CALULATION OF PS CLASS CT ON 220 kV SIDE FOR 100/120 MVA

TRANSFORMER DIFFERENTIAL PROTECTION


Item For 220/ 34.5 kV Transformer
MVA Rating 100 /120
kV 220
Nominal Current A 315 A
Ratio Selected 400 / 1 A
VA Loading & Other Requirements for Transformer Differential Protection
Core For 220 / 34.5 kV Transformer
Max. Burden
Transformer Differential Relay 0.045 ohms
Resistance (Rrel)
Burden due to CT Lead Resistance 0.22 ohms
(4Cx4mm² cable is being used, Approx.
distance 50) (RL)
Burden due to CT winding resistance 11* ohms
(Rct)
Total Burden in case of Ph- Ph fault 11.265 ohms
(Rct+RL+Rrel)
Selected Burden 30 VA
Full Load current on 220kV Side 315 A
Transformer Impedance 12.5%
Max. through fault Current on 220kV 2520 A
Side
Selected CT Ratio 400 / 1A
Fault Current (If) on CT Secondary 6.3
Side
X / R Ratio of the System 40 (Say)
Vk in case of ph-ph faults = 0.14 x If x 397.42 V
(X/R) x (Rct+RL+Rrel)
Total burden in case of phase to earth 11.485 ohms
fault (Rct+2 x RL+Rrel)
Vk in case of ph-earth faults = 0.14 x If x 405.19 V
(X/R) x (Rct+2 x RL + Rrel)
Selected Knee Point Voltage (Vk) of 450 V
the CT
Imag 30 mA @ Vk/2
Rct 11 ohm
Conclusion The Vk value for 220kV side PS class CT for
differential protection is Vk≥ 450V,
Imag≤30mA@Vk/2, Rct ≥ 11 ohms

* - Final Rct value shall be confirmed by the CT manufacturer and hence the value of Vk
shall be accordingly governed by the above formula. In any case, the CT shall be
designed to have Vk such that it does not saturate at system fault.
CALULATION OF PS CLASS CT ON 34.5 kV SIDE FOR 100/120 MVA
TRANSFORMER DIFFERENTIAL PROTECTION
Item For 220/ 34.5 kV Transformer
MVA Rating 100 / 120
kV 34.5
Nominal Current A 2010 A
Ratio Selected 2500 / 1 A
VA Loading & Other Requirements for Transformer Differential Protection
Core For 220 / 33 kV Transformer
Max. Burden
Transformer Differential Relay 0.045 ohms
Resistance (Rrel)
Burden due to CT Lead Resistance 0.22 ohms
(4Cx4mm² cable is being used, Approx.
distance 50m) (RL)
Burden due to CT winding resistance 10* ohms
(Rct)
Total Burden in case of Ph- Ph fault 10.265 ohms
(Rct+RL+Rrel)
Selected Burden 30 VA
Full Load current on 11kV Side 2010 A
Transformer Impedance 12.5%
Max. through fault Current on 11kV 16080 A
Side
Selected CT Ratio 2500 / 1A
Fault Current (If) on CT Secondary 6.432
Side
X / R Ratio of the System 40 (Say)
Vk in case of ph-ph faults = 0.14 x If x 369.7 V
(X/R) x (Rct+RL+Rrel)
Total burden in case of phase to earth 10.485 ohms
fault (Rct+2 x RL+Rrel)
Vk in case of ph-earth faults = 0.14 x If x 377.66 V
(X/R) x (Rct+2 x RL + Rrel)
Selected Knee Point Voltage (Vk) of 400 V
the CT
Imag 30 mA @ Vk/2
Rct 10 ohm
Conclusion The Vk value for 33 kV side PS class CT for
differential protection is Vk≥ 400V,
Imag≤30mA@Vk/2, Rct ≥ 10 ohms

* - Final Rct value shall be confirmed by the CT manufacturer and hence the value of Vk
shall be accordingly governed by the above formula. In any case, the CT shall be
designed to have Vk such that it does not saturate at system fault.