Messung Systems, a leading pioneer in indigenous PLC in India, has constantly innovated to achieve global
standards in designing and manufacturing PLC products. With pride, it has now launched a high performance
series of world class CPUs viz. Nexgen 5000; coupled with basic building blocks of its earlier launched and
established Nexgen 4000 PLC. This Nexgen 5000 PLC family offers a wide range of CPU variants, with
®
IEC 61131-3 compatibility, having performance excellence and Windows based programming software.
This has evolved concept of Programmable Logic Controllers (PLC) which were compact in size, having better
edge over earlier electro-mechanical devices. PLC implementation has resulted in several benefits like:
minimized panel and wiring volume, expedited program development, reliability of operations with an improved
life, PLC re-usability across the applications (conditionally), easy and quick fault finding, and ease of interface
with HMIs, SCADA like external devices.
Over the time, only application specific hardware and software products were developed by various vendors,
which addressed the problem of compatibility and portability. This has initiated necessity of products
standardization in terms of hardware as well as software.
Similarly, with the growing Industrial Automation, industry has started facing typical problems of PLC
processing speed, memory, handling of a complex or very big program, logic re-usability, avoiding
duplicate variables in programming, choice of programming language selection as per application, user
friendly software along with documentation, standardized program interface.
Subsequently, International Electro-technical Commission worked upon complete design of PLC, which
comprised of hardware design, installation, testing, programming and documentation. Several inputs from
various machine manufacturers, end-users and research institutes has evolved five part IEC 61131 standard.
This international standard IEC 61131-3 is the first substantial endeavor to standardize programming languages
for industrial automation. It emphasizes on consistent method of PLC programming which encourages the
development of quality software. IEC 61131-3 provides tools to improve intrinsic quality of software in terms of its
persistent correctness, integrity, reliability, robustness, modularity, flexibility and safety. It also deals with
programming, installation and maintenance phases of software development projects in industrial control.
Nexgen 5000 series of CPU family is programmed with CoDeSys, the Windows® based, IEC 61131-3
compatible programming software.
1
Nexgen 5000 PLC : Product Highlights
NEXGEN 5000 PLC : AN ICON OF THE FUTURE Max. 32
l A truly modular PLC modules
an icon of the future
NEXGEN
Highlights :
l User has an optional choice of pluggable keyboard display
l It has built-in freely programmable 6 functions keys &
4 character alphanumeric display
l The keyboard display can be used as a self diagnostic tool.
This is helpful for assistance in :
n Displaying fault messages
n Displaying systems messages
n Viewing / modifying PLC variables
n Redirection of Digital I/O points
2
Nexgen 5000 PLC : Product Highlights
l The display and keyboard are freely programmable for application specific functionality. Display and
keyboard is accessible in the application program through the system variables. Using these system
variables, the user can develop their own function blocks to handle display and keypad as per the
application need.
l Standard FB library for I/O/M Monitoring, Redirection of Digital I/O points are also available.
l The Keyboard Display Unit can be fixed to / removed from, the Processor module during the
module powered ON condition.
Bootstrap
Loader Tool / CoDeSys
Memory PC COM
Cassette Programming cable 9910 Port
Cassette adapter
30 VAC to 5 VDC
power supply
5 VDC Power supply
3
CoDeSys PLC Program Development Suite
Windows Based IEC Programming Software
IEC 61131-3 : A GLOBAL STANDARD
l Better Structuring of large programs
l High Reusability
l Combination of ladder program and high level programming language
l ST : Structured Text
l FBD : Function Block
Diagram
l IL : Instruction List
l SFC : Sequential
Function Chart
l CFC : Continuous
Function Chart
LD : Ladder Diagram
IEC 61131-3
FBD :
Function
Block Diagram
4
New Possibilities of Remote Operation
REMOTE PROGRAMMING VIA MODEM
PSTN
Network PC
Port - 1,
RS-232 C CoDeSys
5
New Possibilities of Remote Operation
PC2 PC1
COM Port
In this setup, the programming software 'CoDeSys' is running on PC1 and the gateway server is
remote operation
running on PC 2. The link between CoDeSys & Gateway Server is established via TCP/IP bus. The
Nexgen-5000 PLC is connected to COM port of PC2, the link between Gateway Server & PLC is
established via RS-232 bus. Or otherwise the PC2 can be directly interfaced with PLC via
programming cable.
Gateway Icon
6
Nexgen 5000 PLC Based Application Schemes
MODBUS CONNECTIVITY MADE EASIER
l While communicating with SCADA or other Nexgen 5000 PLC, one may implement MODBUS Slave.
l Similarly, while communicating with the field devices like relays, energy meters (which implement
MODBUS), PLC implements MODBUS Master.
MODBUS MASTER
Master
Master : Nexgen 5000 PLC
Slave : Enercon Energy Meter
P : Port - 2 / 3, RS 485
Network having 31 nos. of Enercon Energy Meters as slave connected to one Master Nexgen-522x CPU, using MODBUS Master.
Master FB : This FB handles serial communication with MODBUS RTU Protocol as master device. It is
useful to interface HMI, SCADA as a slave with Nexgen 5000 PLC. PLC communication can be
established with one PLC as Master and other(s) as slave(s). It can also be used to have CPU as data
logger to collect the data from Energy meters, VFDs etc.
Highlights :
l User need not know the MODBUS protocol.
l Protocol implementation is physical layer independent i.e. it can be used with RS232C, RS422 or
RS485.
l Communicates with any third party MODBUS RTU slaves inclusive of Messung PLCs with the
MODBUS RTU_Slave FB
l Easy interface with various SCADA and HMI packages as slaves is possible with appropriate FBs. No
need to develop any special driver.
l Easy connection to multiple Beijer E-terminals with it's MODBUS Slave driver
l Easy application interface by defining data exchange records with various stations
l Allows exchanging data via I, Q and M devices in Nexgen 5000 with MODBUS devices in various
stations
l Data exchange records can be grouped and called in manual, auto-cyclic and super cyclic modes.
l Flexibility in data exchange records programming.
l Programmable Retry and Time-out facility if a station fails to respond.
l Supports variety of baud rates to suit the application needs.
7
Nexgen 5000 PLC Based Application Schemes
P
P P P
Converter for
RS 232C to RS 485
Network having 31 Nos. of Nexgen 522x PLCs as slave connected to one Master Nexgen 5222-B0 CPU, using MODBUS Master and
MODBUS Slave.
MODBUS Slave FB :
It emulates MODBUS slave functionality. This FB handles serial communication with MODBUS RTU
Protocol as slave device. The RTU slave FB is useful to communicate with any external master PLC,
SCADA or DCS systems. Communication speed can be up to 56Kbps.
Highlights :
l User need not know the MODBUS protocol
l Protocol implementation is physical layer independent i.e. it can be used with RS232C, RS422 or
RS485.
l Communicates with any third party MODBUS RTU master or Messung PLC with MODBUS
RTU_Master FB Easy connection to various SCADA and HMI packages. No need to develop any
special driver.
l Easy connection to Beijer E-terminals with it's MODBUS Master driver
l Allows to exchange data via I, Q and M devices in Nexgen.
l Ready to use FB with few parameters to define to go
l Flexibility in station number programming.
l Supports variety of baud rates to suit the application needs.
8
Nexgen 5000 PLC Based Application Schemes
PLC 2
Dial-up modem
Dial-up modem
PSTN
PLC 3 Network
PC
SCADA package with
SCADA protocol driver and
modem connectivity
Dial-up modem
Dial-up modem
Multiple PLCs can be connected to PSTN network via modem. Multiple PLCs can communicate with one
or more PC/PLC at a time through modem. Either of PLC / PC or both can initiate a communication.
Once the communication is established, Protocol FB like MODBUS, Nexgen or Micro can take over a
control for Data Exchange.
PLC 1
PLC initiates a call via modem FB. Now, modem FBs establish a communication between any of the two
Nexgen-522x PLCs ( As shown in above figure ). Once the connection is established, the control is
passed to protocol FBs like MODBUS, Nexgen protocol.
The calling line / connection status can be monitored and failure of the link can be detected. In case of
lines getting busy or unreachable auto redial, auto retry is possible. Dial-In facility with auto connect
modems & Dial-Out predefined number is also feasible. Various communication speeds can be gained
based on line conditions. Connect, Initialize and Hang-up sequence for the modem can be also
controlled.
Nexgen-522x PLC, which initiates a call will implement Dial-Out FB. While PLC at other end i.e.the
responding PLC, will implement Dial-In FB.
Note : The calling PLC ( i.e. PLC which has initiated a communication call ) can be a Master or Slave.
9
Nexgen 5000 PLC Based Application Schemes
Numeric
Message
P PSTN P
Network
ser vo connectivity
Dial-up modem
GSM modem
with SIM card
Dial up modem connected to Nexgen 522x CPU , sends GSM modem connected to Nexgen 522x CPU, sends
Numeric Messages on pager, or only Ring Alert on mobile. SMS (text messages )
Patch Panel
4960
10
Nexgen 5000 PLC Based Application Schemes
Nexgen 5000 CPU provides 2 channels of HSC I/P and 2 channels of PTO O/P. To handle these
hardware resources the OS of Nexgen 5000 CPU supports external FB library PTO lib.
MC-MoveAbsolute
HSC MC-MoveRelative Analog
MFIP MC-MoveVelocity Out
Axis1 MC-Stop
Analog MC-ReadActualPosition
MC-ReadParameter PWM
Pot MC-ReadBoolParameter
Data Data
In MC-WriteParameter Out
MC-WriteBoolParameter
PTO PTO
MC-MoveHome
Under Development
Axis2 2 Axis_Interpolation
Electronic_Gearing
CANbus Phasing CANbus
CAM_Control
Its based on PLC open motion control FB guidelines. It's a universal method of motion control
irrespective of front-end interface.
11
Nexgen 5000 PLC Based Application Schemes
NEXGEN SLAVE
Nexgen slave FB is provided in FB library. By defining input parameters of FB, user can select
communication port and communication parameters to establish communication with HMI. This FB
handles serial communication with Nexgen 5000 as slave device and interfaces HMI, SCADA as a
Master.
This FB is useful to interface -
l Messung make HMIs SMARTLINESr and SMARTLINEJr
l Beijer make E terminals with NEXGEN 4000 Driver
l SCADA software which supports Nexgen protocol
Slave
Converter for
RS 232C to RS 485
Network having 31 Micro PLCs (XMP81x Series i.e. XMP-8 11/12/13/15/16/17) are connected to a Master Nexgen 5000 PLC, where PLC
implements XMP8_10 Master block.
Here, 31 Micro PLCs are networked with one master, where master can be :
- Nexgen 5000 PLC using RS 485 port
- PC with SCADA
Here, FB used is XMP8_10Master.
12
Nexgen 5000 PLC Based Application Schemes
Nexgen5222- BO interfaced with Beijer HMI E-Terminal on 2'nd port and network of Mitsubishi make Inverter is interfaced with 3'rd port.
l User need not know the Inverter interface protocol. It Reads/Writes data to multiple inverters.
It can have direct serial inverter control from user program
l Transfer data to central SCADA / HMI on other port
l Extendible to serial connection up to 31 inverters
l Fast response to set point changes
l Direct Inch, On/Off control
l Cyclic updation of actual data from inverters
l Individual Inverter Error handling
l Automatic communication recovery as soon as Inverter is switched ON
l Inverter data may be modified or controlled from HMI, SCADA or result of application program
l Communication on 9.6K or 19.2K baud
l Easy access to parameters via structured data for each inverter.
l Support some On-demand command execution such as initialisations etc.
l Predefined Parameters Handling (selectable)
- Write control : Start, Stop, Reset, Set Frequency.
- Read info : Frequency, Voltage, Current, Inv-status.
13
CPU Specifications
SPECIFICATIONS :
NEXGEN 521x & 522x SERIES OF CPUs
Attributes Specifications Remarks
CPU 521x CPU 522x
Processor 16 bit Micro controller -
14
CPU Specifications
Attributes Specifications Remarks
CPU 521x CPU 522x
Project File
Application
Program POU Password Facility Read / Write Password available
Security Source Code
Uploading
Cyclic Available Available
Task -
Supported Periodic Event - Available
Interrupt Event - Available
Current
Consumption At 5V DC 600 mA -
15
CPU Specifications
NEXGEN 522x SERIES OF CPUs
Nexgen 521x and 522x series of PLCs is an outcome of fundamental thought of modular PLC with IEC 61131-3 compatible CPU
and windows based programming software. This definitely has widened the scope of communication and interfacing multiple, as
well as variety of third party devices.
To reinforce the standardization, not only in programming techniques, but in hardware also, Messung Systems has launched a
step ahead, Nexgen 522x series of CPUs, with further faster and memory efficient CPU.
In nutshell, Nexgen 522x series of CPUs has an edge over existing Nexgen 521x series of CPUs in terms of ports standardization
and enhanced memory..
This has a well defined ordering code system, which explains the complete portfolio of a Nexgen 522x series of CPUs.
This essentially has Standard CPU, 3 Port CPUs (2 No.), Low cost CPU and Special CPU.
* CP 522x P2, CP 522x P3 and CP 522x P4 requires a patch panel and cables.
The processor module supports three independent serial communication ports with well defined availability criteria as :
All the serial ports are provided on-board and are open for user to define communication parameters and handle serial
communication using function blocks as per requisite protocol.
The communication port-1 is RS 232C hardware interface port and it automatically gets assigned for programming through
programming software 'CoDeSys', if programming cable (having an ordering code 9910) is connected. Otherwise it is open for user
to define protocol and handle serial communication through application program. Port 1 is used to transfer an application program,
from memory cassette to PLC, when ever required.
16
CPU Specifications
The detailed pin configuration is illustrated in below diagram. For the communication port 1, 9-pin D male connector is provided on
the Processor module. The figure below shows front view of the connector.
5
9
GND : 5
9 : Modem Ring Indicator
5V:4
8 : Reserved for programming
TxD : 3
7 : No Connection
RxD : 2
6 : No Connection
Carrier Detect : 1 6
1
Nexgen 522x : Port 1
Pin-1 provides carrier detection status when modem is connected. This status is available in application program on activating
PORT_STATUS. Pin-9 provides ring indicator when modem is connected and if any controlling device is dialing. Pin-4 and Pin-5
provides 5 VDC and Ground, which is used for memory cassette operation.
This 5 V DC is strongly recommended only for restricted use. ( Not for driving the 5V DC operated external devices).
For the communication ports 2 and port 3, 9-pin D male connectors are provided on the Processor module. The figure below
shows front view of the connector. The connections for both ports are identical.
5
GND : 5 9
9 : Rx+ (RS 422)
Tx+(RS 422) : 4
8 : Rx- (RS 422)
TxD (RS 232C) : 3
7 : Tx- (RS 422)
RxD (RS 232C) : 2
6 : No Connection
Carrier Detect (RS 232C) : 1 6
1
Nexgen 522x : Port 2 / 3
The detailed pin configuration is illustrated in above diagram. Pin-1 provides carrier detection status when modem is connected.
This status is available in application program on activating PORT_STATUS.
Special Interfaces
17
CPU Specifications
MOST ADVANCED NEXGEN 522x SERIES OF CPUs
On-board Interrupt Inputs
Industrial automation applications are ever demanding with increased level of sophistication. Especially real-time systems
demand flexible and configurable control over the execution of different parts of program, which can be in response to any
Interrupt Event.
Interrupts suspend the current (normal) execution, completes the interrupt-linked POU execution and then returns back to
suspended point, to resume normal execution.
In case of multiple interrupt events, these event needs to be prioritized. System interrupt events like serial communication interrupt,
internal timer interrupt are executed at highest priority. Here scheduler manages the execution of queued events as per defined
priority.
Two Maximum
Event Number Enum
2 EVENT_Z1_R_TRIG
No . of on-board inputs
3 EVENT_Z1_F_TRIG
5 EVENT_Z2_R_TRIG
6 EVENT_Z2_F_TRIG
RAM
Nexgen 522x series CPU has 256 KB RAM with battery back-up. This has various memory components like Input process image,
Output process image, Application program code memory, Data memory, Marker memory, File marker memory and system
variable memory.
Address Specifier In
Memory Type Application Program Size
18
CPU Specifications
Input Process Image and Output Process Image are input and output status respectively, for the configured IO modules.
These images are stored in global memory area, in every input and output scan. These images are accessible to external devices
like HMI and SCADA. Input and Output scan, can be executed on demand in a logic scan by calling Refresh_In and Refresh_Out
respectively.
Marker Memory is used to store the intermediate results and stored at addressable global memory area, accessible to external
devices like HMI, SCADA.
File Marker Memory is the data memory, which needs to retain after a PLC cold start or even after program change. Thus it is used
to store the reciepe, history and data logged. This memory is accessible to user only by using specific functions and function blocks
in application program. It is possible to access the file marker area for external devices also via serial communication by
MODBUS_RTU and Nexgen protocol.
Data Memory is used to store the intermediate results like instances of function blocks and variables used in application program.
Unlike marker memory, data memory addressing is not handled by application developer, but these addresses are generated by
compiler. Hence data memory is not accessible to external devices like HMI and SCADA.
System Variables are implicitly global and used to exchange the information with PLC operating system and its functionalities.
Flash PROM
Nexgen 522x series CPU has 512 KB Flash PROM. This serves as on-board backup memory.
Operating System
Operating System 198 KB
This contains core code of processor module which
handles various functions of the processor. Operating Application Program Code 256 KB
system code can be upgraded by a software tool Application Program Source
code memory 1 MB
'Bootstap loader’
Battery Back Up
PLC variables are stored in RAM, which is of volatile nature, demands a battery backup to retain its contents. This battery
also serves as a backup to on-board RTC. Nexgen 522x CPUs use 3.6V Ni-MH (Nickel Metal Hydride) rechargeable battery,
which is mounted on board. The battery provides backup period around 6 months, from its fully charge status.
Optional pluggable keyboard display unit can be used as diagnostic tool. It provides 4-character alpha-numeric display with
6 keys keypad. This is helpful for:
l _BKEYSTATUS is the system variable associated with keypad. This is a byte & its six bits are accessible corresponding to
each of the key.
l _ADISPLAY is the system variable associated for four character alphanumeric display. This is a array of 4 bytes & each of
the byte represents individual characters corresponding to display position
19
CPU Specifications
NEXGEN 521x SERIES OF CPUs
Nexgen 521x : CPU Variants And Communication Ports
Nexgen 521x series itself has 5 CPU variants. This wide range of CPU empowers user to select a CPU as per application specific
rd
requirement. This essentially has Standard CPU, 3 Port CPUs (2 Nos.), Low-cost CPU and Special CPU.
CPU 5210 (Standard) CPU 5213 (Low Cost) CPU 5211 CPU 5214 (Specially made
(CPU with 3 Serial Ports) with Motion Control Features)
8 5 2 8 5 2
+12 V +12 V
Rx RxD+
TxD+ TxD-
GND Tx GND RxD-
GND GND
6 3 1 6 3 1
1 5
6 9 Rx-
RTS-
RTS Rx RTS+ Rx+
CTS Tx CTS+ Tx+
GND CTS- Tx-
9 6 GND
5 1
20
CPU Specifications
Nexgen CPU 521x : Faster Instruction Execution
Nexgen 521x series CPUs are faster in execution, which makes it suitable for any sophisticated application, where processing
speed and computation matters.
RAM
Nexgen 521x series CPU has 256 KB RAM with battery back-up. This has various memory components like Input process image,
Output process image, Application source code memory, Data memory, Marker bits memory and other for system variables.
Flash PROM
Nexgen 521x series CPU has 512 KB Flash PROM. This serves as on-board back-up memory.
Programming software (CoDeSys) facilitates user to select source code downloading option. Unless specified explicitly,
Executable Binary code will get transferred to RAM.
21
Motion Control
NEXGEN CPU 5214
WITH MOTION CONTROL FEATURES
For every power ON operation, program gets transferred from Flash PROM to RAM. In case of no program in Flash PROM,
'MEMR' gets displayed on CPU Display.
In case boot project is not created, RAM and Flash PROM will have two different programs. On next power ON, this will cause
copying of old program from Flash PROM to RAM.
Special CPU 5214 has a provision for two independent channels for High Speed Counters (HSC) and Pulse Train Outputs (PTO).
For external interface, a cable with 25-pin D connector at both ends is provided. One end of cable is to be connected to 25-pin male
D connector provided at bottom side of CPU module. Other end of cable is to be connected to 25 pin female D connector on patch
panel for field interface. On this patch panel, connectors are provided where HSC inputs and PTO outputs can be connected. The
technical specifications are as per page 23.
Depending upon type of pulse output interface two varieties of patch panel are provided
for wiring. These are 2 HSC & 2 PTO (PNP type) and 2 HSC & 2 PTO (RS 422 type)
22
Motion Control
High Speed Counters
5214 processor module provides 2 independent channels for high speed counters. Each channel provides three input interfaces
as A, B and Z. This channel provides hardware interface for open collector (PNP/NPN) inputs of 24 VDC or differential 5 V inputs.
To configure for its use, processor 5214 provides driver function blocks for each channel in library PTO.lib. This facilitates
application developer to set the mode of operation and fetch the accumulated count and status of Z input. Counter provides pulse
count in double integer format.
Open collector With patch panel 2 HSC & 2 PNP type PTO
(18-30 VDC including ripple) (Ordering Code-4960)
Type (Selectable by
type of patch panel) With patch panel 2 HSC & 2 RS 422 type PTO
Differential
(Ordering Code-4962)
60 mA maximum for differential output with patch panel 4962.
Current
1.5 Amp maximum for open collector (PNP) output with patch panel 4960.
23
CoDeSys
CoDeSys PLC PROGRAM DEVELOPMENT
SUITE FOR NEXGEN-5000 PLC SERIES
IEC 61131-3 CoDeSys is a Windows ® based, an
international quality software which is IEC
61131-3 compatible.
®
Microsoft Windows (32 bit) Platform
With the Windows® based platform, application developer can avail the inherent benefits like Copy, Cut, Paste
and Delete operations. Using Import-Export facility developer can copy/re-use the Program Organisation Unit
(POU) across the applications. Global Search and Global Replace are features for the ease of program
modifications.
Modular Programming
CoDeSys encourages use of modular programming. Developed application is called as project, which has .pro as
file extension. Every CoDeSys project must have at least one POU. POU stands for program organisation unit
which either could be a program, function-block (FB) or function. One project can have many POUs.
PLC_PRG is a program, which is mandatory POU in every project. This PLC_PRG is a master routine where from
all the other POUs (sub-routines) are called. In a way, PLC_PRG can be viewed as main function in C language.
Hence, rather than dumping the complete logic into one POU (PLC_PRG), multiple POUs are developed, as per
objectives. Thus any project can be developed into split components. This approach resembles with object
oriented programming in higher level languages like C++ or Java.
This reduces development time for a machine manufacturer or end-user. Simply write it once and implement
many times. Password protection facility conceals the application logic in POUs (function & function blocks).
Modular programming and library management has indeed eased the task of application program development,
to a great extent.
24
CoDeSys
LADDER DIAGRAM & INSTRUCTION LIST
Ladder Diagram (LD)
It is the simplest graphical method of PLC
programming comprised of normally open and
normally closed contacts and coils, widely used in
discrete control applications. IEC ladder program
encourages, use of other program organization
units (POU) i.e. functions, function blocks and
programs. This has enhanced its wide acceptance
to process control applications also.
25
STRUCTURED TEXT, FUNCTION BLOCK DIAGRAM
SEQUENTIAL FUNCTION CHART
Structured Text (ST)
It is a textual language resembling with high level
programming language like Ada, Pascal or C. It exhibits
its suitability for logic with complex algorithms or
mathematical computations. It can be used to build
POUs i.e. functions, function blocks or programs.
This can be very well harmonized with ladder.
26
CoDeSys
CONTINUOUS FUNCTION CHART
OFF LINE SIMULATION, ONLINE FUNCTIONALITY
A simplified step consists of an action and flag to indicate whether the step is active. An IEC step has a flag and one or more
associated actions or Booleans. An action has series of instructions in either of IEC language. In addition to step action, there can
be an entry action and/or an exit action. These entry and exit steps get executed once only, right after the step is activated or just
before step is deactivated, respectively.
Off-line Simulation
CoDeSys has an off-line simulation facility. This is very vital utility for an application program developer, as one can develop
complete program logic independent of PLC. This feature helps the developer to complete the application program development
on or before scheduled time. Off-line simulation is built-in* feature of CoDeSys.
Please note that offline simulation does not support some of the CPU resource specific function / function blocks.
(e.g. it does not support RTC related, System variable related functions and function blocks.
*In case of some PLC vendors, Application program development software and simulation software are different.
On-line Functionality
CoDeSys has on-line program monitoring and on-line
program modifications features. This makes it suitable
for continuous process application, where program
modifications without process interrupt may be
required. Watch and Receipt window facilitates to
monitor multiple variables, simultaneously from
multiple program organization units (POUs). On-line
power flow monitoring serves as ready tool for fault
Watch & Receipt window, shows, different variables from, various POUs.
diagnostics.
27
CoDeSys
DYNAMIC DATA EXCHANGE
PLC I/O Configuration
Hierarchical and Graphical method of PLC rack
configuration and module configuration minimises the
chance of errors in I/O addresses.
PLC Browser
CoDeSys facilitates use of PLC Browser for viewing or
setting certain PLC parameters. PLC Browser is textual
command monitor which is a analogous to DOS prompt.
It has command entry line cum result display window,
which is like a combo-box.
It has smart history of latest executed commands, which Sample for using PLC browser, a handy and quick tool for developer
displays it without repetition of command. User can
check /set RTC from PLC browser.
In case direct DDE Server is used, which works with symbols rather than addresses, CoDeSys is not required to read the variables
from PLC and transfer them to application with DDE interface. Direct Addresses are not read with DDE Server. One needs to use
symbolic variables.
®
CoDeSys has assured and tested DDE interface, with Microsoft® Excel 97 and Microsoft Word 97, only with Microsoft
®
Windows NT 4.0
28
CoDeSys
SAMPLE TRACE FUNCTION
Sample Trace Function with Graphical Display
This on-line feature of CoDeSys enables user to
monitor progression of maximum eight different
analog or digital variables, simultaneously in trace
window (graphical format). This sampling rate is user
settable. The sampled values are stored in internal
trace buffer. If this ring buffer gets full, data purging
takes place i.e. older values are overwritten with
newer ones.
Other features like stretch, compress, Y Scaling Typical example of sampled temperature and pressure,
in a process application
allows user to adjust the trace window for the
requisite visibility. Enabled show grid option makes
grid as well as X-Y axis values to be visible.
Parameter Description
Trigger Variable This terminates sampling activity. (Trigger OFF)
Trigger Level This initiates sampling activity. (Trigger ON)
Number Minimum 32
of Samples Maximum 1024
Sampling Minimum 1 ms
Rate (ms) Maximum 20000 ms
Single Displays only once the samples 'Number of samples'
Recording Continuous Displays continuously selects 'Number of samples'
Manual Used to read trace recording with 'Read Trace' from ‘Extras'
Variables These are variable for sampling ( Maximum 8 )
Similarly the saved text file for sampled data can be readily transported to Microsoft Excel, where user can take further
analytical and database storage actions.
29
CoDeSys
PROCESS VISUALISATION &
POUs AND DATA TYPES
Process Visualisation for On-Line Testing
This on-line feature of CoDeSys facilitates a user for
designing interactive graphic user interface or screens.
This allows user to design application specific screens,
using various GUI elements or visualisation elements like:
rectangles, rounded rectangles, ellipse, polygon, polyline,
curves, BMP images, buttons (with limited events) and the
other visualisation itself. It also facilitates a user to have a
regular configuration of these elements. e.g. rectangle has
shape, text, line-width, color, motion-absolute, motion-
relative, variables, input and tool-tip. These configuration
parameters vary as per visualisation element.
In comparison with other front end tools (Visual Basic, Power Builder, Oracle Forms), this has limited capacity and features.
Even though it is comparable to SCADA, one should not use this feature as SCADA, as its response and performance are not
assured. It is strongly recommended to use this tool for test and monitoring purpose rather than control action.
As a general rule, any POU (calling POU) can call other POU (called POU), which is hierarchically at equal or lower level of calling
POU. A POU can not call other POU, which is hierarchically above the calling POU. Thus, a function block can call other function
block or function and cannot call program.
30
CoDeSys
CoDeSys supports other data types, which are specific to date and time.
Type Resolution Remark Example Memory
TIME 1 ms 25 Days ( Max Value ) t#23h02m12s247ms 32 Bit
DATE 1 sec Counts from 1'st Jan.1970 d#2003-05-23 32 Bit
DATE_AND_TIME 1 sec Counts from 1'st Jan.1970 dt#2003-05-12-15:36:57 32 Bit
TIME_OF_DAY 1 ms Counts from 12.00 am, everyday tod#14:27:09.986 32 Bit
Class
Class defines the scope of the variable viz. local and global. Global elements are accessible to all the POUs in a project. CoDeSys
compiler forcibly insists data type declaration for an every variable used in the project, except PLC addresses.
Local Variables:
These variables are declared & defined specifically for the POU, thus the scope is valid only for the declared POU.
Global Variables:
These variables are declared and defined for a POU, with its widen accessibility. Thus these variables can be referred in other
POUs of the same project.
VAR
These are the local variables, necessarily meant for storing intermittent results of any POU. VAR variables restrict their
accessibility to the POU itself.
VAR_IN
These are read only type local variables, acting as inputs to POU (e.g. function block). Value of the variable can be given along with
the call, in calling POU.
VAR_OUT
These are local variables, acting as output to POU (e.g. function block). Value of these variables are returned back at the calling
POU. These variables can be used further, in the POU.
VAR_IN_OUT
These are local variables, acting as input as well as output of any POU. Value of such a variable is always passed by reference
rather than value. These variables are not applicable to the function.
31
CoDeSys
CoDeSys : INSTRUCTIONS & LIBRARIES
COMMUNICATION BASICS
Nexgen 5000 Series of CPUs supports extensive instruction set to built the control logic across variety of applications, from
machine tools to process industry. The CPU is capable of handling various data types.
Data types supported are
l Boolean l String of sequential ASCII characters
l 8, 16, 32 bit signed / unsigned numbers l 1-, 2-, 3- dimensional arrays
l Real numbers (32 bit IEEE floating point format) l Structures (User Defined Data Types)
l Date, Time, Date and Time.
COMMUNICATION BASICS
Communication is handled with seven layers. But, still most of the time communication is handled with Application Layer, Protocol
Layer, Data Link Layer and Physical Layer.
Physical Layer
Physical layer is comprised of several elements viz. media of transmission (like wires, fiber optics, wire-less), signal drivers, method
of transmission, inter connections, connectors and inter signal converters. Most commonly employed physical layer protocols are
RS 232C, RS 422 and RS 485.
* Isolator drivers are required for a distance more than 50 m. ( Maximum supported distance is 1 KM )
32
CommunicationBasics
RS 422 to RS 485 Conversion
As a common practice, RX+ is shorted to TX+ and RX- is shorted to TX-. The RS 485 connected station is called as Half
Duplex as it either receives or transmits the signal. In some cases, TX needs to put to tri-state when receiving starts. Such
convertible ports are marked as RS 422 / RS 485.
Nexgen 521x series having serial 2'nd and 3'rd port, are convertible from RS 422 to RS 485 and vice versa.
This is characterized by :
l Optical isolation between input and output signals l Auto detection of direction, in case of RS 485
l Can be used as RS 422 isolated repeater l Supports 3 baud rates viz. 9600,19.2,38.4 Kbps
l Does signal level correction l Provides output signal short circuit protection
Item Description
Function RS 422(4 Wire) to RS 485(2 Wire) Conversion or Vice versa
Input supply voltage 85-260 VAC,15VA, 50/60Hz
Operating modes RS 422 (4-wire) or RS 485(2 wire ), set by switch settings
Auto direction sensing Facility available for RS 485(2-wire) interface
Baud rates supported 9600, 19200 and 38400 ( set by DIP Switch setting )
Signal isolation 1.5 KV optical isolation
These are used in various networking schemes where PC (RS 232) side is interfaced with RS 422 / RS 485
or vice versa.
l Optical isolation between input and output signals l Auto detection of direction, in case of RS 485
l Operates directly on 85-260 V range l Supports 3 baud rates viz. 9600,19.2,38.4 Kbps
33
Communication Basics
COMMUNICATION BASICS
Item Description
Function RS 232(3 Wire) to RS 422/485(4/2 Wire) Conversion or Vice versa
Input supply voltage 85 260 VAC,15VA, 50/60Hz
Operating modes RS 422 (4-wire) or RS 485(2 wire ), set by DIP switch settings
Auto direction sensing Facility available for RS 485(2-wire) interface
Baud rates supported 9600, 19200 and 38400 ( set by DIP Switch setting )
Signal isolation 1.5 KV optical isolation
Signal short circuit protection Applicable
Model 6010 24 V DC, 250 mA
Auxiliary power output
Model 6015 12 V DC, 250 mA
Model 6016 5 V DC, 500 mA
Supply protection 2 Amp miniature glass fuse protection at input supply
Protocol
Protocol is synonymous to language as both the devices should communicate and understand the same language. It is predefined
sequence of codes for data exchange. By using protocol converter, two devices having un-identical protocols can communicate.
A protocol is command and response having, header, body and a trailer. Header is indicative of a new message begin, body is
comprised of command number, data and any other information need to communicate. Trailer has error checking checksum and
end of transmission character. Protocols work independent of physical layer.
MODBUS is a widely used protocol in industry being established and open for use. Messung Protocols are specific to Messung
products and are not open for its use. To communicate with Messung products, application developer has to write a protocol
converter like SCADA driver.
Typical communication string has Header, Station ID, Length, Command/Response byte, Data, Checksum and Trailer.
Communication parameters are Baud rate, Data bits, Parity bits and Number of stop bits. Typically one byte frame consumes 11
bits and at 9600 bits per seconds, it takes 1ms per byte frame.
Nexgen 5000 has an Application Layer and Protocol Layer, which are open to user, Data Link Layer which is implicitly handled by
PLC operating system and Physical Layer which is hardware dependent.
Function blocks for MODBUS master and slave are developed by Messung, for Nexgen 5000 PLCs.
Nexgen5000 has two buffers viz. RX buffer and TX buffer which simultaneously handle transmission and reception, functions
independently and in parallel to PLC scan. Data Link Layer handles conversion of Data Frame to Byte Frame.
34
CommunicationBasics
Protocol FB get executed in logic scan and consumes application as well as data memory. It delivers same throughput, facilitates
variety of communication speeds and exerts complete control on communication scheme.
MODBUS Protocol
MODBUS protocol, introduced by MODICON, is open to 01 Read Coil Status ( 1 bit )
everybody for use, which has MODBUS RTU (binary),
03 Read Holding Register ( 16 bit )
MODBUS ASCII and MODBUS TCP protocols. Presently
Messung supports MODBUS RTU protocol, which is efficient 04 Read Input Register ( 16 bit )
being in binary format. Messung FB has MODBUS Master
05 Write Single Coil / Preset single holding register
and MODBUS Slave which support various commands as :
15 Write Multiple Coils / Preset multiple holding register
MODBUS RTU_Slave
It emulates MODBUS Slave functionality. User can create only single instance of the block and can be attached to any port . It is
interface able with SCADA, DCS, E Terminals, Nexgen PLC with MODBUS Master FB.
ModeSel can have values as 0, 1 or greater than 1. Its 0 value stands for on-demand or manual updation, only once but in
overriding mode. Its value 1 stands for cyclic execution but only once per network scan. When ModeSel has value greater than 1,
it can be grouped and gets executed along with cyclic.
MODBUS supporting devices may not support all the MODBUS commands, this emphasizes due care while putting such a device
to network. Nexgen 5000 to Nexgen 5000 communication can be established with MODBUS Master function block.
Nexgen_Slave
It emulates Nexgen 4000 HMI port protocol, facilitating connectivity for Smartline Sr., Smartline Jr., E-Series HMIs and SCADA
with Nexgen Drivers. Communication speed is selectable up to 56 Kbps, incase of E-series HMIs and SCADA only. This can be
attached to any of the Nexgen 5000 communication port.
Freqrol Inverter FB
This block facilitates a user to connect 31 freqrol Inverters and user need not know Inverter interface protocol. User can have
control over Direct Inch, ON/OFF operations, Cyclic data updation, Individual error handling and automatic communication
recover on Inverter switched ON. It reflects fast changes to set point changes. Communication speed is settable to 9.6 Kbps or
19.2 Kbps.
35
Power Supply
BASE AND EXPANSION PLATE &
POWER SUPPLY MODULE
Base Plate
The base plate holds Power Supply, CPU and I/O modules. It is available in varieties to suit I/O and expansion requirement. The
base plate is available with or without expansion connector to offer economic solution. Both the base plates are available in 3 I/O, 5
I/O and 8 I/O slots. x mm
NEXGEN
Expansion Plate
161.5mm
190mm
In multi-rack system, the expansion plate can be mounted
next to each other or one below other. The expansion
plate is available in varieties to suit I/O and power supply
requirement. It is available with or without power supply
connection facility. Both the expansion plates are
available in 3 I/O, 5 I/O and 8 I/O slots. At the most 3 3 I/O Base Plate (248 mm) (Depth 145 mm)
expansion plates can be connected to the base plate. 5 I/O Base Plate (332 mm)
36
Digital Modules
DIGITAL I/O MODULES
37
MIXED
DIGITALDIGITAL I/O MODULES
& ANALOG
DIGITAL I/O MODULES
I/O MODULES
16 pt DC Input 16 pt DC Input
8 pt DC Output Module 8 pt Relay Output Module
Output Configuration
Output Load Current(A) Response Time (ms)
Outputs Type Off state
Max Per
Leakage
Total Per Common Output Group On Off
38
ANALOG I/O MODULES
8 Channel Thermocouple Input Module
39
ANALOG I/O MODULES
2 Channel Isolated Analog Output Module (Voltage/Current)
The module provides 2 isolated channels with 12-bit
No. Of Output Channels 2 Isolated, 12 Bit
resolution. Output type can be Voltage/Current. Conversion Method R-2R Ladder
Voltage -10 to +10 VDC
Types
Current 4 to 20 mA
Voltage / Current Significant Resolution
Range Bits per LSB
Resolution
-10 to +10 VDC 12 Bits 4.88 mV
4 to 20 mA 11 Bits 7.8 m A
Voltage > 1 K Ohms
Load Resistance 500 Ohms
Current
Conversion Time 20 m S
Isolation Channel to Channel 1.5 KV optical
Channel to internal circuit
External Power Requirement 24 V DC, 500 mA
External Supply Protection Reverse Polarity Protection
Indications No 24 V Supply
Back-plane current 150 mA
I/O points consumed 32 Input Bits and 32 Output Bits
Terminal/Connection Removable 20 Pin Terminal Block
Ordering Code 4332
Conversion Time 20 m S
40
ANALOG I/O MODULES
4 Channel Non Isolated Analog Output Module
The module converts digital values data from CPU to
No. Of Output Channels 4 Non Isolated, 16 Bit
equivalent analog output voltage.It provides 4 non-
Conversion Method R-2R Ladder
isolated channels with 16 bit resolution.
Input Range -32,000 To +32,000
Output Voltage Range -10 To +10 V DC
Resolution 312.5 m V
Load Resistance > 1 K Ohm
Load Current 10 mA Maximum
Output Protection Infinite Short Circuit Protection.
Accuracy 0.5 % of Full Scale Reading.
50 m S (Irrespective of
Conversion Time
No. of ON Channels)
Voltage 1 M Ohms
Input Impedance
Current 500 Ohms
No. Of Analog
Output Channels 2 Non-Isolated
Indications l No 5 V Supply
l CPU Fault
l Analog Input Channel Status (8)
Back-plane current 1000 mA
I/O points consumed 8 Input Bits And 8 Output Bits
Note: This module does not require any external power supply. Terminal/Connection Removable 38 Pin Terminal Block
Ordering Code 4366
41
COUNTER INPUT MODULE
4 Channel Counter Input Module
The Multifunction Input module provides mix of inputs with programmable filter
time, pulse catch input, interrupt input and counters with programmable 16 bit
operational mode. Programmable filter (10ms) and up counter is the default
configuration. In such case, the inputs are not available as normal inputs.
The pulse having minimum 500 m sec ON time can be detected. Upon detection of
interrupt signal, the operating system of PLC branches to predefined interrupt
task.
The counters can be programmed for external reset using normal inputs.
Counting direction for up/down counter can be selected by external inputs
42
HMIs
MESSUNG MAKE HMIs
Human-Machine Interfaces (HMI) are panel mounted devices that provide effective dialogue between the operator and machine.
Equipped with programmable display and keys, HMIs allow easy operation and monitoring in the production area. HMIs display
operational and fault messages, enable machine specific parameters to be monitored and modified in suitable format. HMI keeps
the operator fully informed of the current status of operations at all times.
! Replaces conventional push button panel (and related wiring), indicating lamps etc.
! Fault messages and instructions help reduce down time thereby improving productivity directly
The table summarises key features of Smartline series of Human Machine Interfaces.
Product development is a continuous process. Consequently specifications are subject to change without prior notice.
For latest information please contact our nearest sales office.
43
E Series
A COMPLETE FAMILY OF
BEIJER MAKE E-SERIES OPERATOR TERMINALS
Display size 2 rows x 2 rows x 2 rows x 4 rows x 240 x 64 pixels 240 x 128 pixels
16 characters 20 characters 20 characters 20 characters
Active area of display
W x H (mm) 55.7 x 11.0 73.5 X 11.5 73.5 X 11.5 70.4 x 20.8 127.2 x 33.9 (5.2”) 120 x 64 (5.3”)
Recipe handler - · · · · ·
Alarm management - - - 1 group Up to 4 groups Up to 4 groups
Time channels - · · · · ·
Real-time clock - · · · · ·
Trend graphs - - - - Real time Historic
Report printouts - · · · · ·
Password for security - 8 levels 8 levels 8 levels 8 levels 8 levels
Buzzer - - - - - -
400 kb Flash / 400 kb Flash /
Memory for application 16 kb Flash 64 kb Flash 64 kb Flash 64 kb Flash 8 Mb expansion 8 Mb expansion
Number of expansion - - - - 1 1
card positions
Communication interfaces RS422 or RS 232C RS422 and RS 232C RS422 and RS 232C RS422 and RS 232C RS422 and RS 232C RS422 and RS 232C
· · · · · ·
TM
Support for Palm handhelds
Support for extended - - - - · ·
keyboard
Ambient temperature 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC
Waterproof front IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2)
EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1, EN 50081 -1,
EMC
EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2 EN 61000-6-2
LVD - - - - - -
UL UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 508, UL 1604 (3)
DNV · · · · · ·
Power supply + 5 V DC ± 5 % + 5 V DC ± 5 % + 5 V DC ± 5 % +24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V
Power consumption 200 mA (5 V) 200 mA (5 V) 200 mA (5 V) 150 mA (24 V) 450 mA (24 V) 450 mA (24 V)
104 X 69 X 38 142 X 100 X 29 142 X 100 X 29 147 X 163.5 X 38 211 X 198 X 69 214 X 232 X 879
Dimensions W x H x D (mm)
(401” X 2.7” X 1.5”) (5.6” X 3.5” X 1.1”) (5.6” X 3.5” X 1.1”) (5.8” X 6.4” X 1.5”) (8.3” X 7.8” X 2.7”) (8.4” X 9.1” X 3.4”)
Weight (kg) 0.2 0.5 0.5 0.7 1.5 1.4
44
E Series
E610 E615 / E615T E700 E710 E900T / E900TD E910T / E910TD
Backlit STN, Backlit STN / TFA Backlit STN colour,
Backlit STN colour Backlit TFT colour Backlit TFT colour, touch
16 grays, touch colour, touch touch
Graphic + Text Graphic + Text Graphic + Text Graphic + Text Graphic + Text Graphic + Text
320 x 240 pixels 320 x 240 pixels 320 x 240 pixels 320 x 240 pixels 640 x 480 pixels 640 x 480 pixels
115.2 x 86.4 (5.7”) 115.2 x 86.4 (5.7”) 115.2 x 86.4 (5.7”) 115.2 x 86.4 (5.7”) 211.25 x 158.4 (10.4”) 211.25 x 158.4 (10.4”)
· · · · · ·
· · · · · ·
· · · · · ·
· · · · · ·
· · · · · ·
· ·/ · ·/ · ·/ · ·/ · ·/ · ·/
· · · · · ·
Uup to 5 groups Up to 5 groups Up to 16 groups Up to 5 groups Up to 16 groups Up to 11 groups
· · · · · ·
· · · · · ·
Historic Historic Historic Historic Historic Historic
· · · · · ·
8 levels 8 levels 8 levels 8 levels 8 levels 8 levels
- - - - - -
400 kb Flash / 400 kb Flash / 400 kb Flash / 400 kb Flash / 1,600 kb Flash / 1,600 kb Flash /
8 Mb expansion 8 Mb expansion 8 Mb expansion 8 Mb expansion 8 Mb expansion 8 Mb expansion
1 1 2 2 2 2
RS485, RS422, RS485, RS422,
RS 232C (4) RS 232C (4) RS422 and RS232C RS422 and RS232C RS422 and RS232C RS422 and RS232C
· · · · · ·
· · · · · ·
0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC 0 ºC - + 50 ºC
IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4X (2) IP65, NEMA 4 / IP65, NEMA 4 /
IP 65, NEMA 4X (2) IP 65, NEMA 4X (2)
EN 50081 -1, EN 50081-2, EN 61000-6-2 / EN 61000-6-3, EN 61000-6-3, EN 50081-2, EN 61000-6-2 / EN 50081-2, EN 61000-6-2 /
EN 61000-6-2 EN 50081-1, EN 61000-6-2 / EN 61000-6-2 EN 61000-6-2 EN 61000-6-4, EN 61000-6-2 EN 61000-6-4, EN 61000-6-2
- - - - EN 60950 / - EN 60950 / -
UL 508, UL 1604 (3) UL 508, UL 1604 (3) / - UL 508, UL 1604 (3) UL 508, UL 1604 (3) UL 1950, UL 1604 (3) / UL 1950, UL 1604 (3) /
UL 508, UL 1604 (3) UL 508, UL 1604 (3)
· · /- · · · ·
+24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V +24 V DC, 20-30 V 100-240 V AC / 100-240 V AC /
24 V DC, 20-30 V 24 V DC, 20-30 V
400 mA (24 V) 450 mA (24 V) 550 mA (24 V) 550 mA (24 V) Max 0.35 A / 1A Max 0.35 A / 1A
200 X 150 X 69 200 X 150 X 69 276 X 198 X 89 276 X 198 X 89 367 X 274 X 90 290 X 250 X 105
(7.8” X 5.9” X 2.7”) (7.8” X 5.9” X 2.7”) (10.9” X 7.8” X 3.5”) (10.9” X 7.8” X 3.5”) (14.4” X 10.8” X 3.5”) (11.4” X 9.8” X 4.1”)
1.5 1.5 1.7 1.7 3.5 3.3
45
HMI Connectivity
ORDERING INFORMATION :
HMI CONNECTIVITY
Nexgen 5000 PLCs and HMI Interface
Note: When HMI Smartline Jr. CPU 521x Setup CPU 522x Setup
Master Master
is interfaced with Nexgen
521x Third port, operational
power for HMI, needs to be 24V 24V
Supply Supply
externally provided. P2 P3 P2 P3
12V
Supply
Nexgen 521x Series of CPU Connectivity to Beijer HMI & Mitsubishi GOT
Nexgen 522x Series of CPU Connectivity to Beijer HMI & Mitsubishi GOT
5221-B0 / P4 & 5222-B0 / P4
HMI Features
Port 2 / Port 3
46
Nexgen 5000 CPU
ORDERING INFORMATION :
NEXGEN CPU 5000 SERIES
Sr.
No.
Item Description Ordering
Code
* Back Plane
Current (mA) at 5 V DC
1 Patch Panel, 2 Ch.,100 KHz Max. HSC & 2 Ch.,5 KHz Max. PNP Type PTO 4960
2 Patch Panel, 2 Ch.HSC,100 KHz Max. & 2 Ch.,100 KHz RS-422 Type PTO 4962
3 Interface Cable (0.5 Meter Length) 4944
4 Interface Cable (1 Meter Length) 4945
Ordering Ordering
Item Description Code Item Description Code
BASE PLATES EXPANSION PLATES
8 I/0 without expansion connector 4906 8 I/0 without Slot for Aux Power Supply 4934
5 I/0 without expansion connector 4932 5 I/0 without Slot for Aux Power Supply 4935
3 I/0 without expansion connector 4930 3 I/0 without Slot for Aux Power Supply 4936
8 I/0 with expansion connector 4937 8 I/0 with Slot for Aux Power Supply 4907
5 I/0 with expansion connector 4938 5 I/0 with Slot for Aux Power Supply 4933
3 I/0 with expansion connector 4939 3 I/0 with Slot for Aux Power Supply 4931
1 meter 4941
2 meters 4942
3 meters 4943
47
I/O Modules
ORDERING INFORMATION :
PSU, I/O MODULES
POWER SUPPLY MODULE Ordering Code
Terminal
I/O MODULES
Ordering * Back Plane
Current (mA) Block
Code Required
at 5 V DC
* Please note that if current consumption at 5 V DC of CPU, for all Digital & Analog Module I/O modules exceeds 5 A,
an additional power supply is required to be ordered.
48
UCING
D
RO
INT
GATEWAY
Nexgen CPU -
523x Series PLC - Master
PC
OPC Server
GATEWAY
GATEWAY
Graphic HMI
Mitsubishi
indiCAN - indiCAN - AC Servo System -
Remote Digital I/Os Remote Analog I/Os Mitsubishi Slave
Text HMI AC VFD / Inverter -
Slave
CANopen GATEWAYS
Under Development
Nexgen CPU -
523x Series PLC - Slave
Highlights
l Nexgen CPU 523x series supports CANbus connectivity
l Distributed configuration: Low cost, shielded, twisted cable
l Maximum of 31 stations of digital / analog remote I/Os over a
distance of 500 meters
l Network configuration through software
Benefits
l Reduced wiring leads to quick installation
l Network expansion by add on
l Easy diagnostics & troubleshooting