Sie sind auf Seite 1von 35

AIR CONDITIONER (SPLIT TYPE)

Installation manual

Outdoor Unit
Model name:

RAV-SP1104AT8-E
RAV-SP1104AT8Z-E
RAV-SP1104AT8ZG-E
RAV-SP1404AT8-E
RAV-SP1404AT8Z-E
RAV-SP1404AT8ZG-E
RAV-SP1604AT8-E
RAV-SP1604AT8Z-E
RAV-SP1604AT8ZG-E

English EN
Super Digital Inverter

Original instruction

ADOPTION OF NEW REFRIGERANT


This Air Conditioner is a new type that has adopted a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in
order to prevent destruction of the ozone layer.

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the
interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to Ssc (*1).
Ssc (*1)
Model Ssc (MVA)
RAV-SP1104AT8(Z)(ZG)-E 1.35
RAV-SP1404AT8(Z)(ZG)-E 1.35
RAV-SP1604AT8(Z)(ZG)-E 1.35

Contents
1 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 ACCESSORY PARTS AND REFRIGERANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER . . . . . . . . . . . . . . . . . . . . . . . 9
4 INSTALLATION CONDITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 REFRIGERANT PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6 AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7 ELECTRICAL WORK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 EARTHING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9 FINISHING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11 ANNUAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
12 AIR CONDITIONER OPERATING CONDITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
13 FUNCTIONS TO BE IMPLEMENTED LOCALLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
14 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
15 APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

EN-i i
Super Digital Inverter

Thank you for purchasing this Toshiba air conditioner.


Please read carefully through these instructions that contain important information which complies with the “Machinery”
Directive (Directive 2006/42/EC), and ensure that you understand them.
Some of the details provided in these instructions differ from the Installation Manual supplied with your product, and the
instructions provided here take precedence.
After reading these instructions, be sure to keep them in a safe place together with the Owner’s Manual and Installation Manual
supplied with your product.

Generic Denomination: Air Conditioner

Definition of Qualified Installer or Qualified Service Person


The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person.
When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table
below.

Agent Qualifications and knowledge which the agent must have


Qualified • The qualified installer is a person who installs, maintains, relocates and removes the air conditioners
installer made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and
remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such operations by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and
removal has the qualifications pertaining to this electrical work as stipulated by the local laws and
regulations, and he or she is a person who has been trained in matters relating to electrical work on the
air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in
such matters by an individual or individuals who have been trained and is thus thoroughly acquainted
with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in
installation, relocation and removal has the qualifications pertaining to this refrigerant handling and
piping work as stipulated by the local laws and regulations, and he or she is a person who has been
trained in matters relating to refrigerant handling and piping work on the air conditioners made by
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an
individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working
at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has
been instructed in such matters by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to this work.
Qualified • The qualified service person is a person who installs, repairs, maintains, relocates and removes the air
service person conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair,
maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such operations by an individual or individuals who have
been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair,
relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local
laws and regulations, and he or she is a person who has been trained in matters relating to electrical
work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been trained and is thus thoroughly
acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in
installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling
and piping work as stipulated by the local laws and regulations, and he or she is a person who has been
trained in matters relating to refrigerant handling and piping work on the air conditioners made by
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an
individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to
working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or
she has been instructed in such matters by an individual or individuals who have been trained and is
thus thoroughly acquainted with the knowledge related to this work.

1 1-EN
Super Digital Inverter

Definition of Protective Gear


When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and “safety”
work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed
in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks
and other injuries.

Work undertaken Protective gear worn


All types of work Protective gloves
“Safety” working clothing
Electrical-related work Gloves to provide protection for electricians and from heat
Insulating shoes
Clothing to provide protection from electric shock
Work done at heights Helmets for use in industry
(50 cm or more)
Transportation of Shoes with additional protective toe cap
heavy objects
Repair of outdoor unit Gloves to provide protection for electricians and from heat

EN-2 2
Super Digital Inverter

Warning Indications on the Air Conditioner Unit


Warning indication Description

WARNING
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote ELECTRICAL SHOCK HAZARD
electric power supplies Disconnect all remote electric power supplies before servicing.
before servicing.

WARNING WARNING

Moving parts. Moving parts.


Do not operate unit with grille Do not operate unit with grille removed.
removed. Stop the unit before the servicing.
Stop the unit before the servicing.

CAUTION
CAUTION
High temperature parts. High temperature parts.
You might get burned You might get burned when removing this panel.
when removing this panel.

CAUTION
CAUTION
Do not touch the aluminum Do not touch the aluminum fins of the unit.
fins of the unit. Doing so may result in injury.
Doing so may result in injury.

CAUTION CAUTION

BURST HAZARD BURST HAZARD


Open the service valves before Open the service valves before the operation, otherwise there
the operation, otherwise there might be the burst.
might be the burst.

3 3-EN
Super Digital Inverter

1 PRECAUTIONS FOR SAFETY

WARNING

General
• Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install
the air conditioner.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to install the air conditioner. If the air conditioner is
installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF
position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior
parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the intake grille of the indoor unit or
service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF
position. Otherwise, electric shocks may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being
carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm or
more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminum fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some
reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and
result in injury.
• When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s
instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
• When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in
progress” sign near the circuit breaker before proceeding with the work.
• When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work.
Parts and other objects may fall from above, possibly injuring a person below.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition.

Selection of installation location


• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit
concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the
measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
• Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas. If a combustible
gas leaks and becomes concentrated around the unit, a fire may occur.
• When transporting the air conditioner, wear shoes with additional protective toe caps.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the
bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric
shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may
cause imperfect combustion.

Installation
• When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be
used.
• Install the air conditioner at enough strong places to withstand the weight of the unit. If the strength is not enough, the unit
may fall down resulting in injury.
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause
the product to fall down or topple over or give rise to noise, vibration, water leakage, etc.
• The designated bolts (M10, M12) and nuts (M10, M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient
durability may cause the outdoor unit to fall, which may result in injury.

EN-4 4
Super Digital Inverter

Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is
operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over
pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in
the flare nut after a long period, which may result in refrigerant leakage.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a
fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air
completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air
completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.

Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may
result in electric shocks and/or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to
provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use
of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
• Be sure to connect earth wire. (Grounding work)
Incomplete grounding causes an electric shock.
• Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for telephone wires.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations
and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended
may give rise to smoking and/or a fire.

Test run
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor
unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an
electric shock if the power is turned on without first conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning,
abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do
not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person.
Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance)
until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical
problems to escalate or result in electric shocks, etc.
• After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2 Mȍ or more
between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such
as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is operating properly.

5 5-EN
Super Digital Inverter

Explanations given to user


• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where
the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF
position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position
until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.

Relocation
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the
air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or
vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting
the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in,
raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.

(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”

EN-6 6
Super Digital Inverter

CAUTION

New Refrigerant Air Conditioner Installation


• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE
LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure
of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new refrigerant, the
refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant,
or refrigeration machine oil does not enter the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and
installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for the new
refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A
only, so that water and/or dust does not enter.

To Disconnect the Appliance from the Main Power Supply


• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
• A 20 A installation fuse (all fuse types can be used) must be used for the power supply line of this conditioner.

7 7-EN
Super Digital Inverter

2 ACCESSORY PARTS AND REFRIGERANT

„ Accessory Parts

Part name Q’ty Shape Usage


Hand this directly to the customer.
(For other languages that do not appear in this
Outdoor unit installation manual 1
Installation Manual, please refer to the enclosed
CD-R.)

Drain nipple 1

Waterproof rubber cap 5

Protective bush 1 For protecting wires (pipe cover)

Guard material for passage part 1 For protecting passage part (pipe cover)

For conforming to EMC standards


Clamp filter 1
(Used for power wire)

EN-8 8
Super Digital Inverter

3 INSTALLATION OF NEW REFRIGERANT AIR


CONDITIONER
• The R410A refrigerant is more susceptible to impurities such as water, oxide membranes, oils, and fats.
With the adoption of the new refrigerant, the refrigerating oil has also been changed.
Be careful not to let water, dust, conventional refrigerant, and/or conventional refrigerating oil enter the refrigerating cycle of
the new refrigerant air conditioner.
• To prevent different refrigerant or refrigerating oil from becoming mixed, the sizes of the charging port of the unit and the
installation tool connection sections are different from those of the conventional refrigerant. Accordingly, the following
exclusive tools are required for the new refrigerant R410A.

„ Required Tools/Equipment and Precautions for Use


Prepare the tools and equipment listed in the following table before starting the installation work.
Newly prepared tools and equipment must be used exclusively.

Legend
: Prepared newly (Use for R410A only. Do not use for refrigerant R22 or R407C etc.)
: Conventional tools/equipment are available

Tools/equipment Use How to use tools/equipment


Gauge manifold Vacuuming/charging refrigerant Prepared newly for R410A only

Charging hose and operation check


Prepared newly for R410A only
Unusable (Use the refrigerant charging measure
Charging cylinder Can not be used
instead.)
Gas leak detector Gas leak check Prepared newly

Vacuum pump Vacuum drying Unusable


Vacuum pump with backflow
Vacuum drying R22 (Conventional tools)
prevention function
Flare tool Flare machining of pipes Usable if dimensions are adjusted.

Bender Bending pipes R22 (Conventional tools)

Refrigerant recovery equipment Refrigerant recovery For R410A only

Torque wrench Tightening flare nuts Exclusive for Ø12.7 mm and Ø15.9 mm

Pipe cutter Cutting pipes R22 (Conventional tools)


Welding machine and nitrogen
Welding pipes R22 (Conventional tools)
cylinder
Refrigerant charging measure Charging refrigerant R22 (Conventional tools)

9 9-EN
Super Digital Inverter

„ Refrigerant Piping

New refrigerant (R410A)

When using the conventional piping kit


• When using the conventional piping kit with no indication of applicable refrigerant types, be sure to use it with a wall
thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, and with a wall thickness of 1.0 mm for Ø15.9 mm. Do not use
the conventional piping kit with a wall thickness less than these thicknesses due to insufficient pressure capacity.

When using general copper pipes


• Use general copper pipes with a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, and with a wall thickness
of 1.0 mm for Ø15.9 mm.
Do not use any copper pipes with a wall thickness less than these thicknesses.

Flare nuts and flare machining


• The flare nuts and flare machining are different from those for the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or those for R410A.
• Before performing flare machining, carefully read “REFRIGERANT PIPING”.

EN-10 10
Super Digital Inverter

4 INSTALLATION CONDITIONS

„ Before installation Earthing


Be sure to prepare to the following items before installation. • Proper earthing can prevent charging of electricity on the
outdoor unit surface due to the presence of a high
frequency in the frequency converter (inverter) of the
Length of refrigerant pipe outdoor unit, as well as prevent electric shock. If the
outdoor unit is not properly earthed, you may be exposed
Length of refrigerant pipe
to an electric shock.
connected to indoor/ Item
• Be sure to connect the earth wire. (grounding work)
outdoor unit
Incomplete earthing can cause an electric shock.
Addition of refrigerant is Do not connect earth wires to gas pipes, water pipes,
3 to 30 m
unnecessary at the local site. lightning rods or earth wires for telephone wires.
<Addition of refrigerant>
Add 40 g of refrigerant for Test Run
*31 to 75 m
every 1 m of piping that
exceeds 30 m. Turn on the leakage breaker at least 12 hours before starting
a test run to protect the compressor during startup.
* Caution during addition of refrigerant
When the total length of refrigerant piping exceeds 30 m,
add 40 g/m of refrigerant up to a maximum total length of
piping at 75 m. (Max. amount of additional refrigerant is
1,800 g.)
Charge the refrigerant accurately. Overcharging may
cause serious trouble with the compressor.
• Do not connect a refrigerant pipe that is shorter than 3 m.
This may cause a malfunction of the compressor or other
devices.

„ Airtight test
1. Before starting an airtight test, further tighten the spindle
valves on the gas and liquid sides.
2. Pressurize the pipe with nitrogen gas charged from the
service port to the design pressure (4.15 MPa) to
conduct an airtight test.
3. After the airtight test is completed, evacuate the nitrogen
gas.

Air purge
• To purge air, use a vacuum pump.
• Do not use refrigerant charged in the outdoor unit to
purge air. (The air purge refrigerant is not contained in
the outdoor unit.)

Electrical wiring
• Be sure to fix the power wires and indoor/outdoor
connecting wires with clamps so that they do not come
into contact with the cabinet, etc.

11 11-EN
Super Digital Inverter

„ Installation Location 1) Install the unit so that its discharge port faces the
wall of the building.
Keep a distance 500 mm or more between the unit
CAUTION and wall surface.
Install the outdoor unit in a location that meets the 500 mm

following conditions after the customer’s consent is


obtained.
• A well-ventilated location free from obstacles near the air
inlets and air outlet
• A location that is not exposed to rain or direct sunlight
• A location that does not increase the operating noise or
vibration of the outdoor unit
• A location that does not produce any drainage problems
from discharged water

Do not install the outdoor unit in the following locations.


• A location with a saline atmosphere (coastal area) or one 2) Consider the wind direction during the operational
that is full of sulfide gas (hot-spring area) (Special season of the air conditioner, and install the unit so
maintenance is required.) that the discharge port is set at a right angle relative
• A location subject to oil, vapor, oily smoke, or corrosive to the wind direction.
gases
• A location in which organic solvent is used
Strong wind
• A location where high-frequency equipment (including
Strong wind
inverter equipment, private power generator, medical
equipment, and communication equipment) is used
(Installation in such a location may cause malfunction of
the air conditioner, abnormal control or problems due to
noise from such equipment.)
• A location in which the discharged air of the outdoor unit
blows against the window of a neighboring house • When using an air conditioner under low outside
• A location where the operating noise of the outdoor unit is temperature conditions (Outside temp: -5 °C or lower)
transmitted in COOL mode, prepare a duct or wind shield so that it
• When the outdoor unit is installed in an elevated position, is not affected by the wind.
be sure to secure its feet. • When installing the unit in an area where snowfalls
• A location in which drain water poses any problems. may be heavy, take steps to prevent the unit from being
adversely affected by the fallen or accumulated snow.
1. Install the outdoor unit in a location where the discharge • Either make the foundation higher or install a stand
air is not blocked. (which is high enough to ensure that the unit will be
2. When an outdoor unit is installed in a location that is above the fallen or accumulated snow) and place the
always exposed to strong winds like a coast or on the unit on it.
high stories of a building, secure normal fan operation by • Attach a snow shield (locally procured).
using a duct or wind shield.
3. When installing the outdoor unit in a location that is <Example>
constantly exposed to strong winds such as on the upper Wind (snow) shield Wind (snow) shield
stairs or rooftop of a building, apply the windproofing
measures referred to in the following examples.

Wind (snow) shield

EN-12 12
Super Digital Inverter

„ Necessary Space for Installation Obstacle in front


(Unit: mm)
Above unit is free
1. Single unit installation
Obstacle at rear side

Upper side is free


1. Single unit installation

500 or
more
2. Serial installation of two or more units

150 or
more
2. Obstacles on both right and left sides

1,000 or
more
The height of the
200 or
more

obstacle should be
lower than the height of
the outdoor unit.

Obstacle also at the above unit


150 or 300 or
more more

1,000 or
1,000 or

more
more
3. Serial installation of two or more units
200 or more

150 or 300 or 300 or 300 or Obstacles in both front and rear of unit
more more more more
Open above and to the right and left of the unit.
The height of the obstacle should be lower than the height The height of an obstacle in both the front and rear of the
of the outdoor unit.
unit, should be lower than the height of the outdoor unit.

Obstacle also above unit Standard installation


1. Single unit installation
500 or

150 or
more

150 or
more
more
1,000 or
more

2. Serial installation of two or more units


200 or
more
1,000 or

300 or 300 or
more

more more

13 13-EN
Super Digital Inverter

Serial installation in front and rear • As shown in the figure below, install the foundation and
Open above and to the right and left of the unit. vibration-proof rubber pads to directly support the bottom
The height of an obstacle in both the front and rear of the unit surface of the fixing leg that is in contact with and
should be lower than the height of the outdoor unit. underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with
Standard installation downward piping, consider the piping work.
GOOD

Absorb vibration
Fixing leg with vibration-proof
rubber pads
1,000 or 300 or 1,500 or 2,000 or 200 or
more more more more more
Foundation

GOOD

„ Installation of Outdoor Unit


Bottom plate of
• Before installation, check the strength and horizontalness outdoor unit
of the base so that abnormal sounds do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts. Foundation
(Anchor bolt, nut: M10 x 4 pairs) Support the bottom surface of the
Drain hole fixing leg that is in contact with and
525 underneath the bottom plate of the
outdoor unit.
150 600 150
45

NO GOOD
If only the end of the Do not support the
fixing leg is supported, it outdoor unit only with
400
365

may deform. the fixing leg.

Drain hole Foundation


Drain nipple
mounting hole Set the out margin of the anchor bolt to 15 mm or less.

15 or less

EN-14 14
Super Digital Inverter

• When water is to be drained through the drain hose, „ For Reference


attach the following drain nipple and waterproof rubber
If a heating operation is to be continuously performed for a
cap, and use the drain hose (Inner diam: 16 mm) sold on
long time under the condition that the outdoor temperature is
the market. Also seal knockout hole and the screws
0 °C or lower, draining defrosted water may be difficult due to
securely with silicone material, etc., to prevent water from
the bottom plate freezing, resulting in trouble with the cabinet
leaking.
or fan.
Some conditions may cause dewing or dripping of water.
It is recommended to procure an anti-freeze heater locally in
• When collectively draining discharged water completely,
order to safely install the air conditioner.
use a drain pan.
For details, contact the dealer.

Waterproof rubber cap

Drain nipple

Drain nipple

Waterproof rubber cap

Knockout hole

5 REFRIGERANT PIPING
„ Knockout of Pipe Cover • Detach the pipe cover and tap on the knockout section a
few times with the shank of a screwdriver. A knockout
hole can easily be punched.
Knockout procedure • After punching out the knockout hole, remove burrs from
the hole and then install the supplied protective bush and
guard material around the passage hole to protect wires
and pipes.
Be sure to attach the pipe covers after pipes have been
connected. Cut the slits under the pipe covers to facilitate
the installation.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off the
slit at the lower part of the pipe cover.
Rear direction

Pipe cover

Side direction

Front direction
Down direction

• The indoor/outdoor connecting pipes can be connected * Be sure to wear heavy work gloves while working.
in 4 directions.
Take off the knockout part of the pipe cover through
which pipes or wires will pass through the base plate.

15 15-EN
Super Digital Inverter

„ Optional Installation Parts Flaring


(Locally procured) 1. Cut the pipe with a pipe cutter.
Be sure to remove burrs that may cause a gas leak.
2. Insert a flare nut into the pipe, and then flare the pipe.
Parts name Q’ty
Use the flare nuts supplied with the air conditioner or
Refrigerant piping those for R410A.
A Liquid side: Ø9.5 mm One each Insert a flare nut into the pipe, and flare the pipe.
Gas side: Ø15.9 mm As the flaring sizes of R410A differ from those of
Pipe insulating material refrigerant R22, the flare tools newly manufactured for
B 1 R410A are recommended.
(polyethylene foam, 10 mm thick)
However, the conventional tools can be used by
C Putty, PVC tape One each adjusting the projection margin of the copper pipe.

Projection margin in flaring: B (Unit: mm)


„ Refrigerant Piping Connection
B

CAUTION

TAKE NOTE OF THESE 4 IMPORTANT POINTS BELOW


FOR PIPING WORK
1. Keep dust and moisture away from inside the connecting Rigid (Clutch type)
pipes.
2. Tightly connect the connection between pipes and the Conventional tool
Outer diam. of R410A tool used
unit. used
copper pipe
3. Evacuate the air in the connecting pipes using a R410A
VACUUM PUMP.
9.5 1.0 to 1.5
4. Check for gas leaks at connection points. 0 to 0.5
15.9

Piping connection Flaring diameter size: A (Unit: mm)

Liquid side A

Outer diameter Thickness


Ø9.5 mm 0.8 mm

Gas side Outer diam. of copper pipe A +0


–0.4
Outer diameter Thickness 9.5 13.2
Ø15.9 mm 1.0 mm 15.9 19.7

* In case of flaring for R410A with the conventional flare


tool, pull the tool out approx. 0.5 mm more than that for
R22 to adjust it to the specified flare size.
The copper pipe gauge is useful for adjusting the
projection margin size.

EN-16 16
Super Digital Inverter

„ Tightening of Connecting Part


CAUTION
1. Align the centers of the connecting pipes and fully tighten
the flare nut with your fingers. Then fix the nut with a 1. Do not put the crescent wrench on the cap or cover.
wrench as shown in the figure and tighten it with a torque The valve may break.
wrench. 2. If applying excessive torque, the nut may break
Half union or packed valve Flare nut
according to some installation conditions.
NO GOOD Cover

Externally Internally threaded


threaded side side

Fix with wrench. Tighten with torque wrench.

2. As shown in the figure, be sure to use two wrenches to Cap


loosen or tighten the flare nut of the valve on the gas
side. If you use a single crescent, the flare nut cannot be
tightened to the required tightening torque.
On the other hand, use a single crescent to loosen or
tighten the flare nut of the valve on the liquid side.

(Unit: N•m)
• After the installation work, be sure to check for gas leaks
Outer dia. of copper pipe Tightening torque of the pipe connections with nitrogen.
9.5 mm (diam.) 33 to 42 (3.3 to 4.2 kgf•m) • Pressure of R410A is higher than that of R22 (Approx.
1.6 times).
15.9 mm (diam.) 68 to 82 (6.8 to 8.2 kgf•m)
Therefore, using a torque wrench, tighten the flare pipe
connecting sections that connect the indoor/outdoor units
at the specified tightening torque.
Cover Incomplete connections may cause not only a gas leak,
but also trouble with the refrigeration cycle.
Do not apply refrigerating machine oil to the flared
Cap
surface.

Loosened Piping valve

Tightened

Flare nut

Valve at gas side

17 17-EN
Super Digital Inverter

„ Refrigerant Pipe Length

Single
Allowable pipe length (m) Height difference (Indoor-outdoor H) (m)
Total length L Indoor unit: Upper Outdoor unit: Lower
75 30 30

Pipe diameter (mm) Number of bent portions


Gas side Liquid side
10 or less
Ø15.9 Ø9.5

Simultaneous twin, triple


Allowable pipe length (m) Height difference (m)
Distributed Distributed Indoor-outdoor H
Total length
pipes pipes
System Model • 1+ 2
• 2 • 3– 2 Indoor-indoor
• 1+ 3 Indoor unit: Outdoor unit:
• 3 • 4– 2 ('h)
• 1+ 4 Upper Upper
• 4 • 4– 3
Maximum
Maximum Maximum
SP110 50 15 10 30 30 0.5
TWIN
SP140, SP160 50 15 10 30 30 0.5
TRIPLE SP160 only 50 15 10 30 30 0.5

Pipe diameter (mm)


Number of bent
System Model Main pipe Branching pipe
portions
Gas side Liquid side Gas side Liquid side
SP110 Ø15.9 Ø9.5 Ø12.7 Ø6.4 10 or less
TWIN
SP140, SP160 Ø15.9 Ø9.5 Ø15.9 Ø9.5 10 or less
TRIPLE SP160 only Ø15.9 Ø9.5 Ø12.7 Ø6.4 10 or less

Figure of Single Figure of Simultaneous twin Figure of Simultaneous triple


Indoor Unit
Indoor Unit Indoor Unit Indoor Unit
Indoor Unit
Indoor Unit

4
Distributor
Outdoor Unit Outdoor Unit Outdoor Unit 2 3 H
H

H
L

2 3

Distributor
1
1

EN-18 18
Super Digital Inverter

6 AIR PURGING

„ Airtight test Vacuum pump


Before starting an airtight test, further tighten the spindle
valves on the gas side and liquid side. As shown in the figure, connect the charge hose after the
Pressurize the pipe with nitrogen gas charged from the manifold valve is closed completely.
service port to the design pressure (4.15 MPa) to conduct L
the airtight test.
After the airtight test is completed, evacuate the nitrogen Attach the connecting port of the charge hose with a
gas. projection to push the valve core (setting pin) to the charge
port of the set.
L
„ Air Purge Open Handle Low fully.
With respect to the preservation of the terrestrial L
environment, adopt “Vacuum pump” to purge air (Evacuate
air in the connecting pipes) when installing the unit. Turn ON the vacuum pump. (*1)
• Do not discharge the refrigerant gas to the atmosphere to L
preserve the terrestrial environment.
Loosen the flare nut of the packed valve (Gas side) a little to
• Use a vacuum pump to discharge the air (nitrogen, etc.)
check that the air passes through. (*2)
that remains in the set. If air remains, the capacity may
decrease. L
For the vacuum pump, be sure to use one with a backflow Retighten the flare nut.
preventer so that the oil in the pump does not backflow into
L
the pipe of the air conditioner when the pump stops.
(If oil in the vacuum pump is put in an air conditioner Execute vacuuming until the compound pressure gauge
including R410A, it may cause trouble with the refrigeration indicates –101 kPa (–76 cmHg). (*1)
cycle.) L
Compound pressure gauge Pressure gauge Close Handle Low completely.

–101 kPa Gauge manifold valve L


(–76 cmHg) Turn OFF the vacuum pump.
Handle Low
Handle High
L
(Keep fully closed) Leave the vacuum pump as it is for 1 or 2 minutes, and
Charge hose
(For R410A only) Charge hose
check that the indicator of the compound pressure gauge
(For R410A only) does not return.
Vacuum pump L
adapter for counter-
flow prevention Open the valve stem or valve handle fully. (First, at liquid
(For R410A only) side, then gas side)
Vacuum L
pump
Charge port Disconnect the charge hose from the charge port.
(Valve core (Setting pin))
L
Packed valve at gas side Tighten the valve and caps of the charge port securely.
*1 Use the vacuum pump, vacuum pump adapter, and gauge
manifold correctly referring to the manuals supplied with each
tool before using them.
Check that the vacuum pump oil is filled up to the specified line
of the oil gauge.
*2 When air is not charged, check again whether the connecting
port of the discharge hose, which has a projection to push the
valve core, is firmly connected to the charge port.

19 19-EN
Super Digital Inverter

„ How to open the valve „ Replenishing refrigerant


Open or close the valve. This model is a 30 m chargeless type that does not need to
have its refrigerant replenished for refrigerant pipes up to
Liquid side 30 m. When a refrigerant pipe longer than 30 m is used, add
Open the valve with a 4 mm hexagon wrench. the specified amount of refrigerant.

Gas side
Refrigerant replenishing procedure
Valve unit
1. After vacuuming the refrigerant pipe, close the valves
and then charge the refrigerant while the air conditioner
is not working.
2. When the refrigerant cannot be charged to the specified
amount, charge the required amount of refrigerant from
the charge port of the valve on the gas side during
Using a minus screwdriver, cooling.
turn it counterclockwise by
90° until it hits the stopper.
(Full open)
Requirement for replenishing refrigerant
Charge port Replenish liquid refrigerant.
When gaseous refrigerant is replenished, the refrigerant
composition varies, which disables normal operation.
Flare nut

Adding additional refrigerant


31~75 m: L
Handle position
40 g × (L-30)
Closed completely Opened fully
• L: Pipe length
Stopper pin • To add additional refrigerant to twin and triple systems,
refer to the installation manual supplied with the
branching pipe (sold separately).
• The refrigerant need not be reduced for a 30 meter (or
less) refrigerant pipe.

Movable part of valve (Stem)


Main stopper

• While the valve is fully opened, after the screwdriver has


reached the stopper, do not apply torque exceeding
5 N•m. Applying excessive torque may damage the
valve.

Valve handling precautions


• Open the valve stem until it strikes the stopper.
It is unnecessary to apply further force.
• Securely tighten the cap with a torque wrench.

Cap tightening torque

33 to 42 N•m
Ø9.5 mm
(3.3 to 4.2 kgf•m)
Valve size
20 to 25 N•m
Ø15.9 mm
(2.0 to 2.5 kgf•m)
14 to 18 N•m
Charge port
(1.4 to 1.8 kgf•m)

EN-20 20
Super Digital Inverter

7 ELECTRICAL WORK
• Remove the panel, and you can see electric parts on the
WARNING front side.
• A metal pipe can be installed through the hole for wiring.
1. Using the specified wires, ensure that the wires are If the hole size does not fit the wiring pipe to be used, drill
connected, and fix wires securely so that the external the hole again to an appropriate size.
tension to the wires does not affect the connecting • Be sure to clamp the power wires and indoor/outdoor
part of the terminals. connecting wires with a banding band along the
Incomplete connection or fixation may cause a fire, etc. connecting pipe so that the wires do not touch the
2. Be sure to connect the earth wire. (grounding work) compressor or discharge pipe.
Incomplete grounding may lead to electric shock. (The compressor and the discharge pipe become hot.)
Do not connect ground wires to gas pipes, water pipes, Furthermore, be sure to secure these wires with the pipe
lightning rods or ground wires for telephone wires. valve fixing plate and cord clamps stored in the electric parts
3. The appliance shall be installed in accordance with box.
national wiring regulations.
Capacity shortages of the power circuit or an incomplete
installation may cause an electric shock or fire. Electric parts box

Panel

Pipe valve fixing


CAUTION plate

• Wrong wiring may cause a burn-out of some electrical


parts. Cord clamp

• Be sure to use the cord clamps attached to the product.


Pipe hole
• Do not damage or scratch the conductive core or inner
insulator of the power and inter-connecting wires when
peeling them.
• Use the power and Inter-connecting wires with specified
thicknesses, specified types and protective devices
required.

„ Wiring between Indoor Unit and Outdoor Unit


The dashed lines show on-site wiring.
Outdoor unit Indoor unit
Wired remote controller
L1
1 1
L2
Input power 2 2 Α
L3
380-415 V 3N~, 50Hz 3 3 Β
N

Leakage breaker

• Connect the indoor/outdoor connecting wires to the identical terminal numbers on the terminal block of each unit.
Incorrect connection may cause a failure.

For the air conditioner, connect a power wire with the following specifications.

Model (RAV-SP Type) 110AT8 140AT8 160AT8


380-415 V 3N~
Power supply
50 Hz
Maximum running current 16.4 A
Recommended field fuse 20 A
5 u 2.5 mm2 or more
Power wire*
(H07 RN-F or 60245 IEC 66)
4 u 1.5 mm2 or more
Indoor/outdoor connecting wires*
(H07 RN-F or 60245 IEC 66)
* Number of wire u wire size

21 21-EN
Super Digital Inverter

How to wire Wiring diagram


1. Connect the connecting wire to the terminal as identified * For details on the remote controller wiring/installation,
with their respective numbers on the terminal block of the refer to the Installation Manual enclosed with the remote
indoor and outdoor units. controller.
H07 RN-F or 60245 IEC 66 (1.5 mm2 or more)
2. When connecting the connecting wire to the outdoor unit Single system
terminal, prevent water from coming into the outdoor unit.
3. Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they do Remote controller
not touch any electrical or metal parts.
Remote controller wiring
4. For interconnecting wires, do not use a wire joined to
another on the way. A B
Indoor side
Use wires long enough to cover the entire length.
5. Wiring connections differ in conformance to EMC 1 2 3
standards, depending whether the system is single, Indoor/Outdoor connecting
wires
twin or triple. Connect wires according to respective
instructions. 1 2 3
Outdoor side

L1 L2 L3 N
CAUTION
Power supply
• An installation fuse must be used for the power supply
line of this air conditioner.
• Incorrect/incomplete wiring may lead to an electrical fire
or smoke. Simultaneous twin system
• Prepare an exclusive power supply for the air conditioner.
• This product can be connected to the mains power.
Fixed wire connections: Remote controller
A switch that disconnects all poles and has a contact Remote controller inter-unit wiring
separation of at least 3 mm must be incorporated in the
Remote controller
fixed wiring. wiring

Indoor side A B A B
Indoor
side
1 2 3 1 2 3
Indoor/Outdoor
connecting wires
Indoor power
1 2 3
inter-unit
Outdoor side
wiring
L1 L2 L3 N

Power supply

Simultaneous triple system (SP160 only)

Remote controller Remote controller


Remote controller inter-unit wiring inter-unit wiring

Remote controller
wiring

Indoor side A B A B A B
Indoor side Indoor side
1 2 3 1 2 3 1 2 3
Indoor/Outdoor
connecting wires
Indoor power Indoor power
1 2 3
Outdoor side inter-unit wiring inter-unit wiring

L1 L2 L3 N

Power supply

* Use 2-core shield wire (MVVS 0.5 to 2.0 mm² or more) for the remote controller wiring in the simultaneous twin and
simultaneous triple systems to prevent noise problems. Be sure to connect both ends of the shield wire to earth leads.
* Connect earth wires for each indoor unit in the simultaneous twin and simultaneous triple systems.

EN-22 22
Super Digital Inverter

Single system, Twin system, Triple system


Stripping length power cord and connecting wire
Indoor/outdoor Power supply wire
connecting wire
1 2 3 10 L1 L2 L3 N 10
10 10
1 2 3 Earth screw L1 L2 L3 N Earth screw

50 50
40 40

(mm) Earth line Earth line

Cord clamp Cord clamp Connecting wire Power supply wire

Clamp filter
(accessory)

Cord clamp Cord clamp

WARNING

Be sure to attach the provided clamp filter to the power supply wire in order to conform to EMC standards.

23 23-EN
Super Digital Inverter

8 EARTHING
Connect the earth line properly following applicable technical standards.
Connecting the earth line is essential to preventing electric shock and to reducing noise and electrical charges on the outdoor
unit surface due to the high-frequency wave generated by the frequency converter (inverter) in the outdoor unit.
If you touch the charged outdoor unit without an earth line, you may experience an electric shock.

9 FINISHING
After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, cover them with finishing tape and clamp them
to the wall with off-the-shelf support brackets or their equivalent.
Keep the power wires and indoor/outdoor connecting wires off the valve on the gas side or pipes that have no heat insulator.

10 TEST RUN
• Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during startup.
To protect the compressor, power is supplied from the 380-415 VAC input to the unit to preheat the compressor.
• Check the following before starting a test run:
• That all pipes are connected securely without leaks.
• That the valve is open.
If the compressor is operated with the valve closed, the outdoor unit will become overpressurized, which may damage the
compressor or other components.
If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may cause a burst
or injury.
• Operate the air conditioner in the correct procedure as specified in the Owner’s Manual.

11 ANNUAL MAINTENANCE
• For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/outdoor units are
strongly recommended.
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be cleaned at
least once every 3 months. This cleaning and maintenance should be carried out by a qualified service person.
Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and even compressor
failure.

12 AIR CONDITIONER OPERATING CONDITIONS


For proper performance, operate the air conditioner under the following temperature conditions:

Cooling operation Dry bulb temp. –15°C to 46°C


Heating operation Wet bulb temp. –20°C to 15°C

If air conditioner is used outside of the above conditions, safety protection may work.

EN-24 24
Super Digital Inverter

13 FUNCTIONS TO BE IMPLEMENTED LOCALLY


„ Handling Existing Pipe „ Recovering Refrigerant
When using the existing pipe, carefully check for the • Use refrigerant recovery switch SW801 on the P.C. board
following: of the outdoor unit to recover refrigerant when the indoor
• Wall thickness (within the specified range) or outdoor unit is moved.
• Scratches and dents • Before recovering the refrigerant in the existing system,
• Water, oil, dirt, or dust in the pipe perform a cooling operation for at least 30 minutes.
• Flare looseness and leakage from welds
• Deterioration of copper pipe and heat insulator
Procedure
1. Turn on the power of the air conditioner.
Cautions for using existing pipe 2. Select the FAN mode for indoor unit operation with the
• Do not reuse a flare nut to prevent gas leaks. remote controller.
Replace it with the supplied flare nut and then process it 3. Set SW804 on the P.C. board of the outdoor unit to all
to a flare. OFF, and then press SW801 for 1 second or more. The
• Blow nitrogen gas or use an appropriate means to keep air conditioner enters the forced cooling mode for up to
the inside of the pipe clean. If discolored oil or much 10 minutes.
residue is discharged, wash the pipe. Operate or handle the valve to recover refrigerant during
• Check welds, if any, on the pipe for gas leaks. this time period.
4. Upon completion of refrigerant recovery, close the valve
When the pipe corresponds to any of the following, do not and press SW801 for at least 1 second to stop operation.
use it. Install a new pipe instead. 5. Turn off the power.
• The pipe has been opened (disconnected from indoor
unit or outdoor unit) for a long period. ON ON

• The pipe has been connected to an outdoor unit that


1 2 3 4 1 2 3 4
does not use refrigerant R22, R410A or R407C. SW804 SW805
• The existing pipe must have a wall thickness equal to or ON ON

larger than the following thicknesses. 1 2 3 4 1 2 3 4

SW802 SW803 SW800 SW801 SW806


Reference outside
Wall thickness (mm)
diameter (mm)
Existing pipe Refrigerant
Ø9.5 0.8 switch SW802 recovery switch
SW801
Ø15.9 1.0
Ø19.0 1.0

• Do not use any pipe with a wall thickness less than these DANGER
thicknesses due to insufficient pressure capacity.
• When using a Ø19.1 mm gas pipe for the existing piping, Be careful of electric shock because the P.C. board has an
set bit 3 of SW802 (switch for existing pipe) on the P.C. electrical current running through it.
board of the outdoor unit to ON. In this case, the heating
performance may be reduced depending on the outside
air temperature and room temperature.

SW802
When shipped from factory When using existing pipe
ON ON

1 2 3 4 1 2 3 4

25 25-EN
Super Digital Inverter

14 TROUBLESHOOTING
You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to using the
check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote controller of the
indoor unit are described in the Installation Manual of the indoor unit.

Verifying current abnormal status


1. Check that DIP switch SW803 is set to OFF.
2. Jot down the states of LED800 to LED804. (Display mode 1)
3. Press SW800 for at least 1 second. The LED status changes to display mode 2.
4. Check the code whose display mode 1 equals the LED states jotted down and display mode 2 equals the current flashing
status of LED800 to LED804 from the following table to identify the cause.

Verifying an abnormal state in the past although the abnormal state no longer occurs
1. Set bit 1 of DIP switch SW803 to ON.
2. Jot down the states of LED800 to LED804. (Display mode 1)
3. Press SW800 for at least 1 second. The LED status changes to display mode 2.
4. Find an error whose display mode 1 equals the LED states jotted down and display mode 2 equals the current flashing
states of LED800 to LED804 from the following table to identify the error.
• An outside air temperature (TO) sensor error can be checked only while it occurs.

EN-26 26
Super Digital Inverter

Display mode 1 Display mode 2


No. Cause
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
1 Normal
2 Discharge (TD) sensor error
3 Heat exchanger (TE) sensor error
4 Heat exchanger (TL) sensor error
5 Outside air temperature (TO) sensor error
6 Suction (TS) sensor error
7 Heat sink (TH) sensor error
8 Outdoor temperature sensor (TE/TS) connection error
9 Outdoor EEPROM error
10 Compressor breakdown
11 Compressor lock
12 Current detection circuit error
13 Thermostat for compressor activated
14 Model data not set (on the service P.C. board)
15 MCU-MCU communication error
16 Discharge temperature error
17 Abnormal power (open phase detected or abnormal voltage)
18 Heat sink overheat
19 Gas leak detected
20 4-way valve reverse error
21 High pressure release operation
22 Outdoor fan motor error
23 Compressor driver short-circuit protection
24 Position detection circuit error in one-line display
25 High pressure SW error

( : OFF : ON : Flashing)
* The LEDs and DIP switches are
located on the lower left of the P.C. ON ON

board of the outdoor unit.


1 2 3 4 1 2 3 4

SW804 SW805 Enlarged view of


ON ON LEDs

1 2 3 4 1 2 3 4 D805
SW802 SW803 SW800 SW801 SW806 D804
D803
LED D802
D805
D804
D803
D801
D802
D801
D800
D800

27 27-EN
Super Digital Inverter

15 APPENDIX
Work instructions 6. When the existing air conditioner is removed after
The existing R22 and R407C piping can be reused for our refrigerant has been recovered.
digital inverter R410A product installations. Check if the oil is judged to be clearly different from
normal oil.
WARNING • The refrigerator oil is copper rust green in color:
There is the possibility that moisture has mixed with the
Confirming the existence of scratches or dents on the oil and rust has been generated inside the pipe.
existing pipes and confirming the reliability of the pipe • There is discolored oil, a large quantity of residue, or a
strength are conventionally referred to the local site. bad smell.
If the specified conditions can be cleared, it is possible • A large quantity of shiny metal dust or other wear
to update existing R22 and R407C pipes to those for residue can be seen in the refrigerant oil.
R410A models. 7. When the air conditioner has a history of the compressor
failing and being replaced.
• When discolored oil, a large quantity of residue, shiny
metal dust, or other wear residue or mixture of foreign
Basic conditions needed to reuse existing pipes matter is observed, trouble will occur.
Check and observe the presence of three conditions in the 8. When temporary installation and removal of the air
refrigerant piping works. conditioner are repeated such as when leased etc.
1. Dry (There is no moisture inside of the pipes.) 9. If the type of refrigerator oil of the existing air conditioner
2. Clean (There is no dust inside of the pipes.) is other than the following oil (Mineral oil), Suniso, Freol-
3. Tight (There are no refrigerant leaks.) S, MS (Synthetic oil), alkyl benzene (HAB, Barrel-freeze),
ester series, PVE only of ether series.
• The winding-insulation of the compressor may
Restrictions for use of existing pipes deteriorate.
In the following cases, the existing pipes should not be
reused as they are. Clean the existing pipes or exchange NOTE
them with new pipes.
1. When a scratch or dent is heavy, be sure to use new The above descriptions are results have been confirmed by
pipes for the refrigerant piping works. our company and represent our views on our air
2. When the existing pipe thickness is thinner than the conditioners, but do not guarantee the use of the existing
specified “Pipe diameter and thickness,” be sure to use pipes of air conditioners that have adopted R410A in other
new pipes for the refrigerant piping works. companies.
• The operating pressure of R410A is high (1.6 times
that of R22 and R407C). If there is a scratch or dent on
the pipe or a thinner pipe is used, the pressure strength Branching pipe for simultaneous operation system
may be inadequate, which may cause the pipe to break • In the concurrent twin system, when TOSHIBA has
in the worst case. specified that branching pipe is to be used, it can be
* Pipe diameter and thickness (mm) reused.
Pipe outer diameter Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0 Branching pipe model name:
RBC-TWP30E2, RBC-TWP50E2, RBC-TRP100E
R410A On the existing air conditioner for simultaneous operation
Thickness R22 0.8 0.8 0.8 1.0 1.0 system (twin, triple system), there are cases of branch
(R407C) pipes being used that have insufficient compressive
strength.
• In case the pipe diameter is Ø12.7 mm or less and the In such case, please change the piping to a branch pipe
thickness is less than 0.7 mm, be sure to use new for R410A.
pipes for the refrigerant piping works.
3. When the outdoor unit was left with the pipes Curing of pipes
disconnected, or the gas leaked from the pipes and the When removing and opening the indoor or outdoor unit for a
pipes were not repaired and refilled. long time, cure the pipes as follows:
• There is the possibility of rain water or air, including • Otherwise rust may be generated when moisture or
moisture, entering the pipe. foreign matter due to condensation enters the pipes.
4. When refrigerant cannot be recovered using a refrigerant • The rust cannot be removed by cleaning, and new pipes
recovery unit. are necessary.
• There is the possibility that a large quantity of dirty oil
or moisture remains inside the pipes. Placement location Term Curing manner
5. When a commercially available dryer is attached to the 1 month or more Pinching
existing pipes. Outdoors
• There is the possibility that copper green rust has been Less than 1 month
Pinching or taping
generated. Indoors Every time

EN-28 28
Super Digital Inverter

YES
Are there scratches or dents on the existing pipes? Existing pipes: Cannot be used.
• Use new pipes.
NO
NO
Is it possible to operate the existing air conditioner?

YES

• After the existing air conditioner is operated in cooling


mode for approx. 30 minutes or longer,* recover the
refrigerant.
• For cleaning the pipes and recovering oil Nitrogen gas pressure 0.5 MPa
• Refrigerant recovery: Pump down method

• Remove the existing air conditioner from the piping and


carry out flushing (nitrogen pressure 0.5 MPa) to remove
any remains inside of the pipe.
Note] In case of twin pipes, also be sure to flush the
branching pipe.

(If there is discharge of remains, it is judged that a


large quantity of remains are present.)
Was largely discolored oil or a large quantity
of remains discharged? (When the oil YES
Clean the pipes or use new pipes.
deteriorates, the color of the oil changes to a
muddy or black color.)

NO

Connect the indoor/outdoor units to the existing pipe.


• Use a flare nut attached to the main unit for the
indoor/outdoor units. (Do not use the flare nut of the
existing pipe.)
• Re-machine the flare machining size to size for R410A.

Piping necessary to change the flare nut/


machining size due to pipe compression
In case that a gas pipe Ø19 mm or bigger is used for the
outdoor unit of SP80 (3 HP): (Our R410A model 3 to 6 HP 1) Flare nut width: H
(mm)
gas pipe size is Ø15.9 mm) Copper pipe
outer Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0
 Turn the existing pipe switch on the cycle control PC diameter
board of the outdoor unit to ON side. At shipment from H For R410A 17 22 26 29 36
factory OFF  ON for existing pipe (Refer to the table Same as
For R22 Same as above 24 27
below.) (Be sure to set the contents in the table below above
in order to restrict the refrigerating cycle pressure of
the equipment in the pipe standard.) 2) Flare machining size: A
(mm)
Existing pipe SW Copper pipe
A outer Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0
Switch
diameter
Bit 3 of SW802  ON
For R410A 9.1 13.2 16.6 19.7 24.0
For R22 9.0 13.0 16.2 19.4 23.3

Becomes a little larger for R410A

• (Airtight test), Vacuum dry, Refrigerant charge, Gas leak Do not apply refrigerator oil to the flare surface.
check

Test run

29 29-EN
Super Digital Inverter

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol
Chemical Name of Gas R410A
Global Warming Potential (GWP) of Gas 1 975

CAUTION

1. Paste the enclosed refrigerant label adjacent to the charging and/or recovering location.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the included transparent
protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is never vented
to the atmosphere during installation, service or disposal. When any leakage of the contained fluorinated greenhouse gas is
detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging the gas,
shall comply under (EC) Regulation No. 842/2006 on certain fluorinated greenhouse gases and any relevant local
legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.

EN-30 30
Super Digital Inverter

IMPORTANT INFORMATION AND WARNING:


READ BEFORE INSTALLING THE UNIT. KEEP IN A SAFE PLACE. THE INFORMATION IN THIS BOOKLET IS NEEDED
FOR END OF LIFE, DISPOSAL OR REUSE OF THE UNIT.
• We are very sensitive to environment and welcome the 2002/96/EC Directive WEEE (Waste Electrical and Electronic Equipment).
• This product is compliant with EU directive 2002/96/EC. It must be collected separately after its use is completed, and cannot be disposed
of as unsorted municipal waste.
• The objectives of EU directive 2002/96/EC are to tackle the fast increasing waste stream of electrical and electronic equipment, increase
recycling of electric & electronic equipment ("EEE"), and to limit the total quantity of waste EEE ("WEEE") going to final disposal.
• The crossed-out wheeled bin symbol that is affixed to the product means that this product falls under the Directive.
• The user is responsible for returning the product to the appropriate collection facility, as specified by your municipality or the distributor.
In case of a new product installation, it may be possible to have the distributor pick up old WEEE directly.
• The producer, importer and distributor of the product are responsible for collection and treatment of waste, either directly or through a
collective system.
The list of our distributor in each country is shown below.
• In case of a violation of the Directive, sanctions are set in each country.
• We are in general following the "CECED interpretation," and consider the WEEE applicable to Portable units, Dehumidifiers, WRACs
(Window Room Air Conditioners), Split Systems up to 12 kW, plug in refrigerators and freezers.
• Nevertheless, there may be differences among member state laws. In case country laws exclude some products from WEEE scope, country
law must be followed, and WEEE obligations do not have to be followed for products that fall out of country low scope.
• This directive does not apply to products sold outside European Community. In case the product is sold outside the EU, WEEE obligations
do not have to be followed, while compliance with local regulations must be ensured.
• For additional information, please contact the municipal facility, the shop/dealer/installer that sold the product, or the producer.

n Country
o Name of Company responsible for WEEE.
n o n o n o
Austria AIRCOND, Klimaanlagen Ireland GT Phelan Unit 30 Southern UK Toshiba Carrier UK Ltd
Handelsgesellshcaft m.b.H Cross Business Park Bray Co Porsham Close, Belliver Ind.
Petesgasse 45, A-8010 Wicklow, Ireland Est. Plymouth, Devon, PL6
Graz Austria Italy Carrier SpA Via R. Sanzio, 9 7DB
Belgium DOLPHIN NV, Fotografi elaan 20058 Villasanta (Milano), Italy Czech AIRCOND, , Klimaanlagen
12, B-2610, Antwerpen Latvia Carrier OY Linnavuorentie 28A Republic Handelsgesellshcaft m.b.H
Belgium 00950 Helsinki, Finland Petersgasse 45, A-8010 Graz
Cyprus Carrier Hellas Airconditioning Lithuania Carrier OY Linnavuorenlie 28A Austria
S.A.- 4g Andersen street- 00950 Helsinki, Finland Slovakia AIRCOND, , Klimaanlagen
11525 Athens, Greece Luxembourg DOLPHIN NV Fotografi elaan Handelsgesellshcaft m.b.H
Denmark GIDEX A/S, Korshoj 10, 3600 12, B-2610, Antwerpen Petersgasse 45, A-8010 Graz
Frederikssund, Denmark Belgium Austria
Estonia Carrier OY Linnavuorentie 28A Malta CUTRICO Services Ltd, Slovenia AIRCOND, , Klimaanlagen
00950 Helsinki, Finland Cutrico Building Psala Street, Handelsgesellshcaft m.b.H,
Finland Carrier OY Linnavuorentie 28A Sta Venea HMR 16, Malta Petersgasse 45, A-8010 Graz
00950 Helsinki, Finland Norway Carrier AB - P.O.BOX 8946- Austria
France Carrier S.A. Route de Thil BP Arods Industrivag 32. S-402 73 Spain Carrier Espana S.L. - Paseo
49 01122 Montiuel Cedex Gothenburg, Sweden Castellana 36-38, 28046
France Poland Carrier Polska Sp. Z.o.o. Madrid
Germany Carrier GmbH & Co. KG Postepu 14 02-676 Warsaw Sweden Carrier AB - P.O.BOX 8946-
Edisonstrasse 2 85716 Poland Arods Industrivag 32 . S-402
Unterschleissheim Portugal Carrier Portugal - AR 73 Gothenburg
Greece Carrier Hellas Airconditioning Condicionado LDA Avenida do Hungary AIRCOND, Klimaanlagen
S.A.- 4g Andersen street- Forte, Nr. 3 Editi cio Suecia Handelsgesellshcaft m.b.H
11525 Athens, Greece l,Piso 1 Camaxide 2794-043 Petersgasse 45, A-8010 Graz
Holland INTERCOOL Technics BV Portugal Austria
Nikkelstraat 39, Postbus 76
2980 AB Ridderkerk
Netherlands

The manufacturer reserves the right to change any product specifications without notice.

31 31-EN
Super Digital Inverter

Declaration of Conformity

Manufacturer: Toshiba Carrier Corporation


336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN

Authorized Nick Ball


Representative/ Toshiba EMEA Engineering Director
TCF holder: Toshiba Carrier UK Ltd.
Porsham Close, Belliver Industrial Estate,
PLYMOUTH, Devon, PL6 7DB.
United Kingdom

Hereby declares that the machinery described below:

Generic Denomination: Air Conditioner

Model/type: RAV-SP1104AT8-E, RAV-SP1104AT8Z-E, RAV-SP1104AT8ZG-E,


RAV-SP1404AT8-E, RAV-SP1404AT8Z-E, RAV-SP1404AT8ZG-E,
RAV-SP1604AT8-E, RAV-SP1604AT8Z-E, RAV-SP1604AT8ZG-E,

RAV-SP1104AT8-TR, RAV-SP1104AT8Z-TR, RAV-SP1104AT8ZG-TR,


RAV-SP1404AT8-TR, RAV-SP1404AT8Z-TR, RAV-SP1404AT8ZG-TR,
RAV-SP1604AT8-TR, RAV-SP1604AT8Z-TR, RAV-SP1604AT8ZG-TR

Commercial name: Super Digital Inverter Series Air Conditioner

Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing
into national law

Complies with the provisions of the following harmonized standard:


EN 378-2: 2008

Note: This declaration becomes invalid if technical or operational modifi cations are introduced without the
manufacturer’s consent.

EN-32 32
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit Important
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas NOTE 2 :
leaking out, its concentration will not exceed a set The standards for minimum room volume are as follows.
limit. (1) No partition (shaded portion)
The refrigerant R410A which is used in the air conditioner
is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws to be imposed which protect
the ozone layer. However, since it contains more than air,
it poses the risk of suffocation if its concentration should
rise excessively. Suffocation from leakage of R410A is
almost non-existent. With the recent increase in the (2) When there is an effective opening with the adjacent
number of high concentration buildings, however, the room for ventilation of leaking refrigerant gas
installation of multi air conditioner systems is on the (opening without a door, or an opening 0.15% or
increase because of the need for effective use of floor larger than the respective floor spaces at the top or
space, individual control, energy conservation by bottom of the door).
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able Outdoor unit
to replenish a large amount of refrigerant compared with Refrigerant piping
conventional individual air conditioners. If a single unit of
Indoor unit
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event of
an emergency, measures can be made before injury can (3) If an indoor unit is installed in each partitioned room
occur). and the refrigerant piping is interconnected, the
In a room where the concentration may exceed the limit, smallest room of course becomes the object. But
create an opening with adjacent rooms, or install when a mechanical ventilation is installed interlocked
mechanical ventilation combined with a gas leak detection with a gas leakage detector in the smallest room
device. where the density limit is exceeded, the volume of the
The concentration is as given below. next smallest room becomes the object.
Refrigerant piping
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
d Concentration limit (kg/m3) Outdoor unit

Very
The concentration limit of R410A which is used in multi air small
room Indoor unit
conditioners is 0.3kg/m3.
Small Medium
room room Large room
NOTE 1 :
Mechanical ventilation device - Gas leak detector
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be
NOTE 3 :
as charged in each independent device.
The minimum indoor floor area compared with the amount
of refrigerant is roughly as follows:
Outdoor unit
e.g., charged
(When the ceiling is 2.7m high)
e.g.,
amount (10kg)
charged amount (15kg)
40
Range below the
2
m 35 density limit of
3
30 0.3 kg/m
(countermeasures
25 not needed)
Min. indoor floor area

20
Room A Room B Room C Room D Room E Room F
Range above the
Indoor unit 15 density limit of
0.3 kg/m3
10 (countermeasures
For the amount of charge in this example: needed)
5
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg. 0
10 20 30
The possible amount of leaked refrigerant gas in Total amount of refrigerant kg
rooms D, E and F is 15kg.

EH99870799

Das könnte Ihnen auch gefallen