Sie sind auf Seite 1von 39

Protection of Transmission

lines

By
Rohini Haridas
Assistant Professor
Dept of Electrical Engineering
SSGM College of Engineering Shegaon
As the length of electrical transmission line is
generally long enough and it runs through open
atmosphere, the probability of occurring fault
in electrical power transmission line is much higher
than that of transformers and alternators .

That is why a transmission line requires much more


protective schemes than a transformer and an
alternator.
Features of protection of transmission line
1. During fault, the only circuit breaker closest to the fault point
should be tripped.

1. If the circuit breaker closest the faulty point, fails to trip


the circuit breaker just next to this breaker will trip as back up.

2. The operating time of relay associated with protection of line


should be as minimum as possible in order to prevent
unnecessary tripping of circuit breakers associated with other
healthy parts of power system.
The main methods of transmission line
protection
Non- unit type Protection Unit type protection

1. Time graded 1. Differential protection


over current protection

2. Current graded over 2. Carrier current protection


current protection.

3. Distance protection.
Protection of Radial Feeder
In radial feeder, the power flows in one direction
only, that is from source to load.

This type of feeders can easily protected by using


either definite time relays or inverse time relays.
Line Protection by Definite Time Relay
ADVANTAGE DISADVANTAGE

simplicity If the number of sections in


the line is quite large, the time
during fault, only setting of relay nearest to the
nearest CB towards the source, would be very long. So
source from fault point during any fault nearer to the
will operate to isolate source will take much time to
the specific position of be isolated. This may cause
the line. severe destructive effect on the
system.
Over Current Line Protection by Inverse
Relay
Over Current Protection of Parallel
Feeders
Protection of Ring main system
The two lines leaving the generating stations should be equipped
with non-directional over current relays ( in this case relay 1 and 8)
At each bus directional relay should be placed in both
incoming and outgoing lines lines (2,3,4,5,6,7)
Direction of tripping should be away from the bus.

**If the direction of flow of power is same as that of the direction of relay
then only relay trips
There should be relative time setting of the relay. Going
round the loop E-A-B-C-D-A-E, the outgoing relays
are set with decreasing time limits (relays 1,3,5,7)
Similarly Going round the loop in opposite direction E-
A-D-C-B-A-E, the outgoing relays are set with
decreasing time limits (relays 8,6,4,2)
Direction of tripping should be away from the bus
Protection of Ring main system
Current graded protection

**The short ckt current along the length of protected ckt decreases with
increase in distance between supply end and fault point
Difficulties in current graded protection

1. The relay can not discriminate between the fault in the next
section and the end of first section.

**Hence for discrimination the relays are set to protect only part
of the line, usually 80%

2. For the ring mains, parallel feeders ,where power can flow to
fault from either direction , a system without directional
control is not suited.
Trip Law for Simple Impedance Relay Using Universal
Torque Equation

The universal torque equation is given as :

T = k1 I + k 2V + k 3VI cos(θ − τ ) + k 4
2 2

Thus trip law for simple impedance relay is as follows :

If Zseen p Zset Then trip, else restrain


Introduction to Distance Protection
Principle of R-X Diagram
Characteristics of impedance relay

** It is non directional. It responds to the faults on both sides of CT,VT location


i.e. forward (I-quadrant )and reverse direction (III-quadrant)
Characteristics of impedance relay on R-X
diagram
Implementation of simple impedance relay using
balance beam structure
Phasor diagram for directional element

Max. Torque line


Zero torque line

τ φ1
θ
v
φ Reference quantity

φ v
Characteristics of directional impedance relay
Effect of Arc resistance on Reach of
SIR (Under-reach)

**The tendency of distance to restrain (not to operate ) at the preset value of


the impedance or impedances less than preset value is known as under-reach
Trip Law for Simple Reactance Relay Using
Universal Torque Equation
The universal torque equation is given as :

T = k1 I + k 2V + k 3VI cos(θ − τ ) + k 4
2 2

Thus ,trip law for simple impedance relay is as follows:

If Xseen p Xset Then trip, else restrain


Characteristics of Reactance Relay
Line fault characteristics
X

Restrain

Xset or Xn
R

Trip Trip
Effect of Arc resistance on Reach of
Reactance relay
Directional property exhibited by reactance relay
Comparison between Distance Relay
Factors Simple Reactance relay Mho relay
impedance relay

Operating Directional
Current Current
quantity element
Restraining Directional Voltage
voltage
quantity element
Directional No No Yes
property
Effect of fault Under reaches Reach
resistance Under reaches
unaffected

Area occupied Moderate Very large Smallest


on R-X diagram
Distance protection of transmission line
Three step Distance protection
Three step Distance protection
Three step Distance protection using
mho relay
Three step Distance protection
Overload or overcurrent protection
Combine overcurrent and earth fault
protection

Das könnte Ihnen auch gefallen