Beruflich Dokumente
Kultur Dokumente
2 Setting Calculations
Relay settings and values of circuit components can be calculated in the following order:
Figure 2-4 Procedure for calculating High Impedance Differential Protection Settings
Plant Data
See diagram above.
Settings Requirements
Assigned through fault current (rated stability limit) = 31.5kA (CB break capacity)
Required Fault Setting (Primary Operate Current):
Approximately 50% of busbar rating, or
10 – 30% of minimum fault current available, or
As specified by the user
From the supplied plant data a primary operate current (POC) of 1000A is chosen i.e. 50% of busbar rating.
The magnetising current is dependent on the relay operate voltage (Vs), this is not finalised yet so a provisional
value (Vs prov) is chosen from the above i.e. 160 < Vs < 300
Say Vs prov = 175V. From the CT magnetising curve Imag = 21mA at 175V.
Irelay = 0.5 – 6(0.021) = 0.374A (use 0.37A)
Rstab = 175/.37 = 470 Ohms
Metrosil Specification
‘C’ Value
Vs = 175V (i.e. > 100V) so a ‘C’ value of 1000 is chosen
4 1
P1SEC 31500 600 12kW
2000
PCONT Is 2 x Rstab
PCONT 0.37 2 x 470
PCONT 64W
VFint 2
P1SEC Where: V Fint 4
(V K 3 x R stab x I Fint ) x 1.3
Rstab
31500
IFint 15.75A
2000
VFint 4
(VK 3 x Rstab x IFint) x 1.3
VFint 4
(600 3 x 470 x 15.75 1.3 1462V
2
1462
P1SEC 4.54kW
470
Plant Data
10MVA
33/11kV
7SR23
7SR23
Relay Circuit
Relay Circuit
Plant Data
See diagram above.
Settings Requirements
Rated current = 10 x 106 / ( 3 x 11000) = 525A
Assigned through fault current (rated stability limit) = 16 x load current = 8.4kA, or, as specified by the user.
Required Fault Setting (Primary Operate Current):
10 – 25% of protected winding rated current, or
As specified by the user.
Required P.O.C. = 53 - 131A. Say 60A.
8400
VS 7.5 0.15 107.1V
600
8400
VS 6 0.15 86.1V
600
VK 300
VS 150V
2 2
The magnetising current is dependent on the relay operate voltage (Vs), this is not finalised yet so a provisional
value is chosen from the above i.e. 107.1 < Vs < 150
Say Vsprov = 120V. From CT magnetising curve: At 120V IMAGLCT = 9mA and IMAGNCT = 12mA
Irelay = 0.1 – (3(0.009) + 0.012) = 0.06A
Rstab = 120/.061 = 1967 Ohms (Say 2000 Ohms giving Vs = 2000 x 0.06 = 120V)
Metrosil Specification
‘C’ Value
Vs = 120V (i.e. > 100V) so a ‘C’ value of 1000 is chosen
4
P1SEC I F T VK
4 1
P1SEC 8400 350 6.24kW
600
PCONT Is 2 x Rstab
PCONT 0.06 2 x 2000
PCONT 7.2W
VFint 2
P1SEC Where: V Fint 4
(V K 3 x R stab x I Fint ) x 1.3
Rstab
8400
IFint 14A
600
VFint 4
(VK 3 x Rstab x IFint) x 1.3
VFint 4
(350 3 x 2000 x 14 1.3 1361V
2
1361
P1SEC 926W
2000
A full explanation of how to specify CTs for use with high impedance protection is available on our Website:
www.siemens.com/energy.
Typically the CT primary rating rated current of protected circuit (where rated current is different on each circuit
use highest rating e.g. Bus Section rating).