Sie sind auf Seite 1von 26

ANSI/I EEE C57.

91-1981
(Revision of ANSI C57.91-1974)

guide for loading


mineral-oil-immersed overhead a n d pad-mounted
d i st ribution tra nsf or me rs
rated 500 k V A and less with
6 5 "C or 5 5 "C average winding rise

July 31, 1981 SH08177

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
An American National Standard

IEEE Guide for Loading


Mineral-Oil-Immersed Overhead and Pad-Mounted
Distribution Transformers
Rated 500 kVA and Less with
65 O C or 55 "C Average Winding Rise
1. Scope [11 ANSI/IEEE C57.12.00-1980, General Re-
quirements for Liquid-Immersed Distribution,
Power, and Regulating Transformers.
1.1 This guide covers general recommenda- 121 ANWIEEE C57.12.90-1980, Test Code for
tions for loading 65 "C rise mineral-oil- Liquid-Immersed Distribution, Power, and
immersed overhead and pad-mounted distribu- Regulating Transformers and Guide for Short-
tion transformers described in American Circuit Testing of Distribution and Power
National Standards and rated 500 kVA and Transformers.
less. (For transformers rated 501 kVA and
larger, see ANSI/IEEE C57.92-1981, [31') [31 ANSMEEE C57.92-1981, Guide for Load-
Recommendations for 55 "C rise transformers ing Mineral-Oil-Immersed Power Transform-
are included in this guide because a substan- ers up to and Including 100 MVA with 55 "C
tial percentage of these transformers are still or 65 "C Winding Rise.
in service. [41 ANSI/IEEE C57.100-1972, American Na-
tional Standard Test Procedure for Thermal
1.2 Loading recommendations in tabular form Evaluation of Oil-Immersed Distribution Trans-
are contained in Section 5 of this guide. A formers
method to establish winding temperature and
loss of life by nomographs is also given in Sec-
tion 5.
3. General
1.3 The method used for the calculation of
the loading guide tables in Section 5 is given
in Section 6 of this guide.
3.1 Transformer Rated Output
1.4 The recommendations of this guide are 3.1.1 The terms rated output or rated load
based on winding hottest-spot calculations used in this guide refer to nameplate rating as
only. Other factors such as listed in 3.6.1 may defined in ANWIEEE C57.12.00-1980 111.
limit the permissible load to lower values. 3.1.2 The temperature rise on which the
rating of a transformer is based takes into
consideration the experience of the industry
2. References regarding:
(1) Insulation life a s affected by operating
temperature
When the following ANSI standards and (2) The ambient- temperature assumed to
guides referred to in this guide are superseded exist throughout the life of the transformer
by a revision approved by the American
National Standards Institute, the latest revi- 'The numbers in brackets correspond to the references
sion shall apply. listed in Section 2 of this guide.

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

3.1.3 The actual output which a trans- Table 1


former can deliver at any time in service Loading on Basis of Ambient Temperature
without undue deterioration of the insulation Other Than 30 "C
may be more or less than the nameplate kVA (for Quick Approximation, 0 "C-50 "C)
rating, depending upon the ambient tempera-
% of
ture and other attendant operating conditions. Rated kVA

3.2 Transformer Temperature Rises Decrease load for each "C


the ambient temperature exceeds 30 "C 1.5
3.2.1 65 "C Rise Transformers. Trans-
formers with an average winding rise of not Increase load for each "C
more than 65 "C and hottest-spot winding rise the ambient temperature is below 30°C 1.0
of not more than 80 "C will be referred to as
65 "C rise transformers.
3.2.2 55 "C Rise Transformers. Trans-
formers with a n average winding rise of not
more than 5 5 "C and hottest-spot winding rise
of not more than 65 "C will be referred to as Loading on the basis of ambient tempera-
55 "C rise transformers. ture with loads permitted by Table 1 will give
3.2.3 In the text of this guide values for approximately the same life expectancy as if
65 "C rise transformers will apvear first fol- transformers were operated at nameplate rat-
lowed by values for 55 "C rise transformers in ing and standard ambient temperatures over
parentheses, that is, 65 (55) "C. the same period.
Table 1 covers a range in ambients of 0 "C
3.3 Factors Affecting Transformer Cooling. to 5 0 ° C for cooling air. A check should be
In daily operation the ambient temperature, made with the manufacturer before loading on
the altitude, and the transformer's exterior the basis of cooling air ambient less than 0 "C
finish may be different than is assumed for or greater than 50 "C.
the basis of rating. These departures may Since ambient temperature is a n important
influence the thermal performance of a trans- factor in determining the load capability of a
former as follows: transformer, it should be controlled for indoor
3.3.1 Influence of Ambient Temperature installations by adequate ventilation and
on Loading. The ambient temperature is an should always be considered in outdoor instal-
important factor in determining the load capa- lations.
bility of a transformer since the temperature 3.3.2 Approximating Ambient Tempera-
rise for any load must be added to the ambient ture. It is often necessary to predict the load
to determine operating temperature. Wher- which a transformer can safely carry at some
ever the actual ambient temperature can be future time when the ambient temperature is
measured, such ambient should be used in unknown. The probable ambient temperature
determination of winding hottest-spot tem- for any month may be approximated as follows
perature and the load capability of the trans- from reports prepared by the Weather Bureau
former. of the US Department of Commerce which are
Average ambient temperatures should cover available for various sections of the country:
periods of time not exceeding 24 h with max-
imum temperatures not more than 10 "C (1) Average Temperature. Use average daily
greater than average temperatures for air. temperature for the month involved, averaged
Table 1 gives the increase or decrease in rated over a number of years
loads for other than average daily ambients of (2) Average of Maximum Daily Temperatures.
30 "C for air. It is recommended that the 5 "C Use average of the maximum daily tempera-
margin described in 3.3.2 be used when apply- ture for month involved, averaged over several
ing the factors from Table 1. It should be years
pointed out t h a t the increase or decrease
obtained from Table 1 is more conservative These ambients should be used a s follows: for
than the corresponding calculated values. loads with normal life expectancy, use item Cl!
Table 1 is used for quick approximations. a s the ambient for the month involved; for

10

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

short-time loads with moderate sacrifice of life cooling medium, the average of the maximum
expectancy, use item (2) for the month involved. and minimum daily temperature may be used.
During any one day the average or max- The value obtained in this manner is usually
imum temperatures may exceed the values slightly higher than the true daily average by
derived from (1) or (2) above. To be conserva- not more than 0.3 "C.
tive, it is recommended t h a t these tempera- 3.3.4 Influence of Exterior Finish on
tures be increased by 5 "C since aging at Loading. The thermal radiation characteris-
higher than average temperature is not fully tic of a transformer is affected by its external
offset by decreased aging a t lower than aver- finish. Temperature limits and tests are based
age temperature. With this margin the upon the use of a pigment paint finish, which
approximated temperature will not be ex- is a standard finish for transformer tanks and
ceeded on more than a few days per month radiators.
and, where it is exceeded, the additional loss Metallic flake paints, such as aluminum,
of life will not be serious. zinc, etc have radiation properties which
3.3.3 Influence of Altitude on Loading. increase the temperature rise of transformers
The decreased air density due to high altitude except in direct sunlight. Particular note
increases the temperature rise of transformers should be made of a coating's radiation proper-
since they are dependent upon air for the dis- ties when a transformer is refinished in the
sipation of heat losses. field.
3.3.3.1 Operation at Rated LVA. Trans-
formers may be operated at rated kVA a t alti- 3.4 Aging of Insulation
tudes greater than 1000 m (3300 ft) without 3.4.1 Aging or deterioration of insulation
exceeding temperature limits provided the is a function of temperature and the time it is
average temperature of the cooling air does a t this temperature. Since, in most apparatus,
not exceed the values of Table 2 for the the temperature distribution is not uniform,
respective altitudes. t h a t part which is operating at the highest
3.3.3.2 Operation at Less than Rated temperature will ordinarily undergo the
kVA. Transformers may be operated a t alti- greatest deterioration. Therefore, in aging
tudes greater than 1000 m (3300 ft) without studies it is usual to consider the aging effects
exceeding the normal temperature limits pro- produced by the highest (hottest-spot) tem-
vided the load to be carried is reduced below perature.
nameplate rating by 0.4% for each 100 m (330 3.4.2 Much of the fundamental insulation
ft) t h a t the altitude is above 1000 m (3300 ft). aging data at different temperatures has been
The manufacturer should be consulted to based on laboratory and model tests in which
ascertain what influence the application of the decrease in mechanical and electrical
fan cooling will have on the rating a t various strength has been measured. This has been
altitudes. supplemented by a series of functional life
3.3.3.3 Recommended Calculation of expectancy tests made under controlled condi-
Average Temperature. I t is recommended tions on commercially produced distribution
that the average temperature of the cooling transformers, under the auspices of the IEEE
air be calculated by averaging 24 consecutive Transformers Committee. For test procedures
hourly readings. When the outdoor air is the see ANSI/IEEE C57.100-1972 [41.
Data from these tests, and judgment, has
resulted in the life expectancy curves shown
in Fig 1. This guide adopts these curves as the
Table 2 normal life expectancy for distribution trans-
Maximum Allowable Average formers with average winding temperature
Temperature of Cooling Air to rises of 65 "C and 55 "C. The loss of life data
Permit Carrying Rated kVA given in this guide are derived from these nor-
mal life expectancy curves. I t is the best dis-
1000 m 2000 m 3000 m 4000 m tribution transformer life information
(3300 ft) (6600ft) (9900 ft) (13200 ft) currently available.
3.4.3 This guide assumes the insulation
~ ~~~~

30 "C 28 "C 25 "C 23 "C


deterioration relationship with respect to tem-

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSMEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDOVERHEAD

500 000 50

200 000 20
C
I00 000
IO

50000 5
0
I

> 20000 2
0
z
2 10000
IIY
v)

a. a
W
2 5000 z
W
k
-1
J 2000
a
2
U
0 1000
z 0.I

500

200

IO0
300 260 220 180 140 120 I00 80
HOTTEST-SPOT TEMPERATURE IN DEGREES CELSIUS
(RECIPROCAL OF ABSOLUTE TEMPERATURE SCALE)

Fig 1
Life Expectancy Curve

perature and time follows a n adaptation of the For the 65 "C insulation systems
Arrhenius reaction rate theory which states B 6328.8
A = -11.269 =
t h a t the logarithm of insulation life is a func-
tion of the reciprocal of absolute temperature:
For the 55 "C insulation systems
B
Log,, life(h)=A + -
T
(Eq 1) A = -11.968 B = 6328.8
3.5 Transformer Life Expectancy
3.5.1 Transformer life expectancy a t any
where operating temperature is not accurately
known, but the information given regarding
T = absolute temperature in loss of insulation life at elevated temperatures
degrees kelvin, = Oh, 273 + is considered to be conservative and the best
(as shown in Eq 14) where t h a t can be produced from present knowledge
O h , equals the temperature of the subject. The effects of temperature on
a t the hottest-spot insulation life are being investigated continu-
ously, and new data may affect future revi-
A and B = constants for appropriate sions of this guide. The word conservative as
life expectancy curve used above is used in the sense that the

12

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANWIEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

expected loss of insulation life for a single voltage. The indicated allowances have there-
overload cycle will not be greater than the fore been obtained from tests made in the lab-
amount stated. oratory.
3.5.2 Because the cumulative effects of (3) The hottest-spot temperature a t rated
temperature and time in causing deterioration load is the sum of the average winding tem-
of transformer insulation are not thoroughly perature and a hottest-spot allowance, usually
established, it is not possible to predict with 15(10)"C. For mineral oil-immersed trans-
any great degree of accuracy the length of life formers operating continuously under the fore-
of a transformer even under constant or going conditions this temperature has been
closely controlled conditions, much less under limited to a maximum of llO(95)"C.
widely varying service conditions. (4) The normal life expectancy at a continu-
Deterioration of insulation is generally ous hottest-spot temperature of llO(9.5) "C is
characterized by a reduction in mechanical 20 years as shown in Fig 1.
strength and in dielectric strength, but these 3.5.5 The many variables and, particularly,
characteristics may not necessarily be directly the many varying conditions of load and
related. In some cases, insulation in a charred ambient to which a transformer can be sub-
condition will have sufficient insulating quali- jected in service make it impossible to give
ties to withstand normal operating electrical definite rules for the loading of transformers.
and mechanical stresses. A transformer hav- I t is possible to give only suggested loadings
ing insulation in this condition may continue under specified conditions, and look to the
in service for many months or even years, if user to make the best use of this information
undisturbed. On the other hand, any unusual for his particular problem.
movement of the conductors, such as may be
caused by expansion of the conductors due to
heating resulting from a heavy overload or to 3.6 Limitations
large electromagnetic forces resulting from 3.6.1 It must be recognized that when
short circuit, may disturb the mechanically loading transformers above nameplate rating,
weak insulation such t h a t turn-to-turn or other limitations may be encountered. Among
layer-to-layer failure will result. these limitations are: oil expansion, pressure
3.5.3 The recommendations of this guide in sealed units, and the thermal capability of
are based upon the life expectancy curves of bushings, leads, tap changers or associated
Fig 1 which relate to the insulation system, equipment such a s cables, reactors, circuit
but do not account for such factors as breakers, disconnecting switches, and current
deterioration of gaskets, rusting of tanks, etc. transformers. Any of these items may limit
which are induced by exposure to the elements the loading and manufacturers should, there-
of the weather in normal operations. fore, be consulted before loading transformers
3.5.4 Normal Life Expectancy. above nameplate rating.
(1) The basic loading of a transformer for Operation at hottest-spot temperatures
normal life expectancy is continuous loading above 140 "C may cause gassing in the solid
at rated output when operated under normal insulation and the oil. Gassing may produce a
service conditions a s indicated in 4.1.6(1) and potential risk to the dielectric strength
4.1.6(2) of ANSIIIEEE C57.12.00-1980 [ll.I t is integrity of the transformer and this risk
assumed that operation under these conditions should be considered when the guide is
is equivalent to operation in a constant 30 "C applied.
ambient. Normal life expectancy will result 3.6.2 Transformers are sometimes installed
from operating continuously with hottest-spot in subsurface manholes and vaults of minimum
conductor temperature of llO(95) "C or an size with natural ventilation through roof grat-
equivalent cycle. ings. This type of installation results in a
(2) The hottest-spot conductor temperature higher ambient temperature than the outdoor
is the principal factor in determining life due air. The amount of increase depends on the
to loading. This temperature cannot be design of the manholes and vaults, net opening
directly measured on commercial designs area of the roof gratings, and the adjacent sub-
because of the hazard in placing any tempera- surface structures. Therefore, the increase in
ture detector at the proper location because of effective ambient temperature for expected

13

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

transformer losses must be determined before 2.0


loading limitations can be estimated. a
3.6.3 The heating effects of loading a 3 1.8
0
transformer and of solar radiation, each may 1.6
result in an enclosure surface temperature a
high enough to present a hazard to personnel t
z
v) 1.4
who might come in contact with the enclosure W

surface where unlimited access to the trans-


r
+
1.2
former exists (such as certain pad-mounted 1.0
-
units). 0 0 20 30 40 50 60 7 0 80 90
1
MAXIMUM TOP-OIL
TEMPERATURE IN DEGREES CELSIUS

4. Loading of Transformers
Fig 2
4.1 Loading f o r Normal Life Expectancy Approximate Continuous Loading for
U n d e r Specific Conditions. When the Normal Life Expectancy Based on
ambient temperature is below the 30 "C Maximum Top-Oil T e m p e r a t u r e
ambient used to establish the transformers'
rating, or when the transformers' temperature
rises a t nameplate rated load, a s determined increased above rated kVA by 1.5%.The 5 "C
by test, are less than the normal limiting margin is taken to provide a tolerance in the
values, some additional load beyond nameplate measurement of temperature rise. The load
rating is possible within normal life expecta- value thus obtained is the kVA load which the
tions. transformer can carry a t 6 5 6 5 ) "C rise. Since
4.1.1 Loading b y Oil Temperature. Oil this may indicate a load capability beyond
temperature alone should not be used as a t h a t comtemplated by the designer, the limita-
guide for loading transformers. The hottest- tions given in 3.6.1 should be checked before
spot winding rise over top-oil temperature a t taking full advantage of this increase.
full load should be determined from the fac- The above is not applicable to all transform-
tory tests and Eq 7 and should then be ers; some transformers are designed to have
corrected for the actual load carried, using Eq the difference between the hottest-spot and
5 or Fig 10. This hottest-spot rise over top-oil, average winding temperatures greater than
subtracted from llO(95) "C, will give the max- the 15(10) "C allowance. This will result in an
imum permissable top-oil temperature for nor- average winding temperature rise of less than
mal life expectancy. It should be recognized 65(55) "C, while the hottest-spot winding rise
that, due to the thermal lag in the oil tem- may be a t the 80(65) "C limiting value. This
perature rise, time is required for a trans- condition may exist in transformers with large
former to reach a stable temperature for any differences between top and bottom oil tem-
change in load. Therefore, higher peak loads peratures.
may be carried for a short duration. This is The manufacturer should be consulted for
reflected in the loading tables. information on the hottest-spot allowances
If the transformer characteristics are not used for these designs.
accurately known, maximum top-oil tempera- 4.1.3 Loading on Basis of Short-Time
tures derived from Fig 2 may be used a s a n Loads Above Rating. Transformers may be
approximate guide. Figure 2 is based on a operated above llO(95) "C average continuous
difference between hottest-spot temperature hottest-spot temperature for short periods pro-
and top-oil temperature of 25(20)"C a t rated vided they are operated for much longer
load. periods a t temperatures below llO(95) "C. This
4.1.2 Continuous Loading Based on Aver- is due to the fact that thermal aging is a
age Winding Test T e m p e r a t u r e Rise. For cumulative process. This permits loads above
each "C in excess of 5 "C that the average the rating to be safely carried under specified
winding test temperature rise is below conditions without encroaching upon the nor-
65(55) "C, the transformer load may be mal life expectancy of the transformer.

14

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

10.00
8.00
6.00

4.00

2.00
c
2
W
U
E 1.00
't 0.80
W
& 0.60
-I

& 0.40
0.30
s 0.20

0.10
0.08
0.06

n
-.-n4.
95 110 I 2 0 130 140 I50 I60 170 180 190 200
HOTTEST-SPOT TEMPERATURE IN DEGREES CELSIUS

Time '% Loss of Life*


(h) 0.05 0.10 0.25 0.50 1.00 2.00 4.00

'h 171 180 193 *


U*
1 161 171 183 193 =*
*
2 153 161 174 183 193 *
U*
4 144 153 164 174 183 193 m*
*
8 136 144 155 164 174 183 193
16 128 136 147 155 164 174 183
24 124 131 142 150 159 168 178

NOTE: For explanation of limitations and accuracy, see 5.3.4.

* Calculated for one occurrence on the assumption t h a t the hottest spot temperature remains constant for the specified
time duration. Tables 5-7 list more accurate loss of life determinations in which the time-temperature response of the
transformer is taken into account. Refer to Section 6 for the time integration method used.
** Maximum permissible value is 200 "C, the underlined values permit interpolation.

Fig 3
Maximum Hottest-Spot Conductor
T e m p e r a t u r e in "C (65 "C Rise)

4.2 Short-Time Loading w i t h Moderate tinuous operation a t rated load, the insulation
Sacrifice of Life Expectancy (Operation deteriorates a t a faster rate than normal. The
above llO(95) "C Hottest-Spot Tempera- rate of deterioration is a function of time and
ture. temperature and is commonly expressed a s a
percentage loss of life per incident. Charts and
(1) When for any given period of time the tables showing relative loss of life for various
aging effect of one overload cycle or the cumu- combinations of time and temperature are
lative aging effect of a number of overload given in Fig 3 for 65 "C rise and Fig 4 for
cycles is greater than the aging effect of con- 55 "C rise transformers.

15

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

SIUS

Time % Loss of Life*


(h) 0.05 0.10 0.25 0.50 1.00 2.00 4.00

vi 150 159 171 180 -


190**
1 142 150 161 171 180 m**
2 134 142 153 161 171 180 m**
4 126 134 144 153 161 171 180
8 118 126 136 144 153 161 171
16 111 118 128 136 144 153 161
24 107 114 124 131 139 148 156

NOTE: For explanation of limitations and accuracy, see 5.3.4.

* Calculated for one occurrence on the assumption t h a t the hottest spot temperature remains constant for the specified
time duration. Tables 8-10 list more accurate loss of life determinations in which the time-temperature response of the
transformer is taken into account. Refer to Section 6 for the time integration method used.
** Maximum permissible value is 180 "C, the underlined values permit interpolation.

Fig 4
Maximum Hottest-Spot Conductor
T e m p e r a t u r e in "C (55 "C Rise)

(2) It should be clearly understood that, life expectancy of transformer insulation.


while the insulation aging rate information is (3) The uncertainty of service conditions
considered to be conservative and helpful in and the wide range in ratings covered are rea-
estimating the relative loss of life due to loads sons why this loading guide is conservative in
above nameplate rating under various condi- its suggested loading schedule. Some of the
tions, this information is not intended to fur- variables are: wide differences in ambient
nish the sole basis for calculating the normal temperature between localities; differences in

16

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

elevation; restricted air circulation caused by Table 3


buildings, fire walls, etc; previous emergency Assumed Transformer Characteristics
loading history which may not be known to at Rated Load
the operator; and variations in design charac- (Based on 30 "C Ambient)
teristics from those in Table 3. As a guide,
65 "C 55 "C
many users consider a n average loss of life of Rise Rise
1% per year or 5% in any one emergency
Maximum allowed hottest-spot conductor
operation to be reasonable. temperature rise above ambient, "C 80 65
Hottest-spot conductor temperature
rise (above ambient), "C 75 65
Top-oil temperature rise (above
5. Determination of Temperature ambient), "C 55 45
and Loss of Life Top-oil time constant, h 3.5 3.0
Hottest-spot conductor time constant,
5.1 General. It is possible to study the h 0.0834 0.0834
effects of a particular load cycle on a trans- Ratio of load loss a t rated load to
former by dividing the cycle in a large number no-load loss 2.7 3.0
of short intervals and to study each interval n' 0.8 0.8
separately. Further details on this type of cal-
culation are presented in Section 6. *n is the exponential power of loss versus temperature rise
The calculation approach, particularly use-
ful when the transformer characteristics are
known, is time-consuming when the calcula-
tions are to be made by hand. The effort will
be much reduced when the shape of the load 5.2.1 Method of Converting Actual to
curve can be simplified to a constant load with Equivalent Load Cycle. A transformer sup-
a superimposed peak load. A method to plying a fluctuating load generates a fluctuat-
achieve this result is given in 5.2. ing loss, the effect of which is about the same
Whenever possible, hottest-spot and top-oil as t h a t of a n intermediate load held constant
temperature rises obtained from factory tem- for the same period of time. This is due to the
perature tests should be used in determining a heat storage characteristics of the materials
transformer's load capability or when calculat- in the transformer. A constant load which
ing winding temperatures for loads above generates losses at the same rate as the aver-
nameplate rating. age rate caused by a fluctuating load is a n
When the transformer characteristics are equivalent load from a temperature stand-
not known, typical values have to be assumed. point. Equivalent load for any part of a daily
Characteristic values used in the following load cycle may be expressed by Eq 2.
sections are given in Table 3. Tables 5-10
present in tabular form the peak loads of a Equivalent load or rms value =
number of simplified load cycles and resulting
loss of life. Nomographs to determine loss of
life during various load cycles are given in 5.4.

5.2 Load Cycles. Transformers usually oper-


ate on a load cycle which repeats every 24 h. (Eq 2)
A typical load cycle such as shown by the solid
line in Fig 5 consists of load fluctuations where
throughout the day.
=
There is usually one period in the daily load L,, L,, L3, . * * various load steps in %, per
cycle when the load builds up to a consider- unit, or in actual kVA or
ably greater value than any reached at other current, and,
times. Generally, the maximum value or peak
load is not reached and passed suddenly, but t,, t,, ... = respective durations of
builds up and falls off gradually. these loads

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSMEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

Fig 5
Actual Load Cycle a n d
Equivalent Load Cycle

5.2.2 Equivalent peak load for the usual 5.3 Tables to Determine Peak Loads for
load cycle is the rms load obtained by Eq 2 for Normal Life Expectancy and Moderate
the limited period over which the major part Sacrifice of Life Expectancy. Calculations
of the actual irregular peak seems to exist. have been made to establish peak load values
The estimated duration of the peak has con- which will result in normal life expectancy
siderable influence over the rms peak value. If and also peak load values which will result in
the duration is overestimated, the rms peak discrete steps of greater than normal loss of
value may be considerably below the max- life. Results are shown in Tables 5-10; the
imum peak demand. To guard against method used is described in 6.5.
overheating due to high, brief overloads dur- 5.3.1 Transformer Characteristics. The
ing the peak overload, the rms value for the calculations were made for transformers with
peak load period should not be less than 90% characteristics as given in Table 4.
of the integrated half-hour maximum demand. 5.3.2 Table Load Cycles. The calculations
5.2.3 Equivalent continuous load is the are based on a load cycle similar to the cycle
rms load obtained by Eq 2 over a chosen shown in Fig 6. The continuous load portion
period of the day. Experience indicates that was assumed to be 50%, 75%, and 90% respec-
quite satisfactory results are obtained by con- tively and peak load durations of l h , 2h, 4h,
sidering the 12 h periods preceding and follow- 8h, and 24 h were used.
ing the peak and by selecting the larger of the 5.3.3 Normal Life Expectancy. The nor-
two rms values so produced. Time intervals (t) mal life expectancy a t a continuous hottest-
of 1 h are suggested as a further simplifica- spot temperature of llO(95) "C is 20 years as
tion of the equation which for a 12 h period determined from Fig 1. The normal life expec-
becomes Eq 3. tancy corresponds to a 0.0137% loss of life per
day.
5.3.4 T e m p e r a t u r e and Load Limits.
Equivalent continuous load =
Temperature and load limits used in preparing
oadLp+Lg+- - - '" Tables 5-10 are given in Table 4. Loading in
excess of 250% of nameplate rating should be
avoided except under emergency conditions.
(Eq 3)

where:
L,, L,, ... L,, = average load by inspection Table 4
for each 1 h interval of Limiting Values of Temperature a n d Load
the 12 h period adjacent Incorporated in Tables 5- 10
to the peak load
65 "C 55 "C
The dashed line in Fig 5 shows the Top-oil temperature 120 "C 110 "C
equivalent load cycle const~ucted from the Hottest-spot conductor temperature ZOO oc 180 "C
Short-time loading ('h hour or less) 300% 300%
actual load cycle.

18

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSMEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

2 HOURS
50% CONTINUOUS LOAD

0' I I I I
6 12 I8 24 HOURS

Fig 6
Equivalent Load Cycle

5.4 Determination of Temperatures and tally and read ultimate oil rise (99 "C) a t left
Loss of Life by Nomograph Method. Fig- of graph.
ures 7, 8, 9, and 10 can be used to determine (3) On Fig 8, set a straight edge a t the ini-
the winding hottest-spot temperature for tial oil temperature rise on left scale (21 "C)
transformers with characteristics different and a t the ultimate top-oil rise on right scale
from Table 3. (99 "Cl. A t the intersection of the line so
To illustrate the use of the nomographs, the determined and the vertical line through the
hottest-spot winding temperature and insula- intersection of line for the desired time (2 h)
tion aging of a 65 "C rise transformer nor- and time constant (3.5 h), determine the top-
mally loaded to 33% of the nameplate rating oil temperature rise (54 "C) a t the end of the
and with a 2 h load of 167% will be worked assumed time (2 h).
out. 5.4.2 Hottest-Spot Conductor Rise Over
Assumed transformer characteristics at Top-Oil Temperature. On Fig 10, start a t
nameplate rating and 30 "C ambient are: percent load (167%) on the horizontal scale
and go up the curve for full load hottest-spot
Ratio of losses (R) 3.2 conductor rise (30 "C). Go to the left and read
hottest-spot conductor rise (68 "C) for the per-
Full load top-oil rise 50 "C cent load in question.
5.4.3 Hottest-Spot Conductor Tempera-
Time constant 3.5 h ture. Obtain the hottest-spot conductor tem-
perature by adding ambient temperature (30
Hot tes t-spot conductor "C), top-oil rise (54 "C), and hottest-spot rise
rise over oil 30 "C over top-oil temperature (68 "C), giving 152
"C.
5.4.1 Top-Oil Rise Determination. 5.4.4 Percent Loss of Life. From Fig 3,
(1) On Fig 7, start at initial percent kVA obtain the loss of life (0.045%)for the hottest-
(33%)and move horizontally to the curve of spot temperature (152 "C) and the duration of
ratio of losses (R = 3.2). Go down to the line the load (2 h). In using this simplified pro-
for full-load oil rise (50 "C). Move horizontally cedure, i t is assumed that the hottest-spot
to read initial oil rise (21 "C). temperature is constant a t its final value
(2) Determine the ultimate top-oil tempera- throughout the peak load period. When this
ture for the short-time load in question assumption is made, the loss of life during the
(167%).On Fig 9, locate 167% on right side of periods prior to and following the peak load
graph and move horizontally across to ratio of are ignored. Thus, this is only a convenient
losses curve (R = 3.2). Move down to the and simplified procedure for estimating the
full-load oil rise curve (50 "C). Move horizon- loss of life for the assumed loading conditions.

19

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

U3
3

w m w m
v
0 ewc-m
i , 4 - 1

mot- t-m-t-
@??: I 9 1°C I
0313

mmt-o
C
R v w t - 0
- 3 - ( N

---
mwwt-
m o o -

m m m v c
? ? ? ? U
- 1 - 4 7

N-mm
C mmmt-
4 4 - 3

* U 3 0 0
EO
0 0 ?
0 ?0

N v m v
N

20

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

e m m
o'm
3 3 i

mm- o m e m
mwt- 3 m m m
3 3 3 3 i - 3

w m m w - 0
???
3 3 3
22: I

%"$(
3 1 4 3

m w e m m m e m
ewt-m memt-
4 3 3 3 3 3 3 4

m m i m
I C ? " ?
4 - 3 3

mt-mm mmr-m 3 m m e
e w t - m m m w m i m m m
4 1 3 3 31,-43 4 3 i 1

m m o t -
?"??
3 3 - i

m m m o
m o o m
3 3 3
8Z2EI
3 3 3

t-at-0 m o m 1 mmmt- m a m e
e w t - 0 m w w m memr- i m m m
3 3 i m 1 3 3 1 A i 3 3 1 3 3 3

w w m m w m m w
4?2? ??Lo?
3 3 3 3

o o m m m e m m
m - 0 1 m m m d
3 3 3 1

m m m o 0 - m - omt-00 m m w m
e w c - 0 e w w m memt- i m m m
1 3 - m 3 1 1 3 3 3 3 3 3 3 3 3

w m m m t-3-3
"(4909 N""?
3 1 3 1 " 3 3 3

o m w m
m w o -
m m o -
3 3
em-
m o o m
3 3 -1 m m m 2

m @ ! o -
ewt-m
3 3 3 3

5 e
N

21

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSIIIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

I I

m
0 I I Z 5 I I I

m w m
I 3
l"?
3 -

d
0

mmmw
O"??
3 1 - 3

o m m w
n 3
o 1
o 1
h

mt-mm
cc:
C m m w m
4 1 3 1

w o m m
@?(4?09
1 - 3 1

i
:ZC
w m w m
mmwm
:m
U 4 3 3 -

!!
;
2
o m w d
m m m1o

m m m o
C
r
mmwm
1 3 4 1

m w m m
t-mmm

U3t-rnC m m m o - com-
C mt-a01 d W t - 0 - e1 w w m
- 1 -NI - - - N N - 3 1

cf, d
N

22

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS c57.91-1981

m w m w
x m m z

mmmm w w m e
m*mt- -mww
3 - 3 3 3 3 - 3

* o m 0 mt-3 t-mm-e m m m o a
x m m z m m o ~ l mmoo-1 r - m m c c
3 -I 3 -

mmmm
i m * w
3 3 3 3

t - w c m
YO"?
3"N

* m w w o w m m o ~ ~ :
a m m o 3 t-mmoc
- 3 3 -

omt-t-
m m e w
3 3 - 3

-mor- mmt-m. m m m w -
t-t-mm o --1
m m m3 r-mmmc
-

m o m o o

m x m m a
(ct-mma

*
N

23

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IhlMERSED OVERHEAD

I I I :-
I
m m c
I

m-o
m
0
1222 I

r-t-0
I"?? I
3 3 3

0
d

3 m N o
O N@?? I
3 3 3 1

m d m m ~
m m m3
o -1 t-mmmc -
m m m m b

mr-dmm
c:
C
ohlmmw
3 3 3 3 3

e m m m m

I
1 3 m w -
J t-mmmc -
i
!
L
{ C o m w w w
m mvwt-
3331.-

i
;
w-mmm m o - r m o
t-mmmo t-mmo-
" 1"

1ot-t-t- N m w m d
C m e e w t - i m m m w
3 3 3 3 3
1 3 3 3 3

i o m m m m w o - w m
r - dm mmoo w
o
t-mmmm t-mmoo " 3
3 -

N d m

24

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

w m m
10'2z!
:E3 3

t-t-w
Iszz

wmt- mm* I a
ms: m I
o=/
m a c
3
m z = I

*mffi I oZ m
Zmf I
c??? I
3 3 1

+ 3 m w -
t-ffimmc
7

cvffi-m t - w c a * wt-mmm
t-t-mm t - f f i m m3
o t - m m3
o o3

cffim*m
3 m m m w
3 3 - 3 1

m * m c m
t-mffico
3 3

3 N * m *
N

25

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSMEEE
C57.9 1- 1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

140

I30

120

I IO

I00

50

40

30

20

IO

0
PERCENT OF FULL LOAD TOP-OIL RISE
n = 0.8

Fig 7
Initial Top-Oil Rise

Fig 8
Top-Oil Temperature at End of Specified
Load Period

26

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

m
2
VI

U
W

m
W
a
0
W
a
f
W
%?
W
a
I-
a
W
a
Bc
2
8
e
W
a
9
3

320 300 280 260 240 220 200 I80 160 140 120 100
PERCENT OF FULL LOAD TOP-OIL RISE
n = 0.8

Fig 9
Ultimate Top-Oil Rise

0 40 80 I20 160 200 240


PERCENT RATEDhVA

Fig 10
Hottest-Spot Conductor Rise Over
Top-Oil Temperature

27

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANWIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDOVERHEAD

6. Calculation of Temperatures and wr average winding temperature rise


Loss of Life over ambient a t rated load
C thermal capacity of the transformer
(watt-hours per degree Celsius)
K load expressed in per unit of trans-
6.1 General. The loading tables in this guide former nameplate rating
are based on average characteristics of a wide
range of transformer ratings and on a simpli- Pr
total loss a t rated load (watts)
fied load cycle. Transformer characteristics R ratio of load loss a t rated
taken from Table 3 and a load cycle similar to load to no-load loss
t h a t shown in Fig 6 were used in generating e base of natural logarithm = 2.71828
Tables 5-10. When the characteristics of a
particular transformer vary appreciably from n exponential power of loss versus
those in Table 3 or where more precise loading temperature rise
capabilities are desired, specific calculations t time interval in hours during which
should be made. load is, or is assumed to be,
constant
T thermal time constant of transformer,
6.2 List of Symbols hours
6.2.1 Subscripts.
Ths thermal time constant of hottest-spot,
a ambient hours
g hottest-spot temperature rise over
top-oil Tr thermal time constant, in hours,
of the transformer rated load,
hs hottest-spot temperature
i initial beginning with zero initial
o oil temperature rise
r rated
U ultimate 6.3 Equations for Hottest-Spot Tempera-
w winding ture and Percent Loss of Life
6.2.2 Main Symbols. All temperature val- 6.3.1 Ultimate Temperature Rises Due to
ues are in "C. Constant Loads.

ambient temperature
hottest-spot conductor rise
over top-oil a t end of time t
initial hottest-spot conductor rise
over top-oil a t start of time inter-
val
hot test-spot conductor rise over
top-oil a t rated load n = 0.8 (Eq 6 )
ultimate hottest-spot conductor
rise over top-oil for any load K
hottest-spot winding temperature
top-oil rise over ambient temperature
a t end of time t 6.3.2 Determination of Top-Oil Time
Constant.
initial top-oil rise over ambient a t
start of time interval
top-oil rise over ambient a t rated load @or
T, = C- (Eq 8)
ultimate top-oil rise over ambient for p,
any load K where

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANWIEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

C = 0.06 .(weight of core and coil assembly (1) Time constant


in pounds) (2) Ultimate conductor loss a t end of load
+ 0.04 .(weight of tank and fitting period
in pounds) (3) Oil viscosity
+ 1.33 .(gallons of oil), (Eq 9)
NOTE: This equation is applicable to transformers with
either copper or aluminum windings. In making general calculations based on
assumptions of transformer characteristics
6.3.3 Calculation of Transient Tempera- and maximum hottest-spot conductor tempera-
tures at End of Time Interval t with Load tures which generally have a large factor of
Constant Throughout Time Interval. safety, results close enough for all practical
purposes are obtained if all of these correc-
-t I T,
] + OOi (Eq 10)
tions are omitted, and the simpler formulas
are used.
The peak load values given in Tables 5-10
were calculated using the equations without
0
g l
= Ogu-Ogi
I[ 1- e
- t 1 Th
]+agi (Eq 11) corrections.
6.4.1 Time Constant. The time constant is
the length of time which would be required for
the temperature of the oil to change from ini-
tial value to the ultimate value if the initial
NOTE: The initial temperature rises WO and (3 . at the
rate of change were continued until the ulti-
beginning of the interval are the (-)o and (4 resgectively mate temperature was reached.
calculated for the preceding interval. The iltimate tem- If n (the exponential power of loss versus
perature rises (*)ou and are the ultimate temperature
rises corresponding to the load K for the interval. When
temperature rise) equals unity, 63% of t h e
the interval load K is less than the load in the preceding temperature change occurs in a length of time
interval, the ultimate temperature rises (-)ou and We may equal to the time constant regardless of the
be less than the respective initial temperature rises, (-))oi
and(-) ..
relationship of initial temperature and ulti-
mate temperature. If n is not unity, the per-
6.3.4 Calculation of Percent Loss of Life centage varies and is a function of both initial
During Time Interval t. temperature rise and ultimate temperature
rise. If n equals 0.8, the percentage is 67 if the
initial temperature rise is zero.
If the initial temperature rise is greater
than zero, the percentage is lower than 67%
with and approaches 63%a s the initial temperature
rise approaches the ultimate temperature rise.
If the initial temperature is greater than t h e
T = (9,,+273 (Eq 14)
ultimate temperature, the percentage is less
than 63.
and A and B are the constants from the Since evaluation of the exact percentage for
appropriate life expectancy curve (3.4.3). cases where n is not unity and the initial tem-
The loss of life in percent for each interval perature rise is not zero becomes very labori-
can then be summed over the 24 h cycle. ous, it is frequently advisable to use the value
of 63%as a n approximation. In the more fre-
NOTE: Equation 13 assumes H h S at end of each interval t quently encountered cases where n is approxi-
to be continuous for the entire interval so increment time
intervals for any load K must be selected which are small mately 0.8, the error resulting from this pro-
enough to avoid serious error. cedure is not large compared to the expected
error in transient thermal calculations.
6.4 Equation Corrections Theoretically, If n = 1, Eq 8 is correct for any load and
several corrections should be made when using any starting temperature. If n is not = 1, t h e
the foregoing equations in calculating tran- time constant for any load and for any start-
sient oil rises, such as corrections for change ing temperature for either a heating cycle or
in : cooling cycle is given in Eqs 15 and 16.

29

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSUIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

separately from the winding stray loss in


accordance with individual transformer design
T= characteristics. Because it is difficult to
separate the tested stray loss into its many
different components, ANSUIEEE C57.12.9&
1980 [21 allows for the assumption t h a t the
(Eq 15) total stray loss varies inversely with winding
resistance.
If starting cold, as @oi = 0, Eq 15 reduces to: 6.4.2.3 If winding resistance correc-
tions to the load loss are desired, a n individual
breakdown of the 12R and stray loss is needed.
Also, one of the following additional adjust-
(Eq 16) ments is required to ensure reasonably accu-
rate determination of top-oil rise and winding
6.4.2 Load Loss. The resistance of the rise over oil.
windings increases with temperature. Nor- The empirical exponent n = 0.8 is based on
mally, the effect of this resistance change is the assumption t h a t variations in winding
considered to be offset by the effect of the resistance are offset by variations in oil
reduced oil viscosity as the oil temperature viscosity. Manufacturers should provide the
increases. If it is desired to include a user with the appropriate adjusted value of
resistance-temperature correction factor in exponent n if the winding resistance is to be
Eqs 4 and 5, then the necessary equations, adjusted without regard to temperature
revised exponent, Z2Rloss and stray loss must effects on oil viscosity.
be obtained from the transformer manufac- The oil viscosity factor should be included in
turer for the specific design. calculations for both top-oil rise and winding
6.4.2.1 Winding loss can be separated rise over oil. Manufacturers should provide the
into a n Z2R component that varies directly user with the appropriate value of exponent n
with winding resistance and a stray com- and also the appropriate value of the exponent
ponent that varies inversely with winding associated with oil viscosity.
resistance. The winding resistance at time t, The equations which allow for resistance
can be calculated by use of the following for- and oil viscosity correction of the top-oil rise
mula: and winding rise over oil are beyond the scope
of this guide. They can be obtained from the
individual transformer manufacturer along
with the other data required.
6.4.3 Viscosity of Oil. The ultimate tem-
(Eq 17)
perature rise of oil for a constant loss
decreases slightly as the temperature of the
where
oil increases. This is due to a decrease in the
R,, = winding resistance a t time t, viscosity of the oil. The viscosity change tends
to offset the effect of increased resistance.
R,, = winding resistance a t time t,
Owl = average winding temperature a t 6.4.4 Atmospheric Effects. The only at-
time t, mospheric effect on loading capability con-
sidered in calculating the tables in this load-
Ow, = average winding temperature at
ing guide is the effect of ambient tempera-
time t2
tures on the hottest-spot and top-oil tempera-
0, = 234.5 "C for copper, 225.0 "C tures. The rated temperature rise under con-
for aluminum tinuous nameplate load is based on tests in a
virtually still air environment, and no solar or
6.4.2.2 Stray loss also occurs in metal- other radiation input to the transformer. I t
lic structures other than the windings. should be recognized that a typical outdoor
Theoretically, these losses should be adjusted transformer installation will be normally sub-
for variations in load current and resistance jected to additional cooling caused by wind,

30

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND PAD-MOUNTED DISTRIBUTION TRANSFORMERS C57.91-1981

and occasionally heat input from solar radia- for the insulation system must also be pro-
tion. The simultaneous occurrence of still air, vided.
maximum solar radiation, and maximum The determination of the percent loss of life
ambient temperature conditions is of very low for normal life expectancy is based on a 24 h
probability, and when it does occur, will be of load cycle and a minimum transformer life
relatively short duration in comparison to the expectancy of 20 years of the daily cycle. The
transformer's oil time constant. For these rea- daily loss of life would, therefore, be a t the
sons it is believed that the assumptions made rate of 0.0137%of the 20 yr life. The loss of
in generating the loading tables are conserva- life values listed in the tables are additional
tive estimates for most outdoor installations. loss of life above the normal basis of 0.0137%
A more conservative approach is warranted per day; t h a t is, for a n extra loss of life of
when transformers are installed indoors, in 0.05% the program converges on a peak load
vaults, or other areas of restricted ventilation. that expends life at 0.05 +
0.0137 = 0.0637%
In the case of most vault installations, a per daily cycle.
transformer with rated temperature rise 10 "C A two-step 24 h load cycle similar to Fig 6 is
lower than normal outdoor rating is recom- assumed with the peak load starting a t time
mended. zero, followed by the continuous equivalent
load from end of peak duration to end of t h e
6.5 Method Used for Computer Calculation 24 h cycle. The initial top-oil rise Ooi and
of Loading Capability Tables. The equa- hottest-spot rise 8 for the first time interval
tions covered in 6.3 were used in the computer are calculated as uvtimate top-oil rise Oou and
program t h a t generated the data for Tables hottest-spot rise 0 for a load K equal to t h e
5-10. continuous equivaf&t load selected, t h a t is,
6.5.1 Method. The program computes the 50%, 75%or 90%of nameplate rating.
maximum peak load that can be impressed on A systematic converging method is used to
a typical distribution transformer to meet obtain the highest allowable peak load. The
specified loss-of-life limitations within a 4% * initial trial is made with a n assumed peak
tolerance. load midway between the initial continuous
Input to the program is as follows: a n load before peak load and the maximum peak
estimated allowable peak load, the continuous load (300%).Using this peak load, temperature
equivalent load assumed before and after the calculations are made for varying time inter-
peak load G O % , 75%,or 90%of nameplate rat- vals during the 24 h, according to Table 11.
ing), ambient temperature (0 "C to 50 "C in The corresponding interval loss of life is then
10 "C steps), peak load duration (1 h, 2 h, 4 h, calculated with Eq 13 and finally all interval
8 h or 24 h), specified percentage loss of life, losses are summed over the 24 h cycle and
and the following transformer characteristics compared to the specified loss.
a t rated load: loss ratio, top-oil rise over
ambient, hottest-spot rise over top-oil, top-oil EXAMPLE: For a 2 h overload, temperatures will be cal-
culated every 0.2 h for the first 4 h, every 0.5 h from 4 h
time constant and hottest-spot time constant. on till 6 h and every hour from 6 h on till the end of the
The normal life expectancy curve constants 24 h cycle.

Table 11
Calculating Intervals for Overload
Temperature Rise Calculation

Peak Load Elapsed Time Limits Calculating Interval


Duration (h) - s Lengths (h) - t
(h)

sl s2 s3 94 tl t2 t3 t4
1 2 3 5 24 0.1 0.2 0.5 1.o
2 4 6 24 - 0.2 0.5 1.0 -
4 6 9 24 - 0.2 0.5 1.o -
8 4 10 13 24 0.5 0.2 0.5 1.0
24 24 - - - 1 .o - - -

31

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.
ANSVIEEE
C57.91-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED OVERHEAD

Depending on the outcome a new estimated load and corresponding values of peak
peak load is tried. The process is repeated hottest-spot, top-oil temperature, total percent
until the calculated loss of life is within +-4% loss of life and the specified loss of life are
of the specified value. At this point, the peak printed.

32

Authorized licensed use limited to: Northeastern University. Downloaded on October 27,2014 at 00:39:56 UTC from IEEE Xplore. Restrictions apply.

Das könnte Ihnen auch gefallen