Settings for 15 MW Generator Date : September 14, 2007

Machine Data :
Make of Alternator TDPS
Rated Capaity of Alternator (KW) 15000
Rated Capaity of Alternator (KVA) 18750
FLC of alternator(A) In 984
Rated voltage(V) Un 11000
Rated frequency (Hz) 50
Combined variation 10
Power factor(lag) 0.8
Excitation current 600
NGR value(OHM) 63.5
E/F current(A) 100
Phase CT Core 1 1200/ 1 Amp, 5 P 10
Phase CT Core 2 1200/ 1 Amp, PS, Ie@Vk/2 = 30 ms, Rct - 6 Ohm, 2RL = 1 Ohm
Neutral CT 100/ 1 Amp, 5 P 10, 15 VA
PT 11000/ 110v
CTR - Core 1 1200
CTR - Core 2 1200
PTR 100
secondary value of Phase Current at Full load 0.82
secondary value of Neutral Current at Full load 1

relay Function Indication / Display unit Basis / Assumption of calculations Programming value Realy Assignment

MRQ1 - Loss of Excitation - CT ; 1 A sec, PT : 110v

Pick up of Under Voltage Element U< V 80 % of rated voltage 88


tripping time of under voltage element tu< sec 0.5 Trip
Pick up of Impedance element Z1A Z1A % Assuming grid impedance of 20 % 24
Pick up of Impedance element Z1B m % as per m/c data 250
tripping time for under impeance of Z1 tz1 sec as per m/c data 2 Trip
Pick up of Impedance element Z2A Z2A % as per m/c data -19
Pick up of Impedance element Z2B Z2B % as per m/c data 206
tripping time for under impeance of Z2 tz2 sec as per m/c data 0.5 Trip
function blocking led of bloked perameter EXIT

MRS1 - Negative Phase Sequance CT ; 1 A sec


Negative seq which leads to waring I2w x In 20 % of FL (sec value) 0.164
Time Delay for I2w tw Sec 20 20 Alarm
Continiously permissible Negaive seq. current I2s x In 21% as per NPS characteriscs 0.1722
Tripping Characteristics CHAR DEFT DEFT
Time Delay for I2s T Sec 10 10 Trip
RS address of serial interface RS as per communication ID 1

MRP2- Reverse & Low Forward Power protection - CT ; 1 A, 110V PT sec,

connections Delta / Star for 110v with N Star


Max Forward Active power increase P> x Pn EXIT
time delay for P> tp> Sec EXIT Alram Only
Low Forward Active Power Increase P< x In Un 3 % of rated capaity (+ 0.0197)
time delay for P< tp< Sec 2 2 Trip
Reverse Active Power Decrease Pr x In Un 5 % (reverse) of rated capaity (- 0.0328)
time delay for Pr tpr< Sec 1 2 Trip
Under Volage dependant reverse power U< Pr volts EXIT
time delay for U< Pr tu< pr sec EXIT
CB Failure detection time t cbfp sec EXIT

MRI1-IU - Voltage Restrain Over Current CT ; 1 A, 110V PT sec,

IDMT - low Set Current at nominal voltage I> ; U (green) x In 125% of FLC 1.025
IDMT - low Set Current at low voltage I> ; U (red) x In 20% of FLC 0.164
Trippiing Characteristics CHAR I> NINV
Time Multiplier setting for IDMT ti> as per Current capability curve 0.15 Trip
reset time I>; CHAR I>, ti> Sec pulse operation 0
Instantenious High Set Current at nominal voltage I>> ; U (green) x In 200% of FLC 1.64
Instantenious Low Set Current at low voltage I>> ; U (red) x In 75% of FLC 0.615
Time Delay ti>> Sec as per machine data sheet 0.1 Trip
Under voltage switch value U volt 80% of rate voltage 88
Nominal frequency f = 50 hz 50

MRU1- Under & over Voltage protection - 110V PT sec,

connections Delta / Star for 110v with N Star


Under voltage (low set) U< Volts 90% of rated voltage 99
tripping delay for under voltage U< tu< Sec 5 sec 5 Alarm
Under voltage (High set) U<< Volts 85% of rated voltage 93.5
tripping delay for under voltage U<< tu<< Sec 2 sec 2 Trip
Over voltage (low set) U> Volts 110% of rated voltage 121
tripping delay for over voltage U> tu> Sec 5 sec 5 Alarm
Over voltage (High set) U>> Volts 115% of rated voltage 126.5
tripping delay for over voltage U>> tu>> Sec 2 sec 2 Trip
MRF2- Under & Over Frequancy Protection 110V PT sec,

nominal Frequency fn Hz 50
Measuring repetation for frequacny measurement T 2
Pick up for first frequency element f1 Hz (-) 4 % of rated freq 48 Alarm
Tripping delay for f1 ft1 sec 5
Pick up for second frequency element f2 Hz (-) 5 % of rated freq 47.5 Trip
Tripping delay for f2 tf2 sec 2
Pick up for third frequency element f3 Hz (+) 4 % of rated freq 52 Alarm
Tripping delay for f3 tf3 sec 5
Pick up for forth frequency element f4 Hz (+) 5 % of rated freq 52.5 Trip
Tripping delay for f4 tf4 sec 3
theshold for df/dt element first fe + df1 Hz veri
theshold for df/dt element second fe + df2 Hz veri
Pick up for rate of change of freq df/ dt first element df1 Hz for fall in frequancy (+) 1 Trip
diffnential period for tripping timer of df1/dt1 dt1 Cycles 6 to 8
Pick up for rate of change of freq df/ dt first element df2 Hz for rise in frequancy (-) 1 Trip
diffnential period for tripping timer of df1/dt1 dt2 Cycles 6 to 8
df/dt - element 2 df2 Hz not applicable EXIT
Voltage Threshold for frequancy mesurement Ub v 70 % 0f rated voltage 77

MRI1-ITE - Over Current with Thermal Replica - CT ; 1 A sec

base currnet for thermal over load protection (Low set) I BA x In 110 % of FLC 0.902
constant ka for thermal pick up to 95% 0.95 Alram
base currnet for thermal over load protection (high set) I BT x In 100 % of FLC 0.82
constant kt for thermal pick up to 110% 1.05 Trip
time constatnt (cooling down) Tc min to be provided by Manufacturer
time constatnt (warming up / heating up) Tw min to be provided by Manufacturer
IDMT - phase Over Current I> x In 100% of FLC 0.82
Trippiing Characteristics CHAR I> as per Current capability curve NINV
Time Multiplier setting for IDMT ti> as per Current capability curve 0.4 Trip
reset time I>; CHAR I>, ti> Sec pulse operation 0
Instantenious High Set over Current I>> x In 200% of FLC 1.64
Time Delay ti>> Sec as per machine data sheet 0.05 Trip
IDMT - earth fault pick up Ie> x In 40% of CTR (100/1) 0.4
waring / tripping setting WARN / TRIP TRIP
Trippiing Characteristics CHAR Ie> as per Current capability curve NINV
Time Multiplier setting for IDMT tie> as per Current capability curve 0.1 Trip
reset time Ie>; CHAR Ie>, tie> Sec pulse operation 0
Instantenious High Set Earth Fault Ie>> x In 50% of CTR (100/1) 0.5
Time Delay tie>> Sec as per machine data sheet 0.1 Trip
Nominal frequency f = 50 hz 50

IRI1-3I-EO - 3 ph o/c with Sensitive E/f protection : Phase CT ; 1200 /1 A , Neutral CT : 100 / 1 amp

IDMT - phase Over Current I> x In 120% of FLC (CTR : 1200) 0.984
Time Multiplier setting for IDMT ti> as per Current capability curve 0.2 Trip
IDMT - earth fault pick up Ie> x In 10% of CTR (100/1) 0.1
Time Multiplier setting for IDMT tie> as per Current capability curve 0.25 Trip
Instantenious High Set over Current I>> x In 200% of FLC 1.64
Time Delay ti>> Sec as per machine data sheet 0 Trip
IDMT Characteriscs NINV
Nominal Frequency 50

IRI1-3ER - Diffrential protection : Phase CT ; 1200 /1 A , PS Class

differntial pick up setting Id> as per CT details provided & calucations 5% Trip
Stablilizing Resistor setting as per Calculations 500 Ohms