LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

1 33kV Cable Feeder -Directional Over Current & Earth Fault Protection (67,67N)

1.1 The CT details


Current Transformer = CT-F1, CORE-1
Rated Primary Current Ipn = 600-400/1A
Rated Secondary Current Isn = 1 A
CT Class = 5 P 20
Secondary Winding Resistance Rct = 2 Ohms at 400 A tap
Selected Tap = 400 A

1.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA

1.3 Relays Proposed


a Make = ABB
b Directional Over Current Relay = SPAS 348 C
c Directional Earth Fault Relay = REJ 527
d Rated Relay secondary current Ir = 1 A

1.4 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.166 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA

1.5 Burden of Relay


Directional Over Current Relay (SPAS 348 C) = 100 mohm
Directional Earth Fault Relay (REJ 527) = 100 mohm

VA Burden of Over Current Relay (SPAS 348 C) = (1x1) x 100.00 / 1000


= 0.10 VA
VA Burden of Over Current Relay (REJ 527) = (1x1) x 100.00 / 1000
= 0.10 VA

2 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

1.6 Burden Details


S.No. Device Burden Make
a. Directional Over Current Relay 0.10 SPAS 348 C, ABB
b. Directional Earth Fault Relay 0.10 REJ 527, ABB
c. Lead Burden 0.33
Total Burden 0.53

1.7 Accuracy Limit Factor of the CT


ABB's Requirement n' > Ikmax/In

Ikmax = Highest Fault Current


In = Nominal Primary Current of the CT = 400 A

Hence as Per ABB (n') must be greater than > 31500 / 400
> 79

Real accuracy Limit Factor n' = nx (PN + PE)


(PB + PE)
n = CT rated Accuracy Limit Factor = 20
PN = Rated CT Power = 15 VA Chosen Value
PE = CT Internal Losses In2 x Rct = 2 Watts
PB = Burden at Rated Current = 0.53
n' = 20 x (15.0 + 2.0) / (0.53 + 2.0)
= 134

n' = 134 > 79 , so the current transformer satisfies the requirement.

1.8 Conclusion
CT Ratio Selected = 600-400/1A
Selected Tap = 400 A
CT Secondary Resistance = 2 Ohms
Rated VA of the CT core Selected for Directional= 15 VA
Accuracy Class = 5 P 20
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

3 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

2 33kV Cable Feeder -Pilot Wire Protection- (85)

2.1 The CT details


Current Transformer = CT-F1 Core-2
Rated Primary Current Ipn = 600-400/1A
Rated Secondary Current Isn = 1 A
CT Accuracy Class = X
Secondary Winding Resistance Rct = 2 Ohms at 400 A tap
Selected Tap = 400 A

2.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA

2.3 Relay Proposed


a Make = M/S Vatech Reyrolle Ltd.
b Type = Solkar Rf
d Rated Relay secondary current Ir = 1 A

2.4 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.166 Ohms
2RL = 0.33 Ohms

2.5 Knee Point Voltage Requirement


As per Manufactureres Requirement
Vk >= (50/In) + (If/N) x (Rct+2RL) Volts
Where
In = Rated current of SOLKAR Rf Relay
If = Primary current under maximum steady
state through fault conditions
N = Current Transformer Ratio
Rct = CT Secondary Winding Resistance
RL = Single Lead Resistance from CT to Relay

Vk >= 50/1 + 31500 / 400 x (2 + 2x0.166)


234 V

2.6 Conclusion
CT Ratio Selected = 600-400/1A
Selected Tap = 400 A
CT Secondary Resistance = 2 Ohms
Class of Accuracy = X
Knee Point Voltage Selected >= 400 V
Magnetising Current at Vk/2 <= 30 mA

4 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

5 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

3 33kV Cable Feeder -Metering

3.1 The CT details


Current Transformer = CT-F1 Core-3
Rated Primary Current Ipn = 600-400/1A
Rated Secondary Current Isn = 1 A
CT Class = 0.5 S
Secondary Winding Resistance Rct = 2 Ohms at 400 A tap
Selected Tap = 400 A

3.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA

3.3 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.166 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA

3.4 Burden Details


S.No. Device Burden Make
a. Bay Control Unit 0.10 ABB, REF 542
b. Multifunction Meter 0.60 CIRCUTOR, CVMK
c. Ammeter Transducer 2.20 CELSA, CRI
d. Lead Burden 0.33
Total Burden 3.23

3.5 Conclusion
CT Ratio Selected = 600-400/1A
Selected Tap = 400 A
CT Secondary Resistance = 2 Ohms
Rated VA of the CT core Selected for Metering = 10 VA
Accuracy Class = 0.5 S
Instrument Security Factor <= 5 at all Taps
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

6 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
Note :
1. Instrument security factor (ISF) shall be less than 5 at all taps and shall be ensured by the CT
manufacturer.
2. Whenever the actual Burden is less than the noted Burden of the CT, protection Panel Manufacturer
shall ensure the Metering and connected Instruments are not stressed beyond its Short time
withstand capacity by providing means like Dummy Resistor etc.

7 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

4 33kV Bus Bar Differential Protection Line Feeder (87B)

4.1 The CT details


Current Transformer = CT-F1 Core-4
Rated Primary Current for CT Ipn = 1200 / 1A
Rated Secondary Current Isn = 1 A
CT Class = 5 P 20
Secondary Winding Resistance Rct = 6 Ohms at 1200 A tap
Selected Tap = 1200 A

4.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA
System X/R Ratio = 20
System L/R ratio = 20 / (2x3.14x50)
= 0.064 sec
= 64 msec

4.3 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.166 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA

4.4 Burden Details


S.No. Device Burden Make
a. Relay Burden 0.02 ABB, REB 500
b. Lead Burden 0.33
Total Burden 0.35

4.5 Current Transformer Requirement


a. Condition -1 (With out Taking DC Time constant in to Consideration)
As per Relay manufacturers Catalogue
n' >= 1xIkmax
5xI1N

8 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4
b. Condition -2 (Taking DC Time constant in to Consideration)
n' >= 10 for TN<= 120ms, or
n' >= 20 for 120ms<=TN<= 300ms
Where
n' = Effective accuracy limit Factor
Ikmax = Maximum Primary through fault current= 31.5 kA
I1N = Rated Primary CT current
TN = DC Time constant

As per Condition-1
n' >= (1x31500) / (5 x 1200)
>= 5.25
As per Condition-2
n' >= 10 For the time constant of 64 msec
Hence the maximum value of the n' form the condition 1 and condition 2 is selected for comparison.
n' >= 10
Rated accuracy Limit Factor n' = n x (PN + PE)
(to be provided by the CT manufacturer) (PB + PE)
Where
n = CT Rated Accuracy Limit Factor = 20
PN = Rated VA = 10 VA Chosen Value
PE = CT Internal Losses In2 x Rct = 6 Watts
PB = Burden at Rated Current = 0.35
n' = 20 x (10.0 + 6.0) / (0.35 + 6.0)
= 50

n'= 50 > 10 , so the current transformer satisfies the requirement.

4.6 Conclusion
CT Ratio Selected Line Feeder = 1200 / 1A
CT Secondary Resistance = 6 Ohms
Rated VA of the CT = 10 VA
Accuracy Class = 5 P 20
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

9 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

5 33kV Bus Bar Differential Protection Transformer Feeder (87B)

The CT details
Current Transformer = CT-T1-1 Core-1
Rated Primary Current for CT = 1200/1 A
Rated Secondary Current = 1 A
Rated VA of the CT = 10 VA
CT Class = 5 P 20
Secondary Winding Resistance = 6 Ohms at 1200 A tap
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

Note : For Detailed calculation refer clause 4 .

10 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

11 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

6 33kV Transformer Feeder -Metering

6.1 The CT details


Current Transformer = CT-T1-1 Core-2
Rated Primary Current Ipn = 600-300/1 A
Rated Secondary Current Isn = 1 A
CT Class = 0.5 S
Secondary Winding Resistance Rct = 1.5 Ohms at 300 A tap
Selected Tap = 300 A

6.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA
Transformer MVA Rating = 15 MVA
Transformer kV Rating = 33 / 11.55 kV
Load Current on 33kV Side = 262.4 A
Load Current on 11.55kV Side = 749.8 A

6.3 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.166 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA

6.4 Burden Details


S.No. Device Burden Make
a. Bay Control Unit 0.10 ABB, REF 542
b. Multifunction Meter 0.60 CIRCUTOR, CVMK
c. Ammeter Transducer 2.20 CELSA, CRI
d. Lead Burden 0.33
Total Burden 3.23

6.5 Conclusion
CT Ratio Selected = 600-300/1 A
Selected Tap = 300 A
CT Secondary Resistance = 1.5 Ohms
Rated VA of the CT core Selected for Metering = 10 VA
Accuracy Class = 0.5 S
Instrument Security Factor <= 5 at all Taps

12 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

13 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

Note :
1. Instrument security factor (ISF) shall be less than 5 at all taps and shall be assured by the
manufacturer.
2. Whenever the actual Burden is less than the noted Burden of the CT, protection Panel Manufacturer
shall ensure the Metering and connected Instruments are not stressed beyond its Short time
withstand capacity by providing means like Dummy Resistor etc.

14 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

7 33kV Transformer Differential Protection Calculation (87T)

7.1 The CT details


Current Transformer = CT-T1-1 Core-3 / CT-T1-2 CORE-1
Rated Primary Current for CT on 33kV side = 600-300/1 A
Rated Primary Current for CT on 11kV side = 1000-800/1 A
Rated Secondary Current Isn = 1 A
CT Class = X
Secondary Winding Resistance on 33kV Side Rct = 1.5 Ohms at 300 A tap
Secondary Winding Resistance on 11kV Side Rct = 4 Ohms at 800 A tap
Selected Tap for 33kV Side 300 A
Selected Tap for 11kV Side 800 A

7.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA
System X/R Ratio = 20
System L/R ratio = 20 / (2x3.14x50)
= 0.064 sec
= 64 msec

7.3 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.17 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA

7.4 Burden Details


S.No. Device Burden Make
a. Relay Burden 0.10 ABB, RET 316*4
b. Lead Burden 0.33
Total Burden 0.43

7.5 System Short Circuit Calculation


Short Circuit Level on 33 kV Side = 31.5 kA
Short Circuit Level on 11.55 kV Side = 31.5 kA
System Impedance on 33 kV Side = 33 / sqrt(3) / 31.5
= 0.60 ohms
System Impedance on 11.55 kV Side = 11.55 / sqrt(3) / 31.5
= 0.21 ohms

15 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4
kV Rating of the Transformer = 33 / 11.55 kV
MVA Rating of the Transformer = 15 MVA
Per Unit Impedance = 10 %
Impedance of the Transformer on 33 kV Side = 0.10x(33 x 33) / 15
= 7.26 ohms
Impedance of the Transformer on 11.55 kV Side = 0.10x(11.55 x 11.55) / 15
= 0.89 ohms
Thus through fault current on 33kV Side = 33 / sqrt(3) / (0.60+7.26)
= 2.42 kA
Thus through fault current on 11.55kV Side = 11.55 / sqrt(3) / (0.21+0.89)
= 6.06 kA

7.6 Current Transformer Requirement


a 33kV Side
As per Relay manufacturers Catalogue
n' <= n x (PN + PE)x IN of CT
(PB + PE)xIN
Where
n' = Effective accuracy limit Factor
IN = Nominal current Related to Protected Object =
15000 / sqrt(3) / 33 = 262 A
IN of CT = Nominal current of CT = 300
n = CT rated Accuracy Limit Factor = 45 (Calculated Below)
PN = Rated CT Power = 10 VA (Selected Value)
PE = CT Internal Losses In2 x Rct = 1.5 Watts
PB = Burden at Rated Current = 0.43
Ikmax = Maximum Primary through fault current= 2.42 kA
For a class X Current Transformer, equivalent value of CT rated accuracy class factor (n)
n = Uk x Insec x 1.3
PN + PE
Where
Uk = CT Knee point Voltage = 400 V (Selected Value)
n = CT rated Accuracy Limit Factor = 45.2 (Calculated Below)
n = (400 x 1x1.3) / (10 + 2)
= 45
Hence,
n' = 45 x (10 + 2) x 300
(0.43 + 2) x 262
n' = 308
For the system under consideration = Ikmax/In
Ikmax = Highest through Fault Current
= 2422 / 262
= 9.23

16 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD
DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4
For Ikmax/In calculated above n' = 9 (from ABB's Relay Catalogue)
(Figure-1 Page 3/3)
n' = 308 > 9 , so the current transformer satisfies the requirement.

a 11kV Side
As per Relay manufacturers Catalogue
n' <= n x (PN + PE)x IN of CT
(PB + PE)xIN
Where
n' = Effective accuracy limit Factor
IN = Nominal current Related to Protected Object =
15000 / sqrt(3) / 11.55 = 750 A
IN of CT = Nominal current of CT = 800
n = CT rated Accuracy Limit Factor = 37 (Calculated Below)
PN = Rated CT Power = 10 VA (Selected Value)
PE = CT Internal Losses In2 x Rct = 4 Watts
PB = Burden at Rated Current = 0.43
Ikmax = Maximum Primary through fault current= 6.06 kA
For a class X Current Transformer, equivalent value of CT rated accuracy class factor (n)
n = Uk x Insec x 1.3
PN + PE
Where
Uk = CT Knee point Voltage = 400 V (Selected Value)
n = CT rated Accuracy Limit Factor = 37.1 (Calculated Below)
n = (400 x 1x1.3) / (10 + 4)
= 37
Hence,
n' = 37 x (10 + 4) x 800
(0.43 + 4) x 750
n' = 125
For the system under consideration = Ikmax/In
= 6056 / 750
= 8.08
For Ikmax/In calculated above n' = 8.5 (from ABB's Relay Catalogue)
Where (Figure-1 Page 3/3)
Ikmax = Highest through Fault Current
n' = ### > 8.5 , so the current transformer satisfies the requirement.

17 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4
7.7 Conclusion
CT Ratio Selected for 33kV Side = 600-300/1 A
CT Ratio Selected for 11kV Side = 1000-800/1 A
Rated VA of the CT on 33kV Side = 10 VA
Rated VA of the CT on 11kV Side = 10 VA
Selected Tap on 33kV Side = 300 A
Selected Tap on 11kV Side = 800 A
CT Secondary Resistance on 33kV side = 1.5 Ohms
CT Secondary Resistance on 11kV side = 4 Ohms
Accuracy Class = X
I magnetising = 30 mA @ Vk/2
Knee point Voltage on 33kV Side = 400
Knee point Voltage on 11kV Side = 400
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

18 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

8 33kV Transformer Feeder -Directional Over Current Protection (51-51N)

8.1 The CT details


Current Transformer = CT-T1-1,CORE-4
Rated Primary Current Ipn = 600-300/1A
Rated Secondary Current Isn = 1 A
CT Class = 5 P 20
Secondary Winding Resistance Rct = 1.5 Ohms at 300 A tap
Selected Tap = 300 A

8.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA
Transformer MVA Rating = 15 MVA
Transformer kV Rating = 33 / 11.55 kV
Load Current on 33kV Side = 262.4 A
Load Current on 11.55kV Side = 749.8 A

8.3 Relays Proposed


a Make = ABB
b Directional Over Current and Earth fault Relay = SPAJ 140C
c Rated Relay secondary current Ir = 1 A

8.4 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.17 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA
8.5 Burden Details
S.No. Device Burden Make
a. Directional Over Current Relay 0.10 SPAJ 140C
c. Lead Burden 0.33
Total Burden 0.43

8.6 Accuracy Limit Factor of the CT


ABB's Requirement n' >= Ikmax/In
>= 31500 / 300
Hence as Per ABB (n') must be greater than >= 105

19 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

For the System under Consideration

Real accuracy Limit Factor n' = nx (PN + PE)


(PB + PE)

Where
n = CT rated Accuracy Limit Factor = 20
PN = Rated CT Power = 10 VA (Selected Value)
PE = CT Internal Losses In2 x Rct = 1.5 Watts
PB = Burden at Rated Current = 0.43
n' = 20 x (10 + 1.5) / (0.43 + 1.5)
= 119

n' = 119 > 105 , so the current transformer satisfies the requirement.

8.7 Conclusion
CT Ratio Selected = 600-300/1A
Selected Tap = 300 A
CT Secondary Resistance = 1.5 Ohms
Rated VA of the CT core = 10 VA
Accuracy Class = 5 P 20
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

20 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

9 33kV Transformer Feeder -Restricted Earth Fault Protection- (64R)

9.1 The CT details


Current Transformer = CT-T1-N CORE-1
Rated Primary Current Ipn = 1000-800/1A
Rated Secondary Current Isn = 1 A
CT Class = X
Secondary Winding Resistance Rct = 4 Ohms at 800 A tap
Selected Tap = 800 A
I magnetising = 30 mA @ Vk/2

9.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA

9.3 Relays Proposed


a Make = ABB
b Restricted Earth Fault Relay = SPAJ 115C
d Rated Relay secondary current Ir = 1 A

9.4 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.17 Ohms
2RL = 0.33 Ohms

9.5 Through fault current calculation


KV Rating of the Transformer = 33 / 11.55 kV
MVA rating of the transformer = 15 MVA
Transformer Per unit impedance = 10 p.u
Short Circuit MVA = 15 / 0.10
= 150 MVA
Hence Maximum through fault current on = 150000 / (sqrt(3) x 11.55)
the secondary side = 7498.06 A
Ikmax = 7.5 kA

9.6 Knee point voltage calculation


The Knee Point Voltage Vk = 2 Us
Where Us is the Voltage setting of the Relay

The setting Voltage Us = Ikmax/n x ( Rct + 2 RL)

21 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

Ikmax = Maximum through fault current for which relay


must not operate
n = Current Transformer turns ratio
Rct = Secondary Resitance ( Ohms)
RL = Total resistance of the longest measuring circuit
Us = 7498.1 / 800(4 + 0.33)
Us = 40.6
Set value of Us = 50
Hence Knee point voltage >= 2Us
>= 2 x 50
>= 100
Knee point Voltage selected Uk >= 100
approx.
Adopted Value of Uk = 400 V

9.7 Sensitivity Check


The Primary operating Current Iop = n x ( Ir + m * Ie + Iu)
n = CT transformation ratio
= 800
Ir = Relay Operating Current >= m*Ie
= 30 mA
Ie = Current Transformer Mag. Current at
setting voltage
= (30x50) / (400/2)
= 7.5 mA
m = Number of CT's in the differential current circuit
= 4 Nos
Iu = Current through varistor at Us
= 10 mA (As per Relay Catalogue for SPAJ 115C)
(Figure-4, Operating Characterstic of the voltage dependant Resistor)
( Voltage Dependant Resistor Type 5248 831-C)
Hence, the primary operating Current = 800 ( 0.030 + 4x0.008 + 0.010)
= 56

9.8 Value of stabilising Resistor (Rs)


Maximum Possible value of Us = 50 V
Minimum value of start Current Ir = 30 mA (It is m x Ie as recommended in
the catalogue for SPAJ 115C)
Value of stabilising Resistor (Rs) = Us/Ir
= 1666.7 Ohms Type - (5248 831-C)

22 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

The input Impedance of the SPAJ115C relay = 0.1 Ohms


Since the input impedance of the relay is negligible in comparison to the value of stabilising resistor,
the same is not substracted from the calculated value of Rs above.

9.9 Conclusion
CT Ratio Selected = 1000-800/1A
Selected Tap = 800 A
CT Secondary Resistance = 4 Ohms
Rated VA of the CT core Selected for Restricted= 10 VA
Earth fault protection
Minimum Knee point Voltage Requirement = 400 V
Accuracy Class = X
I magnetising = 30 mA @ Vk/2
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

23 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

10 33kV Transformer Feeder -Stand By Earth Fault Protection (SBEF)

10.1 The CT details


Current Transformer = CT-T1-N CORE-2
Rated Primary Current Ipn = 1000-800/1A
Rated Secondary Current Isn = 1 A
CT Class = 5 P 20
Secondary Winding Resistance Rct = 4 Ohms at 800 A tap
Selected Tap = 800 A

10.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA

10.3 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.17 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA

10.4 Burden Details


S.No. Device Burden Make
a. Stand By Earth Fault Relay 0.10 ABB, REJ 521
B. Lead Burden 0.33
Total Burden 0.43

10.5 Accuracy Limit Factor of the CT


ABB's Requirement n' > Ikmax/In

Ikmax = Highest Fault Current


In = Nominal Primary Current of the CT = 800 A

Hence as Per ABB (n') must be greater than > 31500 / 800
> 39

Real accuracy Limit Factor n' = nx (PN + PE)


(PB + PE)
n = CT rated Accuracy Limit Factor = 20
PN = Rated CT Power = 15 VA Chosen Value
PE = CT Internal Losses In2 x Rct = 4 Watts

24 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
PB = Burden at Rated Current = 0.43

25 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
n' = 20 x (15.0 + 4.0) / (0.43 + 4.0)
= 86

n' = 86 > 39 , so the current transformer satisfies the requirement.


10.6 Conclusion
CT Ratio Selected = 1000-800/1A
Selected Tap = 800 A
CT Secondary Resistance = 4 Ohms
Rated VA of the CT core Selected for Metering = 10 VA
Accuracy Class = 5 P 20
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

26 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

11 11kV Cable Feeder -Directional Over Current Protection (51-51N)

11.1 The CT details


Current Transformer = CT-3 CORE-1
Rated Primary Current Ipn = 600-300/1A
Rated Secondary Current Isn = 1 A
CT Class = 5 P 20
Secondary Winding Resistance Rct = 1.5 Ohms at 300 A tap
Selected Tap = 300 A

11.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA @ 33 kV

11.3 Relays Proposed


a Make = ABB
b Directional Over Current Relay = REF 542 Plus
c Directional Earth Fault Relay = REF 542 Plus
d Rated Relay secondary current Ir = 1 A

11.4 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 30 Mtrs
Single Lead Resistance from CT to = 0.030 x 5.52
Relay RL = 0.17 Ohms
2RL = 0.33 Ohms
VA Burden of the Lead = (1x1) x 0.33 VA
= 0.33 VA
11.5 Burden Details
S.No. Device Burden Make
a. Directional Over Current Relay 0.10 REF 542 Plus
c. Lead Burden 0.33
Total Burden 0.43

11.6 Accuracy Limit Factor of the CT


ABB's Requirement >= Ikmax/In
>= 31500 / 300
Hence as Per ABB (n') must be greater than >= 105

27 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

For the System under Consideration

Real accuracy Limit Factor n' = nx (PN + PE)


(PB + PE)

Where
n = CT rated Accuracy Limit Factor = 20
PN = Rated CT Power = 10 VA (Selected Value)
PE = CT Internal Losses In2 x Rct = 1.5 Watts
PB = Burden at Rated Current = 0.43
n' = 20 x (10.0 + 1.5) / (0.43 + 1.5)
= 119

n' = 119 > 105 , so the current transformer satisfies the requirement.

11.7 Conclusion
CT Ratio Selected = 600-300/1A
Selected Tap = 300 A
CT Secondary Resistance = 1.5 Ohms
Rated VA of the CT core Selected for Directional= 10 VA
Overcurrent Earth fault protection
Accuracy Class = 5 P 20
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

28 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

12 11kV Transformer Feeder -Directional Over Current Protection (51-51N)

12.1 The CT details


Current Transformer = CT-T1-2, CORE-4
Rated Primary Current Ipn = 1000-800/1A
Rated Secondary Current Isn = 1 A
CT Class = 5 P 20
Secondary Winding Resistance Rct = 4 Ohms at 800 A tap
Selected Tap = 800 A

12.2 Assumptions :
The Max.3Ph.S.C Current of 33kV Bus = 31.5 kA @ 33 kV
Transformer MVA Rating = 15 MVA
Transformer kV Rating = 33 / 11.55 kV
Load Current on 33kV Side = 262.4 A
Load Current on 11.55kV Side = 749.8 A

12.3 Relays Proposed


a Make = ABB
b Directional Over Current and Earth fault Relay = SPAJ 140C
c Rated Relay secondary current Ir = 1 A

12.4 Calculation of Lead Burden RL


Cable considered for CT connection = 4 sq.mm Cu
AC Resistance of the cable @ 70deg C = 5.52 Ohms/km
Length between CT and the Relay = 10 Mtrs
Single Lead Resistance from CT to = 0.010 x 5.52
Relay RL = 0.06 Ohms
2RL = 0.11 Ohms
VA Burden of the Lead = (1x1) x 0.11 VA
= 0.11 VA
12.5 Burden Details
S.No. Device Burden Make
a. Directional Over Current Relay 0.10 SPAJ 140C
c. Lead Burden 0.11
Total Burden 0.21

12.6 Accuracy Limit Factor of the CT


ABB's Requirement >= Ikmax/In
>= 31500 / 800
Hence as Per ABB (n') must be greater than >= 39

29 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : CT Parameter Calculations 25.03.200
RAJIV SKA / AKS KRJ
4

For the System under Consideration

Real accuracy Limit Factor n' = nx (PN + PE)


(PB + PE)

Where
n = CT rated Accuracy Limit Factor = 20
PN = Rated CT Power = 10 VA (Selected Value)
PE = CT Internal Losses In2 x Rct = 4 Watts
PB = Burden at Rated Current = 0.21
n' = 20 x (10 + 4.0) / (0.21 + 4.0)
= 67

n' = 67 > 39 , so the current transformer satisfies the requirement.

12.7 Conclusion
CT Ratio Selected = 1000-800/1A
Selected Tap = 800 A
CT Secondary Resistance = 4 Ohms
Rated VA of the CT core Selected for Directional= 10 VA
Overcurrent Earth fault protection
Accuracy Class = 5 P 20
Rated Continuous Thermal Current = 150 %
Rated Short Time Thermal Current = 31.5 kA for 3 Sec

30 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

1 33kV LINE VT

1.1 VT Details
VT = PT-F1, CORE-1
Voltage Rating = 33/Ö3 / 110/Ö3
VA Rating = 100 VA
Core-1 = Cl :1

1.2 VT Burden Calculation


Burden on Core-1
Voltage Rating of the VT = 110 V
VA Rating of the VT = 100 VA
Current Supplied by VT at maximum VA Rating = (100 x sqrt(3) ) / (110)
IVT 1.575 A
(a) Lead Burden on Core-1
Cable 2 Way
S. Cable Cable Size Resistance Cable Total Lead
No in (Sq.mm) (R) in Length Loss (VA)=
From To (Ohms/km) (L) in (m) (IVT2xRxL/1000)

1 VT Synchronising Circuit 4C x 2.5 8.87 2 x 30 1.320

Cu. Conductor 60

(b) Other Burdens on Core-1


S.No. Device Burden (VA) Make Type
1 Tarrif Metering
Not Applicable
2 Backup Metering
Voltmeter 5 - -
3 Protection Relays
Not Applicable
4 Synchronisation
a. Check Synchronisation Relay 0.25 ABB SPAU140 C
b. Synchroscope 6 ABB
c. Double Frequency Meter 1.2 ABB
d. Double Volt Meter 5 ABB
e. No Voltage Relay 1.2 ABB
5 Lead Burden
a. Lead Burden under S.No-1 above 1.32
Total Burden 19.97

31 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
1.3 Conclusion
Actual Burden of the Line-1 VT Core-1 : 19.97 VA
Selected Parameters
VA rating Selected : 100.0 VA
Accuracy Class of Core-1 : Cl :1

32 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

2 33kV LINE VT

2.1 VT Details
VT = PT-F1, CORE-2
Voltage Rating = 33/Ö3 / 110/3
VA Rating = 50 VA
Core-2 = Cl :3P

2.2 VT Burden Calculation


Burden on Core-2
Voltage Rating of The VT = 110 V
VA Rating of the VT = 50 VA
Current Supplied by VT at maximum VA Rating = (50 x sqrt(3) ) / (110)
IVT 0.787 A
(a) Lead Burden on Core-1
Cable 2 Way
S. Cable Cable Size Resistance Cable Total Lead
No in (Sq.mm) (R) in Length Loss (VA)=
From To (Ohms/km) (L) in (m) (IVT2xRxL/1000)

1 VT SPAS 348C Relay 4C x 2.5 8.87 2 x 30 0.330

Cu. Conductor 60

(b) Other Burdens on Core-2


S.No. Device Burden (VA) Make Type
1 Tarrif Metering
Not Applicable
2 Backup Metering
Not Applicable
3 Protection Relays
Directional O/C and Earth Fault Relay 0.5 ABB SPAS 348 C
4 Synchronisation
Not Applicable
5 Lead Burden
a. Lead Burden under S.No-1 above 0.33
Total Burden 0.83

33 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
2.3 Conclusion
Actual Burden of the Line-1 VT Core-2 : 0.83 VA
Selected Parameters
VA rating Selected : 50.0 VA
Accuracy Class of Core-2 : Cl :3P

34 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

3 33kV BUS VT

3.1 VT Details
VT = PT-BUS-1, CORE-1
Voltage Rating = 33/Ö3 / 110/Ö3
VA Rating = 100 VA
Core-1 = Cl :1

3.2 VT Burden Calculation


Burden on Core-1
Voltage Rating of The VT = 110 V
VA Rating of the VT = 100 VA
Current Supplied by VT at maximum VA Rating = (100 x sqrt(3) ) / (110)
IVT 1.575 A
(a) Lead Burden on Core-1
Cable 2 Way
S. Cable Cable Size Resistance Cable Total Lead
No in (Sq.mm) (R) in Length Loss (VA)=
From To (Ohms/km) (L) in (m) (IVT2xRxL/1000)

1 VT Synchronising Circuit 4C x 2.5 8.87 2 x 30 1.320

Cu. Conductor 60

(b) Other Burdens on Core-1


S.No. Device Burden (VA) Make Type
1 Tarrif Metering
Not Applicable
2 Backup Metering
Not Applicable
3 Protection Relays
Not Applicable
4 Synchronisation
a. Check Synchronisation Relay 0.25 ABB SPAU140 C
b. Synchroscope 6 ABB
c. Double Frequency Meter 1.2 ABB
d. Double Volt Meter 5 ABB
e. No Voltage Relay 1.2 ABB
5 Lead Burden
a. Lead Burden under S.No-1 above 1.32
Total Burden 14.97

35 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
3.3 Conclusion
Actual Burden of the Line-1 VT Core-1 : 14.97 VA
Selected Parameters
VA rating Selected : 100.0 VA
Accuracy Class of Core-1 : Cl :1

36 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004

4 11kV VT

4.1 VT Details
Voltage Rating = 11/Ö3 / 110/Ö3
VA Rating = 100 VA
Core-1 = Cl :1

4.2 VT Burden Calculation


Burden on Core-1
Voltage Rating of The VT = 110 V
VA Rating of the VT = 100 VA
Current Supplied by VT at maximum VA Rating = (100 x sqrt(3) ) / (110)
IVT 1.575 A
(a) Lead Burden on Core-1
Cable 2 Way
S. Cable Cable Size Resistance Cable Total Lead
No in (Sq.mm) (R) in Length Loss (VA)=
From To (Ohms/km) (L) in (m) (IVT2xRxL/1000)

1 VT Synchronising Circuit 4C x 2.5 8.87 2 x 30 1.320

Cu. Conductor 60

(b) Other Burdens on Core-1


S.No. Device Burden (VA) Make Type
1 Tarrif Metering
Not Applicable
2 Backup Metering
Not Applicable
3 Protection Relays
Voltmeter 5 - -
4 Synchronisation
a. Check Synchronisation Relay 0.25 ABB SPAU140 C
b. Synchroscope 6 ABB
c. Double Frequency Meter 1.2 ABB
d. Double Volt Meter 5 ABB
e. No Voltage Relay 1.2 ABB
5 Lead Burden
a. Lead Burden under S.No-1 above 1.32
Total Burden 19.97

37 of 41
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

PROJECT : 33/11kV S/S IN AL AIN AREA Ref : G1409--RL7440J353 A


PREP CHKD APPRD DATE
TITLE : VT Parameter Calculations
RAJIV SKA / AKS KRJ 25.03.2004
4.3 Conclusion
Actual Burden of the 11kV Feeder VT Core-1 : 19.97 VA
Selected Parameters
VA rating Selected : 100.0 VA
Accuracy Class of Core-1 : Cl :1

38 of 41
Revision : A Date : 12.04.2004

Description CT No. Ratio Class Burden Ukp Rct Relay


(A/A) (VA) (V) (Ohm)
33kV Cable Feeder -Directional
Over Current & Earth Fault CT-F1, CORE-1 600-400/1A 5 P 20 15 - 2 SPAS 348 C
Protection (67,67N)
33kV Cable Feeder -Pilot Wire
CT-F1 Core-2 600-400/1A X - 400 2 Solkar Rf
Protection- (85)
33kV Cable Feeder -Metering CT-F1 Core-3 600-400/1A 0.5 S 10 - 2 -
33kV Bus Bar Differential
CT-F1 Core-4 1200 / 1A 5 P 20 10 - 6 ABB, REB 500
Protection Line Feeder (87B)
33kV Bus Bar Differential
Protection Transformer Feeder CT-T1-1 Core-1 1200/1 A 5 P 20 10 -
(87B)
33kV Transformer Feeder
CT-T1-1 Core-2 600-300/1 A 0.5 S 10 -
-Metering

600-300/1 A 10 -
33kV Transformer Differential CT-T1-1 Core-3 / CT-T1-
X
Protection Calculation (87T) 2 CORE-1
1000-800/1 A 10 400
33kV Transformer Feeder
-Directional Over Current CT-T1-1,CORE-4 600-300/1A 5 P 20 10 400
Protection (51-51N)

33kV Transformer Feeder


-Restricted Earth Fault Protection- CT-T1-N CORE-1 1000-800/1A X 10 400
(64R)

33kV Transformer Feeder -Stand


CT-T1-N CORE-2 1000-800/1A 5 P 20 10 -
By Earth Fault Protection (SBEF)

11kV Cable Feeder -Directional


CT-3 CORE-1 600-300/1A 5 P 20 10 -
Over Current Protection (51-51N)

11kV Transformer Feeder


-Directional Over Current CT-T1-2, CORE-4 1000-800/1A 5 P 20 10 -
Protection (51-51N)

VT Data VT No. Ratio Burden Class


(V/V) (VA)
33kV LINE VT PT-F1, CORE-1
33kV LINE VT PT-F1, CORE-2
33kV BUS VT PT-BUS-1, CORE-1
11kV VT Core-1
Additional CTs
Technical Data: requirements
Rated Voltage 36 kV
Service Voltage 33 kV
Frequency 50 Hz
Short time Current (1 sec.) 31,5 kA
Making Current 80 kA
Withstand Voltage (1 min) 70 kV
BIL (kV) 170 kV
Ambient Temperature -7°C....+50°C
Standard IEC
Polarity P1 to CB
Revision : A Date : 12.04.2004

Description Function Ratio Class Burden Ukp Rct Relay


(A/A) (VA) (V) (Ohm)

VT Data Ratio Burden Class


(V/V) (VA)

Technical Data: Additional CTs requirements


Rated Voltage 12 kV
Service Voltage 11 kV
Frequency 50 Hz
Short time Current (1 sec.) 25 kA
Making Current 63 kA
Withstand Voltage (1 min) 28 kV
BIL (kV) 75 kV
Ambient Temperature -7°C....+50°C
Standard IEC
Polarity P1 to CB