protection
5SU1, 10kA

40 1.2 1.5 2.3 4.7 6 8.6 1.3 1.5 2.3 4.6 6.5 8.5 1.2 1.4 2.2 4.4 6.4 8.6
6 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 9.3 T T 1.2 2 2.6 4.1 9 T T 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 8.4 T T
8 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.5 7 9.8 T 1.1 1.8 2.2 3.5 6.8 T T 0.2 0.3 0.5 0.8 1.1 1.3 1.7 2 3.4 6.3 T T
10 0.2 0.4 0.7 1.1 1.3 1.7 2.2 3.4 6.6 8.7 T 1.1 1.7 2.2 3.4 6.4 T T 0.2 0.4 0.7 1.1 1.3 1.7 2 3.3 6.1 T T
13 0.2 0.4 0.6 1 1.1 1.4 1.8 2.8 4.8 5.9 T 1 1.5 1.8 2.8 4.8 6.8 T 0.2 0.4 0.6 1 1.1 1.4 1.7 2.7 4.6 6.7 T
16 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 6.6 T 1 1.5 1.9 3 5.2 7.7 T 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 7.7 T
10
C

20 0.6 0.9 1 1.3 1.6 2.5 4.3 5.1 T 0.9 1.3 1.6 2.5 4.2 5.8 9.9 0.6 0.9 1 1.3 1.5 2.4 4 5.7 T
25 0.6 0.9 1.1 1.3 1.6 2.5 4.5 5.6 T 0.9 1.3 1.6 2.5 4.4 6.3 9.9 0.6 0.9 1.1 1.3 1.5 2.4 4.3 6.3 T
32 1.1 1.4 1.7 2.5 4.2 5.2 9.9 1.4 1.7 2.5 4.1 6 9.6 1.1 1.4 1.6 2.4 3.9 5.9 9.9
40 1.2 1.5 2.2 3.9 4.8 8.6 1.2 1.5 2.2 3.8 5.4 8.4 1.2 1.3 2.1 3.7 5.3 8.6
6 0.1 0.2 0.6 1 1.5 2 2.7 3.9 T T T T 1.5 2.8 3.9 T T T T 0.2 0.3 0.6 1 1.5 2 2.7 3.4 T T T T
10 0.1 0.2 0.5 0.9 1.2 1.4 1.9 2.4 3.9 T T T 1.2 1.9 2.4 3.9 T T T 0.2 0.3 0.5 0.9 1.2 1.4 1.8 2.2 3.7 T T T
downstream residual current device (RCBO)

13 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.4 T T T 1.1 1.8 2.2 3.4 5.9 T T 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2 3.3 5.7 T T
4,5 / 6

16 0.2 0.4 0.7 1 1.2 1.6 2 3.1 5.4 T T 1 1.6 2 3.1 5.3 T T 0.2 0.4 0.7 1 1.2 1.6 1.9 3 5.1 T T
B

20 0.4 0.7 1 1.2 1.5 1.9 2.9 5.2 T T 1 1.5 1.9 2.9 5.1 T T 0.4 0.7 1 1.2 1.5 1.7 2.8 4.9 T T
25 0.6 0.9 1.1 1.3 1.7 2.5 4.7 5.8 T 0.9 1.4 1.7 2.5 4.6 T T 0.6 0.9 1.1 1.3 1.6 2.5 4.4 T T
32 1.1 1.3 1.6 2.5 4.4 5.3 T 1.3 1.6 2.5 4.4 5.8 T 1.1 1.3 1.5 2.4 4.2 5.8 T
5SU1, 4.5/6kA

line protection

40 1.2 1.5 2.3 4.7 T T 1.3 1.5 2.3 4.6 T T 1.2 1.4 2.2 4.4 T T
6 0.1 0.2 0.5 0.9 1.2 1.5 2 2.6 4.1 T T T 1.2 2 2.6 4.1 9 T T 0.2 0.2 0.5 0.9 1.2 1.5 2 2.4 3.9 T T T
8 0.1 0.2 0.5 0.8 1.1 1.3 1.7 2.2 3.5 T T T 1.1 1.8 2.2 3.5 6.8 T T 0.2 0.3 0.5 0.8 1.1 1.3 1.7 2 3.4 6.3 T T
10 0.2 0.4 0.7 1.1 1.3 1.7 2.2 3.4 T T T 1.1 1.7 2.2 3.4 6.4 T T 0.2 0.4 0.7 1.1 1.3 1.7 2 3.3 6.1 T T
13 0.2 0.4 0.6 1 1.1 1.4 1.8 2.8 4.8 5.9 T 1 1.5 1.8 2.8 4.8 T T 0.2 0.4 0.6 1 1.1 1.4 1.7 2.7 4.6 T T
4,5 / 6

16 0.2 0.4 0.7 1 1.2 1.5 1.9 3 5.2 T T 1 1.5 1.9 3 5.2 T T 0.2 0.4 0.7 1 1.2 1.5 1.8 2.9 5 T T
C

20 0.6 0.9 1 1.3 1.6 2.5 4.3 5.1 T 0.9 1.3 1.6 2.5 4.2 5.8 T 0.6 0.9 1 1.3 1.5 2.4 4 5.7 T
25 0.6 0.9 1.1 1.3 1.6 2.5 4.5 5.6 T 0.9 1.3 1.6 2.5 4.4 T T 0.6 0.9 1.1 1.3 1.5 2.4 4.3 T T
32 1.1 1.4 1.7 2.5 4.2 5.2 T 1.4 1.7 2.5 4.1 T T 1.1 1.4 1.6 2.4 3.9 5.9 T
40 1.2 1.5 2.2 3.9 4.8 T 1.2 1.5 2.2 3.8 5.4 T 1.2 1.3 2.1 3.7 5.3 T

G3.50 3NA - 5SU1 112 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 1 2
characteristic

Icn [kA]

In [A] 16 20 25 35 40 50 63 80 100 125 160 200 224 250 35 50 63 80 100 125 160 200 224 250 300 315 355 400

6 0.1 0.2 0.6 1.4 1.6 2.7 3.4 6.9 T T T T T T 1.5 2.7 3.6 6.9 T T T T T T T T T T
10 0.1 0.2 0.5 1.1 1.2 1.8 2.2 3.7 7.6 T T T T T 1.2 1.8 2.3 3.7 7.3 T T T T T T T T T
downstream residual current device (RCBO)

13 0.1 0.2 0.5 1 1.1 1.7 2 3.3 5.7 8.8 T T T T 1.1 1.7 2.1 3.3 5.5 8.6 T T T T T T T T
16 0.2 0.4 1 1.1 1.6 1.9 3 5.1 7.9 T T T T 1 1.6 1.9 3 5 7.8 T T T T T T T T
10
B

20 0.4 0.9 1 1.5 1.7 2.8 4.9 7.1 T T T T 1 1.5 1.8 2.8 4.8 7 T T T T T T T T
25 0.8 1 1.3 1.6 2.5 4.4 6.5 9.9 T T T 0.9 1.3 1.6 2.5 4.3 6.4 9.8 T T T T T T T
32 1 1.3 1.5 2.4 4.2 5.8 8.5 T T T 1.3 1.6 2.4 4.1 5.7 8.4 T T T T T T T
line protection
5SU1, 10kA

40 1.2 1.4 2.2 4.4 6.4 8.6 T T T 1.2 1.5 2.2 4.2 6.4 8.6 T T T T T T T
6 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 8.4 T T T T T 1.2 2 2.4 3.9 8.1 T T T T T T T T T
8 0.1 0.2 0.5 1 1.2 1.7 2 3.4 6.3 T T T T T 1.1 1.7 2.1 3.4 6.1 T T T T T T T T T
10 0.2 0.4 1 1.1 1.7 2 3.3 6.1 T T T T T 1 1.7 2.1 3.3 5.9 9.9 T T T T T T T T
13 0.4 0.9 1 1.4 1.7 2.7 4.6 6.7 T T T T 0.9 1.4 1.7 2.7 4.5 6.6 T T T T T T T T
16 0.2 0.4 0.9 1 1.5 1.8 2.9 5 7.7 T T T T 1 1.5 1.8 2.9 4.8 7.5 T T T T T T T T
10
C

20 0.8 0.9 1.3 1.5 2.4 4 5.7 T T T T 0.8 1.3 1.6 2.4 4 5.6 T T T T T T T T
25 0.8 0.9 1.3 1.5 2.4 4.3 6.3 T T T T 0.8 1.3 1.6 2.4 4.2 6.2 T T T T T T T T
32 0.9 1.4 1.6 2.4 3.9 5.9 9.9 T T T 1.4 1.7 2.4 3.8 5.8 9.9 T T T T T T T
40 1.2 1.3 2.1 3.7 5.3 8.6 T T T 1.2 1.4 2.1 3.6 5.2 8.6 T T T T T T T
6 0.1 0.2 0.6 1.4 1.6 2.7 3.4 T T T T T T T 1.5 2.7 3.6 T T T T T T T T T T T
10 0.1 0.2 0.5 1.1 1.2 1.8 2.2 3.7 T T T T T T 1.2 1.8 2.3 3.7 T T T T T T T T T T
downstream residual current device (RCBO)

13 0.1 0.2 0.5 1 1.1 1.7 2 3.3 5.7 T T T T T 1.1 1.7 2.1 3.3 5.5 T T T T T T T T T
4,5 / 6

16 0.2 0.4 1 1.1 1.6 1.9 3 5.1 T T T T T 1 1.6 1.9 3 5 T T T T T T T T T


B

20 0.4 0.9 1 1.5 1.7 2.8 4.9 T T T T T 1 1.5 1.8 2.8 4.8 T T T T T T T T T
25 0.8 1 1.3 1.6 2.5 4.4 T T T T T 0.9 1.3 1.6 2.5 4.3 T T T T T T T T T
32 1 1.3 1.5 2.4 4.2 5.8 T T T T 1.3 1.6 2.4 4.1 5.7 T T T T T T T T
5SU1, 4.5/6kA

line protection

40 1.2 1.4 2.2 4.4 T T T T T 1.2 1.5 2.2 4.2 T T T T T T T T T


6 0.1 0.2 0.5 1.2 1.3 2 2.4 3.9 T T T T T T 1.2 2 2.4 3.9 T T T T T T T T T T
8 0.1 0.2 0.5 1 1.2 1.7 2 3.4 T T T T T T 1.1 1.7 2.1 3.4 T T T T T T T T T T
10 0.2 0.4 1 1.1 1.7 2 3.3 T T T T T T 1 1.7 2.1 3.3 5.9 T T T T T T T T T
13 0.4 0.9 1 1.4 1.7 2.7 4.6 T T T T T 0.9 1.4 1.7 2.7 4.5 T T T T T T T T T
4,5 / 6

16 0.2 0.4 0.9 1 1.5 1.8 2.9 5 T T T T T 1 1.5 1.8 2.9 4.8 T T T T T T T T T
C

20 0.8 0.9 1.3 1.5 2.4 4 5.7 T T T T 0.8 1.3 1.6 2.4 4 5.6 T T T T T T T T
25 0.8 0.9 1.3 1.5 2.4 4.3 T T T T T 0.8 1.3 1.6 2.4 4.2 T T T T T T T T T
32 0.9 1.4 1.6 2.4 3.9 5.9 T T T T 1.4 1.7 2.4 3.8 5.8 T T T T T T T T
40 1.2 1.3 2.1 3.7 5.3 T T T T 1.2 1.4 2.1 3.6 5.2 T T T T T T T T

G3.50 3NA - 5SU1 113 / 114


SIEMENS AG upstream NH-fuse 3NA
Limit current with selectivity Is [kA]
for 230 / 400V AC utilization category gG
acc. to IEC 60898
Icu [kA] 120

edition 06/2017 Un fuse [V] 400 / 500 / 690

frame size 3 4 4a
characteristic

Icn [kA]

In [A] 200 224 250 300 315 355 400 425 500 630 630 800 1000 1250 500 630 800 1000 1250

6 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
downstream residual current device (RCBO)

13 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T T T
10
B

20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
line protection
5SU1, 10kA

40 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T T T T T
16 T T T T T T T T T T T T T T T T T T T
10
C

20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
downstream residual current device (RCBO)

13 T T T T T T T T T T T T T T T T T T T
4,5 / 6

16 T T T T T T T T T T T T T T T T T T T
B

20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
5SU1, 4.5/6kA

line protection

40 T T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T T
8 T T T T T T T T T T T T T T T T T T T
10 T T T T T T T T T T T T T T T T T T T
13 T T T T T T T T T T T T T T T T T T T
4,5 / 6

16 T T T T T T T T T T T T T T T T T T T
C

20 T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T

G3.50 3NA - 5SU1 114 / 114

Das könnte Ihnen auch gefallen