STRUCTURAL COMMENTS FOR THE JALAN BANI BU ALI HOSPITAL - ICU CCU
FOR THE SUBMITTED GEOTECHNICAL REPORT / REVISED CALCULATIONS AND DRAWINGS
1. ITEM A : AL RAWAS DRILLING GEOTECHNICAL REPORT No. OM – SI / 350 / 2011 FOR JALAN BANI BU
ALI A&E ADOPTED FOR THIS PROJECT
We have no objections to the results of the Geotechnical Report but please take careful note of the
following excerpts from the soil report as parameters and conditions in the design ;
It is recommended to use isolated reinforced concrete footings. concrete footings and reinforced
with continuous equal upper and lower steel reinforcements.
The net allowable soil bearing stresses at the required foundation level should not exceed value
of 250 KN/m2.
o Cube strength of R.C. after 28 days must not be less than 25 N/mm2.
Suitable designed shoring system should be implemented for temporary side support of the the
excavated area sides.
Old foundations and fill layer should be completely removed before starting construction of
foundation
Along with the previous suggestion , provide additional girders through thes additional columns
For Column C3 , the drawings for link and vertical bars do not match.
For Columns C2 and C5 , provide clearer detail , for the bar bundle , to be included in dwg S-04.
Typically for all column drawings with mixed bar diameters , provide clearer detail to indicate the
bar placement for these mixed diameters.