5 Pull boxes – provide one box for every 18 meters of conduits length depending upon the 
length of run. Other pull boxes may be designated by plans. Check with the 
designer/consultant about the sizes.

6. Fittings

6.1 For PVC pipes

6.1.1 Couplings – provide 1 coupling for every length plus 1 coupling for every termination.

6.1.2 Elbows – provide 1‐900 elbow for every quarter turn for sizes of 32 mm (1 1/4”) and 
above.

6.1.3 Cement – provide 1 can for every 10 length of conduit.

6.1.4 End bells – provide 1 for every termination.

6.2 For RSC conduits

6.2.1 Coupling – provide 1 additional coupling for every 5 lengths

6.2.2 Elbows‐ provide one 90‐degree elbow every 90‐degree turn for sizes of 25 mm (1”) 
diameter above.

6.2.3 Locknut and bushing – provide one pair for every termination.

6.3 For electrical metallic tubing

6.3.1 Couplings‐ one set for every length

6.3.2 Elbows‐ use on site bended EMT

6.3.3 Adapters w/ locknut and bushing‐ for every termination are 1 adapter and 1 pair of 
locknut and bushings.

6.4 Straps – two (2) straps for every length of conduit. In sizes of 25 mm diameter and above 
use clamps especially for RSC or EMT conduits.

6.5 Other fittings

6.5.1 Wire trays/cable trays – check with drawings and consultant/designer

6.5.2 Cable trough / duets – check w/ drawings especially that the drawings may have 
specific sizes.