Beruflich Dokumente
Kultur Dokumente
viewpoint on redundancy
Abstract— Available solutions for redundancy in electric hand, too simple configuration would increase the risk of total
propulsion are outlined, emphasizing their benefits and loss of propulsion.
drawbacks. Two different state-of-the art solutions of redundant
electric propulsion are presented. The first example is a cruise Another feature to be aware of in modern design of marine
ship with two azimuthal thrusters, both of which are equipped power systems is the tendency to increase the number of
with 18 to 21 MW dual-stator synchronous motors and driven crossovers, changeovers etc. This means that a lot of
by two voltage source inverters (VSI) in a redundant dependencies are introduced in the system which in some
configuration. The phase shift between the stator windings in cases may be hidden, and hence reduce the total availability,
each motor is 30 degrees, and the motors can also operate with see Fig. 1.
only one stator system in case that another system is lost. The
second example is LNG carriers, where one propeller is driven This article will focus on transportation vessels where
through a gearbox by two 12 to 15 MW dual-stator synchronous redundancy in the electric propulsion design ensures a safe
motors. The motors are supplied by VSI-type frequency and reliable operation for the intended purpose, however
converters with double inverter units and supply units, allowing keeping the complexity of the system at a minimum.
each motor to operate in half power mode in case of a fault in Examples on typical configurations are presented,
any of these modules. The both configurations provide 75% concentrating on two large application areas, namely cruise
redundancy in case of the most common single faults without ships and LNG carriers.
notably increasing the cost and complexity of the system.
I. INTRODUCTION
From the ship operator’s point of view, redundancy is part
of the performance. Any sudden faults at open sea should
never prohibit further operation, since it would set the crew
and passengers in danger and result in costly service actions.
Certain level of redundancy is nowadays required by
authorities and classification societies, but also shipowners are
increasingly asking for redundant solutions in order to
increase reliability and availability. The redundancy
requirements vary from ship type to ship type, from full 100%
redundancy, meaning full normal operation in case of any
single failure (typically for Dynamic Positioning operated
vessels and standby vessels) to 50% redundancy where
operation at a reduced power level is acceptable in case of
single failures (typically for transportation vessels).
The level of redundancy is usually a trade-off between
availability and simplicity. High availability requires higher Figure 1. Illustration of the system complexity.
redundancy level, that is, more installed components, higher
complexity and higher cost. Also the failure rate would
probably increase with more installed equipment. On the other
500
faulty system will be disconnected and the application will 3) Frequency converter
automatically continue at lower capacity. Due to the power ratings of frequency converters, high-
A slightly lower level of fault tolerance can be identified in power drives typically utilize two or more converters in
cases, where an interruption is allowed for a short period after parallel. The principle is presented in Fig. 5. However, this
the fault. Typically, the automatic protection will shut down configuration has relatively low level of redundancy and fault
the application and possibly disconnect the faulty system, tolerance, because the converters are hard coupled to the same
before the remaining systems can be started again. In stator winding. Fig. 6 presents a redundant configuration, in
improved configurations, the whole process may be which the two converters supply a dual-stator motor.
automated. 4) Drive components
At the lowest level, only the most critical components of
C. Redundant drive configurations the drives are redundant. Such components typically include
The following chapters describe the basic configurations, data links, control boards, shaft encoders, excitation units, DC
which are used for gaining redundancy in the propulsion links or even whole inverter units. The level of redundancy
systems. The solutions not only provide different levels of and fault tolerance in the whole systems is strongly dependent
redundancy and fault tolerance, but also affect on the system on the number of redundant components and is usually
cost and complexity. The actual systems often combine specifically agreed on case-by-case basis.
several solutions and are specifically engineered to meet the
requirements and optimize the balance between system cost IV. EXAMPLE 1: CRUISE SHIP
and productivity.
A. Overview of the propulsion system
1) Drive train Typical characteristics of the cruise ships are alternating
A simple propulsion system with only one drive train, as speed profile, high hotel load, low noise and vibration, and
illustrated in Fig. 2, is extremely vulnerable in fault situations. strict requirements on safety and availability. Especially with
When there are two propulsion trains in parallel, half of the increasing vessel size, diesel-electric propulsion system can
rated power is available regardless of any fault in the system. usually provide the most economical solution to fit these
Such configurations provide high level of redundancy and characteristics. Such system allows for high flexibility in the
fault tolerance, but the system cost is high. electric plant and machinery layout and enables high level of
2) Propulsion motor redundancy in all parts of the propulsion system.
The cost of redundancy can be reduced by coupling two Figure 7 presents a modern propulsion system for large
motors into a single shaft. Fig. 3 presents a configuration, cruise vessels. The electric plant with 11 kV main
where the motors are mounted directly to the shaft. Another switchboards is powered by four diesel generators, and there
configuration, shown in Fig. 4, utilizes a reduction gearbox, are two separate drive trains with propellers. Each of the drive
when the motors are smaller in size and can be mounted side trains comprises two parallel frequency converters with drive
by side. The both configurations are capable of running the transformers, auxiliary devices and excitation units, supplying
shaft with only one motor in case of a fault in the other drive Azipod® propulsion units with dual-stator synchronous
system. motors.
The system layout features high level of redundancy in all
parts of the propulsion system. In two-propeller configuration,
at least 50% of the rated power/torque is available after a fault
in the main switchboard, electric motor or the propulsion unit
Figure 2. Simple propulsion system with one drive train. itself. After a single fault in any other part of the system, at
least 75% of the rated power/torque is retained.
Figure 3. Two motors on single shaft. Figure 5. Two parallel converters supplying a single-winding motor.
~
~
M
~
~
Figure 4. Two motors coupled through a gearbox. Figure 6. Two parallel converters supplying a double-winding motor.
501
G G G G The frequency converters operate normally in master-
follower mode, where the master receives a speed reference
from the upper control and creates the torque reference for the
follower. In case of any fault in one of the converters, the
system will automatically continue with one converter as the
faulty converter is switched off. Because of electrical
isolation, service actions can be performed on one converter
while the other is still operating. When the converter is
switched back into operation, the system will continue with
the full available power without interruptions in the
propulsion.
502
of the power level that requires double inverter units in the
frequency converter. The double winding does not provide
any special design compared to single winding, only taking 6
phases out to the terminal box instead of 3. Hence, the motor
can be operated with a single winding in case of faults in the
power supply or in the other winding.
This provides additional redundancy on the motor side, as
75% of the total power/torque is available for certain faults
without increasing the complexity of the propulsion motor
fabrication and system design.
C. Frequency converters
In principle there is one frequency converter per
propulsion motor. However, each converter consists of several
input and output modules in order to match the required
propulsion power. This gives some possibility to implement a
certain level of redundancy without increasing the complexity
and cost. For these ships, each converter consists of double
Figure 8. Propulsion system of an LNG carrier. rectifier modules and double inverter modules. The applied
redundancy is implemented in a way that it is possible to
operate the converter system in half power mode for the
• High efficiency also in the lower power range, for following cases:
example when sailing at reduced speed.
• One propulsion transformer or related circuit breaker
• Redundancy in the electrical power, distribution and is out of operation.
propulsion plant. A minimum of two split on the
electrical side gives a reliability and availability at • Failure in one rectifier module
least on the same level as the traditional steam turbine. • Single failure in one inverter module
• Increased maneuverability and crash stop In all these cases, the converter will trip and restart in half
performance. This is ensured by the excellent torque power mode. For the failures on the input side, half power will
characteristics of variable speed electric drive be available for the converter and operation can continue with
systems. both motor windings. If the failure is on the output side, the
fault will be isolated from the motor by opening the related
B. Gearbox and synchronous motors
output isolator, and the operation can continue with half motor
The LNG shipping industry is very familiar with using torque.
gearbox solution in combination with steam turbines. Hence,
the use of a reduction gear box (twin input/single output) was VI. CONCLUSION
a natural choice, when electric propulsion was chosen for the
single propeller vessels. Also the initial cost and arrangement State of the art in electric propulsion was presented from
solutions were better than compared to other possible the viewpoint of redundancy. Emphasis of the presentation
configurations, such as tandem motors etc. For the twin was on commercially successful solutions applied on
propeller arrangements the use of gearbox was not the first passenger and transportation vessels. After reviewing the basic
choice in the early stage but considering cost and arrangement redundant configurations, examples of the propulsion systems
benefits this solution was also applied for this system. were presented for cruise ships and LNG carriers.
This means that the motor and drive configuration is A typical propulsion system of a large cruise ship provides
practically the same for the both configurations. The redundancy in all components, from the engines to the
propulsion requirement for LNG Carriers is in the range of 25 propellers. The azimuthal thrusters are powered by dual-stator
to 30MW. In this power range, it is natural to have two synchronous motors, which in turn are supplied by two
propulsion motors rated about 12 to 15MW each. This gives independent frequency converters in redundant configuration.
automatically 2 x 50% total electric redundancy, which is a The system provides minimum 50% redundancy in terms of
minimum requirement for this type of vessels. Hence for any available propulsion capacity against the most severe faults in
single failure, at least 50% propeller torque would be available the system, and the most common single faults only cause
from the electrical propulsion system. 25% loss of the available capacity without even shutting down
the system in between.
The propulsion motors are of standard synchronous
design, which provides the highest efficiency and lowest The electric propulsion system of a single propeller LNG
weight to power ratio at this power level among the available carrier uses a gearbox for two medium-speed synchronous
designs today. The motor speed is around 675 rpm, which motor drives. The motors have two stator windings, which are
allows the construction yards to use gear box with single stage supplied by frequency converters with several input and
design. The motor has two stator windings, basically because output modules. The drive system from the power plant to the
503
gearbox provides 50% to 75% redundancy against faults, REFERENCES
although shutdown of one converter may be required for a [1] H. Burzanowska, P. Sario, C. Stulz, “Redundant Drive with Direct
short period of time. Torque Control (DTC) and Dual-Star Synchronous Machine,
Simulations and Verifications,” EPE 2007 – 12th European Conference
Both of the presented solutions provide high level of on Power Electronics and Applications, Aalborg, Denmark, 2–5
redundancy and reliability for applications that require high September 2007.
availability and safety. The solutions have been tailored to [2] Khan K.S., Arshad W.M., Kanerva S., “On Performance Figures of
meet the specific requirements in an economical manner, and Multiphase Machines,” ICEM’08, Vilamoura, Portugal, 6–9 September
without notably increasing the system complexity. 2008.
[3] Kanerva S., Toivanen O., Sario P., Arshad W.M., “Experimental Study
on Dual-Stator Synchronous Motor with Redundant Voltage Source
Inverter (VSI) Drive,” ICEM’08, Vilamoura, Portugal, 6–9 September
2008.
504