Current Limiting Reactors
Faults on Electrical System - Basic Concepts
3 - Equipment wear-out
Current Limiting Reactors
Reactor as current limiting device
• Used to limit fault currents to values lower than would otherwise exist;
• Can be applied in a variety of different configurations at:
Distribution Voltages
• Used to limit fault currents to values lower than would otherwise exist;
• Can be applied in a variety of different configurations at:
Transmission Voltages
50MVA
12.5%
3 [kA] 14.4 25.4
N.C. / N.O.
SLG[kA] 15.7 28.6
13.8 kV
2. Add Series Reactors : 13.8 kV- 300 A, 2.9%, 0.77 ohms Distribution Circuits
HV Bus
13.8 kV
3. Add NGR Reactors @ both Transformers: 13.8 kV-300 A, 0.77 ohms Distribution Circuits
HV Bus
13.8 kV
Distribution Circuits
Applying Current Limiting Reactors
Options
Very Expensive
Extensive down time (hence not practical)
Due to the importance and high profile of the installation, Eletronorte also specified
the following:
500 kV 500 kV
500 kV 500 kV
CLR
69 kV Maraba 1 Maraba 2 V. Conde 1 Maraba 3 Maraba 4 V. Conde 2 230 kV
Supply Supply
Current Limiting Reactors
Case Studies
TUC # 1 TUC # 2
A1 B1 C1 C2 B2 A2
Current Limiting Reactors
Case Studies
22 nF CC
(across reactor)
14 nF
(line to ground)
Current Limiting Reactors
Case Studies
11.5 m
Mechanical Peak: 27 KA
BIL / SIL : 1550 / 1180 kV
Losses / Efficiency : 280 kW / 99.79 %
RRTRV control: < 5.0 kV/sec
Weight : 32,000 kg (2 coils)
(insulator excluded)
HUANGDU
500 kV SIJING
500 kV
HVDC From
3 Gorges HUXI
(Future) 500 kV
Current Limiting Reactors
Case Studies
TEHCP 500S
C = 2 X 14.000 pF
Line Station
L = 53.05 mH
TEHCP 500H
C= 2 X 16.000 pF
Current Limiting Reactors
Case Studies
Impedance = 5.9