135,8+- 0.5
– The supplier neither guarantees that the PWS is suitable for your particular application, nor assumes re-
sponsibility for your product design, installation or operation. 1. Cut out the control front panel to match the dimensions (mm) specified under the External and Cut-out
dimensions chapter.
Power Source 2. Mount the PWS into the cut-out. Insert the fixtures to the holes on the unit and fasten the screws into
– The PWS is equipped with a 24 V DC input. Supply power other than 24 V DC ± 15% will severely dam- the front panel. Do not tighten the screws with too much or uneven force, or it may cause deformation
age the PWS. Thus, check the power supply supporting the DC power regularly. of the PWS. 40,2
– To avoid electric shock, be sure the power cable is unplugged from the power input when connecting the
CUTOUT DIMENSION
cable to the PWS.
STEP 1 STEP 2 STEP 3
195 (4)
Installation
– Communication cables must be separated from the power cables for operational circuits. Use shielded ca-
bles or it may cause unpredictable problems.
-
+
FG
145
135
During Use
90º
– Emergency stop and other safety functions may not be controlled from the PWS. DC 24V
– Do not use force or sharp objects when touching the keys, display etc. 135º
135º
Use Copper Conductors Only
y
Service and Maintenance
la
sp
Di
– Only qualified personnel should carry out repairs. (UNIT:mm)
– Before carrying out any cleaning or maintenance operations, disconnect the equipment from the electrical Wire Gauge
supply. Type Stripped Length Torque
Max torque: 0.3 Nm (2.65 lb-in) (AWG)
– Clean the display and surrounding front cover with a soft cloth and mild detergent. 0º Solid 28-12 7-8 mm 4.5 lb-in
– Replacing the battery incorrectly may result in explosion. Only use batteries recommended by the supplier. Display
Stranded 30-12 7-8 mm 4.5 lb-in
3. The PWS must be installed within an angle of 0° to 135° as shown above.
9 8 7 6 9 8 7 6
Note:
When using the PWS for the first time, remember to reset Real Time Clock (RTC). PIN Function PIN Function
1 NC 1 RS422 TX+ (RS485 +)
2 RS232 RXD 2 NC
3 RS232 TXD 3 NC
4 NC 4 RS422 RX+
5 GND 5 GND
Beijer Electronics AB Beijer Electronics Corp.
6 NC 6 RS422 TX- (RS485 -) Box 426
DC Power 7&8F, No.108, Minquan Rd., Xindian City,
Outlet COM1 (RS232, RS422, RS485) 7 RS232 RTS 7 NC SE-201 24 Malmö, Sweden
Taipei County, Taiwan 23141
8 RS232 CTS 8 NC Tel: +46 40 35 86 00
Tel: +886-2-2218-3600
Fax: +46 40 93 23 01
9 NC 9 RS422 RX- Fax: +886-2-2218-9547
www.beijerelectronics.com www.beijerelectronics.com.tw
09/09/2010/V.1 561018+01