Sie sind auf Seite 1von 3

Date: 31.01.

2018 / US
Easy Product Finder Project 1

Project Structure
Position.01 - - - - - - - - - - - - - - - - - - ASL-AG/325x225/A1/0/0/E6-C-0
- - - - - - - - - - - -
Position.02 - - - - - - - - - - - - - - - - - - ASL-AG/325x225/A1/0/0/E6-C-0
- - - - - - - - - - - -

Version: 2.3.16 (12-Jan-18) Page: 1/3


Date: 31.01.2018 / US
Easy Product Finder Project 1
Position.01

ASL-AG/325x225/A1/0/0/E6-C-0
Rear assemblies AG Opposed blade action volume control damper
Size 325 Length [mm]
Size 225 Height [mm]
Installation Subframe A1 with subframe
Fixing variants 0 concealed fixing
Surface 0 Standard finish E6-C-0
Total amount 1

Top view with ceiling effect

Volume flow V: 1000 m³/h with ceiling effect


Temperature difference Δtz: 0.0 K L = 6.00 m
Effective air velocity veff: 6.48 m/s b = 0.00 m
Temperature difference ΔtL: 0.0 K
Induction i: 9
Max. air velocity vL: 2.03 m/s
b0,2: 1.03 m
Critical, effective air velocity veff: < 0.10 m/s

Acoustic Data - Supply air Acoustic Data - Extract air


Damper settings 100% 50% 25% Damper settings 100% 50% 25%
Δpt 31 76 159 Pa Δpt 16 36 91 Pa
LWA 37 51 61 dB(A) LWA 36 41 47 dB(A)
LWNC 32 46 56 LWNC 32 38 43

Description

TROX grille type ASL for wall installation consists of a diffuser-type front border with horizontal, individually adjustable blades.
Border and blades are extruded aluminium sections.

Version: 2.3.16 (12-Jan-18) Page: 2/3


Date: 31.01.2018 / US
Easy Product Finder Project 1
Position.02

ASL-AG/325x225/A1/0/0/E6-C-0
Rear assemblies AG Opposed blade action volume control damper
Size 325 Length [mm]
Size 225 Height [mm]
Installation Subframe A1 with subframe
Fixing variants 0 concealed fixing
Surface 0 Standard finish E6-C-0
Total amount 1

Top view with ceiling effect

Volume flow V: 333 m³/h with ceiling effect


Temperature difference Δtz: 0.0 K L = 6.00 m
Effective air velocity veff: 2.16 m/s b = 0.00 m
Temperature difference ΔtL: 0.0 K
Induction i: 9
Max. air velocity vL: 0.67 m/s
b0,2: 0.71 m
Critical, effective air velocity veff: < 0.10 m/s

Acoustic Data - Supply air Acoustic Data - Extract air


Damper settings 100% 50% 25% Damper settings 100% 50% 25%
Δpt <5 10 22 Pa Δpt <5 <5 12 Pa
LWA <15 25 35 dB(A) LWA <15 20 25 dB(A)
LWNC <9 20 30 LWNC <9 14 19

Description

TROX grille type ASL for wall installation consists of a diffuser-type front border with horizontal, individually adjustable blades.
Border and blades are extruded aluminium sections.

Version: 2.3.16 (12-Jan-18) Page: 3/3