Beruflich Dokumente
Kultur Dokumente
The distribution grid brings power directly to consumers and is operated by a large number of
regional and municipal operators (883 DSOs, source BNetzA 2016).
The German transmission grid comprises the portions at extra-high voltage, 220–380 kV,
and at high voltage, 110 kV, with about 350 substations.
The distribution grids at medium voltage (MV), 1–50 kV, and low voltage (LV), 0.4 kV,
include about 600.000 MV/LV substations.
Electricity customers only have to expect power interruptions of 12 minutes on average during
the year.
The medium and low-voltage distribution networks are changing into a multidirectional dynamic
network. Monitoring and control of this system are a prerequisite for keeping the network
efficiently balanced, working in cooperation with network users. It is important to take account
of the fact that every distribution network must be individually assessed in terms of its network
structure (e.g. consumers and generators connected to it) and public infrastructures (e.g. load
and population density).
In the past, distribution networks were operated in a single direction to distribute electricity from
the higher voltage level, with the network structure designed for this specific task.
Through to today, only very few distribution networks proceed with detailed visualization and
analysis of the network situation together with real automation. Furthermore, only limited use is
made of the efficiency of control and regulation possibilities
This must be changed if the energy transition is to be managed. Transmission and distribution
networks must respond even faster and more frequently to changes in generation and load-flow
directions, particularly through the feed-in of increasing amounts of energy from wind power and
photovoltaic.
Improvements has already begun…
Northern Germany:
The development in Northern Germany shows that the future has already begun in certain
networks. Here, network operators already issue warnings about overloading of energy networks
due to the rapid development of renewable energies in rural and windy regions. In and around
Lower Saxony today, the installed renewables-based feed-in capacity exceeds the annual
maximum load by almost 70 percent.
Already 50 percent of the total electricity volume transported by certain network operators
originates from renewable energy sources.
Southern Germany:
Bavaria has seen a considerable increase in the number of photovoltaic plants over the last two
years.
More than 350,000 photovoltaic plants with a capacity of more than 7,000 MW are currently
connected to the network. This figure not only exceeds the Bavarian demand during low-load
hours but it also corresponds to about 35 percent of the PV capacity installed throughout the
country.
Protection and Relays Used In Main Circuit Board at a Power Grid
Substation
1. Directional inverse time overcurrent and earth fault relays
This type of relays are applied for directional or earth fault protection of ring mains, parallel
transformers or parallel feeders with the time graded principle. It is induction disc type relay with
induction cup used to add directional feature.
The type of relay is an instantaneous protection against abnormal voltage conditions such as over
voltage, under voltage or no voltage in AC and DC circuits and for definite time operation when
used with a timer. It is an attracted armature type relay.
This relay is applied for after closing or continuous supervision of the trip circuit of circuit
breakers.
An instantaneous phase or earth fault protection and for definite time operation when used with a
timer. It is a CAG 12/12G standard attracted armature relay with adjustable settings. It may be a
single pole or triple pole relay.
5. Auto reclose
a) VAR21 giving one reclosure. The dead time and reclaim time are adjustable form 5 to 25 secs.
If the circuit breaker reopens during reclaim time, it remains open and locked out.
b) VAR41B is a single shot scheme for air blast circuit breakers. Reclaim time is fixed at
between 15 to 20 secs. Dead time adjustment is from 0.1 to 1.0 sec of which first 300 millisec
will be circuit breaker opening time.
c) VAR 42 giving four reclosure. It is precision timed from 0 to 60 sec. it can be set for max four
enclosures at min intervals of 10 sec and instantaneous protection can be suppressed after the
first reclosure so that persistent faults are referred to time graded protection.
d) VAR 71 giving single shot medium speed reclosure with alarm and lockout for circuit breaker.
This allows up to 10 faults clearance before initiating an alarm. The alarm is followed by lockout
if selected no. of faults clearances exceed. If the circuit breaker reopens during reclaim time, it
remains open and locked out. It offers delay in reclosing sequence. Instantaneous lockout on low
current earth fault and suppressing instantaneous protection during reclamation time.
e) Var81 is a single shot high-speed reclosure with alarm and lockout for circuit breaker This
allows up to 10 faults clearance before initiating an alarm.
6. Distance protection
Some utilities install distance relays (ANSI 21) for line protection. The distance relay compares
the fault current against the voltage at the relay location to calculate the impedance from the
relay to the faulty point. As a rule of thumb distance relay has three protection zones: zone 1
covers 80-85% length of the protected line, zone 2 covers 100% length of the protected line plus
50% next line, zone 3 covers 100% length of the protected line plus 100% second line, plus 25%
third line. If a fault
occurs in the operating zone of the distance relay, the measured impedance is less than the
setting and the distance relay operates to trip the circuit breaker. Unfortunately, the distance
protection can be affected by DERs and loads since the measured impedance of the distance
relay is a function of in-feed currents and might cause the relay to operate incorrectly.
7. Differential protection
Differential over-current protection relays (ANSI 87) are mainly used to protect an important
piece of equipment such as distributed generators and transformers. Today, differential
protection is also widely used to protect underground distribution lines using a communication
(pilot wires, fibre optics, radio or microwave, etc.) between line terminals. It has the highest
selectivity and only operates in the case of an internal fault but it requires a reliable
communication for instantaneous data transfer between terminals of the protected element (pilot
wire, optical fibres, or free space via radio or microwave). Because of a vulnerability to possible
communication failures, differential protection requires a separate back-up protection scheme. It
increases a total cost of protection system and limits its application in microgrids.
Although several protection principles can be used in low voltage distribution grid, over-current
protection dominates this segment. Therefore, we focus on issues related to over-current
protection in microgrids.
Distribution grid operation and protection having
distributed generation
Objective 1
Investigate what effect DG has on the protective system of distribution grids and when
protection problems are to be expected
To this objective the following research question is posed:
i. What type of protection problems are to be expected in distribution grids including
DG
Objective 2
Investigate what the fault ride-through behavior of DG-units is and how it interferes with the
current grid protection.
The research questions related to this objective are:
i. What is the impact of keeping DG connected to the distribution grid during and after
a grid disturbance
ii. Can DG stay connected to a distribution grid protected by a traditional protective
system without loosing stability during and after a grid disturbance
Objective 3
Investigate how the grid or generator protective system has to be modified to minimize the
disconnection of DG during and after disturbances and guarantee stability of the connected DG
For the last objective the following research questions are defined:
i. What types of fault in the transmission grid result in the disconnection of DG
connected to the distribution grid
ii. What are the minimum fault ride-through criteria needed to prevent disconnection
of DG during transmission grid faults
Grid structure:
Generally three grid structures can be distinguished:
1. Radial grid structure
a. Simplest structure
b. Each substation or customer is coupled via a single line or cable to a central point
of supply.
c. The service interruption time covers the complete repair time of the line or cable
2. Loop grid structure
a. All substations or customers are connected via two lines or cables
b. During a disturbance the faulted line section is isolated and the loop is split-up
into two parts.
c. Service interruption time is the time needed for fault localization and the
necessary switching actions
2. The effect of fault ride-through criteria on the dynamic behavior of the distribution
system
a. Problem -- immediate disconnection of DG-units restore the distribution grid to a
grid with only one source of supply can cause of load and generation mismatch
b. For voltage dips with a certain duration the DG have to stay connected to the grid.
Depending on the size of the DG-unit the fault ride-through criteria can also
oblige additional grid support, such as voltage and frequency support, during and
after a disturbance. Keeping DG during a local disturbance connected to the grid
can cause interference with the local protective system.
3. The effect of grid protection and fault ride-through criteria on the stability of the
distribution generation
Both problems can manifest themselves for either temporary or permanent faults.
Distribution grids having large number of DGs can lead to a disconnection of a significant part of
these units due to disturbances in the transmission, sub-transmission and distribution grids. And
the traditional distribution grid protection is too slow to prevent disconnection of the DG.
The stability limits of the DGs are exceeded when they are kept connected during and after a
disturbance in the distribution grid.
As a solution, the distribution grid operation can be changed from radial operation to loop
operation. It is demonstrated that it is possible by this to clear the fault without disconnection of
the DGs or violation of the stability margins.
Distribution grid faults cause deep dips for which the stability margin of the DGs is small and
fast fault clearing is a necessary condition to prevent disconnection and instable operation of the
DG.
Disconnection of all DG due to a disturbance leads to a large change of active power flow
although the accompanying steady-state voltage deviation is limited. This voltage deviation can
easily be corrected with the tap changer of the transformers. Keeping the DG connected after a
disturbance results in a large active power swing which is also noticeable in the sub-transmission
and distribution grid voltage.
Another consequence of keeping the DG connected to the grid is the delayed voltage recovery
due to the reactive power consumption of the generator for a small period of time after the fault
is cleared. This delayed voltage recovery leads to a violation of the fault ride-through criteria and
a disconnection of the DG although, even when the voltage dip is survived.
For the improvement of the voltage recovery, integrate a STATCOM as a source of reactive
power in the local distribution grid.
i. STATCOM has a positive effect on the voltage recovery and as a result of this improved
voltage recovery the disconnection of the DG is prevented.
ii. STATCOM also limits the maximum amplitude of the rotor angle swing which for the
DG results in reaching the steady state faster.
Protective systems
The main objective of a protective system is to detect an abnormal system condition as quickly
as possible and take an appropriate action to bring the system back in the normal system
condition. The protective system is per definition a reacting system and is equipped with
reactionary devices.
The time required to take the corrective action is called the clearing time and can be defined as:
Tc = Tp + Td + Ta (3.1)
Tc: Clearing time
Tp: Comparison time
Td: Decision time
Ta: Action time, including the time necessary to open the circuit breaker
The clearing time of the protection device is an important quantity because other protection
devices in the protective system have to be time-coordinated with this protection device in order
to disconnect the faulted section of the network only.
Reliability of a protective system: The ability of the protective system to operate correctly.
Security of a protective system: The ability of a system or device to refrain from unnecessary
operation.
Sensitivity of a protective system: The ability of the system to identify an abnormal operating
condition that exceeds a certain threshold value.
Selectivity of a protective system: The ability of maintaining continuity of supply by disconnecting
the minimum section of the network necessary to isolate the fault.
Protection devices:
In the protective system the protection devices are often classified in accordance with their
construction, the incoming signal and function. For a regular protection device often the term
relay is used.
Overcurrent protection:
The simplest class of protection relays is the class of overcurrent relays. This class of protection
relays is widely used in distribution grid protection. To operate this relay only the current has to
be measured. When the current exceeds a certain threshold a trip signal is generated and send to
the circuit breaker. Roughly, the overcurrent relays can be classified into two groups:
1. Definite-time overcurrent relays
2. Inverse-time overcurrent relays
Directional protection
In radial distribution grids normally there is only one source of supply and application of
overcurrent relays as protection devices are prevalent. However, selective protection with
overcurrent relays of distribution grids with a ring or meshed grid structure is almost impossible.
In these grid structures disturbances can lead to fault currents which can flow in both directions
through a power system component and causes unnecessary disconnection of circuits. To provide
proper protection of these grid structures and cope with bi-directional fault currents a directional
element has to be added to the overcurrent relay.
Reclosers
Another class of overcurrent protection devices, especially applied in distribution grids
consisting overhead lines, is the automatic recloser or simply a recloser. In these grids 80% of
the faults are temporarily and permanent switching off of the distribution feeder is not necessary.
To limit the interruption time in case of a fault the recloser switches off the faulted section of the
feeder and allows the arc to deionize. After a brief time delay the recloser energizes the line
again. When the arc is extinguished and the fault is removed the feeder can stay in service. For
permanent faults this procedure is repeated several times and finally the recloser will lock out
and the permanent fault is cleared by switching off the faulted feeder part.
Differential protection
Differential protection is based on a comparison of, at least, two current quantities which are
measured on either side of the protected element. In normal operation of the protected element
these currents should be equal. The differential protection trips when:
In above equation Im is the mth current quantity and n is the total number of branches
incorporated in the differential protection.
Distance protection
A protection device which makes use of the linear relation between U and I is the distance
protection. The relation between U and I , which is better known as Ohm’s law, is:
In distance protection the impedance of the protected grid section is used as a threshold. This is
an attractive quantity because the impedance is linear with the line-length and independent of the
loading situations. The distance protection measures the fault current and the busbar voltage and
determines the impedance. This is the impedance to the fault location. The measured impedance
is compared with the threshold impedance and when Zmeas < Zm a trip signal is generated.
To clarify the settings and grading of the protection devices in a loop structure, in figure 3.15 this
structure is represented as a generic radial feeder including two sources and q sections. Because
of the directional sensitivity of the protection devices source 1 and source 2 can be considered as
decoupled. Hence for determining the time grading for the subsequent relays Reln and Reln+1
source 1 has to be used and for setting the relays Relm and Relm+1 Source 2 has to be used.
Because of this decoupling the relays of both directions are set independently and can be treated
as an ordinary radial feeder protection.
Integration of Distributed Energy Resources: The Sample Case of
Photovoltaic Systems
The integration and management of distributed energy resources (DERs) is one of the most
significant challenges of future grids. In this context, the microgrid concept may facilitate the
integration by coordinating the automation of a sub-section of the grid. At present, most of the
DERs are not involved in the automation process, hence they do not increase local efficiency and
they are not involved in the reactive power management, so they do not support network
stability.
During normal grid operation, the active power flows from sources to loads (grid node S[L). The
magnitude and direction of reactive power flow can be influenced by reactive power injection via
PV inverters. Due to this reactive power control the voltage magnitude at the Point of Common
Coupling (PCC) ‘‘L’’ can be actively influenced.
A voltage violation larger than the acceptable limit can be compensated for by setting the PV
inverter to an ‘‘inductive angle’’ equal to uPV = arctan (QPV/PPV), which implies shifting the
operating point along the characteristic. This control method requires the ability of the PV
inverter to control reactive power injection, which is not currently a common feature.
Furthermore, the presence of multiple PV systems connected to the same PCC requires
coordination, which may be better realized in a distributed manner and result in low voltage
being regulated.