POWER CUBE:

SET ALMPORT: CN=0, SRN=40, SN=0, PN=0, SW=ON, AID=65111, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=1, SW=ON, AID=65109, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=2, SW=ON, AID=65125, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=3, SW=ON, AID=65107, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=4, SW=ON, AID=65103, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=5, SW=ON, AID=65105, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=6, SW=ON, AID=65104, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=7, SW=ON, AID=65101, PT=BOOL, AVOL=HIGH;

SET ENVALMPARA: ALMID=65111, ANM="Generator #1 running", ALVL=Major, ASS=ENV;

SET ENVALMPARA: ALMID=65109, ANM="Generator #1 failure ", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65125, ANM="Rectifier fault alarm", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65107, ANM="Telecom shelter tower light alarm", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65103, ANM="Telecom/General shelter fire alarm", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65105, ANM="Telecom shelter high temperature alarm", ALVL=Major,


ASS=ENV;

SET ENVALMPARA: ALMID=65104, ANM="Telecom/General shelter door alarm", ALVL=Major, ASS=ENV;

SET ENVALMPARA: ALMID=65101, ANM="Telecom shelter air condition fault alarm", ALVL=Major,
ASS=ENV;
POWER CUBE LOW polarity:

SET ALMPORT: CN=0, SRN=40, SN=0, PN=0, SW=ON, AID=65111, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=1, SW=ON, AID=65109, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=2, SW=ON, AID=65125, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=3, SW=ON, AID=65107, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=4, SW=ON, AID=65103, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=5, SW=ON, AID=65105, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=6, SW=ON, AID=65104, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=7, SW=ON, AID=65101, PT=BOOL, AVOL=LOW;

MINI SHELTER SITES:

SET ALMPORT: CN=0, SRN=40, SN=0, PN=0, SW=ON, AID=65110, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=1, SW=ON, AID=65108, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=2, SW=ON, AID=65125, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=3, SW=ON, AID=65107, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=4, SW=ON, AID=65103, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=5, SW=ON, AID=65105, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=6, SW=ON, AID=65104, PT=BOOL, AVOL=LOW;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=7, SW=ON, AID=65101, PT=BOOL, AVOL=LOW;
SET ENVALMPARA: ALMID=65110, ANM="AC power fault alarm", ALVL=Major, ASS=ENV;

SET ENVALMPARA: ALMID=65108, ANM="DC power low voltage", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65125, ANM="Rectifier fault alarm", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65107, ANM="Telecom shelter tower light alarm", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65103, ANM="Telecom/General shelter fire alarm", ALVL=Critical, ASS=ENV;

SET ENVALMPARA: ALMID=65105, ANM="Telecom shelter high temperature alarm", ALVL=Major,


ASS=ENV;

SET ENVALMPARA: ALMID=65104, ANM="Telecom/General shelter door alarm", ALVL=Major, ASS=ENV;

SET ENVALMPARA: ALMID=65101, ANM="Telecom shelter air condition fault alarm", ALVL=Major,
ASS=ENV;

Mini Shelter High polarity:

SET ALMPORT: CN=0, SRN=40, SN=0, PN=0, SW=ON, AID=65110, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=1, SW=ON, AID=65108, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=2, SW=ON, AID=65125, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=3, SW=ON, AID=65107, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=4, SW=ON, AID=65103, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=5, SW=ON, AID=65105, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=6, SW=ON, AID=65104, PT=BOOL, AVOL=HIGH;

SET ALMPORT: CN=0, SRN=40, SN=0, PN=7, SW=ON, AID=65101, PT=BOOL, AVOL=HIGH;