Sie sind auf Seite 1von 4

Compensation of Current Transformer Saturation

Based on Improved ESPRIT Algorithm

Jun Guan, Zhiguo Hao, Wenzhe Chen Zhiyuan Liu, Xiaojun Yu


School of Electric Engineering Ningxia Electric Power Overhauling Company
Xi’an Jiaotong University Ningxia Electric Power Company
Xi’an, China Yinchuan, China
Email: guanjun@stu.xjtu.edu.cn

Abstract—Current transformer is prone to get into transient detected in the external fault, the traditional differential protec-
saturated during the fault in the power system. Operation per- tion will be locked for several cycles. During the several cycles,
formance of relay protection will be influenced severely due to if in-zone fault happens, the protection may refuse operation in
serious distortion in the secondary side. An improved ESPRIT time which may reduce the reliability of protection.
algorithm that can be applied in relay protection for anti-
saturation is presented in this paper. The improved ESPRIT can Much work has done on the CT saturation detection and
accurately obtain the frequency, magnitude and phase angle of compensation. Some research focus on the detection of CT
the fault current with unsaturated data segment of CTs’ distort- saturation, such as the harmonics calculation of secondary cur-
ed secondary current in a relatively short time window. In order rent [1], the time difference method [2], parameter identifica-
to reduce the calculation amount, singular value decomposition tion method [3]. These methods are employed to judge the CT
(SVD) is employed to determine the valid order of the signal. saturation. In order to obtain and utilize the unsaturated data,
Moreover, the improved ESPRIT algorithm could reduce the some work has done such as the wavelet transform [4], HHT
computational load with little influence on calculative result [5], the third difference [6] and the magnetic restrain principle
through the dimension reduction of singular value decomposi- [7].
tion. In order to obtain the magnitude and phase angle more ac-
curate, AR model and least square method are employed to im- Methods to obtain main information of primary current
prove the robustness of algorithm. Finally, the accuracy of the with distorted secondary current in saturation case include the
improved ESPRIT is verified by CT’s transient experiment data. compensation method [8], the linear neural network [9], the
The improved SEPRIT algorithm could be applied in the differ- least squares method [10], the Prony’s algorithm [11] as well as
ence protection to avoid the malfunction by CTs’ transient satu- matrix pencil algorithm [12]. The above methods may be not
ration and ensure the validity of protection. performed well in relay protection for they may use long time
window or large amount of calculation.
Keywords—current transformer; transient saturtion; improved
ESPRIT algorithm; AR model; short time window The ESPRIT algorithm uses a sum of decaying complex
exponentials to fit distorted signals. The ESPRIT algorithm [13,
I. INTRODUCTION 14] is presented to track the time-varying DOAs, identify the
parameter of synchronous generators and estimate harmonics in
The current transformer (CT) is fundamental equipment in the electrical power system. The improved ESPRIT algorithm
the relay protection and monitoring system of power system. can be employed to extract fundamental frequency component
It’s significant to transform the primary current in to a smaller accurately with shorter time window. It’s very effective to pro-
scale current accurately in the secondary side. Due to the non- pose an anti-saturation algorithm to obtain fault current.
linear excitation characteristics of iron core, current transform-
er is susceptible to get into transient saturated during the fault The layout of the paper is as follows. Section II briefly in-
in the power system. The main reasons of CT’s saturation in- troduces the principle of the basic ESPRIT algorithm. In sec-
clude the following aspects. The DC component in the fault tion III, the improved ESPRIT algorithm is introduced in three
current can cause single-direction excitation in the core of CTs. aspects. The accuracy of the improved ESPRIT is verified by
What’s more, the remanence in the core delays slowly which CT’s transient experimental data in section IV. Finally, the
can cause CT susceptible to get into transient saturation. How- conclusions and the significance of the algorithm for the differ-
ever, the ratio brake is employed to reduce the influence of the ential protection are discussed.
CT saturation. It’s difficult to balance the performance of anti-
saturation and sensitivity of differential protection. However, II. THE BASIC ESPRIT ALGORITHM
the severe CT saturation during external fault may cause action
The ESPRIT (estimation of signal parameters via rotational
current get into quick-break protection, then, the protection
invariance techniques) algorithm models can be expressed as
malfuction will happen. Moreover, when the CT saturation is
the sum of sinusoidal components and noise.
This work was supported in part by the National Natural Science Founda-
tion of China (51277142).

978-1-5090-2320-2/16/$31.00 ©2016 IEEE


p some severe saturation, it is only about 2.5ms. What’s more,
 x(n) = ¦ ai e jθi e( −δi + j 2π fi ) nTs + w(n)  (1) the basic ESPRIT may not obtain accurate amplitude and phase
i =1
angle due to the ignorance of noise. In order to apply the
It is assumed that gi = ai e jθi , zi = e( −δi + j 2π fi )Ts , it can be ESPRIT algorithm in CTs’ saturation, we have improved the
written in a unified exponential function form as follows algorithm to obtain accurate parameters in short time window.
p Moreover, the calculation amount has been reduced by obtain-
 x( n) = ¦ g i zin + w( n)  (2) ing effective order of signal and decreasing dimension of sin-
i =1 gular value decomposition.
where p is the order of the ESPRIT algorithm, w(n) is the
white noise. The N point measure value can be expressed as A. Improve the Robustness of Algorithm
[ x (n), x(n + 1)," , x(n + N − 1)]T 1) Determine valid order of signal
According to the data sequence, the Hankel sample matrix
ª 1 " 1 º ª g1 z1n º ª w(n) º can be written in matrix form as
« z » « n » «
" z p » « g 2 z2 » w(n + 1) »» ª x ( n) x(n + 1) " x(n + M − 1) º
=« +«
1
« # # # »« # » « # » « x(n + 1) x (n + 2) " x(n + M ) »»
« N −1
z " z N −1 » « n
» « »  X=«  (10)
¬« 1 p ¼» «¬ g p z p »¼ ¬ w(n + N − 1˅¼ « # # # »
« »
¬ x(n + L − 1) x (n + L) " x (n + N − 1) ¼
n
ª 1 " 1 º ª z1 0 0 0 º ª g1 º
 « z (3)
" z p »» «« 0 z2 " 0 »» «g » where L + M − 1 = N , L > p , M > p , for unsaturated seg-
=« « 2»
1
« # ment of CTs’ current signal with power frequency and decay
# # »«0 # % 0 » « # »
« N −1 N −1 » « » « » DC component, the valid order is far lower than L or M .
«¬ z1 " z p »¼ «¬ 0 0 0 z p »¼ «¬ g p »¼
where H is conjugate transpose, the column vectors of matrix
+[ w(n), w(n + 1)," , w(n + N − 1)]T Vs correspond to the p singular value which has the great
= Z N Φ n g + w ( n) magnitudes. Vs is signal subspace matrix, and the Vn is noise
= S ( n) + w ( n) subspace matrix.

ª S1 º ªthe first rowº For the improved ESPRIT algorithm, form a L × M sample
Let S = « =« » , we can obtain matrix according to (10), then analyze the sample matrix by
¬ the last row»¼ ¬ S2 ¼ SVD [15] and take the logarithm of singular values for they are
 S1 = Z N −1Φ g = Z1 g 
n
(4) great different in magnitudes.
 S2 = Z N −1Φ n +1 g = Z 2 g  (5) ªΣ 0 º ªVsH º
 X = U ΣV H = [U s , U n ] « s » « H »  (11)
Finally, rotational matrix can be expressed as ¬ 0 Σ n ¼ ¬Vn ¼
 Φ =Z1−1 Ζ 2  (6) 2) Total least square method
The characteristic roots zi (i = 1," , p ) can be obtained from According to (3)-(6), the signal subspace matrix Vs can be
rotational matrix. Equation (2) can be rewritten in matrix form written in similar matrix form as
 Zg = xˆ  (7) ª V1 º ªthe first row º
 Vs = « »=« » (12)
The least square solution of (7) is ¬the last row ¼ ¬ V2 ¼
 g = ( Z H Z ) −1 Z H xˆ  (8) Take measure noise and disturbance error E into account,
Finally, parameters of each component in the original sig- we can obtain
nal can be obtained as follows  V2 + E 2 = (V1 + E1 )Φ  (13)
­ai = gi In order to ensure the minimum E1 , E 2 F , form the matrix
° [V1 ,V2 ] and perform singular value decomposition.
°θ i = arctan[Im( gi ) Re( gi )]
 ®  (9)  [V ,V ]=U ΣV  (14)
°δ i = ln zi Ts 1 2

°f 
The matrix V can be divided into 4 p × p matrix, which
¯ i = angle(zi ) 2π Ts
can be expressed as
ªV V12 º
 V = « 11 
III. THE IMPROVED ESPRIT ALGORITHM   » (15)
¬V21 V22 ¼
The basic ESPRIT algorithm requires longer time window. According to the property of similar matrix, the characteris-
The high order noise in the signal and singular value decompo-
tic roots can be obtained from rotational matrix Φtls , which can
sition lead to large amount of calculation. However, during the
CTs’ transient saturation, unsaturated and saturated segment be calculated by
alternatively appear in one cycle. The length of unsaturated  Φtls = −V12V22−1  (16)
segment is determined by the degree of CTs’ saturation. In
B. Modification of Initial Sample Data D. Calculation process
In order to obtain more accurate amplitude and phase angle, Fig.1 shows the calculation process of improved ESPRIT
the estimated signal is transformed into an AR (Autoregressive) algorithm to obtain the power frequency parameters from fault
model. current.
p
 xˆ(n) = −¦ am x(n − m) + ε (n)  (17) obtain rotation matrix ψ by matrix Vs
m =1
p
where ε (n) = ¦ am e(n − m) , the principle to obtain the param- calculate the frequency and decay
m =0 factor of each signal componnets

eters is to guarantee the optimal approximation, namely to ob-


obtain the coefficient of AR model
N −1
tain the minimum value of the function E = ¦ ε (n)
2
. AR equation 1 + a1 z −1 + " + a p z − p = 0

set Hankel data matrix A L× M
n= p
modify data matrix according AR
model coefficient and characteristic roots form the characteris- p

tic equation 
SVD of sampling matrix A L× M model xˆ (n) = −¦ am xˆ ( n − m)
m =1

 1 + a1 z −1 + " + a p z − p = 0  (18)
obtain valid order and subspace matrix Vs calculate the amplitude and phase
The AR model coefficient ai (i = 1," , p) can be obtained. of each frequency components
Initial sample data can be modified as follows
end
­ x ( n) 1≤ n ≤ p
° p
 X ( n ) = ®  (19)
° − ¦ am x ( n − m ) p + 1 ≤ n ≤ N Fig. 1. Calculation process of improved ESPRIT algorithm
¯ m =1
C. Reduce Calculation Amount IV. EXPERIMENT AND RESULTS
For the improved ESPRIT algorithm, estimate the valid or- The CT transient saturation experiment tested on a 5P30
der of the main components by SVD. In addition, division of type current transformer. The transformation ratio was 1000:1.
sampling rate can also be employed to reduce calculation CTs’ secondary current was connected with a wave recorder,
amount. Moreover, the improved ESPRIT algorithm could and the sampling rate was 25kHz, namely 500 points per cycle.
reduce the computational load with little influence on calcula- Automatic reclose was applied in the primary system, and the
tive result through the dimension reduction of singular value reclosing interval was 600ms. The fault was set permanent. The
decomposition [16]. fault current was the superposition of power frequency and DC
It is assumed that V1 = gS , V2 = gΦ S , then define V12 as decay component. The parameters are listed in Table IAs
shown in Fig.2, the unsaturated data length of the first fault is
follows about 5ms. Due to the influence of remanence, the unsaturated
ªV H º ª SH º data length of the second fault is only about 2.5ms.
 V12 = « 1H » [V1 V2 ] = « H H » g H g [ S Φ S ]  (20)
¬V2 ¼ ¬S Φ ¼
The matrix V12 can be expressed as
ªV HV V1HV2 º
Current A

 V12 = « 1H 1 H » (21)
¬V2 V1 V2 V2 ¼
Then, perform partition decomposition for matrix V12 in (20) primary current
secondary current

ªv v12 º ª ΛΛH 0 º ª v11H H


v21 º
V12 = « 11 « »« H »
v22 »¼ ¬ 0
Time ms
¬ v21 0 ¼ ¬ v12H v22 ¼ (a) The first fault
  (22)
ª v ΛΛH v H v11ΛΛH v21
H
º
= « 11 H 11H H H »
¬ v21ΛΛ v12 v22 ΛΛ v22 ¼
where Λ =diag( λ1 , λ2 ," , λ p ) , the characteristic roots
Current A

λi (i = 1," , p) can be obtained from V12 , theoretical derivation


of above equations, we can obtain primary current
secondary current

 S −1Φ S = −v12 v22


−1
= v11− H v21
−H
= (V1HV1 ) −1V1HV2  (23)
Time ms
The dimension of SVD can be reduced by calculating the (b) The second fault
characteristic roots of matrix (V1HV1 ) −1V1HV2 . Fig. 2. Waveform of the fault current
The valid order of unsaturated current can be estimated as REFERENCES
3. In order to reduce calculation, divide the sample rate to the [1] Zhuihong Wang, Yuping Zheng and Jiali He, “A algorithm to
4/25 of the original one, namely 10 sample points correspond- distinguish current transformer's saturation by calculating the harmonics
ing to the 2.5ms time window for calculation. The improved ratio of branch current,” Proceeding of EPSA, vol. 12, no. 5, pp. 19-24,
ESPRIT calculation result is listed in Table IIIt can be known 2000.
from the result that the improved ESPRIT algorithm could [2] Yan Li, Deshu Chen and Zhe Zhang, “Research of the improved time
difference method to distinguish TA's saturation,” Relay, vol. 29, no. 11,
obtain parameters of signals accurately during short time win- pp. 1-4, 2001.
dow. [3] Xuyang Deng, Jiale Suonan and Guang Li, “ A novel current
transformer saturation detecting method based on parameter
TABLE I. PARAMETERS OF FAULT CURRENT identification,” Power System Protection and Control, vol. 18, no. 7, pp.
38-43, 2011.
Decaying
Amplitude Phase Decay [4] Yuning Cao, Yongli Li and Xinghua Zhang, “A new on-line criterion for
DC initial
50Hz(kA) 50Hz(rad) factor Current Transformer saturation based on Wavelet Transform,”
values(kA)
Automation of Electric Power System, vol. 10, no. 9, pp. 27-30, 2001.
first fault 46.29 0.2471 45.44 -10.80
[5] Maofa Gong, Wenhua Xia and Xiaoming Zhang, “New method to
second fault 43.43 0.5361 39.72 -12.64 identify transformer fault with anti-CT saturation based on HHT,”
Power System Protection and Control, vol. 22, no. 11, pp. 64-70, 2013.
[6] Y.C.Kang, S.H.Ok and S.H.Kang, “A CT Saturation Detection
Algorithm,” IEEE Trans. On Power Delivery, vol. 19, no. 1, pp. 78-85,
TABLE II. RESULTS OF THE IMPROVED ESPRIT ALGORITHM 2004.
[7] Zhiyuan Huang, Benteng He and Xuesong Zhang, “Research on the
Decaying
Time win- Amplitude Phase Decay practicality of Current Transformer saturation detection using the
DC initial
dow 50Hz(A) 50Hz(rad) factor magnetic restraint principle,” Automation of Electric Power System, vol.
values(A) 4, no. 15, pp. 75-79, 2006.
first fault
45.16 0.2623 45.07 -10.80 [8] Y.C.Kang, UJ Lim and S.H.Kang, “Compensation of the Distortion in
2.5ms
second fault the Secondary Current Caused by Saturation and Remanence in a CT,”
41.47 0.5556 39.34 -12.64 IEEE Transactions on Power Delivery, vol. 19, no. 4, pp. 1642-1649,
2.5ms
2004.
DC initial Decay
Time win- Amplitude Phase [9] Qingwu Gong and Zhijun Long, “ANN based algorithm to solve
values factor
dow error error(deg) transforming errorcaused by current transformer saturation,” Automation
error error
of Electric Power Systems, vol. 12, no. 6, pp. 34-36, 2001.
first fault
-2.4% 0.87 -0.9% 0 [10] Jiuping Pan, Khoi Vu and Yi Hu, “An Efficient Compensation
2.5ms
second fault Algorithm for Current Transformer Saturation Effects,” IEEE Trans. On
-4.5% 1.12 -0.96% 0 Power Delivery, vol. 19, no. 4, pp. 1623-1628, 2004.
2.5ms
[11] Hongchun Shu, Signal Processing in Electric Powerengineering and Its
Application, Beijing: Science Press, 2009, pp. 185-216.
[12] Jiale Suonan, Bin Wang, Li Wang, Jinfeng Sun and Min Xiao, “A Fast
V. CONCLUSION Phasor Calculation Algorithm in Power System,” Proceedings of the
CSEE, vol. 33, no. 1, pp. 123-129, 2013.
In this paper, an improved ESPRIT algorithm to obtain the [13] R.Roy, and T.Kailath, “ESPRIT-estimation of signal parameters via
fault current parameters in CTs’ saturation case was proposed. rotational invirance techniques,” IEEE Trans, vol. 37, no. 7, pp. 984-995,
AR model and least square method are employed to improve 1989.
the robustness of algorithm. Moreover, the improved ESPRIT [14] Hongqi Yu, “An improved ESPRIT algorithm without eigenvalues
algorithm could reduce the computational load with little influ- decomposition,” Signal Processing, vol. 24, no. 3, pp. 357-360, 2008.
ence on calculative result through the dimension reduction of [15] Xuezhi Zhao, Bangyan Ye and Tongjian Chen, “Principle of singularity
singular value decomposition and the estimation of the valid detection based on SVD and its application,” Journal of Vibration and
order of the main components by SVD. The performance of the Shock, vol. 27, no. 6, pp. 11-14, 2008.
algorithm was verified in the time window of 2.5ms. Errors of [16] Binshen Zhang, Le Yu and Jinghan He, “Inter-harmonic detection based
on fast TLS-ESPRIT,” Electric Power Automation Equipment, vol. 31,
the calculation results are in the limitation of relay protection. no. 2, pp. 2-360, 2008.
The improved SEPRIT algorithm could be applied in the dif-
ferential protection to avoid the malfunction by CTs’ transient
saturation and ensure the validity of protection.

Das könnte Ihnen auch gefallen