Sie sind auf Seite 1von 1

A56341 Wed, 1 Jun 2016 03:35

From: Technical Product Shipping


<technical@product-shipping.com@SMT>
To : M/T NORTHERN LIGHT Sent 01/06/2016 03:35
Cc : Technical Product Shipping Sent 31/05/2016 03:27
<technical@product-shipping.com@SMT>
Date: 31 May 2016 03:27 Msg: AMOS-957189445
Path: \ADMIN\IN BOX
Sub : M/T Northern Light - Salwico MN 3000 malfunction

Dear Chief Engineer,

Reference is made to the fault alarm in the Local fixed fire fighting
system ( Salwico MN 3000)

Please follow below instructions :

1) First verify the number of units exist in section 1.

2) Change authorization level from the menu by using access level


code "3333".

3) Choose SEC 1 and scroll to menu with F4 until "NO OF UNITS" is


displayed

4) Press F3(no. of units), then enter the correct number of units


and press F1(ready).

The fault alarm should now be resettable.

Kindly test the above procedure and revert with results

Best Regards,

Christos Karagounis
Fleet Technical Superintendent
Technical Department
Product Shipping & Trading
Tel.: +30 210 6194 129
Fax: +30 210 6194 109
Mob.: +30 6980 086 522