General Data
Relay Identifier (13 characters) ID = _____________________________________
Current Transformer Ratio (CTR:1); (1–6000) CTR =
Demand Ammeter Time Constant (Off, 5–60 minutes) DATC =
Programmable Input Function (EN, BLK, ET)
{EN = Enable, BLK = Block, ET = External Trigger} IN =
{N = none, 1 = TRIP 1, 2 = TRIP2, B = both} 50NTT =
50NT controlled by input IN or remote bit (N, Y, IN, RB)
(N = none, Y = input, IN = input, RB = remote bit) 50NTC =
Ground Instantaneous Overcurrent Pickup—step size 0.1 A
(Off, 0.5–80 A sec {5 A Model}, 0.1–16 A sec {1 A Model}) 50NH =
Assign 50NH to trip output contacts (N, 1, 2, B)
{N = none, 1 = TRIP 1, 2 = TRIP2, B = both} 50NHT =
50NH controlled by input IN or remote bit (N, Y, IN, RB)
(N = none, Y = input, IN = input, RB = remote bit) 50NHC =
Ground TimeOvercurrent TimeDial—step size 0.01
(0.50–15 {US Curves}, 0.05–1.0 {IEC Curves}) 51NTD =
Ground TimeOvercurrent Electromechanical Reset (Y, N) 51NRS =
Assign 51NT to trip output contacts (N, 1, 2, B)
{N = none, 1 = TRIP 1, 2 = TRIP2, B = both} 51NTT =
51NT controlled by input IN or remote bit (N, Y, IN, RB)
(N = none, Y = input, IN = input, RB = remote bit) 51NTC =
Protocol = SEL
If PROTOCOL is set to SEL, the following are the applicable fields that need to be entered by
the user.
Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400) SPEED =
Data Bits (7, 8) DATA_BITS =
Parity (None [N], Even [E], Odd [O]) PARITY =
Stop Bits (1, 2) STOP =
Protocol = LMD
If PROTOCOL is set to LMD, the following are the applicable fields that need to be entered by
the user.
Communications Settings
LMD Prefix (@, #, $, %, &) PREFIX =
LMD Address (1–99) ADDRESS =
LMD Settling Time (0–30 seconds) SETTLE_TIME =
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400) SPEED =
Data Bits (7, 8) DATA_BITS =
Parity (None [N], Even [E], Odd [O]) PARITY =
Stop Bits (1, 2) STOP =
Protocol = MOD
If PROTOCOL is set to MOD, the following are the applicable fields that need to be entered by
the user.
Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200) SPEED =
Parity (None [N], Even [E], Odd [O]) PARITY =
Stop Bits (1, 2) STOP =
Modbus Slave ID (1–247) SLAVEID =