Sie sind auf Seite 1von 8

Medium Voltage Dynamic Voltage Restorer (DVR)

Based on DFCM Converter for Power Quality


Improvement
Vahid Dargahi1, Student Member, IEEE, Arash Khoshkbar Sadigh2, Member, IEEE, and Keith Corzine1, Senior
Member, IEEE
1
Microgrid and Power Electronics Laboratory, Holcombe Department of Electrical and Computer Engineering, Clemson
University, Clemson, SC 29634, USA
2
Extron Electronics, Anaheim, CA 92805, USA

Abstract— In the present electric power grids, power sudden changes of load, energizing of transformers or
quality issues are recognized as a crucial concerns and a switching operations in the grid [8]–[10]. According to the
frequently occurring problem possessing significant costly IEEE STD 1159-2009, voltage sag (also called voltage dip
consequence such as sensitive load tripping and production in the IEC terminology) is defined as a decrease of 0.1 to
loss. Consequently, demand for high power quality and 0.9 p.u. in the rms voltage at system frequency and with the
voltage stability becomes a pressing issue. Dynamic duration of half cycle to one minute [11].
voltage restorer (DVR), as a custom power device, is one of Due to the above mentioned effects of voltage sags on
the most effective solutions for “restoring” the quality of sensitive loads, compensating voltage sags and minimizing
voltage at its load-side terminals when the quality of their effects is necessary. Traditional methods of
voltage at its source-side terminals is disturbed. In this suppressing voltage variations include tap-changing
paper, a new DVR topology based on double flying transformers and uninterruptible power supplies (UPS)
capacitor multicell (DFCM) converter for medium-voltage [12]. However, tap-changing transformer is bulky, costly
application has been proposed. The advantage of the and not fast enough to eliminate the voltage sag effects at
proposed DVR is that it does not need any line-frequency load side. On the other hand, UPS is bulky and expensive
step-up isolation transformer, which is bulky and costly, to device whose power rating should be same as load power
be connected to medium-voltage power grid. The proposed rating [13]. Furthermore, there are custom power devices
DVR topology obtains the required active power from the such as static synchronous compensator (STATCOM),
energy storage feeding the dc link of the DFCM converter. distribution-STATCOM (D-STATCOM), unified power-
The pre-sag compensation method, which is explained in quality conditioner (UPQC), and dynamic voltage restorer
detail, is used to restore amplitude and angle of the (DVR) as power electronics based solutions to minimize
sensitive load voltage. Moreover, an approach based on d-q costly outcomes of voltage sags [12]. In comparison, DVR
synchronous reference frame to determine DVR reference is more effective and direct solutions for “restoring” the
voltages is utilized. The proposed DVR topology is quality of voltage at its load-side terminals when the
simulated and results to illustrate its performance under quality of voltage at its source-side terminals is disturbed
various conditions of voltage sag compensation are [14]–[17].
provided. DVRs compensate voltage sags by injecting the proper
Index Terms – Double Flying Capacitor Multicell amount of voltages in series with the supply voltage, in
Converter; Dynamic Voltage Restorer; Multilevel Power order to maintain the load side voltage within the
Converters; Power Quality; Voltage Sag. specification [18]–[21]. Typically, a DVR consists of an
I. INTRODUCTION energy storage device and an inverter which is coupled via
a series transformer to grid. The purpose of inverter is
In recent years, the number of sensitive loads injecting the series voltage with a controlled magnitude and
integrated to the power grid has been increased [1]–[3]. phase angle to restore the quality of load voltage and avoid
Consequently, the demand for high power quality and load tripping [2], [22], [23].
voltage stability becomes a significant issue. In the present It is worth mentioning that for medium voltage
power grids, voltage sags are recognized as a serious threat applications it is needed to use step up line-frequency
and a frequently occurring power-quality problem and have transformer at the output of DVR to be able to connect
costly consequence such as sensitive loads tripping and DVR to medium-voltage power grid. However, this
production loss [4]–[7]. transformer is bulky and heavy and can be a concern in
Voltage sags are results of transient phenomenon in cases with limited area. To avoid this issue, this paper
power grid such as short circuits in the upstream power proposes new DVR topology based on double flying
transmission line or parallel power distribution line capacitor multicell (DFCM) converter for medium-voltage
connected to the point of common coupling (PCC), inrush application. With this approach, there is no need to utilize
currents involved with the starting of large machines, line-frequency step-up transformer at the output of DVR to

978-1-5090-0687-8/16/$31.00 ©2016 IEEE


match power grid voltage rating. This paper is organized as phasors are line-to-neutral voltages. For this strategy, the
follows. Section II discusses pre-sag compensation method PLL is synchronized with the load voltage. As soon as a
with detailed analysis. In Section III, new DVR topology failure occurs, the PLL will be locked and so, the phase
based on DFCM converter is proposed and its advantages angle can be restored [22].
are discussed. In Section IV, DVR reference voltage
determination is explained in detail and requisite equations The magnitude of DVR injected series voltage in this
are derived based on d-q synchronous reference frame. compensation method is not minimal and it depends on
Comprehensive simulation results of the proposed DVR both amount of voltage drop and phase jump during the
based on the DFCM converter are provided in Section V to voltage sag because the phase jump of the grid voltage has
show its performance and ability to compensate different also to be compensated by the DVR. Consequently, DVR
power quality problems. Finally, Section VI offers has to be designed for the highest possible voltage sag
concluding observations. compensation. Furthermore, voltage rating of dc link in
DVR controlled with this method needs to be larger than
one controlled with in-phase compensation method.
Moreover, this compensation strategy leads to the lowest
distortions at the load-side because both phase angle and
magnitude of the voltage at the load-side are restored
during the sag. Thus, the sensitive load doesn’t sense any
voltage disturbance. This method is so reliable and proper
to protect sensitive loads without having any possible
transient and circulating currents. Moreover, even if the
phase jumps of the grid voltage in each phase are not the
same, DVR controlled with pre-sag compensation method
can eliminate the voltage disturbance completely. This
strategy is able to compensate any kind of voltage sags
Figure 1. General topology of DVR.
including balanced or unbalanced voltage sags with or
without any phase-variations in each phase of grid voltages.
Regarding the amount of power exchanged between
DVR and power grid, pre-sag compensation method injects
both active and reactive power depends on magnitude of
injected voltage, grid voltage phase jump and phase angle
difference between load voltage and load current phasors.
The reason for injecting active power is that the injected
voltage phasor is not certainly perpendicular to the load
current phasor in this method as like as in-phase
compensation method. Consequently, it needs the active
power to be supplied at dc link side otherwise this method
can’t compensate deep voltage sags for a long time. Thus,
without supporting the active power at the dc link, dc link
voltage will drop during the compensation and as a result,
the maximum producible voltage of DVR will decrease and
the modulation index of series converter will increase
continuously and therefore, over-modulation may occur.
Figure 2. Phasor diagram of pre-sag compensation strategy. The power rating of DVR controlled by pre-sag
compensation method and the amount of the exchanged
active power between DVR and power grid are as follows:
II. PRE-SAG COMPENSATION METHOD
S DVR =  Vgrid
′ , k ⋅ I load  (1)
The basic concept of DVR is shown in Figure 1. A k =a , b , c

commonly used method for compensating voltage sags is PDVR = Pload − Pgrid
restoring the load voltage to the level and condition before
the sag [2], [18]. Therefore, the amplitude and the phase of 3 ⋅ Vload ⋅ I load ⋅ cos(φ )  (2)
= − 
the voltage before the sag have to be exactly restored [2],   Vgrid , k ⋅ I load ⋅ cos (φ − δ k )  
 ′ 
[18]. The phasor diagram of the pre-sag compensation  k =a , b , c 
strategy is shown in Figure 2. In this figure, dashed where, δk is the phase jump in phase k. The magnitude of
′ , Vload
quantities ( Vgrid ′ , Vdvr
′ and Iload
′ ) indicate variables injected voltage is:
after the sag. The phasors prior to the sag are represented
+ (Vgrid
′ ,k )
2
(Vload )
2

by Vgrid , Vload and Iload . Moreover, angle of φ is phase ′ ,k = 2 ⋅


VDVR (3)
′ , k ⋅ cos (δ k )
−2 ⋅ Vload ⋅ Vgrid
angle difference between the load voltage and load current
phasors and angle of δ is phase jump of grid voltage and the phase angle of injected voltage phasor is:
during the voltage sag. All of the load and grid voltage
 V ⋅ sin (ϕ ) − Vgrid
′ , k ⋅ sin (ϕ − δ k )  voltages to compensate voltage disturbances. Generally, FC
′ ,k = arctan  load
∠VDVR
 V ⋅ cos (ϕ ) − V ′ ⋅ cos (ϕ − δ )  (4)
voltages in FC-based converters are more diverse whenever
 load grid , k k  the number of cells is high and so it is not more practical to
have high number of cells. To negate this disadvantage, a
III. PROPOSED DVR BASED ON DFCM CONVERTER topology called DFCM converter has been proposed in [33]
Figure 3 illustrates general scheme of proposed DVR wherein the number of FCs and power switches is half of
which is based on DFCM converter. The main advantage of those in the conventional topology of an FCM converter for
the proposed DVR is that it has the capability of direct generating the same stepped output voltage. More details
connection to medium-voltage power grid without any about the principles of DFCM converter operation are
step-up line-frequency transformer which is bulky and presented in [33].
heavy. This advantage is obtained thanks to utilization of
DFCM converter as a core inverter of DVR to inject series

Figure 3. Proposed DVR based on DFCM converter for medium-voltage applications.


determining the reference of DVR series injected voltage is
IV. DVR REFERENCE VOLTAGE DETERMINATION
to measure the line-to-neutral grid voltages and transfer
The control system of DVR has two main parts; the them from abc coordinate system to SRF as follows:
first one is voltage sag detection part and the second part of  
DVR control system is determining the reference of DVR Vgrid , d  cos(ωt ) cos(ωt − 120) cos(ωt + 120)  Vgrid , a 
  2    (5)
series injected voltage. The approach to determine Vgrid , q  = 3  sin(ωt ) sin(ωt − 120) sin(ωt + 120)  ⋅ Vgrid ,b 
reference signal of DVR series injected voltage is based on Vgrid ,0   1 1 1  V 
     grid ,c 
the type of energy storage device and its ability to support  2 2 2 
active power. One of the methods for compensating voltage where, Vgrid , a , Vgrid ,b , Vgrid ,c are the measured line-to-
sags is restoring the load voltage to the level and condition
neutral grid voltages of phases a, b and c, respectively and
before the sag, called pre-sag method [2], [18]. Therefore,
the amplitude and the phase angle of the voltage before the Vgrid , d , Vgrid ,q , Vgrid ,0 are the d-component, q-component
sag have to be exactly restored. For this strategy, the PLL is and zero-component of grid voltages in the SRF,
synchronized with grid voltage and its phase angle is respectively. The phase angle of phase a voltage in pre-sag
backed up and stored in memory continuously. As soon as state (no-fault condition) is stored as the reference angle as
a voltage sag is detected, the PLL will be locked to the follows:
phase angle stored in the memory and so, the phase angle  Vgrid , d 
can be restored [2], [18]. The magnitude of DVR injected θ ref = arctan  dc 
(6)
series voltage in the pre-sag compensation method depends  Vgrid , q 
 dc 
on both amount of voltage drop and phase jump during the
voltage sag; because the phase jump of the grid voltage has where, V grid , d and V grid ,q are dc values of d- and
dc dc
also to be compensated by the DVR. In the synchronous q-components of grid voltages in SRF, respectively. After a
reference frame (SRF)-based method, the first step of voltage sag is detected using the proper detection method,
the reference fundamental amplitude of line-to-neutral grid A. Shallow and Deep Balanced Voltage Sag Compensation
with Phase Jump in Grid Voltages
) and the obtained reference angle ( θ
ref ref
voltages ( V g1 ) are
used to determine the values of reference grid voltages in In this case study, shallow and deep balanced voltage
the SRF as follows: sag with a phase jump in all three-phases of grid voltages is
considered to occur as a power quality issue. The system is
ref
V grid ref
, d = V g 1 ⋅ sin θ
ref
(7)( ) subjected to shallow balanced voltage sag which takes
ref
V grid ref
, q = Vg1 ⋅ cos (θ ) ref
(8) place at = 0.12 s and restores to its normal condition at
= 0.2 s. During this shallow balanced voltage sag,
ref ref voltage amplitudes drop to 90% of their rated values
where, Vgrid ,d and Vgrid ,q are the reference d- and q-
coinciding with a −15 ° phase shift in voltage angles in all
components of grid voltages in the SRF, respectively. Next, three-phases. Moreover, to demonstrate deep balanced
the differences between the dq0 values of line-to-neutral voltage sag incident, voltage sag occurring at = 0.22 s
grid voltages and the dq0 values of reference line-to-neutral and lasting for 4 cycles is considered as a power quality
grid voltages are taken into account as dq0 values of DVR concern. During this balanced voltage sag, voltage
reference injected voltages as follows: amplitudes drop to 60% of their nominal value coinciding
ref ref
Vdvr ,d = Vgrid ,d − Vgrid ,d (9) with a +15 ° phase shift in voltage angles in all three-
ref ref phases. As depicted in Figure 4, proposed voltage sag
Vdvr ,q = Vgrid ,q − Vgrid ,q (10) detection method is able to detect voltage sag promptly and
ref
Vdvr = −Vgrid ,0 (11) the SRF-based approach determines three reference
,0
voltages for DVR. According to Figure 4 and Figure 5,
ref ref ref
where, V dvr ,d
, V dvr ,q
and V dvr ,0
are the reference d- proposed topology for DVR achieves both objectives of the
component, q-component and zero-component of DVR voltage sag mitigation across sensitive load, and natural
series injected voltages in the SRF, respectively. These voltage balancing mechanism for flying capacitors for
values are transferred to abc coordinate system and then, DFCM converter safe and proper operation.
three single-phase reference voltages of DVR are obtained
as follows: B. Shallow and Deep Unbalanced Voltage Sag
Compensation with Phase Jump in Grid Voltages
Vdvr
ref   ref 
 ,a
  cos(ωt ) sin(ωt ) 1 Vdvr , d 
In this case study, shallow and deep unbalanced
V ref  =  cos(ωt − 120) sin(ωt − 120) 1 ⋅ Vdvr
ref  (12)
 dvr ,b     ,q
 voltage sag with a phase jump in two phases of grid
Vdvr
ref  cos(ωt + 120) sin(ω t + 120) 1  ref  voltages is considered to occur as a power quality concern.
 , c  Vdvr ,0  The system is subjected to shallow unbalanced voltage sag
ref
where, Vdvr ,a , Vdvr
ref ref
,b and V dvr , c are DVR reference
which takes place at = 0.12 s and restores to its normal
condition at = 0.2 s. During this shallow unbalanced
injected voltages of phase a, b and phase c, respectively.
voltage sag, voltage amplitudes of two-phases (phase a and
V. SIMULATION RESULTS phase b) drop to 90% of their rated values coinciding with a
−15 ° phase shift in their angles. Moreover, to demonstrate
Computer simulation results are provided to verify deep unbalanced voltage sag incident, voltage sag
performance of the proposed DVR topology. The occurring at = 0.22 s and lasting for 4 cycles is
parameters used in the simulation are abridged in Table-1. considered as a power quality concern. During this
The simulations are performed for two different case unbalanced voltage sag, voltage amplitudes of two phases
studies of voltage sag disturbances. Simulation results are (phase b and phase c) drop to 60% of their nominal value
given in the following subsections. coinciding with a +15 ° phase shift in their voltage angles.
As depicted in Figure 6, proposed voltage sag detection
TABLE-1: SIMULATED SYSTEM PARAMETERS OF THE method is able to detect voltage sag promptly and the SRF-
PROPOSED DVR TOPOLOGY FOR VOLTAGE COMPENSATION based approach determines three reference voltages for
System Parameters Values DVR.
Nominal voltage (line-to-line), Vgrid (kV rms) 20 VI. CONCLUSION
Voltage rating of main dc link in DVR, E (kV) 4.2 Power quality problems are one of the major concerns
in present electric power grids. To suppress the power
System frequency (Hz) 50
quality problems, DVRs are suitable devices to compensate
Capacitance of flying capacitors employed in these voltage disturbances, protect sensitive loads and
2000
DFCM converter (μF)
restore their voltage during voltage sag. In this paper, a new
Carrier frequency for switching of DFCM topology of DVR suitable for medium-voltage applications
2
converter (kHz)
is proposed. The proposed configuration of DVR is based
Resistance, inductance, and capacitance of output
filter Rf (Ω), Lf (mH), Cf (μF)
0.2, 0.25, 300 on DFCM converter whose dc link is fed from battery. The
Resistance & inductance of the sensitive load RL
advantage of the proposed DVR is that it can connect to
50; 0.15 medium-voltage power grid without any line-frequency
(Ω), LL (H)
Nominal voltage (line-to-line), Vgrid (kV rms) 20
step-up isolation transformer which is bulky and costly.
Furthermore, the procedure and method of pre-sag
compensation is reviewed, investigated and discussed in calculate the reference voltage are derived. Finally, the
detail. The amplitude of the injected voltage by DVR and proposed topology is tested under different power quality
amount of active power exchanged between DVR and problems. It has been shown that proposed DVR utilizing
power grid for pre-sag compensation method are analyzed. discussed DVR reference voltage determination method
In addition, DVR reference voltage determination method can compensate voltage sag effectively and protect the
is discussed in detail and the requisite equations to sensitive loads.
Grid Voltage (phase a) Grid Voltage (phase b) Grid Voltage (phase c)
20.0k
15.0k
10.0k
5.0k
Volt

0.0
-5.0k
-10.0k
-15.0k
-20.0k
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

DVR Voltage (phase a) DVR Voltage (phase b) DVR Voltage (phase c)


10.0k
7.5k
5.0k
2.5k
Volt

0.0
-2.5k
-5.0k
-7.5k
-10.0k
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

Load Voltage (phase a) Load Voltage (phase b) Load Voltage (phase c)


20.0k
15.0k
10.0k
5.0k
Volt

0.0
-5.0k
-10.0k
-15.0k
-20.0k
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

DVR Reference (phase a) DVR Reference (phase b) DVR Reference (phase c)


1.00
0.80
0.60
0.40
Per Unit

0.20
0.00
-0.20
-0.40
-0.60
-0.80
-1.00
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

Figure 4. Simulation results of the first case study performed for voltage sag mitigation using pre-sag compensation method: (a) grid voltages; (b) DVR
injected voltages; (c) sensitive load voltages; (d) DVR reference voltages in per unit.
EC1 (phase a) EC2 (phase a) EC3 (phase a) EC4 (phase a) EC5 (phase a)
4.2k
3.5k
2.8k
Volt

2.1k
1.4k
0.7k
0.0
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

EC1 (phase b) EC2 (phase b) EC3 (phase b) EC4 (phase b) EC5 (phase b)
4.2k
3.5k
2.8k
Volt

2.1k
1.4k
0.7k
0.0
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

EC1 (phase c) EC2 (phase c) EC3 (phase c) EC4 (phase c) EC5 (phase c)
4.2k
3.5k
2.8k
Volt

2.1k
1.4k
0.7k
0.0
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

Figure 5. Simulation results of the first case study performed for voltage sag mitigation using pre-sag compensation method: (a) flying-capacitor voltages
in phase a of the DFCM converter; (b) flying-capacitor voltages in phase b of the DFCM converter; (c) flying-capacitor voltages in phase c of the DFCM
converter.
Grid Voltage (phase a) Grid Voltage (phase b) Grid Voltage (phase c)
20.0k
15.0k
10.0k
5.0k
Volt

0.0
-5.0k
-10.0k
-15.0k
-20.0k
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

DVR Voltage (phase a) DVR Voltage (phase b) DVR Voltage (phase c)


10.0k
7.5k
5.0k
2.5k
Volt

0.0
-2.5k
-5.0k
-7.5k
-10.0k
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

Load Voltage (phase a) Load Voltage (phase b) Load Voltage (phase c)


20.0k
15.0k
10.0k
5.0k
Volt

0.0
-5.0k
-10.0k
-15.0k
-20.0k
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

DVR Reference (phase a) DVR Reference (phase b) DVR Reference (phase c)


1.00
0.80
0.60
0.40
Per Unit

0.20
0.00
-0.20
-0.40
-0.60
-0.80
-1.00
t (sec) 0.100 0.120 0.140 0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320

Figure 6. Simulation results of the second case study performed for voltage sag mitigation using pre-sag compensation
method: (a) grid voltages; (b) DVR injected voltages; (c) sensitive load voltages; (d) DVR reference voltages in per unit.
REFERENCES Electronics Conference and Exposition (APEC), 2001, vol. 2,
pp. 1267–1273.
[1] F. Badrkhani Ajaei, S. Farhangi, and R. Iravani, “Fault Current [19] Y. W. Li, P. C. Loh, F. Blaabjerg, and D. M. Vilathgamuwa,
Interruption by the Dynamic Voltage Restorer,” IEEE Trans. “Investigation and Improvement of Transient Response of DVR
Power Deliv., vol. 28, no. 2, pp. 903–910, Apr. 2013. at Medium Voltage Level,” IEEE Trans. Ind. Appl., vol. 43, no.
[2] P. Roncero-Sanchez, E. Acha, J. E. Ortega-calderon, V. Feliu, 5, pp. 1309–1319, 2007.
A. Garcia-Cerrada, P. Roncero-sánchez, and S. Member, “A [20] C.-S. Lam, M.-C. Wong, and Y.-D. Han, “Voltage Swell and
Versatile Control Scheme for a Dynamic Voltage Restorer for Overvoltage Compensation With Unidirectional Power Flow
Power-Quality Improvement,” IEEE Trans. Power Deliv., vol. Controlled Dynamic Voltage Restorer,” IEEE Trans. Power
24, no. 1, pp. 277–284, Jan. 2009. Deliv., vol. 23, no. 4, pp. 2513–2521, Oct. 2008.
[3] B. Wang and G. Venkataramanan, “Dynamic Voltage Restorer [21] Y. W. Li, F. Blaabjerg, D. M. Vilathgamuwa, and P. C. Loh,
Utilizing a Matrix Converter and Flywheel Energy Storage,” “Design and Comparison of High Performance Stationary-
IEEE Trans. Ind. Appl., vol. 45, no. 1, pp. 222–231, 2009. Frame Controllers for DVR Implementation,” IEEE Trans.
[4] T. Jimichi, H. Fujita, and H. Akagi, “Design and Power Electron., vol. 22, no. 2, pp. 602–612, Mar. 2007.
Experimentation of a Dynamic Voltage Restorer Capable of [22] S. R. Naidu and D. A. Fernandes, “Dynamic voltage restorer
Significantly Reducing an Energy-Storage Element,” IEEE based on a four-leg voltage source converter,” IET Gener.
Trans. Ind. Appl., vol. 44, no. 3, pp. 817–825, 2008. Transm. Distrib., vol. 3, no. 5, pp. 437–447, May 2009.
[5] E. Babaei, M. F. Kangarlu, and M. Sabahi, “Mitigation of [23] B. Polajzer, G. Stumberger, S. Seme, and D. Dolinar,
Voltage Disturbances Using Dynamic Voltage Restorer Based “Generalization of Methods for Voltage-Sag Source Detection
on Direct Converters,” IEEE Trans. Power Deliv., vol. 25, no. 4, Using Vector-Space Approach,” IEEE Trans. Ind. Appl., vol. 45,
pp. 2676–2683, Oct. 2010. no. 6, pp. 2152–2161, 2009.
[6] F. M. Mahdianpoor, R. A. Hooshmand, and M. Ataei, “A New [24] B. Delfino, F. Fornari, and R. Procopio, “An Effective SSC
Approach to Multifunctional Dynamic Voltage Restorer Control Scheme for Voltage Sag Compensation,” IEEE Trans.
Implementation for Emergency Control in Distribution Power Deliv., vol. 20, no. 3, pp. 2100–2107, Jul. 2005.
Systems,” IEEE Trans. Power Deliv., vol. 26, no. 2, pp. 882– [25] H. Awad, J. Svensson, and M. Bollen, “Mitigation of
890, Apr. 2011. Unbalanced Voltage Dips Using Static Series Compensator,”
[7] M. Moradlou and H. R. Karshenas, “Design Strategy for IEEE Trans. Power Electron., vol. 19, no. 3, pp. 837–846, May
Optimum Rating Selection of Interline DVR,” IEEE Trans. 2004.
Power Deliv., vol. 26, no. 1, pp. 242–249, Jan. 2011. [26] A. Campos, G. Joos, P. D. Ziogas, and J. F. Lindsay, “Analysis
[8] P. Kanjiya, B. Singh, A. Chandra, and K. Al-Haddad, “‘SRF and design of a series voltage unbalance compensator based on a
Theory Revisited’ to Control Self-Supported Dynamic Voltage three-phase VSI operating with unbalanced switching
Restorer (DVR) for Unbalanced and Nonlinear Loads,” IEEE functions,” IEEE Trans. Power Electron., vol. 9, no. 3, pp. 269–
Trans. Ind. Appl., vol. 49, no. 5, pp. 2330–2340, Sep. 2013. 274, May 1994.
[9] J. D. Barros and J. F. Silva, “Multilevel Optimal Predictive [27] B. Wang, G. Venkataramanan, and M. Illindala, “Operation and
Dynamic Voltage Restorer,” IEEE Trans. Ind. Electron., vol. 57, Control of a Dynamic Voltage Restorer Using Transformer
no. 8, pp. 2747–2760, Aug. 2010. Coupled H-Bridge Converters,” IEEE Trans. Power Electron.,
[10] A. M. Massoud, S. Ahmed, P. N. Enjeti, and B. W. Williams, vol. 21, no. 4, pp. 1053–1061, Jul. 2006.
“Evaluation of a Multilevel Cascaded-Type Dynamic Voltage [28] D. Vilathgamuwa, H. M. Wijekoon, and S. S. Choi, “A Novel
Restorer Employing Discontinuous Space Vector Modulation,” Technique to Compensate Voltage Sags in Multiline
IEEE Trans. Ind. Electron., vol. 57, no. 7, pp. 2398–2410, Jul. Distribution System-The Interline Dynamic Voltage Restorer,”
2010. IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1603–1611, Oct.
[11] C. N.-M. Ho and H. S.-H. Chung, “Implementation and 2006.
Performance Evaluation of a Fast Dynamic Control Scheme for [29] D. M. Vilathgamuwa, A. A. D. R. Perera, and S. S. Choi,
Capacitor-Supported Interline DVR,” IEEE Trans. Power “Voltage sag compensation with energy optimized dynamic
Electron., vol. 25, no. 8, pp. 1975–1988, Aug. 2010. voltage restorer,” IEEE Trans. Power Deliv., vol. 18, no. 3, pp.
[12] A. Prasai and D. Divan, “Zero Energy Sag Correctors - 928–936, Jul. 2003.
Optimizing Dynamic Voltage Restorers for Industrial [30] A. Ghosh and G. Ledwich, “Compensation of distribution
Applications,” in 2007 IEEE Industry Applications Annual system voltage using DVR,” IEEE Trans. Power Deliv., vol. 17,
Meeting, 2007, pp. 1585–1592. no. 4, pp. 1030–1036, Oct. 2002.
[13] A. Y. Goharrizi, S. H. Hosseini, M. Sabahi, and G. B. [31] A. G. Ghosh, A. K. Jindal, and A. Joshi, “Design of a Capacitor-
Gharehpetian, “Three-Phase HFL-DVR With Independently Supported Dynamic Voltage Restorer (DVR) for Unbalanced
Controlled Phases,” IEEE Trans. Power Electron., vol. 27, no. 4, and Distorted Loads,” IEEE Trans. Power Deliv., vol. 19, no. 1,
pp. 1706–1718, Apr. 2012. pp. 405–413, Jan. 2004.
[14] N. H. Woodley, A. Sundaram, T. Holden, and T. C. Einarson, [32] A. Khoshkbar Sadigh and K. M. Smedley, “Review of voltage
“Field experience with the new platform-mounted DVR,” in compensation methods in dynamic voltage restorer (DVR),” in
PowerCon 2000. 2000 International Conference on Power IEEE Power and Energy Society General Meeting, 2012, pp. 1–
System Technology. Proceedings (Cat. No.00EX409), vol. 3, pp. 8.
1323–1328. [33] A. Khoshkbar Sadigh, S. H. Hosseini, M. Sabahi, and G. B.
[15] Y. W. Li, P. C. Loh, F. Blaabjerg, and D. M. Vilathgamuwa, Gharehpetian, “Double Flying Capacitor Multicell Converter
“Investigation and Improvement of Transient Response of DVR Based on Modified Phase-Shifted Pulsewidth Modulation,”
at Medium Voltage Level,” IEEE Trans. Ind. Appl., vol. 43, no. IEEE Trans. Power Electron., vol. 25, no. 6, pp. 1517–1526,
5, pp. 1309–1319, 2007. Jun. 2010.
[16] C. S. Lam, M. C. Wong, and Y. D. Han, “Voltage Swell and
Overvoltage Compensation With Unidirectional Power Flow
Controlled Dynamic Voltage Restorer,” IEEE Trans. Power
Deliv., vol. 23, no. 4, pp. 2513–2521, Oct. 2008.
[17] Y. W. Li, F. Blaabjerg, D. M. Vilathgamuwa, and P. C. Loh,
“Design and Comparison of High Performance Stationary-
Frame Controllers for DVR Implementation,” IEEE Trans.
Power Electron., vol. 22, no. 2, pp. 602–612, Mar. 2007.
[18] J. G. Nielsen, F. Blaabjerg, and N. Mohan, “Control strategies
for dynamic voltage restorer compensating voltage sags with
phase jump,” in Sixteenth Annual IEEE Applied Power

Das könnte Ihnen auch gefallen