0.30 m
Soil Data Assumed:
1' - 0"
0.37 m
1' - 3"
Ht. water level = 7' - 0" Clasify: M-S. Sandy Silt
Variable Actions 1.50 0.00 1.30 0.00
Unit Weight σ = 18 kN/m3
Stress State = Effective 1.00
Water Load 1.35
Angle of Internal Friction φef= 26.50°
Cohesion of soil = 12.0 kPa
Friction Angle Structure-Soil δ = 15°
Soil : Cohesionless Combinations: Permanent Design Situation (Partial Factor for Soil Parameters)
Water Volume = 466 930 US gallons
Satured unit weight σ = 18.50 kN/m3
2.00 m
6' - 7"
Combination 1 Combination 2
Determine Ht :
1.69 m
5' - 7"
(Considering NFPA 30 Code for FLAMABLE AND COMBUSTIBLE LIQUIDS CODE) Internal Friction 1.00 1.25
2.50 m
8' - 3"
(B)* The volumetric capacity of the diked area shall not be less than the greatest amount of liquid that can be released from the largest tank www.facebook.com//mecengineeringsolutions
within the diked area, assuming a full tank.
2.13 m
Effective Cohesion 1.00 1.25
7' - 0"
To allow for volume occupied by tanks, the capacity of the diked area enclosing more than one tank shall be calculated after deducting the LOCATION
volume of the tanks, other than the largest tank, below the height of the dike.
Undrained Shear Strength 1.00 1.40 NORTH
(D)* Walls of the diked area shall be of earth, steel, concrete, or solid masonry designed to be liquidtight and to WITHSTAND A FULL
11' - 6"
3.50 m
0.10 m
12' - 6"
0.30 m
Tf= 1' - 0"
Mres > Movr (Wall for Overturning 56 % is SATISFACTORY) Mres > Movr (Wall for Overturning 39 % is SATISFACTORY)
NOTES
Check for slip: Check for slip:
Resisting Horizontal Force HRES = 38.69 kN/m Resisting Horizontal Force HRES = 36.30 kN/m
Active horizontal Force HACT =- -42.77 kN/m Active horizontal Force HACT =- -34.33 kN/m
HRES > HACT (Wall for slip 0.0% is SATISFACTORY) HRES > HACT (Wall for slip 0.0% is SATISFACTORY)
6' - 11"
Overall check = Wall is SATISFACTORY. Overall check = Wall is SATISFACTORY.
2.10 m
Maximum stress in footing bottom = 48.15 kPa Maximum stress in footing bottom = 48.15 kPa
REVIEWS
NOMBER DATE
01/05/18
01/05/18
01/05/18
REFERENCE FILES
FILE N° DESCRIPTION APROVED
12' - 6"
12' - 6"
12' - 6"
3.80 m
3.80 m
(0.30,-0.77)
3.80 m
3.80 m
Fx = 51.16 kN/m ENGINEER:
Water Pressure
(0.30,-0.33)
Water Pressure
ENG. RAUDEL MORENO
DRAFTSMAN:
ENG. RAUDEL MORENO
Fx = 4.97 kN/m Fx = 0.03 kN/m PROJECT
(0.0,-0.05) (0.3,-0.03) Fx = 61.25 kN/m
FF resistance Pressure at rest Fz = 35.52 kN/m (1.48,-1.17) DIKE WALL FOR COMBUSTIBLE
(0.9,-1.14) Water Pressure
Fx = 67.52 kN/m Fx = 2.67 kN/m Weight - wall Fz = 6.72 kN/m
AND FLAMMABLE LIQUID
X Fx = 95.58 kN/m Fx = 95.58 kN/m
(0.0,-0.45) (0.3,-0.33)
(0.35,-0.57) (0.35,-0.57)
(1.42,-0.73) STORAGE TANKS AREA
FF resistance Pressure at rest (x=0.0,z=0.10) Fz = 6.72 kN/m Weight - earth wedge
FF resistance FF resistance
(1.42,-0.73)
Z Weight - earth wedge
CLIENT
Fz = 7.92 kN/m
(x=0.0,z=0.0) X (1.55,-0.15) DIKE WALL DESIGN
Weight - wall
6' - 0"
1.82 m
(x=0.0,z=0.00) X (x=0.0,z=0.00) X
Z
Fz = 8.59 kN/m
6' - 11" 6' - 11" DESCRIPTION
46.53 kN/m
(1.27,0.00)
2.10 m 2.10 m Contact stress Ideal dike wall design in compliance with applicable
Z standards (NFPA 30)
WALL STEM ACTING FORCE CONSTRUCTION JOINT CHECK WALL JUMP CHECK WALL HEEL VERIFICATION
1/25/2018 9:19:24 PM
SCALE
Z 1/2" = 1'-0"
UNITS
FORCE ACTING IN TYPICAL SECTION. FEET-INCHES
DATE
Jan/2018