COMMENT RESPONSE and RESOLUTION SHEET

Company Drawing No. TEP-901-DWG-CU-BP5-6413


Contractor Drawing No. 870123-PTS-901-MET-DWG-101432
Rev. B01

No COMPANY Comments Name & Title CONTRACTOR Response Name and COMPANY resolution Section
Title Affected
1 refer to data sheet for Lighting and Small Changed MCB to RCBO 10A, 300mA,
Power Panel,Lighting circuit should be 4.5kA
completed with ELCB (300 mA) and Please
check kA rating in supplier, is it 4.5 kA?
2 All MCCB and MCB circuit shall be Note : All MCCB and MCB circuit shall
equipped with CB padlocking be equipped with CB padlocking
3 Please refer to attached data sheet TEP-
2300-EDS-EL-BP5-0005