Sie sind auf Seite 1von 4

1

Calibration Services in Support of Smart Grid


Applications
R. Arseneau, Senior Member, IEEE, and E. So, Fellow, IEEE

harmonics at other frequencies. This results in higher


Abstract—Deregulation of the electricity market in North harmonic distortion in the current waveforms and to a lesser
America has resulted in many new challenges for electrical degree in the voltage waveforms. Harmonics can affect the
utilities, their regulators and the national laboratories that performance of metering equipment and therefore impact the
provide calibration and traceability for their equipment. The billing charges of the customers and the revenues paid to
deregulated marketplace now allows small distributed generation private producers. Measurement problems due to harmonics
installations often connected in rural distribution networks
are more common in distribution networks where harmonic
where power quality is more likely to be an issue. It is therefore
important to know what impact the increased level of harmonics levels are higher.
will have on measuring equipment, particularly equipment used Revenue meters have traditionally been designed and tested
in revenue billing applications and for the safe operation and for sinusoidal operations only. They are however, increasingly
control of the new "smarter" power grid. This paper discusses being operated in the field under waveform conditions, which
some of the research and development initiatives undertaken at are not pure sinusoids. Under these conditions the measuring
the National Research Council of Canada to address the method implemented in the conventional revenue meter is
changing test and calibration requirements of the electrical critical. For example, distortion even if only in the current
power industry. waveforms can result in significantly different voltampere
demand and power factor charges depending on the type of
Index Terms—Smart grids, power quality, IEEE-1459-2000,
meters used [1].
meters, phasor measuring unit, calibration, on-site testing.
The question of selecting the proper measuring strategy for
a location where harmonics are known to be present is a
I. INTRODUCTION
difficult choice for metering engineers. The process is linked

T he development of the power system is a world-wide


evolutionary process. At the beginning and for many
decades there were basically only small regional grids
to the parameters approved by the regulatory agency having
jurisdiction and / or the contractual agreement with the power
producer. In North America all quantities currently used such
where loads and generation capacity were more or less in as energy, demand and power factor all imply a nominal 60
balance within a relatively restricted regional territory. There Hz operation. Regulations are not in place that would allow a
was not much need for interconnections to the neighbouring utility to consider harmonics in its billing charges [2].
grids. Often everything within these regional grids, the A simpler approach is to separate the main product, the
generating stations, the transmission and distribution networks fundamental 60 Hz quantities, from the pollution that is the
down to the meter at the customer entrance was owned by a unwanted non-fundamental components. This was the
single organization which had full control without much need underlying philosophy followed in the preparation of IEEE
to consider what happened outside of its territory. Standard 1459-2000 [3]. This method provides for a
Deregulation of the electricity market has changed all this. convenient measure of the traditional metering quantities
Today most utilities have been restructured so that at least defined in the Standard as the fundamental apparent power S1,
generation, transmission and distribution are not controlled by the fundamental active power P1, the reactive power Q1 and
the same organization. There are opportunities for privately the fundamental power factor PF1. These quantities identify
owned large generating stations and for alternate energy the main product generated by the utility or a private
producers. All these changes have created a need for more producer, transmitted, distributed and sold by the electric
measuring points for billing and the introduction of new utilities and bought and used by the customers. Fortunately
equipment such as phasor measuring units (PMUs) and total modern digital meters are available today that can measure the
harmonic distortion (THD) meters in the new marketplace. required quantities even in non-sinusoidal conditions.
Over the past few years an increasing number of loads The paper investigates the performance of the widely used
operated by industrial, commercial and residential customers conventional revenue meters in comparison with the emerging
are non-linear. Non-linear loads can be viewed as consuming generation of meters which are based on fundamental
energy at the fundamental frequency and generating measurements only. The paper will also discuss some of the
test and calibration requirements of new measuring equipment
The authors are with the Institute for National Measurement Standards, particularly THD meters and PMUs.
National Research Council of Canada, Ottawa, ON, K1A-0R6, Canada.
(e-mail: rejean.arseneau@nrc.ca, eddy.so@nrc.ca;)

978-1-4673-2729-9/12/$31.00 ©2012 IEEE


2

II. CALIBRATING REVENUE METERS AND PMUS To better understand the test results, a short review of
Today there are many types of revenue meters common equations is provided. The first set follows closely
implementing measuring equations that are not based on the equations of IEEE Standard 1459. The Standard provides
fundamental frequency billing as defined in 1459. In addition, for a convenient measure of the metering quantities defined
new instruments known as Phasor Measurement Units such as the fundamental active power P1, the fundamental
(PMUs) which also measures ac voltages, currents, phases and reactive power Q1, the fundamental apparent power S1 and the
adds a time stamp are increasingly being used in power fundamental power factor PF1. These quantities identify the
systems. It is important to review known harmonic situations useful product generated, transmitted, distributed and sold by
and evaluate how this measuring equipment would be the electric utilities and used by the customer. They are,
affected. For example could there be changes in billing
P1 = V1 x I1 Cos θ1 (1)
charges resulting from different metering strategies, if the
waveforms were not pure sinusoidals. Would PMUs still
Q1= V1 x I1 Sin θ1 (2)
provide the correct information regarding the stability of the
power systems being monitored? To investigate
S1= V1 x I1 (3)
this, field recordings shown in Fig. 1, of an industrial load
were reproduced on the National Research Council of Canada
PF1= P1 / S1 (4)
calibration system. Different types of revenue meters and a
new PMU were tested. The field data was collected on the
In older meters, measurements of the active power P and
secondary of the metering CT’s and PT’s, thus the recorded
reactive power Q are used. Active and reactive powers are the
signals are those that the revenue meters were subjected to at
sum of the fundamental and all the harmonic components.
the time of the test. The load consists of variable speed drive
pumps. The voltage waveform has a THD value of 15.5%.
P = P1 + PH (5)
The current waveform has a THD value of 47.0% and is
visibly different from a sinusoidal waveform. Q = Q1 + QH (6)

Active power is clearly defined and is usually measured


correctly even in previous generations of meters. The
harmonic components PH are included in the measurements of
traditional revenue meters even though this is unwanted by
customers. In most applications however harmonic power is
rather small and has little influence on billing charges.
Reactive power in older revenue meters is usually measured
as defined by Budeanu and includes all the harmonic
components of the reactive power. Other definitions have
been used, for example Fryze which defines all non-active
power as reactive power. Many meters also measured the
apparent power S. Two different methods are commonly used,

S= V x I (7)

S PQ = P 2 + Q 2 (8)

Power factor PF, the ratio of the measured power and


apparent power, is sometime used as an extra charge if it falls
below a predetermined value. The two methods of measuring
apparent power results in two power factors,

PF= P/S (9)

PF= P/ SPQ (10)

PMUs are relatively new and need to be studied to know


which equations are used and how they respond in non-
sinusoidal situations.

Fig. 1 Field recorded waveforms


3

Test results were obtained for one revenue meter with a differences even though measureable, are small mostly within
specified accuracy of 0.1% and a PMU whose accuracy is the specifications of the equipment.
0.025%. The results summarized in Table 1 are for the THD measuring equipment is also tested with field
waveforms of Fig.1. The fundamental quantities of the recorded waveforms such as those shown in Fig. 1. Table 2
waveforms as recommended in 1459 are also included in this shows the THD measurements obtained with the same meter
Table. As expected the power measurement results of the and PMU reported in Table 1. The results of the meter for its
meter and PMU are close to the fundamental active power P1. voltage THD measurement is relatively close to the reference
There are larger differences for the measurements of reactive value. However the differences are more significant for the
power Q as compared to the fundamental reactive power Q1. current THD measurements. The THD measurements of the
The differences are much more significant for the PMU are the same as the reference value for the waveforms.
measurements of apparent power S and power factor PF.
Clearly the meter and PMU are programmed to use different TABLE 2
THD MEASUREMENTS WITH THE WAVEFORMS OF FIG. 1
equations as noted in (7) to (10).
TABLE I Quantity Reference Meter PMU
RESULTS WITH THE WAVEFORMS OF FIG. 1
THD v 15.5% 15.3 % 15.5%
THD i 47.0% 43.0 % 47.0%
Quantity IEEE 1459 Meter PMU
Power 546.28 547.86 W 548.04 W
Reactive Power 0.59 11.15 Var 0.75 Var IV. CONCLUSIONS
Apparent Power 546.32 600.02 VA 548.03 VA
Deregulation and the increasing use of distributed generation
Power Factor 1.0 0.91 1.0 in the electricity market have resulted in the introduction of
new measuring equipment particularly multifunction digital
revenue meters and phasor measurement units. This has
III. CALIBRATING THD METERS created new requirements for national laboratories that need to
In Canada electrical utilities and other organizations provide calibration and traceability services for this new
providing calibration services use THD measuring devices to measuring equipment. The paper presented some of the
verify the quality of the voltage and current waveforms research and development initiatives undertaken or under way
measured by revenue meters. These THD measurements are at the National Research Council of Canada to address these
not used directly to establish a billing charge and their new calibration requirements of the power industry. As an
calibrations are not subjected to the same regulatory example of the calibration services provided, test results
requirements as those of revenue meters. However, many obtained for a revenue meter, a phasor measurement unit and a
NRC clients have added the THD measuring functions to their THD meter operating under non-sinusoidal waveform
normal calibration requests. conditions are presented and discussed in the paper.
The THD measuring functions are usually tested under
distorted voltage and current waveforms of 1, 3 and 5 % THD. V. ACKNOWLEDGEMENT
The test waveforms consist of the fundamental component and The authors would like to thank Mrs. Michelle Frigault of
a single harmonic component either in phase or at 180 degrees NRC/INMS for her contributions to this project. We also
with respect to the fundamental. The frequency of the want to thank Y. Tang from NIST Gaithersburg and G. N.
harmonic component does not usually exceed 1500 Hz. The Stenbakken from GNS Consulting for their discussions and
non-sinusoidal test conditions are produced with a reference advice on testing and evaluating PMUs.
source with independent voltage and current outputs. The test
waveforms are entered into the reference source as a set of VI. REFERENCES
voltage and current amplitudes and phase angles. The NRC
[1] R Arseneau and P.S. Filipski, “Application of a Three Phase
reference system for verifying the THD measurements is Nonsinusoidal Calibration System for Testing Energy and Demand
based on two precision sampling voltmeters, used as 18 bit Meters under Simulated Test Conditions”, IEEE Trans. On Power
A/D converters [4]. Normally the current THD values are Delivery, Vol. PWRD-3, No.2, July 1988,pp 874-879.
verified at 2.5, 5, 10 and 50 A. The voltage THD
[2] R Arseneau and M B Hughes, “Selecting Revenue Meters for Harmonic
measurements are calibrated at 120, 240 and 600 V. Producing Loads”, IEEE 11th International Conference on Harmonics
In general, for most equipment tested, very similar errors and Quality of Power, Lake Placid, NY, USA, 2004.
have been observed for both voltage and current THD
measurements during their calibrations. These errors were also [3] IEEE Standard Definitions for the Measurement of Electric Power
Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced
practically identical at each current and voltage level tested. Conditions, IEEE Std. 1459, 2000.
One unexpected result of the tests is that there are differences
in THD measurement errors depending if the harmonic [4] R Arseneau M. E. Sutherland and J. J. Zelle, “A New Transfer Device
component is in phase or at 180 degrees with respect to the for the NRC Travelling Standard Program”, IEEE Trans. On Instrum.
fundamental component of the test waveforms. These And Meas., Vol. IM-52, No.2,pp 411-414, April 2003.
4

VII. BIOGRAPHIES Eddy So (M’74–SM’84–F’90) received the M.Sc. and D.Sc. degrees in
electrical engineering from George Washington University, Washington, DC.
In 1977, he joined the National Research Council of Canada, Ottawa, ON,
Rejean Arseneau (M’81–SM’90) received the B.Sc. and M.Sc. degrees in Canada. In 1979–1989, he was an Adjunct Professor with the University of
electrical engineering from the University of New Brunswick, Fredericton, Ottawa, Ottawa, and Carleton University, Ottawa. In 1991–2004, he was the
NB, Canada, in 1975 and 1979, respectively. In 1980, he joined the National Director of the Electromagnetic and Temperature Standards Section, Institute
Research Council of Canada. He is currently a Principal Research Officer and for National Measurement Standards, National Research Council of Canada,
Leader of the Electrical Power Measurements Group, Institute for National where he is currently a Principal Research Officer and Leader of the High
Measurement Standards, National Research Council of Canada, Ottawa, ON, Voltage Power and Energy Measurements Program. His research interests
Canada. His research interests include high-accuracy measurements and power include the development of measurement techniques and instrumentation for
quality, particularly the effects of harmonics on measuring equipment. accurate measurements of active/reactive power and energy under difficult
Mr. Arseneau is a member of the Association of Professional Engineers of operating conditions and for assessing the operating conditions of different
Ontario. He is the Chair of the IEEE Power Systems Instrumentation and types of high-voltage insulation.
Measurements (PSIM) Technical Committee. He is a Past Chair of the IEEE Dr. So is a registered Professional Engineer in the Province of Ontario. He is
Ottawa Section. He is an Editor for PSIM of the IEEE Transactions on Power the Past Chair of the IEEE Power Systems Instrumentation and Measurements
Delivery. Technical Committee, the Chair of its Subcommittee on Electricity Metering,
the Chair of its Working Group on Low-Power-Factor Power Measurements,
and is also its Standards Coordinator. In 2002–2008, he was the Chair of the
Conference on Precision Electromagnetic Measurements Executive
Committee.

Das könnte Ihnen auch gefallen