Sie sind auf Seite 1von 7

SPEC. No.

C 3 8 3 4 3 0 4 5 0 4 A
D A T E : A p r . 1 2 , ‘ 1 2

SPECIFICATIONS

ENGINE-DRIVEN AC GENERATOR

MODEL DCA-400ESEI

[50Hz、380V]

HEAD OFFICE

2-8-5 Nihonbashi-horidomecho, Chuo-ku, Tokyo, 103-8566 Japan


TEL +81 - 3 - 6861 - 1111
FAX +81 - 3 - 6861 - 1181
1. APPLICATION

1.1 This specification covers the water-cooled, diesel engine driven AC


generator model DCA-400ESEI (hereafter referred to as generating set).

1.2 The generating set shall be designed, manufactured and tested in accordance
with the latest standards of ISO 8528.
Other matters which are not specifically mentioned in the above standards
shall be subject to Denyo Co., Ltd.'s production regulations.

2. GENERAL

2.1 Materials and Workmanship


The materials used in the manufacture of this equipment shall be of the
high quality, and shall be free from defects and imperfections.
All materials and apparatus not manufactured by Denyo Co.,Ltd. shall be
the products of well-known manufacturers. The workmanship shall be of the
high grade and in accordance with the most efficient, up-to-date procedures.

2.2 Change
Minor changes after the final design may be made by Denyo Co., Ltd.
without prior notice to the purchaser. In case of major changes or
additional equipment which may result in an increase or decrease of
equipment's cost, modifications shall be made in writing and agreed to by
both parties prior to production and shall constitute an amendment to these
specifications.

2.3 Tests and Inspection


Routine tests and inspections shall be final in our factory.
If any tests and inspections beyond the scope of ISO 8528 standard
commercial procedures are required by the purchaser, charges for such
inspections or tests shall be added to our estimate. Conditions of any such
tests and inspections shall be mutually agreed upon between both parties.

2.4 Ambient Conditions


The generating set should meet the following conditions:
(1) Ambient temperature : -5゚C or higher, 35゚C or lower
(2) Altitude : Up to 1000 m above sea level
(3) Relative humidity : 85 % or lower
(4) Place of installation : Indoor and outdoor

- 1 -
3. STRUCTURE

The machine possesses a solid structure, and is comprised of a water cooled


diesel engine and a generator, which are directly coupled on a common base.
A coupling housing is employed to connect the generator to the engine. Firm
coupling of the engine and generator is ensured by tight connection of the
housing exterior. The rotating section of the generator is directly coupled to
the flywheel of the engine with a flexible coupling plates made of laminated
thin steel.
The generator is of single bearing construction.
The standard generator is of the brushless type.
A heavy gauge steel bonnet and side door completely covers the engine,
generator and accessories, protecting the unit from effects of weather or
possible handling damages at the site.
A lifting hook is attached to the common base, and it extends to the balance
point through the bonnet top.

4. SPECIFICATIONS

4.1 AC Generator

Generator model : DF-4400I


Type : Rotating-field, synchronous generator
Excitation : Brushless type (with AVR)
Continuous duty rating : 350 kVA
Voltage : 380 V
Current : 532 A
Frequency : 50 Hz
Speed : 1500 min - 1
Direction of rotation : Clockwise (viewed from the coupling side)
Power factor : 0.8 (lagging)
Phase : 3 (4 wires)
No. of Pole : 4
Winding connection : Star
Insulation system : Class F
Cooling system : Self-ventilation
Protection type : IP20
Rating : Continuous

- NOTE -

Continuous Duty Rating : The generating set is designed for continuous


operation under normal load conditions with an
overload capacity (110% of rating capacity) up
to the standby rating for intermittent periods.

- 2 -
4.2 Diesel Engine

Maker & Model : ISUZU 6WG1


Type : 4 cycle, water cooled diesel engine, direct
injection, turbocharged with after-cooler
Rated output : 309 kW, 1500 min - 1
No. of cylinders : 6L
Bore × stroke : 147 mm × 154 mm
Total displacement : 15.681 L
Direction of rotation : Clockwise (viewed from the fan side)
Governor : Electronic governor
Cooling system : Water cooling by radiator with fan
Air cleaner : Dry paper element type
Lubricating system : Gear pump
Starting motor : 24 V – 7.0 kW
Charging generator : 24 V – 50 A
Battery : 24V-200Ah (210H52) × 2
Lubricating oil : API service class CD or higher
Fuel : Diesel fuel
(ASTM No.2 or equivalent)

- NOTE -

“Rated Output” is in accordance with ISO 3046-1 standard ambient conditions.

4.3 Voltage Regulation


The voltage regulation from rated load to no load under a rated power
factor shall be with in ±1.0 % of rated voltage.

4.4 Speed Regulation


The speed regulation from rated load to no load under a rated power
factor shall be with in 5 % of rated speed at droop controlled.
(In case of isochronous Controlled, shall be with in ±0.25 % of rated speed.)

4.5 Limits of Temperature


Limits of temperature rise of the generator shall be in accordance with
relevant IEC34-1 standards, based on ambient temperature not exceeding
35℃, and shall not exceed the following:

Armature windings Insulation class F


Field windings Insulation class F

- 3 -
4.6 Dielectric Strength Test
The strength of the windings of the generator and control box shall
meet the specifications of the high voltage test according to IEC 34-1
standards:

Armature windings - Grounding AC 1760V (one minute)


Field windings - Grounding AC 1500V (one minute)
Control box - Grounding AC 1500V (one minute)

4.7 Sound Power Level


Guaranteed sound LwA 97dB
The LwA is the measurement of machine noise level as per European
regulations.
(The Directive 2000/14/EC requires that the manufacturer makes the
machine specifying the Guaranteed sound power level.)

[For reference: 66dB(A) at 7 meters from machine (No load, Average


value in 4 directions.)]

4.8 Dimension
Length : approx. 4620 mm
Width : approx. 1450 mm
Height : approx. 2200 mm

4.9 Weight
Dry weight : approx. 5460 kg
Total weight : approx. 6020 kg

- 4 -
5. INSTRUMENT PANEL AND SYSTEM

5.1 Generator Control Panel


The following meters and apparatus are mounted on the control panel:

Frequency meter 1 pc.


AC Ammeter 1 pc.
Ammeter change-over switch 1 pc.
AC Voltmeter 1 pc.
Voltage regulator 1 pc.
Circuit breaker (3-Phase molded case circuit breaker) 1 pc.
Earth leakage relay 1 pc.
Panel light switch 1 pc.
Panel light 1 pc.
Over current relay (in the control box) 1 pc.

5.2 Engine Control Panel


The following meters, gauges and other control equipment are mounted on
the panel:

Engine Indicator 1 set


Engine speed / Oil pressure / Water temp. /
Battery charging voltage / Integrating time
Fuel level indicator
Warning lamp
(Low lubricating oil pressure, High water temp,
Air element blinding, Over speed, Fuel level failure)
Starter switch 1 pc.
Preheat lamp 1 pc.
Battery Switch 1 pc.
Local-remote change-over switch(in the control box) 1 pc.
Isochronous-Droop change-over switch(in the control box) 1 pc.

5.3 Output Terminal

Output terminal (3-Phase 4-wires) 1 set


PE earthing terminal 1 pc.
Terminal block (for remote control) 1 pc.

- 5 -
5.4 Safety Controls
The generating set shall be equipped with automatic safety controls
which will shut down the engine in the event of any abnormal condition,
such as :

Engine Circuit breaker Warning


shut down will trip lamp

Side door open ○ - -

Emergency stop
○ - -
button
Low lubricating
○ - ○
oil pressure
High jacket water
○ - ○
temp.
Over current of
- ○ -
generator

Earth leakage - ○ ○

Over speed ○ - ○

Fuel level failure ○ - ○

Air element
- - ○
blinding
Mark ○: Operate Mark -: Not operate

6. CAPACITY

Cooling water capacity : approx. 60.0 L


Lube oil capacity : approx. 55.0 L
Fuel tank capacity : approx. 490 L
Environment tank capacity : approx. 770 L

7. ATTACHMENT

Parts list 1 set


Instruction manual 1 set
Instruction manual (Engine) 1 set
Cancellation connector 1 pc.

8. COATING

The color of the generator proper and the engine shall be the manufacturer's
standard colors, and that of the bonnet shall be RAL7011, RAL7045, and N-1.

- 6 -

Das könnte Ihnen auch gefallen