PPD UTILITIES: CHILLED WATER PLANTS; CHILLER INVENTORY 2011 Last Updated: 40634

CHILLED WATER PLANT NO. 1 Location: Weil Hall Heat Plant 1 Bldg Numbers: 0025
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Notes Refrigerant Remarks
No. KW/Ton Installed (Years)
1 Trane CVHF1470 L07E02608 1700 0.575 Elec Centrifugal 2007 4 1,5 3,100# R-123
2 Trane CVHF1470 L05C01077 1700 0.569 Elec Centrifugal 2005 6 1,5 3,150# R-123
3 Trane CVHB155NAT-22B2701 L86A34425 1425 0.649 Elec Centrifugal 1986 25 1,5 2,500# R-11 CVHB 155 NA PF CAP 158KVAR?
4 Trane CVHB155NAY-23BZ2951 L89E02060 1425 0.649 Elec Centrifugal 1989 22 1,5 2,500# R-11 CVHB 155 NA PF CAP 158KVAR?
TOTAL TONNAGE: 6250
Subtract Tonnage of Largest Chiller: -1700 0.607
PLANT FIRM CAPACITY: 4550

CHILLED WATER PLANT NO. 2 Location: Heat Plant No. 2 Rabon Bldg Number: 0473
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane CDHF3000K1ADD L0RH04075 2600 0.553 Elec Centrifugal 2004 7 2,5 R-123
2 Trane CVHF1470 L05D01986 1700 0.585 Elec Centrifugal 2006 5 2,5 3,150# R-123
3 Trane CVHF1470 L05D02014 1700 0.585 Elec Centrifugal 2006 5 2,5 3,150# R-123
4 Carrier 19FA561AEA 762425017 1226 0.754 Elec Centrifugal 1977 34 2,5 3,950# R-134a Cnvrtd. Effic .754KW/Ton ( .713KW/Ton Orig)
5 Carrier 19FA561AEA 762425018 1226 0.754 Elec Centrifugal 1977 34 2,5 3,950# R-134a
6 Carrier 19EF521504 39863 1440 0.583 Elec Centrifugal 1988 23 2,5 3,802# R-500
7 Carrier 19EF85DP 39864 1260 0.671 Elec Centrifugal 1988 23 2,5 3,802# R-500
TOTAL TONNAGE: 11152
Subtract Tonnage of Largest Chiller: -2600 0.624
PLANT FIRM CAPACITY: 8552

CHILLED WATER PLANT NO. 3 Location: Walker Hall Bldg Numbers: 0003
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 York YTL6L6F1-CVE YDXM504385 750 0.595 Elec Centrifugal 1989 22 1,5 1,590#R-11
2 York YTL6L6F1-CVE YDXM504417 750 0.595 Elec Centrifugal 1989 22 1,5 1,590# R-11
3 Trane CVHF147N L03D04614 1500 0.523 Elec Centrifugal 2003 8 1,5 2900# R-123
4 Trane CVHE100N L91K09427 1000 0.586 Elec Centrifugal 1991 20 2,5 2500# R-11
TOTAL TONNAGE: 4000
Subtract Tonnage of Largest Chiller: -1500 0.566 OA:
Chiller 1 and 2 had refrigerant
PLANT FIRM CAPACITY: 2500 conversion and panel upgrad
7/2010

CHILLED WATER PLANT NO. 4 Location: Southwest Plant Bldg Number: 0295
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Notes Refrigerant Remarks
No. KW/Ton Installed (Years)

1 Trane CVHEO71 L89J03101 625 0.606 Elec Centrifugal 1989 22 2,5 1,400# R-123 650 Tons, .583 KW/Ton(Orig)
2 Trane CVHEO71 L89J03130 625 0.606 Elec Centrifugal 1989 22 2,5 1,400# R-123 650 Tons, .583 KW/Ton(Orig)
3 Trane CVHF065 L96C02993 650 0.555 Elec Centrifugal 1996 15 2,5 1,800# R-123
4 Trane CVHF065 L03D04272 650 0.525 Elec Centrifugal 2003 8 2,5 1,800# R-123
TOTAL TONNAGE: 2550 OA:
Subtract Tonnage of Largest Chiller: -650 0.573 Chiller 1 and 2 had refrigerant
conversion and panel upgrad 7/2010
PLANT FIRM CAPACITY: 1900

CHILLED WATER PLANT NO. 5 Location: McCarty Hall Bldg Number: 1053
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane CVHF1280 L94J09150 1200 0.594 Elec Centrifugal 1994 17 1,5 2,100# R-123
2 Trane CVHF1280 L94J09290 1200 0.594 Elec Centrifugal 1994 17 1,5 2,100# R-123
3 Trane CVHF1280 L96F05785 1200 0.596 Elec Centrifugal 1996 15 1,5 2,300# R-123
4 Trane CVHF1280 L96F05784 1200 0.596 Elec Centrifugal 1996 15 1,5 2,300# R-123
5 Trane CVHF1280 LOOFO3446 1200 0.590 Elec Centrifugal 2000 11 1,5 2,100# R-123
6 Trane CVHF1280 LOOFO3445 1200 0.590 Elec Centrifugal 2000 11 1,5 2,100# R-123
TOTAL TONNAGE: 7200
Subtract Tonnage of Largest Chiller: -1200 0.593
PLANT FIRM CAPACITY: 6000

CHILLED WATER PLANT NO. 6 Location: West Plant Bldg Number: 0317
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane CVHE080NA1 L93L10927 600 0.555 Elec Centrifugal 1993 18 1,5 2,100# R-123
2 Trane CVHE080NA1 L93L10931 600 0.555 Elec Centrifugal 1993 18 1,5 2,100# R-123
3 York YCIV0267PA46 258 1.209 2010 1 VSD, 2 COMPRESSORS
TOTAL TONNAGE: 1458
Subtract Tonnage of Largest Chiller: -600 0.555
PLANT FIRM CAPACITY: 858

CHILLED WATER PLANT NO. 7 Location: Law School Bldg Number: 0758
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton

1 Trane CVHF650 LO6MO5975 600 0.530 Elec Centrifugal 2007 4 2,5 1,700# R-123
This chiller was scrapped in July 2008.
3 York YTL3L3E2-CRGS GHCM-260651 450 0.562 Elec Centrifugal 1995 16 2,5 1,240# R-123
4 Trane CVHF0650 L02L221055 600 0.518 Elec Centrifugal 2003 8 2,5 2,200# R-123
TOTAL TONNAGE: 1650
Subtract Tonnage of Largest Chiller: -600 0.535
PLANT FIRM CAPACITY: 1050

CHILLED WATER PLANT NO. 9 Location: Southeast Plant Bldg Number: 1056
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane CVHF1280 L96J07050 1200 0.592 Elec Centrifugal 1997 14 1,5 1,280# R-123
2 Trane CVHF1280 L96J07042 1200 0.592 Elec Centrifugal 1997 14 1,5 1,280# R-123
3 Trane CVHF1280 L96H06989 1200 0.592 Elec Centrifugal 1997 14 1,5 1,280# R-123
4 Trane CVHF1280 L96H06936 1200 0.592 Elec Centrifugal 1997 14 1,5 1,280# R-123
TOTAL TONNAGE: 4800
Subtract Tonnage of Largest Chiller: -1200 0.592
PLANT FIRM CAPACITY: 3600

377399504.xls,Attachment A
PPD UTILITIES: CHILLED WATER PLANTS; CHILLER INVENTORY 2011 Last Updated: 40634

CHILLED WATER PLANT NO. 10 Location: Pathogens Plant Bldg Number: 1378
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Notes Refrigerant Remarks
No. KW/Ton Installed (Years)
1 Trane CVHF147N L09A05930 1200 0.572 Elec Centrifugal 2009 2 1,5 2,700# R-123
2 Trane CVHF147N L09A05938 1200 0.572 Elec Centrifugal 2009 2 1,5 2,700# R-123
TOTAL TONNAGE: 2400
Subtract Tonnage of Largest Chiller: 0 0.572 At ARI Conditions, 0.536 KW/Ton
PLANT FIRM CAPACITY: 2400

TONNAGE TOTAL ALL CHILLERS 41460

377399504.xls,Attachment A
2011

BUILDING MAINTENANCE: REMOTE CHILLERS INVENTORY 4/1/2011


PROGRESS CENTER Location: Alachua, FL Bldg Numbers: 1040, 1041, 1380, 1383
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Remarks
No. KW/Ton Installed (Years)
1 Carrier 30XA1406L 3909Q90635 130 Wtr./ Air Screw 2009 2 223# R-134a Bldg 1040 - Large Animal Containment Unit
2 Carrier 30XA1406L 3909Q90635 130 Wtr./ Air Recip. 2009 2 223# R-134a Bldg 1040 - Large Animal Containment Unit

1 Carrier 23XLZ020EC60 3294J48713 250 Electric Screw 1994 17 650# R-22 Bldg 1041 - Sid Martin Biotechnology Bldg
2 Carrier 23XLZ020EC60 3294J48712 250 Electric Screw 1994 17 650# R-22 Bldg 1041 - Sid Martin Biotechnology Bldg
3 McQuay AGZ050A 57D8131401 50 Wtr./ Air Recip. 1998 13 750# R-22 Bldg 1041 - Sid Martin Biotechnology Bldg

1 York YTC3C1B1CFE MRP410018 175 Elec Centrifugal 1990 21 730# R-11 Bldg 1380 - Center of Excellence - North
2 York YTC3C1B1CFE MRP410167 175 Elec Centrifugal 1990 21 730# R-11 Bldg 1380 - Center of Excellence - North

1 York YTC3C1B1CFE MRP410166 175 Elec Centrifugal 1990 21 730# R-11 Bldg 1383 - Center of Excellence - South
2 York YTC3C1B1CFE MRP410017 175 Elec Centrifugal 1990 21 730# R-11 Bldg 1383 - Center of Excellence - South

TOTAL TONNAGE: 1510

HR BUILDING Location: 903 W. University Ave Bldg Number: 3381


Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Notes
No. KW/Ton Installed (Years)
1 Carrier 30RBA07058006-777 4606Q82507 70 Wtr./Air Screw 2006 5 R-410a
2 Carrier 30RBA07058006-777 4606Q82508 70 Wtr./Air Screw 2006 5 R-410a
TOTAL TONNAGE: 140

JOHNNY WALKER BUILDING Location: 2008 NE WALDO ROAD Bldg Number: 1603
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Notes
No. KW/Ton Installed (Years)
1 YORK YCAL0080EC17XCASDTCLXXRL RFPM011813 80.9 Air Cooled 0 #80+80 R-22 MODEL # IS THE SAME FOR BOTH CHILLERS
2 YORK XXXX42SX1XXXXDTAXXBXX7BX RFPM011812 80.9 Air Cooled 0 #80+80 R-22
TOTAL TONNAGE: 161.8
EAST CAMPUS OFFICE BUILDING Location: 2008 NE WALDO ROAD Bldg Number: 1628
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Notes
No. KW/Ton Installed (Years)
3 YORK YC1V0177SA46VABS RMVM025644 186.6 Air Cooled 2010 1 R-134A
4 YORK YC1V0177SA46VABS RMVM025648 186.6 Air Cooled 2010 1 R-134A
TOTAL TONNAGE: 373.2
ELMORE HALL Location: RADIO ROAD Bldg Number: 0465
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Notes
No. KW/Ton Installed (Years)
1 YORK YCAL0061EC17XDASDXXXXXXL RNPM013377 56 Air Cooled 2006 5 R-22 #450

TOTAL TONNAGE: 56
NANO BUILDING Location: 100 CENTER DRIVE Bldg Number: 0070
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Notes
No. KW/Ton Installed (Years)
1 McQuay WGZ060AW27-ER-10 STNU070500064 60 Wtr-Cooled Scroll 2008 3 R-22 #172

TOTAL TONNAGE: 60
WHITNEY LAB Location:9505 OCEAN SHORE Blvd. St. AUGUSTINE Bldg Number: 1712
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Refrigerant Notes
No. KW/Ton Installed (Years)
1 CARRIER 30RBA09062 0906Q80869 90 Air Cooled 0 172# 410A

TOTAL TONNAGE: 90
TOTALTONNAGE REMOTE CHILLERS 2391

377399504.xls,Attachment C1
BUILDING MAINTENANCE: PK YONGE - REMOTE CHILLERS INVENTORY 4/1/2011
PK YONGE Location: 1080 SW 11 STREET Bldg Number: '0510
Orig. Chiller Year Age
Chiller No. Mfg. Model No. Serial No. Tonnage Refrigerant Notes
KW/Ton Type Installed (Years)
1 TRANE RTAA1004YN01A3 DOB KMN U03A08299 100 Air Cooled 0 R-22 #73+73
2 McQuay AGZ035BS12-ER11 STNU040300027 Air Cooled 0 R-22 #29+29
TOTAL TONNAGE: 100
HSC CHILLERS
COLLEGE OF VETERNARY MEDICINE Location: Bldg Number:
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton

1 Trane CVHF770 L95E05254 700 Elec Centrifugal 1995 16 R-123


2 Trane CVHF1070 L10B00691 850 Elec Centrifugal 2010 1 R-123
3 Trane R123CVHE089R00 N07B01677 850 Elec Centrifugal 1989 22 R-123
4 Trane R123CVHE06300P NO5C03465 500 Elec Centrifugal 1988 23 R-123
5 Trane CVHF770 L95E05448 700 Elec Centrifugal 1995 16 R-123
6 Trane CVHF770 L95E05449 700 Elec Centrifugal 1995 16 R-123
TOTAL TONNAGE: 4300
CANCER/GENETICS Location: Bldg Number:
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Notes Refrigerant Remarks
No. KW/Ton Installed (Years)
1 Trane CVHF1280 L04MO5637 1200 Elec Centrifugal 2005 6 R-123
2 Trane CVHF1280 L04M05660 1200 Elec Centrifugal 2005 6 R-123
3 Trane CVHF1280 L04M05668 1200 Elec Centrifugal 2005 6 R-123
4 Trane CVHF770 L04M05640 750 Elec Centrifugal 2005 6 R-123
TOTAL TONNAGE: 4350
ORTHOPAEDICS Location: Bldg Number:
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Carrier 30HXC171RZE66OKA 0804Q03543 175 SCREW CHILLER 2004 7 HFC-134A
2 Carrier 30HXC186RZE660KA 0804Q03561 175 SCREW CHILLER 2004 7 HFC-134A
3 Carrier 30HXC186RZE660KA 0804Q03556 175 SCREW CHILLER 2004 7 HFC-134A

TOTAL TONNAGE: 525


DERISO HALL Location: Bldg Number: 0165
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane RAUCC604BY C05M11563 60 Air-Cooled Scroll 2005 R-407C

TOTAL TONNAGE: 60
RACI
NG RACE LAB Location: Bldg Number: 0727
LAB
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane CGAFC60EAB C98M00467M 60 Air-Cooled Scroll 1998 R-407C

TOTAL TONNAGE: 60
CLINICAL TRIALS Location: Bldg Number: 0892
Chiller Orig. Year Age
Manufacturer Model No. Serial No. Tonnage Chiller Type Installed (Years)
Notes Refrigerant Remarks
No. KW/Ton
1 Trane RTAA070XM UO1K02206 70 Air-Cooled Screw 2001 R-22

TOTAL TONNAGE: 70

TONNAGE TOTAL ALL HSC CHILLERS 9,365